Engine brand Tide Power Alternator brand Tide Power Engine model LR4B5-D Coupling/N° of bearings Direct / Single Bearing Speed control type Mechanical Phase / Poles 3-Phase / 4-Pole Starter motor voltage 12V Power Factor Cos Φ = 0.8 Engine speed (RPM) 1800 AVR Regulation Yes standby power 14.43 Voltage Regulation ± 0.5 % Fuel 100% prime power 13.12 Insulation Class H Consumption (L/H) 75% prime power 11.15 Drip Proof IP23 50% prime power 9.84 Excitation Shunt
Ratings: All three phase generator sets are rated at 0.8 power factor. All single-phase generator sets are rated at 0.8 or 1.0 power factor.
(1) PRP (Prime Power):
Available continuously at variable load in lieu of commercially purchased power for an unlimited number of hours per year accordance with ISO8528-1, and an overload of 10% permitted for one hour in every twelve hours of operation in accordance with ISO 3046-1.
(2) ESP (Standby Power):
Emergency Standby Power in variable load applications in accordance with ISO8528-1 in the event of a utility power failure. No overload available for this service as relevant alternators are peak continuous rated at 27℃. ■ Engine Specification: ■ Standard Configuration
Basic technical data Accesories
No. of cylinders 4 Radiator Cylinder arrangement In-line Oil sensor Cycle 4 stroke Water temperature sensor Injection system Direct Oil drainage pump Aspiration type Naturally Aspirated air filter, oil filter, fuel filter Compression ratio 17:1 Rubber anti-vibration mount Bore 108mm Ground Protection Stroke 135mm AVR Displacement 5.18L Battery charger Governor type Mechanical Maintenance free battery Oil capacity 14L Breaker Coolant capacity-engine 6L Control panel IP42
■ Dimensions ■ Control Panel Function Summary
Dimension and Weight Generator Protection and Functions
Dimension Open Silent Abnormal voltage Length (L) - 2724mm Over current Protection Width (W) - 1150mm Over Frecuency Protection Height (H) - 1420mm Short Circuit Protection Net Weight - 1345Kg Low Oil Pressure Protection Fuel Tank (L) - 310 High Temperature Protection Noise(dB) at 7m N/A - Alternator Charger Remote Start AMF (Auto Main Failure) Fault History Oil Pressure Visualization Water Temperature Visualization Fuel Meter Speed Battery Voltage Runing Hours
Standard reference Conditions:
Note: Standard reference condition 25°C[77°F] air inlet temp, 1000m(328ft) A.S.L 30% relative humidity. Fuel consumption data with diesel fuel with specific gravity of 0.85 and conforming to BS 2869: 1998, Class A2.