Project No.:
Tank: Fire Water Tanks
Tank Tag No.
No. of Tanks 2
Tank Minimum Capacity 225 m3
Design Margin on Capacity 8 %
Stored Product Distilate Fuel Oil
S.G (from Data Base) 0.85
Bottom 3 mm
Corrosion mm
Allowance Shell 3
Corrosion
Allowance
Roof 3 mm
Note:
Fill the Price List in the next sheet "Material Price List"
THESE RESULTS ARE VALID AS PRELIMINARY ESTIMATES .AND DOES NOT REPRESENT ACCURATE DESIGN REAULTS , MANY DESIGN FACTORS ARE DISREGARDED FOR THE
OF SIMPLICITY
Note:
User Entry Required , if not entered the sheet can not present results.
Optional User Entry , if not entered the sheet shall assume reasonable values and present results.
Presented Values ,The Value is shown only for user convienince, User is not allowed to edit in this sheet.
The bottom calculations is in the scope of API 650 , Results shall be presented for the tank bottom.
Error , out of scope of API , or beyond limits of this sheet
Enter the project and tank identifications
Do not edit , this value is only presented for convinience , edit or fill the Price list in the
next sheet "Material Price List"
That will only be included in calculating the required height of the tank , to leave a
proper margin for the foam nozzles to be installed .
User can enter a design liquid level (Overflow level) , the sheet also asumes a design
level based on predefined assumption , the larger of the two shall be used in
calculations
If not a contract requirement , Please do not enter a value the sheet shall use
API 650 recommended value , if a vlaue is entered the larger of the two values shall be
used in calculations
RESENT ACCURATE DESIGN REAULTS , MANY DESIGN FACTORS ARE DISREGARDED FOR THE SAKE
Plate Thickness of First Shell Course (mm) Stress in First Shell Course
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
For one tank
Minimum Plate Thickness= 6 mm
26 mm
The maximum height of the 12.2941 m
unstiffened shell
Intermidiate Wind Griders Not Required
A 19 6 6 7 9
B 25 6 7 10 11
C 32 6 9 12 14
D 40 8 11 14 17
E 45 9 13 16 19
Product Stress -3.73388052 MPa
Hydrostatic test Stress 27.18813434 Mpa
Thickness of First Shell course (Product) 6 mm
Thickness of First Shell course (Test) 9 mm
These codes represent in which category the thickness is , this code only for the purpose of this
sheet and have no further indication
Annular Plates
Minimum width 24.896
Number of annular Plates #VALUE!
Design data
Capacity 225 m3
Design Level 6.904 m
Tank Diamater 8.5 m
Shell Height 7.16 m
Corrosion Allowance
Bottom 3 mm
Sheel 3 mm
Roof 3 mm
Bottom Plates
Plate Dimensions Required Weight
Course # (mm x mm x mm) Quantity
t W L # (kg)
- 9 1800 x 11980 7 10664 kg
Roof Plates
Plate Dimensions Required Weight
Course # (mm x mm x mm) Quantity
t W L # (kg)
- 9 1800 x 11980 7 10664 kg
Surface Area
One side surface area , (can be used to estimate
the required quantity of insulation , internal
coating and/or Exterior coating)
Bottom 59 m2
Shell 191 m2
Roof 59 m2
Note:
This BoM Does not include the following :
1- Ma
2- Materials for Manholes , Handholes , Dip Hatches , or any
other openings/Attachments to tank
3- Ma
4- St
5- W
Weld Lines
Horizontal 100 m
Shell
Vertical 16 m
Bottom to Shell Double Fillet Weld 27 m
Roof to Shell Fillet weld 27 m
Lap Weld
Bottom
Butt weld