The Performance Test of Unit IV was conducted on 21 May 2016 with blended coal of 57.39 % Indonesian
and 42.61 % of Australian Coal.
6 Loss due to Sensible heat in Ash(Bed and Fly ash) L6 % 0.2 0.18 0.28
Station Heat Rate Comparison with GCV of 4114kcal/kg and 4760 kcal/kg
28-Mar-16 21-May-16
S.No PARAMETERS UOM (Indonesian (Blended
coal) coal)
1 M/S PRESSURE kcal/kwh -5.34 -24.31
2 M/S TEMPERATURE kcal/kwh -1.83 -1.05
3 FLUE GAS TEMP. kcal/kwh 22.37 9.29
4 WET FLUE GAS LOSS kcal/kwh 4.01 1.28
5 R/H TEMPERATURE kcal/kwh 1.15 5.29
6 VACUUM kcal/kwh 2.91 15.86
7 RH SPRAY kcal/kwh 18.87 10.02
8 Feed Water Temperature kcal/kwh 0.27 7.62
9 RADIATION LOSS kcal/kwh 30.04 30.04
10 D.M MAKE UP kcal/kwh 0 0
11 BLOWDOWN LOSS kcal/kwh 0 0
12 MOISTURE IN AIR kcal/kwh 1.17 0.5
13 UNACCOUNTED kcal/kwh 10 10
14 TOTAL LOSSES kcal/kwh 83.62 64.54
15 Actual SHR (2385+total losses) kcal/kwh 2468.62 2449.54
16 Actual SHR (GCVxSp.Coal) kcal/kwh 2686 2613.4
17 Difference in SHR(16-15) kcal/kwh 217.38 163.86
a. There is an improvement of 72.6kcal/kwh with firing of blended coal when compared with Indonesian
coal.
b. Increased losses in Vacuum due to high ambient temperature effect is 12.95 kcal/kwh, otherwise the
SHR would be 2436.59kcal/kwh
c. SHR calculation with heat loss method is 2449.54 kcal/kwh but station heat rate (2613.4kcal/kwh)
by coal loss method is more by 163.86 kcal/kwh. Difference is due to coal feeder measurement
accuracy and coal losses in handling. Average difference should be normally below 50kcal/kwh.
Auxiliary Power Consumption of BTG Data recorded during Internal Performance test
There is a reduction of 0.0.21 % in BTG auxiliary power consumption when blended coal of 4760 kcal/kg is fired when
compared to 4114 kcal/kg coal and optimization of process parameters.