Check all battery bank connections and breaker ratings. Ensure the rectifier mode changer switch is in normal mode and battery test mode settings like end voltage, test time, and low and high voltage disconnect settings are correct. Put the rectifier in test mode and monitor cell and bank voltages every 15 minutes for 60-80 minutes, identifying any faulty cells. Stop the test and upload required photos.
Check all battery bank connections and breaker ratings. Ensure the rectifier mode changer switch is in normal mode and battery test mode settings like end voltage, test time, and low and high voltage disconnect settings are correct. Put the rectifier in test mode and monitor cell and bank voltages every 15 minutes for 60-80 minutes, identifying any faulty cells. Stop the test and upload required photos.
Check all battery bank connections and breaker ratings. Ensure the rectifier mode changer switch is in normal mode and battery test mode settings like end voltage, test time, and low and high voltage disconnect settings are correct. Put the rectifier in test mode and monitor cell and bank voltages every 15 minutes for 60-80 minutes, identifying any faulty cells. Stop the test and upload required photos.
NEED TO FOLLOW THE FOLLOWING INSTRUCTION BEFORE TO TEST THE BATTERY BANKS
CHECK ALL THE CONNECTION BETWEEN
BREAKERS TO BATTERY BANKS AND CELL TO CELL ,CHECK RATING OF INSTALLED BRAKERS ,CHECK LLVD AND BLVD BREAKERS AND STATUS OF CCONNECTIONS .
OF
CHECK RECTIFIER MODE CHANGER
SWITCH WHICH SHOULD BE ON 0 MODE OR NORMAL MODE
CHECK BATTERY TEST MODE SETTING ,
LLVD AND BLVD AND CHANGE ACCORDING TO GIVEN REQUIREMENT AND STANDARD
BATTERY TEST MODE SETTINGS
TEST END VOLTAGE :45.2
TEST TIME:120 MINS
LLVD AND BLVD SETTINGS
LLVD: 44 V
BLVD: 43.2 V
AFTER ABOVE STEPS PUT RECTIFIER ON
TEST MODE AND CONTINUE THE TEST ON TERMINAL SITES FOR 60 MINS AND 80 MINS FOR HUBS IN BETWEEN REGISTER THE READING OF EACH CELL AND BANK AFTER EVERY 15 MINS AND SORT THE FAULTY CELLS IF FOUND ANY