PH-IMS-SP-08-1-FR02
REVISION / ISSUE:00/01
DATE:1/12/2014
Generator Inspection Report
Page | 1 OF 1

Project:CAT 3406 Client: Power House Report NO. GPR 10/2015


Maximum LOAD : 292 KW \ 60 HZ Machine Code: 230 Work order NO: Lifting Certificate NO.
Date of Inspection: 11/1/2015 Fuel type: Diesel Run hours: 15422.4 Hrs.

Engine serial number :2GG01914 Ambient temp : 14.3 C Sound proof N/A CR N/A

Oil Water Battery


Duration
Press Temp.
Exhaust Temp. C
Volt. P.f A1 A2 A3 Hz V KW
load Blowby Boost Exhaust
Min R-L % inch H20 pressure colour
bar C V

10 5.11 57 190 25.2 1 0 0 0 50.8 400 0 0 0.19 8 Normal

10 4.61 77 342 25.2 1 114 114 114 50.7 398 79 27 0.226 23 Normal

10 4.25 78 446 27.1 1 213 213 213 50.7 397 146 50 0.304 51 Normal

10 4.3 81 510 27.1 1 312 312 312 50.3 397 215 73 0.342 87 Normal

10 4 85 570 27.2 1 413 413 413 50 393 281 96 0.456 125 Normal

ENGINE INSTRUMENTS Available Check ALTERNATOR CONTROLS Available Check

High Coolant Temperature P Emergency Stop P P


Oil /Low Oil Pressure P O/U Voltage Fault
Water /Low water Level P O/U Frequency Fault
High Oil Temperature Reverse Power
Exhaust Temp. 3 Start attempts
Fuel Level Overload 110%
Audible Alarm Over speed
Compression Test Records
Cylinder NO: 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16
Pressure (Bar) N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A N/A

VIBRATION RECORDS (VELOCITY MM/S

POINT X Y Z
1 2.6 4.4 5.4
2 21.6 10.7 7
3 3.2 7 7.4
4 6.3 13.1 10.9
5 4.4 5.2 6.1
6 4.7 11 7.6
7 5.8 9.9 7.9
8 8.1
Evaluation:
1- Generator tested till 96 % (413 A ) and 50 % sudden load ( 210 A ) from its full load
2- Generator accepted till 96% from its full load
3- Test done wihtout exhaust muffler

Result:
Accepted

Inspected By Q C DEP Reviewed By Witnessed By

Name: Wagih Abd El Aziz , Said Mahmoud Name: Mohamed Wageh Name: Abd El Rahman

Signature: Wagih Abd El Aziz Signature: Mohamed Wageh Mechanical Dep.

Date : 11/1/2015 Date : 11/1/2015 Date : 11/1/2015