You are on page 1of 14

Spectrum® 760 Message Light

Communication System
System Design Guide
.
Spectrum 760 Message Light Communication System
System Design Guide

System Design Guide


Fill in information below before completing form.

Distributor/Dealer:
Name:______________________________________
Address: ___________________________________
___________________________________________
___________________________________________
Phone:_____________________________________
Fax/email:___________________________________

Installation For:
Name:_____________________________________
Address: ___________________________________
___________________________________________
___________________________________________
Phone:_____________________________________
Fax/email:___________________________________

Project Size

Total Number of
Total Number of Total Number of Room
Pushbutton/Indicator
Control Annunciators Stations
Stations

Please list any special requirements or optional equipment (i.e multiple control
annunciators, etc.):

________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
________________________________________________________________________
Use the System Design Guide in conjunction with the price list (Exhibit B)

. © 2007 Jeron Electronic Systems Inc.


Spectrum 760 Message Light Communication System
System Design Guide

© 2007 Jeron Electronic Systems Inc.


.
ROOM #1 ... ... ROOM #8 COLOR KEY
PATIENT STATION PATIENT STATION RD - P (+28V)
(7620, 7621, 7631) (7620, 7621, 7631)
YL GR R D B K YL GR RD BK
BK - G
GR - DH
YL - DL
PUSHBUTTON/ PUSHBUTTON/
INDICATOR STATION INDICATOR STATION
(7641, 7642, 7643, YL GR R D BK (7641, 7642, 7643, YL G R RD BK
7644) 7644)

2-22 GA. TWISTED PAIR


WEST PENN #651
DOME LIGHT OR EQUIVALENT (NOTE 2) DOME LIGHT

1
(7604, 7606) (7604, 7606)
YL GR R D B K 6270 JUNCTION BOX YL GR R D B K 6270 JUNCTION BOX

6271 PLUG-IN MOUNTING CORD 6271 PLUG-IN MOUNTING CORD

FACTORY FURNISHED 3' CABLE 2-18 GA. TWISTED PAIR


WEST PENN #751
OR EQUIVALENT (NOTE 2)
YL
GR
RD
BK

CONTROL ANNUNCIATOR 6269 WALL PLATE JACK


(7662, 7664) 18 GA.
(NOTE 2) R
NOTES: NOTE 5
JERON
1) REFER TO POWER SUPPLY WORKSHEET TO DETERMINE NUMBER OF
ELECTRONIC SYSTEMS, INC. 1743 W. ROSEHILL DR. CHICAGO, IL. 60660
POWER SUPPLIES REQUIRED FOR SYSTEM. + -
2) SIZE POWER BUS WIRE GAUGE TO ASSURE VOLTAGE DROP BETWEEN POWER P G TITLE SPECTRUM 760 DETAILED WIRING FOR
SUPPLY AND LAST STATION DOES NOT EXCEED 10% OF SUPPLY TERMINAL VOLTAGE. 7690 POWER SUPPLY
(NOTE 1)
REMOTE FIELD EQUIPMENT: ONE POWER
3) WIRE IN ACCORDANCE WITH N.E.C. AND LOCAL CODES FOR CLASS 2 SIGNALS.
SUPPLY
4) MAXIMUM 22 GA. WIRE INTO JUNCTION BOX.
5) USE 3M #558 T-TAP CONNECTORS OR EQUIVALENT TO JOIN 18 GA. AND 22 GA. WIRES
DFX/DFXDWG/766251.DWG
DATE 16 APR 97 BY C.P.
760 Wiring for Remote Equipment: One Power Supply
System Design Guide
Spectrum 760 Message Light Communication System

© 2007 Jeron Electronic Systems Inc.


ROOM #1 .... ... ROOM #8 ROOM #9 .... ... ROOM #16
Supplies

PATIENT STATION PATIENT STATION PATIENT STATION PATIENT STATION


(7620,7621,7631) YL GR RD BK (7620,7621,7631) YL GR RD BK (7620,7621,7631) YL GR RD BK (7620,7621,7631) YL GR RD BK

PUSHBUTTON/ PUSHBUTTON/ PUSHBUTTON/ PUSHBUTTON/


INDICATOR INDICATOR INDICATOR INDICATOR
STATION STATION STATION STATION
YL GR RD BK YL GR RD BK YL GR RD BK YL GR RD BK
(7641,7642, (7641,7642, (7641,7642, (7641,7642,
7643,7644) 7643,7644) 7643, 7644) 7643,7644)

6270 DOME LIGHT


DOME LIGHT DOME LIGHT
(7604,7606) JUNCTION (7604,7606) DOME LIGHT
YL GR RD BK YL GR RD BK (7604, 7606) YL GR RD BK YL GR RD BK
BOX (7604, 7606)
2-22 GA. TWISTED PAIR
WEST PENN #651 6271 PLUG-IN
6269 WALL PLATE JACK OR EQUIVALENT MOUNTING CORD

2
YL
GR
RD
BK 2-18 GA. TWISTED PAIR COLOR KEY
NOTE 5 WEST PENN #751 OR RD - P (28V)
FACTORY 18 GA. EQUIVALENT BK - G
FURNISHED (NOTE 2) G R - DH
3' CABLE YL - DL
+ - + -
P G
P G NOTE 1 R

7690 POWER SUPPLY 7690 POWER SUPPLY JERON


(ROOMS #1 TO #8) (ROOMS #9 TO #16)
CONTROL ELECTRONIC SYSTEMS, INC.
ANNUNCIATOR 1743 W. ROSEHILL DR. CHICAGO, IL. 60660
NOTES: 1) REFER TO POWER SUPPLY WORKSHEET TO DETERMINE NUMBER OF POWER SUPPLIES REQUIRED FOR SYSTEM.
(7662, 7664) TITLE
SPECTRUM 760 DETAILED WIRING FOR
2) SIZE POWER BUS WIRE GAUGE TO ASSURE VOLTAGE DROP BETWEEN POWER SUPPLY AND REMOTE FIELD EQUIPMENT:
LAST STATION DOES NOT EXCEED 10% OF SUPPLY TERMINAL VOLTAGE. TWO POWER SUPPLIES
760 Wiring for Remote Equipment: Two Power

3) MAXIMUM 22 GA. WIRE INTO JUNCTION BOX. DWG. NO. DFX/DFXDWG/766252.DWG


4) WIRE IN ACCORDANCE WITH N.E.C. AND LOCAL CODES FOR CLASS 2 SIGNALS.
5) USE 3M #558 T-TAP CONNECTORS OR EQUIVALENT TO JOIN 18 GA. AND 22 GA. WIRES. DATE 18 APR 97 BY J.G.
System Design Guide

© 2007 Jeron Electronic Systems Inc.


Spectrum 760 Message Light Communication System
.
7690 POWER SUPPLY 7690 POWER SUPPLY
-G G-
+P P+

2-18 GA. TWISTED PAIR WEST PENN #751 OR EQUIVALENT

6270 PLUG-IN
MOUNTING CORD 2-22 GA. TWISTED PAIR
WEST PENN #651
OR EQUIVALENT
DOME LIGHT DOME LIGHT

3
DOME LIGHT DOME LIGHT
(7604,7606) YL GR RD BK (7604,7606) YL GR RD BK 6270 JUNCTION
(7604,7606) YL GR RD BK (7604,7606) YL GR RD BK
BOX
7662 CONTROL 7662 CONTROL
ANNUNCIATOR YL GR RD BK ANNUNCIATOR YL GR RD BK
7662 CONTROL 7662 CONTROL 6269 WALL PLATE
ANNUNCIATOR YL GR RD BK ANNUNCIATOR YL GR RD BK JACK
DOME LIGHT DOME LIGHT
(7604,7606) Y L G R RD B K (7604,7606) Y L G R RD B K COLOR KEY
RD - P (28V) FACTORY FURNISHED
BK - G 3' CABLE
7662 CONTROL 7662 CONTROL
ANNUNCIATOR G R - DH
ANNUNCIATOR YL GR RD BK YL GR RD BK
Y L - DL R

NOTES: JERON
ELECTRONIC SYSTEMS, INC.
1) REFER TO POWER SUPPLY WORKSHEET TO DETERMINE NUMBER OF POWER SUPPLIES REQUIRED FOR SYSTEM. 1743 W. ROSEHILL DR. CHICAGO, IL. 60660
2) SIZE POWER BUS WIRE GAUGE TO ASSURE VOLTAGE DROP BETWEEN POWER SUPPLY AND TITLE
LAST STATION DOES NOT EXCEED 10% OF SUPPLY TERMINAL VOLTAGE. SPECTRUM 760 DETAILED WIRING :SIX
3) MAXIMUM 22 GA. WIRE INTO JUNCTION BOX. CONTROL ANNUNCIATORS W/CORRIDOR
DOME LIGHTS.
4) WIRE IN ACCORDANCE WITH N.E.C. AND LOCAL CODES FOR CLASS 2 SIGNALS. DWG. NO. 766253
5) USE 3M #558 T-TAP CONNECTORS OR EQUIVALENT TO JOIN 18 GA. AND 22 GA. WIRES. DATE 21 APR 97 BY G.J.
760 Wiring for Control Annunicators with Dome Lights
System Design Guide
Spectrum 760 Message Light Communication System

© 2007 Jeron Electronic Systems Inc.


Spectrum 760 Message Light Communication System
System Design Guide

Overview
The Spectrum® 760 Message Light Communication System is used in hospitals
and clinics to provide:

• Staff-Patient Sequencing System: multicolored light annunciators direct


staff members by displaying the present location of the doctor as well as
the location of the next patient and all other patients to be seen by that
doctor.
• Room Status System: room status light annunciation display identifies
available rooms and rooms requiring service.
• Call System: call system allows staff to alert control annunciator of a need
for assistance.

The system is microprocessor-controlled with a basic capacity of 15 rooms and


four color categories. The system is expandable to eight color categories or 30-
room capacity.

Control Annunciators may be located in every room, in a centralized location, or


both. Control Annunciators indicate the status of every room and the location of all
registered staff members.

Pushbutton/Indicator Stations may be located in the corridor or in rooms to report


to the central Control Annunciator. The Corridor Dome/Zone Lights may be used
above rooms or in hallways and call stations may be used in rooms.

System Capacity

Rooms per Control


Total Per System of Total per Room of
Annunciator with
Any Combination of Any Combination of
Any Combination
Control Control
of Control Zone Areas Per
Annunicators, Annunicators,
Annunciators, System
Pushbutton/ Pushbutton/
Pushbutton/
Indicator Stations Indicator Stations
Indicator Stations,
and Call Stations and Call Stations
and Call Stations

128 4 30 32

Corridor Dome/Zone Lights do not count against the maximum four stations per
room or the maximum 128 stations per system.
7621 Call Stations in the non-locking mode do not count against the maximum
four stations per room or the maximum 128 stations per system.

4 © 2007 Jeron Electronic Systems Inc.


Spectrum 760 Message Light Communication System
System Design Guide

Determining the Type of Power Supply


Fill out the worksheet. To determine the number of power supplies needed for the
system, compare the number in Total against the tables below.
Job Name ________________ Date____________

1. Total # Dome/Zone Lights ________ x 7 = ___________

2. Total # 7621, 7631 Stations ________ x 14 = ___________

3. Total # 7641 Room Stations ________ x 14 = ___________


Total # 7642 Room Stations ________ x 21 = ___________
Total # 7643 Room Stations ________ x 28 = ___________
Total # 7644 Room Stations ________ x 35 = ___________

Total # Dome Light Colors (subtotal)


4.
used for Room Status or ________ x 70 = ________
Sequencing
(Subtotal)________ x (Total # Dome/Zone Stations)_______= ___________

(subtotal)
5. Total # Dome Light Colors
________ x 0.2 x 70= ________
used for Room Call
(Subtotal)________ x (Total # Dome/Zone Stations)_______= ___________
Dome/Zones with Audible ________ x 10 = ___________
6.
Total # Master Stations
7.
15 Capacity ________ x 350 = ___________
30 Capacity ________ x 620 = ___________

___________
Total:

#7680 2A Power Supply #7690 3A Power Supply


Minimum Minimum
Total Total
Required Required
0-2000 1 0-3000 1
2001-4000 2 3001-6000 2
4001-6000 3 6001-9000 3
6001-8000 4 9001-12000 4
8001-10000 5 12001-15000 5

. 5 © 2007 Jeron Electronic Systems Inc.


Spectrum 760 Message Light Communication System
System Design Guide

Central Equipment
Control Annunciators
A minimum of one Control Annunciator is required.

7662 Control Annunciator Quantity Unit Price Total Price


Displays the activity of 15 rooms and four color
categories. Furnished with wall jack and three-foot $ $
plug-in cable.

7664 Control Annunciator Quantity Unit Price Total Price


Maximum four color category and 30 room
capacity; or maximum eight color category and 15
$ $
room capacity. Furnished with wall jack and three-
foot plug-in cable.

Power Supplies
A minimum of one Power Supply is required. Refer to “Determining the Type of
Power Supply” on page 5.

7680, Power Supply 2A Quantity Unit Price Total Price


28V@2.0A UL Listed. Refer to “Determining the
$ $
Type of Power Supply” on page 5.

7690, Power Supply 3A Quantity Unit Price Total Price


28V@3.0A UL Listed. Refer to “Determining the
$ $
Type of Power Supply” on page 5.

Pushbutton/Indicator Stations (Addressable Bus


Stations)
Each bus station is furnished with a 6270 Modular Junction Box and 6271 Plug-In
Mounting Cord. All stations mount in dual-gang device boxes with single-gang
cover (Raco 232 2-gang with Raco 772 1-gang trim ring), except 7604/7606
Corridor Dome Lights and Cat. 7605/7607 Zone Lights, which may instead use a
dual-gang, cover. Maximum 4 stations per room (see “System Capacity” on
page 4). For a system exceeding four color categories, double the number of
Corridor Dome/Zone Lights, Pushbutton/Indicator Stations, and Power Supplies
used.

6 © 2007 Jeron Electronic Systems Inc.


Spectrum 760 Message Light Communication System
System Design Guide

7641 Pushbutton/Indicator Station Quantity Unit Price Total Price


Communicates with Control Annunciators and
Dome/Zone Lights. Indicates status of associated
$ $
room. Red pushbutton with integral matching LED
indicator.

7642 Pushbutton/Indicator Station Quantity Unit Price Total Price


Two color coded ABS buttons: red and yellow, each
$ $
with a matching integral LED indicator.

7643 Pushbutton/Indicator Station Quantity Unit Price Total Price


Three color coded ABS buttons: red, yellow, and
$ $
green, each with matching integral LED indicator.

7644 Pushbutton/Indicator Station Quantity Unit Price Total Price


Four color coded ABS buttons: red, yellow, green,
and blue, each with a matching integral LED $ $
indicator.

Dome/Zone Lights
Color and sequence of the bulbs match those of the Control Annunciator and
Pushbutton/Indicator Station.

7604 Corridor Dome Light Quantity Unit Price Total Price


Provides visual call signals above rooms in
$ $
corridors. Red/yellow/green/blue colored bulbs.

7605 Corridor Zone Light Quantity Unit Price Total Price


Provides visual call signals in corridors where
Dome Lights are not visible. Red/yellow/green/blue $ $
colored bulbs.

7606 Corridor Dome Light with


Quantity Unit Price Total Price
Audible
Similar to 7604 except produces a pulsed tone every
three seconds. The tone may be preprogrammed to $ $
pulse when any of the four color bulbs are active.

. 7 © 2007 Jeron Electronic Systems Inc.


Spectrum 760 Message Light Communication System
System Design Guide

7607 Corridor Zone Light with


Quantity Unit Price Total Price
Audible
Similar to 7605 except produces a pulsed tone every
three seconds. The tone may be preprogrammed to $ $
pulse when any of the four color bulbs are active.

Call/Room Stations

7621 Pullcord Call Station Quantity Unit Price Total Price


Used by staff to place calls from patient locations or
bathrooms. Equipped with Pullcord, Cancel $ $
pushbutton, and Call placed LED indicator.

7631 Pushbutton Call Station Quantity Unit Price Total Price


Used by staff to place calls from patient locations or
bathrooms. Equipped with Pushbutton, and Call $ $
placed LED.

Accessories

6160 Wall Bracket Quantity Unit Price Total Price


Used to wall mount the Control Annunciator.
$ $

6269 Wall Plate Jack Quantity Unit Price Total Price


Used with Control Annunciator. Converts the
modular cable to the screw terminal block for
$ $
connection to the main bus. Back box: Raco 232 2-
gang with Raco 772 1-gang trim ring.

6270 Modular Junction Box Quantity Unit Price Total Price


The Cat. 6270 Junction Box, RJ11 to Screw
Terminal, converts a modular RJ11 jack to a two-
place screw terminal block. The Cat. 6270 Junction
Box consists of a cover and block assembly which $ $
has four color-coded screw terminals. Supplied with
all room stations and Dome/Zone Lights. Back box:
Raco 232 2-gang with Raco 772 1-gang trim ring.

6271 Plug-In Mounting Cord Quantity Unit Price Total Price


Connects the room station or Dome/Zone Light to
the Cat. 6270 Junction Box. Supplied with each $ $
6270.

8 © 2007 Jeron Electronic Systems Inc.


Spectrum 760 Message Light Communication System
System Design Guide

Total Price
Total Price

. 9 © 2007 Jeron Electronic Systems Inc.


Spectrum 760 Message Light Communication System
System Design Guide

10 © 2007 Jeron Electronic Systems Inc.

You might also like