CONSTRUCTION - General Notes
CONSTRUCTION - General Notes
5. Not more than half the column bars shall be lapped at a section.
6. Confining stirrups in beam column junction shall be provided in Z
portion at the spacing indicated. However if beams are connected on all the
four directions of columns the spacinf should be doubled in case of difficulty
in providing closed stirrups, u type stirrups may be provided
7. Lap length shall be 50 times the diameter of bar.
8. Column longitudinal reinforcement ELL for eccentric footing 85cm for
other 60cm
9. Provided continuous chairs to keep the top reinforcement in position.
10.Spacer bar to be provided in between two layers of reinforcement of same
dia at every 1000 c/c
11.Not more than 40% of reinforcement shall be lapped at the particular
junction.
12.Cantilever props should not be released until the roof is concreted
13.For earthquake analysis zone 3 is taken as per IS: 1893-1984code.
14.Removal of formworks
For Slab:
Slab spanning up to 4.5m (15-0) 7 days