SINCOR, C.A.
UPSTREAM SURFACE FACILITIES PROJECT
POWER AND CONTROL CABLES
REVISION INDEX:
This Document Consists of 16 Pages
NOTE: Any technical change from the original Sincor document is indicated by | in the right hand
margin.
APPROVAL REGISTER
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 2/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
Contents
SECTION N
1. SCOPE 3
3. CABLE CONSTRUCTION 5
4. CABLE SPECIFICATION 8
6. CABLE IDENTIFICATION 12
7. TEMPERATURE RATINGS 13
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 3/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
1. SCOPE
A. This specification covers the basic requirements, features, general construction, design
and fabrication and testing of 600V-35 kV cable suitable for operation in dry or wet
locations.
B. This specification is to be used jointly with the Material Requisition (MR). Unless
otherwise specified in the MR, the Seller shall comply with the requirements of this
specification. Should any conflict arise between this specification and the MR, the MR
shall take precedence. In the event of ambiguity of any portion of the subject
documents, it shall be the responsibility of the Seller to contact the Buyer for
clarification.
In Particular:
IEC 60331 Test for electric cables under fire conditions (all applicable
parts)
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 4/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
IEC 60502 Extruded solid dielectric insulated power cables for rated
voltages from 1 kV up to 30 kV
IEC 60811 Common test methods for insulating and sheathing materials
of electric cable.
IEC 60840 Testing For 34.5 kV Cables
C. The cables may conform to the standards of the country and the countrys approval
authority as follows:
D. Alternative Standards
The offered power cables may conform to the standards of the country of manufacture,
provided these standards are based on, or comparable to the above-preferred standards.
Each bidder proposing other standards must specifically indicate from the above codes.
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 5/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
3. CABLE CONSTRUCTION
A. The cables shall in all respects be suitable for operation under the service conditions
stated in the attachments to the Material Requisition. They shall have a design life of at
least twenty years.
a) Direct buried in the ground (Note: Cables shall be suitable for direct burial in
water-logged ground.)
b) In underground ducts
d) Aboveground, fastened to cable ladder rack or tray in the open air exposed to
direct sunlight (UV).
C. Cable fillers shall be solid, non hygroscopic and fill the cross section such that the
transmission of gas and hydrocarbons along the length of the cable, under normal
pressure, is not possible.
D. When specified, cables shall be flame retardant to reduce risk of fire spread. Cable flame
retardancy shall comply with the applicable IEC publications.
E. When specified, cables shall be fire resistant in accordance with the applicable IEC
publications.
F. Power Cables shall have insulation level adequate for the system category A per IEC
60183, sub-clause 4.2 (where earth faults are cleared as rapidly as possible but in any
case within 1 minute).
G. Cables shall have uniformity in insulation and outer sheath color and be resistant to
hydrocarbons in the soil. The overall jacket shall be PVC.
H. The cable outer protective sheath shall be color-coded depending on the system voltage
as follows:
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 6/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
6.9 kV -Red
13.8 kV -Red
34.5 kV -Red
125VDC -Black
I. Color Coding
b) Multiwire lighting circuits and wire branch circuits connected to the same system
shall conform to the following:
480-277 V 208-120 V
c) All control leads, including those for push-button stations, interlock circuits,
instrument control circuits, current and potential transformer circuits, etc., and
shall be red.
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 7/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
d) Power supplies to/from instruments shall be yellow (live line) and white for the
neutral.
J. Cable cross sectional area, conductor material, number of cores, rated voltage and type
shall be as stated in the Material Requisition.
K. The type of armoring which encases the cable core(s) shall be as follows and shall be as
specified in the MR:
L. The cable insulation voltage in relation to the system voltage shall be as follows:
M. Insulation shall be extruded solid dielectric of one of the types listed below and good for
90 OC rating.
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 8/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
4. CABLE SPECIFICATION
A. In general cables shall be as specified below.
1. Single conductor, XLPE or EPR insulated, armored power cable for cables above
1 kV.
b) The copper tape shield shall be sized based on the fault current
magnitude & duration (refer to IEC 60183 and/or Covenin 200) as
specified in the MR.
2. There conductor, XLPE or EPR insulated, armored power cable for cables above
1 kV.
b) Suitable approved filler shall be utilized to from basis for the inner binder
material. A PVC jacket intermediate sheath shall then be applied with.
wire or double galvanized steel tape armoring, and with an outer PVC
jacket of the color specified in the MR. The ground conductor shall be
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 9/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
sized based on the fault current magnitude & duration (refer to IEC 60183
and/or Covenin 200) as specified in the MR.
1. ARMORED
a) Three conductor XLPE or EPR insulated, armored power cables for 1 kV.
2. NON-ARMORED
c) Three conductor with neutral and ground, XLPE or EPR insulated, non-
armored power cables for 1 kV.
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 10/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
1. NON-ARMORED
a) One or three phase conductor, with neutral and ground, XLPE or EPR or
PVC insulated, non-armored cables for 600V or 750V for lighting and
small power.
2. ARMORED
a) One or three phase conductor, with neutral and ground XLPE or EPR or
PVC insulated, armored cables for 600V or 750V for lighting (external)
and small power.
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 11/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
a) Cable Derating
Cable Ampacity :
Group rating factors for depth of laying (triad and flat formation)
DC Resistance microhm/meter at 25 OC
Outside diameter mm
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 12/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
Note : Rac/Rdc = 1 + Yc + Ys
Capacitance n F/meter
b) Cable Pulling
c) Short circuit and load flow/voltage drop calculations for each cable size at rated
insulation level (75 OC or 90 OC)
6. CABLE IDENTIFICATION
A. The outer surface of each cable shall be durably marked throughout its length with the
manufacturers identification, type of insulation (e.g., XLPE, EPR, PVC etc., in addition to
the manufacturers trade name), size of copper conductor in mm2 (AWG or kcmil), rated
voltage, year of manufacture, insulation thickness, number of cores, nominal cross
sectional area of conductors and progressive length of cable at every meter.
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 13/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
C. The proceeding identifications shall be repeated along the cable at regular intervals. The
cable size mm2 shall be repeated at intervals not exceeding 600 mm. All other markings
shall be repeated at intervals not exceeding one meter.
7. TEMPERATURE RATINGS
A. Highest rated temperatures for the different types of insulating compound shall comply
with IEC 60502, paragraph 1.4.
a) The Seller shall provide certificates for routine tests, type tests and special tests
carried out on cables. Tests shall be those listed in the relevant IEC Publications,
this specification and any additionally specified requirements within the material
requisition.
b) The Buyer reserves the right to witness all tests specified on completed cables.
c) The Seller shall give two weeks notice of test prior to commencement
d) The Buyer reserves the right to inspect all cables at the Sellers works at any time
prior to shipment to prove compliance with the specifications.
e) Cables shall not be shipped unless the test certificates have been approved by
the Buyer
a) Samples of cables shall be checked by the following tests and shall comply with
IEC-60332 requirements:
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 14/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
If temperature at the time of measurement differs from 15.6C, the resistance shall
be corrected to that at 15.6O C, by multiplying the measured value by the proper
correction factor per IEC 60502.
Upon completion of the insulation resistance test, the DC voltage test shall be
made. The test voltage shall be per IEC 60502.
The completed cable shall be tested for type tests and special tests in accordance
with IEC 60502 requirements if specified in the MR.
D. Dimensional Verification
a) Each length of insulated conductor shall be examined to verify that the conductor
is of correct size.
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 15/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
b) Each length of insulated conductor shall be measured to verify that the insulation
wall thickness is of the correct dimension.
c) Each length of completed cable shall be measured to verify that the protective
covering or jacket wall thickness is of the correct dimension.
B. Each end of each length of cable shall be durably sealed before shipment to prevent
entrance of moisture.
C. Reels shall be securely blocked in position so that they will not shift during transit.
D. The Seller shall be responsible for corrosion and any damage to the cable during transit
which in the result of the cable reels not having been properly fastened, sealed, packed
or blocked.
E. The reels shall be lagged or covered with suitable material to provide physical protection
for the cables during transit and during ordinary storage and handling operations.
F. Identification labels shall be attached to the outside of each cable reel flanges. Labels
shall be protected by transparent plastic envelopes or other weather resistant material
and give the following information:
CA04-04-33-P-SP-008_X2.DOC
SINCOR
Sincor Document No: CA04-04-33-P-SP-008
Sincor Interface Code: 0
Project Title: SINCOR, C. A. Sincor Document CLASS: 00
UPSTREAM SURFACE FACILITIES PROJECT Page /File: 16/CA040433PSP008
Rev./Date: X2/ 23 Junio 2006
Manufacturers name
Year of manufacture
B. For the required quantity of drawings, test reports, instruction manuals and spare parts
requirements refer to MR.
C. All electrical symbols on the drawings and diagrams furnished by vendor shall be in
accordance with IEC 60617.