Settings Editor sbef relay.

rsf2 Page 1 of 3

Printed From Reydisp Evolution On 2017/09/12 @ 11:51

File : D:\afsar project\UNITED IRON STEEL\relay file\sbef relay.rsf2

Relay Type : 7SR1101-1xA12-xCA0


Software Revision : 2436H80003R4b-3b#18b2
Boot Block Revision : 2436S81516R7
Configuration : 10w-4g-3i-5o
User Information : 7SR11
Circuit Identifier :
MLFB : 7SR1101-1JA12-1CA0/EE
Serial Number : BF1606511148
Firmware Revision : 2436S81127R4b

SYSTEM CONFIG
System Frequency (50..60) 50Hz
Setting Dependencies (Disabled..Enabled) Enabled
Favourite Meters Timer (Off..60) 60min
Backlight timer (Off..60) 5min
E/F Curr Set Display (xNom..Secondary) xNom
Select Grp Mode (Edge triggered..Level triggered) Edge triggered
Clock Sync. From BI (Disabled..Minutes) Disabled
Operating Mode (Out Of Service..Local Or Remote) Local Or Remote
Disk Activity Symbol (Disabled..Enabled) Disabled
Archiver Blocking Time (0..60) 0.5min
Unexpected Restart Blocking (Disabled..Enabled) Disabled
Setting Password (Password) NONE
Control Password (Password) 340701675
Trip Alert (Disabled..Enabled) Enabled
General Alarm Alert (Disabled..Enabled) Enabled
Relay Identifier (16 Character String) 7SR11
Circuit Identifier (16 Character String)
CT/VT CONFIG
Earth Current Input (1..5) 1A
Earth CT Ratio Prim ( 6 Character String) 3000
Earth CT Ratio Sec (0.2..7) 1
FUNCTION CONFIG
Gn Measured E/F (Enabled..Disabled) Enabled
Gn Restricted E/F (Enabled..Disabled) Disabled
Gn Under Current (Enabled..Disabled) Disabled
Gn Line Check (Enabled..Disabled) Disabled
Gn Trip Cct Supervision (Enabled..Disabled) Disabled
Gn Close Cct Supervis'n (Enabled..Disabled) Disabled
Gn Inrush Detector (Enabled..Disabled) Disabled
Gn CB Counters (Enabled..Disabled) Disabled
CURRENT PROT'N
MEASURED E/F
Gn 50G Measurement (RMS..Fundamental) RMS
Gn 51G Measurement (RMS..Fundamental) RMS
51G-1
Gn 51G-1 Element (Disabled..Enabled) Enabled
Gn 51G-1 Setting (0.05..2.5) 0.2xIn
Gn 51G-1 Char (DTL..ANSI-EI) DTL
Gn 51G-1 Delay (DTL) (0..20) 5s
Gn 51G-1 Min Operate Time (0..20) 0s
Gn 51G-1 Follower DTL (0..20) 0s
Gn 51G-1 Reset ((IEC/ANSI) Decaying..60) 0s
51G-2
Gn 51G-2 Element (Disabled..Enabled) Enabled
Gn 51G-2 Setting (0.05..2.5) 0.2xIn
Gn 51G-2 Char (DTL..ANSI-EI) DTL
Gn 51G-2 Delay (DTL) (0..20) 0.3s
Gn 51G-2 Min Operate Time (0..20) 0s
Gn 51G-2 Follower DTL (0..20) 0s
Gn 51G-2 Reset ((IEC/ANSI) Decaying..60) 0s
50G-1
Gn 50G-1 Element (Disabled..Enabled) Disabled
50G-2
Gn 50G-2 Element (Disabled..Enabled) Disabled
CONTROL & LOGIC
MANUAL CB CONTROL
Gn Close CB Delay (0..900) 10s
Gn Blocked Close Delay (0..600) 5s
Gn Open CB Delay (0..900) 10s