3 Shr oud ed Co nduc tor Sys te m Fo r Cr anes / Ho is t

SHROUDED CONDUCTORS El ec tr ic Tro l li es / M a te ri al H and lings Equ ipmen ts


VOLTAGE DROP CALCULATIONS

VO LTAG E DRO P Vd = Voltage Drop in Volts


32 Itotal = Total Current in Amps
Zac = Impedence in Ohms/Mtr
A.C Vd = 3 . . Itotal . Z ac Rdc = Resistance in Ohms/Mtr

42 = Effective Length in Mtrs

D.C Vd = 2 . . Itotal . Rdc L = System length in Mtrs


= Power Feed
= Collector

CONDUCTOR 500A 800A 1000A 500A 800A 1000A


Material Aluminium/SS Copper

Impedence Ohms/M +35 OC .000158 .000145 .000138 .000162 .000138 .000128


DC Resistance Ohms/M +35 OC .000098 .000075 .000052 .000105 .000058 .000035

Po we r Fe ed P os i t i on Schematic Diagram . Collec to r Sym bo l In dica tes Effective


P os i t ion Of M a x imu m V o l ta ge D r o p Length for
voltage drop
calculation

L
E n d Fe ed =L

F or two cr an es ; to ta l
current assumed 900A Vd = 3 . . Itotal . Z ac
W i th 1 000A A lu mi n iu m = 1.73 245 900 .000138
B us bar Bay l en g th 2 45 M trs = 52.6 Volts drop

F or two cr an es ; to ta l
current assumed 900A Vd = 3 . . Itotal . Z ac
W i th 1 000A c op per bus bar = 1.73 245 900 .000128
B a y Len g th 2 45 Mt r s = 48.8 Volts drop

F or o ne c r a ne ; to t al
cu rren t assu me d 10 00A Vd = 3 . . Itotal . Z ac
W i th 1 000A A lu mi n iu m = 1.73 250 1000 .000138
B us bar Bay l en g th 2 50 M trs = 59.7Volts drop

F or o ne c r a ne ; to t al
cu rren t assu me d 10 00A Vd = 3 . . Itotal . Z ac
W i th 1 000A c op per bus bar = 1.73 250 1000 .000128
B a y Len g th 2 50 Mt r s = 55.4 Volts drop

Mfrr : Susheel Engineering Corporation , D-7, GHATKOPAR INDUSTRIAL ESTATE, OFF L.B.S.MARG, GHATKOPAR ( WEST ) MUMBAI -400 086
TEL 0226798 8642, 6796 9715, 2500 7976. FAX 2500 8039 MBL 98201 92091 Email safetrack@vsnl.com , vishu@bom2.vsnl.net.in
3 Shr oud ed Co nduc tor Sys te m Fo r Cr anes / Ho is t
SHROUDED CONDUCTORS El ec tr ic Tro l li es / M a te ri al H and lings Equ ipmen ts
VOLTAGE DROP CALCULATIONS

VO LTAG E DRO P Vd = Voltage Drop in Volts


32 Itotal = Total Current in Amps
Zac = Impedence in Ohms/Mtr
A.C Vd = 3 . . Itotal . Z ac Rdc = Resistance in Ohms/Mtr

42 = Effective Length in Mtrs

D.C Vd = 2 . . Itotal . Rdc L = System length in Mtrs


= Power Feed
= Collector

CONDUCTOR 500A 800A 1000A 500A 800A 1000A


Material Aluminium/SS Copper

Impedence Ohms/M +35 OC .000158 .000145 .000138 .000162 .000138 .000128


DC Resistance Ohms/M +35 OC .000098 .000075 .000052 .000105 .000058 .000035

Po we r Fe ed P os i t i on Schematic Diagram . Collec to r Sym bo l In dica tes Effective


P os i t ion Of M a x imu m V o l ta ge D r o p Length for
voltage drop
calculation

Tw o Powe r F eeds a t L L
6 6
L from eac h end of =L
6 s ys tem
6

F or two cr an es ; to ta l Vd = 3 . . Itotal . Z ac
current assumed 900A
= 1.73 245 900 .000138
W i th 1 000A A lu mi n iu m 6
B us bar Bay l en g th 2 45 M trs = 8.8 Volts drop

F or two cr an es ; to ta l Vd = 3 . . Itotal . Z ac
current assumed 900A
= 1.73 245 900 .000128
W i th 1 000A c op per bus bar 6
B a y Len g th 2 45 Mt r s = 8.15 Volts drop

F or o ne c r a ne ; to t al Vd = 3 . . Itotal . Z ac
cu rren t assu me d 10 00A
= 1.73 250 1000 .000138
W i th 1 000A A lu mi n iu m 6
B us bar Bay l en g th 2 50 M trs = 9.9 Volts drop

F or o ne c r a ne ; to t al Vd = 3 . . Itotal . Z ac
cu rren t assu me d 10 00A
= 1.73 250 1000 .000128
W i th 1 000A c op per bus bar 6
B a y Len g th 2 50 Mt r s = 9.2 Volts drop
Mfrr : Susheel Engineering Corporation , D-7, GHATKOPAR INDUSTRIAL ESTATE, OFF L.B.S.MARG, GHATKOPAR ( WEST ) MUMBAI -400 086
TEL 0226798 8642, 6796 9715, 2500 7976. FAX 2500 8039 MBL 98201 92091 Email safetrack@vsnl.com , vishu@bom2.vsnl.net.in