• PH-IMS-SP08-WI1-FR03
REVISION / ISSUE:00/01
Generator Performance Report DATE:6/5/2015
Page | 1 OF 1
Model : Volvo TD710G Client: Power House Report NO.: GPR ( 81-1 ) / 2016
Maximum LOAD : 132 KW \ 50 HZ Machine Code: 15 Work order NO: 219 / 2015
Date of Inspection: 11/5/2016 Fuel type: Diesel Run hours: 18190 Hrs. Lifting Certificate NO.
Engine serial number : 2071108233 Ambient temp : 28 °C Sound proof: No CR code: N/A
10 3.7 80 496 28 1 150 160 145 49.8 402 105 80 0.39 N/A Normal
10 3.7 85 533 28 1 180 175 164 49.5 402 120 91 0.312 N/A Normal
Pressure (Bar)
POINT X Y Z
1 3.1 8.1 7
2 3.1 8 4
4 6.1 11.6 5
Evaluation:
1- Generator test till 91% from its full load & 50% sudden load and all parameters are in the acceptance range.
2- Vibrations of generator are in the acceptance range.
3- No code on the skid of generator.
4- No guard for the fan of belts of radiator and dynamo.
5- The cover of breaker is pending and not working good.
6- Oil leakage from oil plug from the engine.(cleared)
7- Defect on the oil cap of refill.
8- The wiring of control is not systemized and check.(Cleared)
9- Leakage from the elbow after the turbo and the flange of muffler.
10- Defect on the reading of KW is zero.
11- The skid of generator is dirty.
12- The coolant of radiator is very dirty need to drain, flush and refill.
13- No batteries.
14- No cap for the fuel tank.
15- The cover of control module is not fixed.
16- Defect on painting of generator.
Result:
Action
Page 1 of 1