Professional Documents
Culture Documents
Electrical Distribution System Voltage Selection PDF
Electrical Distribution System Voltage Selection PDF
S
electing voltage level of the electrical distribution system and dewaxing). The reason is to change their product mix in
in a large industrial installation is related to several fac- favor of an increased proportion of light products in line with
tors that shall be analyzed from technical and economical market trends.
points of view. The main factor is plant total power demand. When EU environmental regulations did not allow prod-
Usually, the bigger the total plant load, the higher the supply ucts with a sulfur content over 0.250.30 wt% to be burned
voltage. As a consequence, for a plant with high power demand in power stations without flue gas desulfurization fitted, a sharp
(reference figure may be 30 MW) in addition to the 6 kV dis- decline in the high (2.53%) and medium (12%) sulfur fuel
tribution/utilization voltage commonly used to feed large oil market resulted. This has forced refiners to make a sub-
motors, a second voltage level shall be selected as the primary dis- stantial investment to change their product mix or find new
tribution system to distribute the energy to several load cen- outlets for their tar.
ters within the plant. Several options were available and the one that better fitted
To select the most suitable voltage level, it is necessary to com- these requirements is the IGCC, a multiunit complex designed to
pare the various alternative solutions considering the basic require- process the high-sulfur byproducts of the refinery and produce
ments (e.g., fault duty, rating current and maximum allowable electric energy and hydrogen. The solution is globally environ-
voltage drop in normal operating condition and during large mentally beneficial. In fact, control of the combustion emissions
motor startup) and taking into account the standardized equip- is more efficient in an IGCC than in a conventional power station.
ment available on the market. The latter point is important to Electricity is normally delivered to the electrical grid while hydro-
avoid installing special equipment, which would lead to cost gen is returned to refinery to upgrade the refinery oil products.
increases and maintenance problems. The IGCC complex includes the following main units:
A second step of the analysis is relevant to selecting the level for Process unit:
low-voltage (LV) users. Air separation plant
The most common low voltage used in European industrial Gasification
plants is 400 V. This level is largely used because it is the same volt- Syngas treatment and conditioning line
age used for the public electrical distribution network, so that Gas enrichment
equipment, apparatus and components are readily available. How- Sulfur recovery with tail gas recycle
ever, adopting a higher voltage level (i.e., 690 V) may present Hydrogen production.
some advantages, mainly in cost savings. Power island:
These considerations have been extensively analyzed during the Gas turbines
basic design of the electrical system of a new integrated gasifica- Heat recovery steam generators
tion combined cycle (IGCC) plant. It is characterized by a total Steam turbine.
consumption of about 180 MW, 40% of which is fed at the LV Utilities units:
level. Cooling water
Study targets were to: Demineralized water system
Select the voltage level for the primary distribution net- Plant and instrument air system.
work between two possible alternatives (66 kV and 30 kV) The plant under examination is designed to generate a gross
Evaluate the convenience of 690 V with respect to the 400 power of about 900 MW, with a total load demand of about 180
V for the LV distribution/utilization system. MW. Total load demand is split among the following main plant
This article gives a general view of the approach used in the units:
study that may be used for any other installation and presents Combined cycle unit: ~8 MW
several examples related to the considered plant. Gasification unit: ~10 MW
Air separation unit (ASU): ~140 MW
Plant description. In recent years, many refineries world- Utilities: ~20 MW
wide have been reequipped with severe processes, both ther- The air separation unit includes two trains with the following
mal (cooking) and catalytic (hydrocracking, catalytic cracking large motors:
HYDROCARBON PROCESSING JULY 2003
HP07 Electrical distribution sy 10/6/03 1:18 PM Page 58
TABLE 1. Voltage drop on main distribution busbar TABLE 3. Capital cost comparison between 30-kV and
caused by air and nitrogen compressor startup 66-kV systems
Configuration Voltage drop, %, on distribution bus Components Capital cost, M
Air compressor Nitrogen compressor 30 kV 66 kV
30 kV s.s.s.1 11.9 3.4 SF6 AIS GI MEnc
TABLE 2. Load, fault current and power losses for TABLE 4. Area required for main distribution
different voltage levels switchgear installation
Configuration Current, A Fault duty, kA Power losses, kW Solutions Substation dimension, m
Load Rating Expected Rating
30 kV SF6 40 10 4 (h)
66 kV s.s.s. ~870 3,150 ~14 31.5 ~1,150
66 kV AIS 60 20 9.5 (h)
66 kV s.e.s. ~1,750 3,150 ~21.6 31.5 ~1,400
66 kV metal-enclosed 55 10 6 (h)
30 kV s.s.s. ~960 2,500 ~18 31.5 ~1,350
66 kV GIS 40 11 6 (h)
30 kV s.e.s. ~1,920 2,500 ~25 31.5 ~1,800
TABLE 5. Motor size and number installed in the main TABLE 6. Voltage drop during motor starting
IGCC process units, ASU excluded
400 V 690 V 690 V 690 V
Motor size, kW 5.5 11 30 45 90 160 200 250 Motor rating, kW 200 200 630 800
Motor number 63 38 30 16 24 10 2 8 Cable 2(3 185) 3 240 3(3 240) 4(3 240)
V mot, % 13.9 10.4 14.5 18.2
Motor size, kW 350 500 630 800 1,200 1,400 1,800 2,200
V bus, % 5.3 3.7 8.56 10
Motor number 9 13 2 4 2 3 2 4
Direct online starting of nitrogen compressor asynchronous Capital costs of the 66-kV solution are about 15% to 40%
motor, via proper captive transformer higher than the 30-kV system, partially compensated by the
Starting of air compressor synchronous motor, rated about power loss savings. Nevertheless, since the technical reasons play
40 MW, via a two-step autotransformer system (the synchronous a more important role for the best plant design and operation, the
motor is started as asynchronous). 66-kV system is recommended.
Results of voltage drop calculations are reported in Table 1.
From the results, the following can be concluded: Low voltage selection
Voltage drop caused by large motor starting on the 30-kV General considerations. The most common voltage used in
system is about twice that on the 66-kV one; voltage variation European industrial installations to feed LV electrical distribu-
exceeds the immunity limits proper of Class 3 (12%) recom- tion networks is 400 V. The 400-V level is usually boosted in
mended by EN Code for industrial installations. industrial plants to 6,000 V to feed MV users, typically motors.
To reduce voltage variation in the 30-kV system, all ASU Use of these two voltage levels allows installing well-tested stan-
large motors shall be started either via an autotransformer sys- dardized equipment and machinery that can be provided by many
tem, with several tapping steps, or via a soft-start device, solid manufacturers.
state-type, at higher costs and larger space requirement. However, adopting a higher LV level (i.e., 690 V) offers some
Load currents, short circuit levels and power losses. Load advantages that could make this choice quite interesting and con-
current, fault duty and power losses, as listed in Table 2, show venient; main advantages relate to capital cost savings and
that in both cases required performance is well within the rating improved global network efficiency.
of standard industry switchgear. Several key factors must be considered to compare the two
Further, with respect to power losses, a reduction of about alternatives (i.e., 690 V and 400 V):
1520% shall be expected in a 66-kV system. Induction motor size and cost
Capital and operating cost. Comparison of capital costs is Maximum load current and fault duty of switching appa-
reported in Table 3; different types of 66-kV switchgear have ratus available on the market
been compared. Capital cost of the 66-kV solution is from 15% Cable voltage drop during normal operating conditions
(AIS) to 30% (GIS) higher than the 30-kV one. and motor startup
On the other hand, the 66-kV option would imply lower Cable cross-section
power losses on the distribution system. The losses, capitalized Sizing and number of feeding transformers
based on a five-yr period at a fee of 0.0363 per kWh and at a 7% Total power losses.
interest rate, would result in a saving of about 40% (1.39 M These items have been analyzed for the plant with the aim of
for the 66-kV system, 1.61 M for the 30-kV system). verifying the real benefits of using 690 V rather than 400 V. User
Occupied area. Depending on the selected constructive solu- loads related to the IGCC units, ASU excluded, are character-
tions, area required for installing the AIS-type main 66-kV dis- ized by different induction motor sizes (Table 5.)
tribution switchgear is about 200% larger than the correspond- Induction motors. One key point in comparing 400 V and
ing 30-kV solution. It becomes only 20% larger in the GIS 690 V is capital cost of the induction motors. On the European
solution. Table 4 compares the various solutions. market, 690-V motors are available in the 0.181,000 kW range
Selecting distribution system voltage. To sum up, the 66-kV with totally enclosed fan-cooled construction and up to 630 kW
system is the most appropriate selection for the plant because: with EEx-d, EEx-e, Ex-n protection for hazardous areas (EEx-p
Voltage drops on main distribution busbars, caused by for larger motors).
large motor starting, is limited within 6% Vn, both in normal It is common in industry to use 400 V motors up to 160200
(secondary-selective scheme) and emergency (single-ended kW to keep voltage drop during normal and startup conditions
scheme) operating conditions. within acceptable limits up to a distance of about 200 m; larger
Maximum load currents are well below the maximum motors are fed at 6,000 V.
equipment rating, with benefits for reducing component aging. In general, capital cost of 690-V motors is the same as 400-V
Maximum fault currents are around 20 kA, i.e., lower than motors. Capital cost of 6 kV motors is, however, about two to
the switchgear ratings (31.5 kA). Lower fault currents reduce three times higher than the corresponding LV-motor size. From
fault energy, thus reducing potential equipment damage. this, the greater the number of motors that can be fed at 690 V
Only one main switchgear, a two-section-type, is suffi- instead of 6,000 V, the higher the capital cost savings. Conse-
cient; no load sharing problem exists and easy distribution network quently, it is necessary to establish the upper motor size that can
control is provided. be fed at 690 V.
Starting large ASU motors can be implemented with sim- Switchboards and switching equipment. LV switchboards are
ple systems (DOL and two-step autotransformer). generally designed, with regard to dielectric withstand, for nom-
HYDROCARBON PROCESSING JULY 2003
HP07 Electrical distribution sy 10/6/03 1:18 PM Page 60
TABLE 7. Total capital cost of motor feeders up to TABLE 8. Weight of different items on total
800 kW of the entire plant capital cost
Motor size, Total 400-V capital 6,000-V capital 690-V capital Items 400 V6,000 V 690 V6,000 V Cost saving
kW motors cost, M cost, M cost, M M % M % M %
5.5 63 0.100 0.100 Motor feeder
11 38 0.0864 0.0836 total cost 4.395 71.5 3.506 63.7 0.889 20
even though the distribution network and power loss costs are
higher. Therefore, the greater the number of motors in the
250800 kW size range, the greater the savings.
As a general rule, with a large number of motors in the
Roberto Brambilla is chief electrical engineer for FWI-Foster
200800 kW size range, the 690-V solution should be recom- Wheeler Italiana, Milan, Italy. Prior to Foster Wheeler he was an
mended. HP electrical systems engineer for PIRELLI Cavi S.p.A. Mr. Brambilla
holds a degree in electrical engineering from Politecnico Di Milano.
BIBLIOGRAPHY
IEEE Std. 141-1993, Recommended Practice for Electric Power Distribution in Industrial
Plant.
IEEE Std. 666-1991, Design Guide for Electric Power Service System for Generating Sta-
tions.
Lionetto, P. F., A. Cerretti, G. Rizzi, B. Savasta and E. Mizia, Study of a New Electrical
Distribution Network as a Consequence of a Very Large Load Increase in an Oil-Refinery
Plant, CIRED, London,1989. Giuliana Invernizzi is an electrical engineer with FWI-Fos-
Gambirasio, D., P. F. Lionetto and F. Tommazzolli, Co-ordinated Design of Industrial Elec- ter Wheeler Italiana, Milan, Italy. She holds a degree in electrical
trical Network and its Protection System, LElettrotecnica, LXXVII, 33444 (Italian), engineering from the Universita degli Studi of Pavia and is a mem-
1990. ber of the Italian Electrotechnical Committee. Ms. Invernizzi is also coauthor of sev-
eral technical papers.
Article copyright 2003 by Gulf Publishing Company. All rights reserved. Printed in U.S.A.