You are on page 1of 5

HP07 Electrical distribution sy 10/6/03 1:18 PM Page 57

PLANT UTILITIES/HEAT TRANSFER SPECIALREPORT

Electrical distribution system


voltage selection
Use these guidelines to determine the most economical solution
P. LIONETTO, R. BRAMBILLA and G. INVERNIZZI,
FWI-Foster Wheeler Italiana, Milan, Italy

S
electing voltage level of the electrical distribution system and dewaxing). The reason is to change their product mix in
in a large industrial installation is related to several fac- favor of an increased proportion of light products in line with
tors that shall be analyzed from technical and economical market trends.
points of view. The main factor is plant total power demand. When EU environmental regulations did not allow prod-
Usually, the bigger the total plant load, the higher the supply ucts with a sulfur content over 0.250.30 wt% to be burned
voltage. As a consequence, for a plant with high power demand in power stations without flue gas desulfurization fitted, a sharp
(reference figure may be 30 MW) in addition to the 6 kV dis- decline in the high (2.53%) and medium (12%) sulfur fuel
tribution/utilization voltage commonly used to feed large oil market resulted. This has forced refiners to make a sub-
motors, a second voltage level shall be selected as the primary dis- stantial investment to change their product mix or find new
tribution system to distribute the energy to several load cen- outlets for their tar.
ters within the plant. Several options were available and the one that better fitted
To select the most suitable voltage level, it is necessary to com- these requirements is the IGCC, a multiunit complex designed to
pare the various alternative solutions considering the basic require- process the high-sulfur byproducts of the refinery and produce
ments (e.g., fault duty, rating current and maximum allowable electric energy and hydrogen. The solution is globally environ-
voltage drop in normal operating condition and during large mentally beneficial. In fact, control of the combustion emissions
motor startup) and taking into account the standardized equip- is more efficient in an IGCC than in a conventional power station.
ment available on the market. The latter point is important to Electricity is normally delivered to the electrical grid while hydro-
avoid installing special equipment, which would lead to cost gen is returned to refinery to upgrade the refinery oil products.
increases and maintenance problems. The IGCC complex includes the following main units:
A second step of the analysis is relevant to selecting the level for Process unit:
low-voltage (LV) users.  Air separation plant
The most common low voltage used in European industrial  Gasification
plants is 400 V. This level is largely used because it is the same volt-  Syngas treatment and conditioning line
age used for the public electrical distribution network, so that  Gas enrichment
equipment, apparatus and components are readily available. How-  Sulfur recovery with tail gas recycle
ever, adopting a higher voltage level (i.e., 690 V) may present  Hydrogen production.
some advantages, mainly in cost savings. Power island:
These considerations have been extensively analyzed during the Gas turbines
basic design of the electrical system of a new integrated gasifica- Heat recovery steam generators
tion combined cycle (IGCC) plant. It is characterized by a total Steam turbine.
consumption of about 180 MW, 40% of which is fed at the LV Utilities units:
level.  Cooling water
Study targets were to:  Demineralized water system
Select the voltage level for the primary distribution net-  Plant and instrument air system.
work between two possible alternatives (66 kV and 30 kV) The plant under examination is designed to generate a gross
Evaluate the convenience of 690 V with respect to the 400 power of about 900 MW, with a total load demand of about 180
V for the LV distribution/utilization system. MW. Total load demand is split among the following main plant
This article gives a general view of the approach used in the units:
study that may be used for any other installation and presents Combined cycle unit: ~8 MW
several examples related to the considered plant. Gasification unit: ~10 MW
Air separation unit (ASU): ~140 MW
Plant description. In recent years, many refineries world- Utilities: ~20 MW
wide have been reequipped with severe processes, both ther- The air separation unit includes two trains with the following
mal (cooking) and catalytic (hydrocracking, catalytic cracking large motors:
HYDROCARBON PROCESSING JULY 2003
HP07 Electrical distribution sy 10/6/03 1:18 PM Page 58

SPECIALREPORT PLANT UTILITIES/HEAT TRANSFER

TABLE 1. Voltage drop on main distribution busbar TABLE 3. Capital cost comparison between 30-kV and
caused by air and nitrogen compressor startup 66-kV systems
Configuration Voltage drop, %, on distribution bus Components Capital cost, M
Air compressor Nitrogen compressor 30 kV 66 kV
30 kV s.s.s.1 11.9 3.4 SF6 AIS GI MEnc

66 kV s.s.s. 5.6 7.1 Step-down transformers 4.4 3.3 3.3 3.3

30 kV s.e.s.2 12.7 3.6 Main switchgear 1.0 2.5 4.0 1.8


Distribution cables 0.75 1.1 1.1 1.1
66 kV s.e.s. 5.9 7.4
1 2
Total 7.95 9.0 10.5 8.3
s.s.s.= secondary-selective scheme s.e.s. = single-ended scheme

TABLE 2. Load, fault current and power losses for TABLE 4. Area required for main distribution
different voltage levels switchgear installation
Configuration Current, A Fault duty, kA Power losses, kW Solutions Substation dimension, m
Load Rating Expected Rating
30 kV SF6 40  10  4 (h)
66 kV s.s.s. ~870 3,150 ~14 31.5 ~1,150
66 kV AIS 60  20  9.5 (h)
66 kV s.e.s. ~1,750 3,150 ~21.6 31.5 ~1,400
66 kV metal-enclosed 55  10  6 (h)
30 kV s.s.s. ~960 2,500 ~18 31.5 ~1,350
66 kV GIS 40  11  6 (h)
30 kV s.e.s. ~1,920 2,500 ~25 31.5 ~1,800

 Air compressor motor: ~40 MW  Rated continuous current up to: 2,500 A


 Nitrogen compressor motor: ~22 MW  Rated withstand fault current up to: 31.5 kA.
 Oxygen compressor motor: ~6 MW From this, it results:
 Booster compressor motor: ~4 MW With the 30 kV voltage level, total load must be shared
between two main switchgear
Primary distribution system voltage selection Each switchgear shall be supplied by two dedicated distri-
Voltage levels and total load demand. IGCC plant total bution transformers
load supply needs a primary distribution network in addition to Total loads shall be balanced between the two switchgear
the utilization system. A secondary selective scheme shall be (and the relative transformers)
selected for both systems to enhance supply reliability and oper- The ASU users shall be distributed on both switchgear.
ation flexibility of process users. A 100% of circuit redundancy is 66 kV switchgear. Three constructive solutions are available:
therefore ensured.  Conventional air insulated substation (AIS)
Voltage selection for the primary distribution system depends  Metal-enclosed switchgear, air insulated type
on many factors:  Gas insulated metal-enclosed switchgear (GIS).
Maximum power demand (i.e., maximum load current) 66 kV AIS and GIS are available with the following maxi-
Size of standardized manufacturing components mum ratings:
Voltage profile during normal operating conditions and Rated continuous current: up to 3,150 A
large motor starting Rated withstand fault current: up to 31.5 kA.
Maximum fault current The metal-enclosed switchgear has a rated current up to 2,000
Power losses A, with a rated withstand fault current limited to 20 kA. By com-
Capital cost paring these figures with the maximum load currents, the 66 kV
Available room for the substation. voltage level allows supplying total plant load with only one
Based on total power demand, two primary voltage levels can switchgear, fed by two transformers.
be selected for total IGCC load supply: Voltage profile. To ensure correct operation of users, voltage
 66 kV (highest voltage 72.5 kV) profile on the overall distribution network should be kept around
 30 kV (highest voltage 36 kV) the rated value during different possible steady-state operating
The higher the voltage, the lower the load currents, fault cur- conditions. Further, voltage variation during transient condi-
rents and power losses. On the other hand, higher capital cost tions shall not exceed the tolerable limits of user loads as recom-
and larger area shall be expected by using a higher voltage level. mended by EN Code 61000-2-4 (12% of rated voltageClass
Load currents corresponding to the maximum expected plant 3 of EMC compatibility for sudden voltage changes).
power demand are: Due to large motors in the ASU plant, sudden voltage varia-
1,850 A (66 kV) tion caused by motor starting shall be expected throughout the
4,050 A (30 kV). plants electrical system. It is, therefore, necessary to assess voltage
Rating standard components. 30 kV switchgear. Metal-clad drop caused by the large motor starting for both alternatives
switchgear, both air insulated and containing gas-filled (SF6) under examination. Voltage drops caused by ASU large motor
compartments, are available on the market for this voltage level, starting have been evaluated by considering the following sim-
with the following maximum ratings: ulations:
HYDROCARBON PROCESSING JULY 2003
HP07 Electrical distribution sy 10/6/03 1:18 PM Page 59

PLANT UTILITIES/HEAT TRANSFER SPECIALREPORT

TABLE 5. Motor size and number installed in the main TABLE 6. Voltage drop during motor starting
IGCC process units, ASU excluded
400 V 690 V 690 V 690 V
Motor size, kW 5.5 11 30 45 90 160 200 250 Motor rating, kW 200 200 630 800
Motor number 63 38 30 16 24 10 2 8 Cable 2(3  185) 3  240 3(3  240) 4(3  240)
V mot, % 13.9 10.4 14.5 18.2
Motor size, kW 350 500 630 800 1,200 1,400 1,800 2,200
V bus, % 5.3 3.7 8.56 10
Motor number 9 13 2 4 2 3 2 4

 Direct online starting of nitrogen compressor asynchronous Capital costs of the 66-kV solution are about 15% to 40%
motor, via proper captive transformer higher than the 30-kV system, partially compensated by the
 Starting of air compressor synchronous motor, rated about power loss savings. Nevertheless, since the technical reasons play
40 MW, via a two-step autotransformer system (the synchronous a more important role for the best plant design and operation, the
motor is started as asynchronous). 66-kV system is recommended.
Results of voltage drop calculations are reported in Table 1.
From the results, the following can be concluded: Low voltage selection
Voltage drop caused by large motor starting on the 30-kV General considerations. The most common voltage used in
system is about twice that on the 66-kV one; voltage variation European industrial installations to feed LV electrical distribu-
exceeds the immunity limits proper of Class 3 (12%) recom- tion networks is 400 V. The 400-V level is usually boosted in
mended by EN Code for industrial installations. industrial plants to 6,000 V to feed MV users, typically motors.
To reduce voltage variation in the 30-kV system, all ASU Use of these two voltage levels allows installing well-tested stan-
large motors shall be started either via an autotransformer sys- dardized equipment and machinery that can be provided by many
tem, with several tapping steps, or via a soft-start device, solid manufacturers.
state-type, at higher costs and larger space requirement. However, adopting a higher LV level (i.e., 690 V) offers some
Load currents, short circuit levels and power losses. Load advantages that could make this choice quite interesting and con-
current, fault duty and power losses, as listed in Table 2, show venient; main advantages relate to capital cost savings and
that in both cases required performance is well within the rating improved global network efficiency.
of standard industry switchgear. Several key factors must be considered to compare the two
Further, with respect to power losses, a reduction of about alternatives (i.e., 690 V and 400 V):
1520% shall be expected in a 66-kV system. Induction motor size and cost
Capital and operating cost. Comparison of capital costs is Maximum load current and fault duty of switching appa-
reported in Table 3; different types of 66-kV switchgear have ratus available on the market
been compared. Capital cost of the 66-kV solution is from 15% Cable voltage drop during normal operating conditions
(AIS) to 30% (GIS) higher than the 30-kV one. and motor startup
On the other hand, the 66-kV option would imply lower Cable cross-section
power losses on the distribution system. The losses, capitalized Sizing and number of feeding transformers
based on a five-yr period at a fee of 0.0363 per kWh and at a 7% Total power losses.
interest rate, would result in a saving of about 40% (1.39 M These items have been analyzed for the plant with the aim of
for the 66-kV system, 1.61 M for the 30-kV system). verifying the real benefits of using 690 V rather than 400 V. User
Occupied area. Depending on the selected constructive solu- loads related to the IGCC units, ASU excluded, are character-
tions, area required for installing the AIS-type main 66-kV dis- ized by different induction motor sizes (Table 5.)
tribution switchgear is about 200% larger than the correspond- Induction motors. One key point in comparing 400 V and
ing 30-kV solution. It becomes only 20% larger in the GIS 690 V is capital cost of the induction motors. On the European
solution. Table 4 compares the various solutions. market, 690-V motors are available in the 0.181,000 kW range
Selecting distribution system voltage. To sum up, the 66-kV with totally enclosed fan-cooled construction and up to 630 kW
system is the most appropriate selection for the plant because: with EEx-d, EEx-e, Ex-n protection for hazardous areas (EEx-p
 Voltage drops on main distribution busbars, caused by for larger motors).
large motor starting, is limited within 6% Vn, both in normal It is common in industry to use 400 V motors up to 160200
(secondary-selective scheme) and emergency (single-ended kW to keep voltage drop during normal and startup conditions
scheme) operating conditions. within acceptable limits up to a distance of about 200 m; larger
 Maximum load currents are well below the maximum motors are fed at 6,000 V.
equipment rating, with benefits for reducing component aging. In general, capital cost of 690-V motors is the same as 400-V
 Maximum fault currents are around 20 kA, i.e., lower than motors. Capital cost of 6 kV motors is, however, about two to
the switchgear ratings (31.5 kA). Lower fault currents reduce three times higher than the corresponding LV-motor size. From
fault energy, thus reducing potential equipment damage. this, the greater the number of motors that can be fed at 690 V
 Only one main switchgear, a two-section-type, is suffi- instead of 6,000 V, the higher the capital cost savings. Conse-
cient; no load sharing problem exists and easy distribution network quently, it is necessary to establish the upper motor size that can
control is provided. be fed at 690 V.
 Starting large ASU motors can be implemented with sim- Switchboards and switching equipment. LV switchboards are
ple systems (DOL and two-step autotransformer). generally designed, with regard to dielectric withstand, for nom-
HYDROCARBON PROCESSING JULY 2003
HP07 Electrical distribution sy 10/6/03 1:18 PM Page 60

SPECIALREPORT PLANT UTILITIES/HEAT TRANSFER

TABLE 7. Total capital cost of motor feeders up to TABLE 8. Weight of different items on total
800 kW of the entire plant capital cost
Motor size, Total 400-V capital 6,000-V capital 690-V capital Items 400 V6,000 V 690 V6,000 V Cost saving
kW motors cost, M cost, M cost, M M % M % M %
5.5 63 0.100 0.100 Motor feeder
11 38 0.0864 0.0836 total cost 4.395 71.5 3.506 63.7 0.889 20

30 30 0.1291 0.1127 Distribution


net. total cost 1.24 20 1.481 26.8 0.241 20
45 16 0.0947 0.0831
Network losses
90 24 0.2452 0.219 total cost 0.486 8.5 0.520 9.5 0.034 7
160 10 0.1949 0.1712 Total cost 6.121 100 5.507 100 0.614 10
200 2 0.0461 0.040
250 8 0.4076 0.1840
350 9 0.512 0.300 For motors above 200 kW, use of 690 V requires cables with
500 13 0.768 0.510 a larger cross-section than motors of the same size fed at 6,000 V.
630 2 0.132 0.091 Capital and operating costs are, therefore, greater since the con-
800 4 0.316 0.2479 ductor material cost is the most important factor in cable cost.
LV transformers. Use of 690 V instead of 400 V provides the
possibility to increase transformer rated power. Its maximum
inal voltage up to 690 V. Therefore, standard LV switchboards can value is, however, limited by fault current duty on LV switch-
be used either at 400 V or 690 V. On the other hand, short-cir- boards and their switching devices and motor starters. Since 50
cuit breaking and making capacity of circuit breakers, motor kA shall not be exceeded, motor contribution included, LV trans-
starter and any switching devices are strongly de-rated when the former ratings shall not exceed 3.15 MVA, with a short-circuit
operating voltage increases. In general, fault duty capacity of impedance not below 67%.
molded-case and open-air circuit breakers is reduced when used Consequently, since many motors usually fed at 6,000 V shall
at 690 V compared to the corresponding 400-V ratings in the be fed at 690 V, the number of LV transformers will increase
6575% and 1525% ranges, respectively. with respect to those necessary with 400 V. Moreover, if the LV
Moreover, for 690 V, the manufacturers certify motor pro- network is supplied from 6 kV busbars, MV transformer size
tection coordination (i.e., fuses and contractors, molded-case cir- cannot be reduced. Hence, the higher number of 690 V trans-
cuit breakers and contractors, and limitors and contractors) only formers involves an increase in both capital cost and transformer
up to 50 kA and for motor size up to 350 kW. Open-air circuit power losses.
breakers with higher breaking capacity could be used, but they are Upper size of 690-V motors. The upper motor size to be fed
available only for motor starters above 300 kW. Therefore, with at 690 V can be determined by fixing, at motor starting condition,
690 V, the fault level of 50 kA shall not be exceeded; this limita- the same maximum voltage drop accepted for 400 V motors
tion does not exist for 400 V, although a fault duty above 50 kA (maximum 200 kW). Calculations (Table 6) have been carried out
is usually not recommended for good engineering practice. assuming a cable length of 200 m and a motor starting current 6.5
For motor starters, different solutions are possible. Coordi- times the respective rated current. Assumed maximum allowable
nated molded-case circuit breaker and contactor combinations bus voltage drop during motor starting is 10%, with the voltage
are available up to 315 kW and 335 kW, respectively for 400 V at motor terminals not below 80% of rated voltage. From the
and 690 V. In the latter case, the molded-case circuit breaker table, upper limit of the 690-V motor size is about 800 kW.
shall be the current-limiting type, with a capital cost increase of Larger motors shall be fed at 6,000 V.
about 20%. Cost comparison. Capital cost evaluation shall include:
The fuse-contactor combination is cheaper (cost reduction  Motor feeders, complete with motor, cable, motor starter
of about 40% to 20% from low to high ratings) and offers the and switching protective device
most reliable short-circuit protection level also at the highest  LV transformers and transformer feeders
fault duties. Again, the coordination is ensured up to the same lim-  LV switchboards composed of two incomers and one tie-
its of molded-case circuit breakers. breaker (secondary selective scheme).
For motor sizes above 355 kW, motorized open-air circuit Motor feeder capital cost. The cost of 400-V, 690-V and 6,000-
breakers shall be used for 690 V. V motor feeders are shown in Table 7, referring to the entire
Cables. LV cables, rated 0.6/1 kV, can be used either for 400 plant. The combination of fuse and contactor has been considered
V or 690 V without affecting insulation withstand. With respect for 400-V and 6,000-V motors up to 1,200 kW. The same
to cable ampacity, use of 690 V motors involving lower load arrangement has been taken into account for 690 V for motor
currents than 400 V motors, makes possible reducing both con- ratings up to 250 kW; an open-air circuit breaker is used for the
ductor cross-section (at the same voltage drop) and cable power higher size.
losses or, at the same conductor cross-section, feed motors located Transformer feeders. To compare the two choices (i.e., 400
at longer distances. V and 690 V), determine the number of LV and MV trans-
Reduced cross-section is true for motor ratings above 5.5 kW, formers required to feed the total load. The number of trans-
since for smaller motors cable cross-section is determined, both formers is calculated based on the criteria that each process unit
for 400 and 690 V, by the maximum let-through energy. is fed by a proper load center and that the electrical system is
HYDROCARBON PROCESSING JULY 2003
HP07 Electrical distribution sy 10/6/03 1:18 PM Page 62

SPECIALREPORT PLANT UTILITIES/HEAT TRANSFER

arranged, for reliability reasons, according to the secondary


selective scheme.
Due to the limitation on fault duty, the 690-V solution requires Pierfranco Lionetto is manager of electrical engineering
more transformers than the 400-V solution. Hence, cost of the dis- for power plants with FWI-Foster Wheeler Italiana, Milan, Italy. Prior
tribution network, i.e., transformer feeders and switchboards, is to Foster Wheeler he worked for Centro Elettrotecnico Speriman-
tale Italiano in Milan. Mr. Lionetto holds a degree in electrical engineering from the
higher for 690 V than for 400 V (Table 8). University of Padova. He is a member of the Italian Electrotechnical Committee, Ital-
Overall capital cost. Overall capital cost for the two solutions ian Institution of Electrical and Electronic Engineers, the International Conference
is compared in Table 8. The lower motor feeder costs allow achiev- on Large High-Voltage Electric Systems and the Institute of Electrical and Electronic
ing a total cost saving of 10% by using 690 V instead of 400 V, Engineers. Mr. Lionetto is also the author of several technical papers.

even though the distribution network and power loss costs are
higher. Therefore, the greater the number of motors in the
250800 kW size range, the greater the savings.
As a general rule, with a large number of motors in the
Roberto Brambilla is chief electrical engineer for FWI-Foster
200800 kW size range, the 690-V solution should be recom- Wheeler Italiana, Milan, Italy. Prior to Foster Wheeler he was an
mended. HP electrical systems engineer for PIRELLI Cavi S.p.A. Mr. Brambilla
holds a degree in electrical engineering from Politecnico Di Milano.
BIBLIOGRAPHY
IEEE Std. 141-1993, Recommended Practice for Electric Power Distribution in Industrial
Plant.
IEEE Std. 666-1991, Design Guide for Electric Power Service System for Generating Sta-
tions.
Lionetto, P. F., A. Cerretti, G. Rizzi, B. Savasta and E. Mizia, Study of a New Electrical
Distribution Network as a Consequence of a Very Large Load Increase in an Oil-Refinery
Plant, CIRED, London,1989. Giuliana Invernizzi is an electrical engineer with FWI-Fos-
Gambirasio, D., P. F. Lionetto and F. Tommazzolli, Co-ordinated Design of Industrial Elec- ter Wheeler Italiana, Milan, Italy. She holds a degree in electrical
trical Network and its Protection System, LElettrotecnica, LXXVII, 33444 (Italian), engineering from the Universita degli Studi of Pavia and is a mem-
1990. ber of the Italian Electrotechnical Committee. Ms. Invernizzi is also coauthor of sev-
eral technical papers.

Article copyright 2003 by Gulf Publishing Company. All rights reserved. Printed in U.S.A.

You might also like