Eurovent 2/2 Air Tightness For Installed Duct Testing:

Air Tightness Air leakage limit (fmax)


Class m3/s/m2
A

DW/143: A Practical Guide to Ductwork Leakage Testing

Static Pressure Maximum


Duct Limit Air Air leakage
Pressure Positive Negative Velocity limits
Class Pa Pa m/s l/s/m2
Low-pressure 500 500 10 0.027*pt0.65
Class A
Medium- 1000 750 20 0.009*pt0.65
pressure
Class B
High pressure 2000 750 40 0.003*pt0.65
Class C

Figure 11. Allowable Air Leakage Rates from DW/143