Professional Documents
Culture Documents
The power (or load) center can be considered to be a portable substation. It transforms
the distribution voltage to utilization levels and provides protection for each outgoing
circuit. Like the substation, typical components include the transformer, switches, and
protection equipment. Additional details on substations, switchhouses, and power
centers are given later in this chapter.
Several basic distribution arrangements are utilized for the mining industry, and
selection of a particular one is a function of need, cost, and mining method. For this
overview, only the most widely used arrangements will be discussed, including the
radial, expanded radial, primary selective, and primary loop systems.
(1) The radial system is the simplest and least expensive topology. There is one
substation and electricity is distributed throughout the mine at utilization levels.
Switchhouses are used to disconnect and distribute power to loads. A disadvantage of
the radial system is the lack of redundancy (i.e., a failure at the substation will result in
loss of service throughout the mine). Another disadvantage is high line loss and poor
voltage regulation because electricity is distributed throughout the mine at utilization
levels (IEEE 141-1993). The radial system is typically not used in the modern mining
industry but provides a conceptual foundation for other distribution systems that will be
discussed.
5. Mine Electrical Power
OVERVIEW OF MINE POWER SYSTEMS
Distribution Arrangements
(2) The expanded radial system (Figure 5.3) also has a single source and substation, but
unlike the radial system, electricity is distributed at voltage levels that are higher than
utilization voltages. Power (or load) centers are used to reduce voltages from
distribution to utilization levels. Compared with the radial system, the expanded radial
system has the advantage of distributing electricity at higher voltage levels, thereby
reducing losses and permitting the use of smaller distribution cables. However, like the
radial system, the loss of the substation will result in loss of service throughout the mine
(IEEE 141-1993). The majority of surface and underground coal mines use the
expanded radial system.
By far, the majority of coal mine electrical loads are alternating current (AC). Some
direct current (DC) trolley systems and a significant number of battery-powered
vehicles are in use in today’s mines; however, many of them actually use AC drive
systems. For example, the Joy battery hauler uses an inverter to convert DC to AC
in conjunction with an AC variable frequency drive (AC-VFD) system (a DC drive
system is also available). The Phillips Freedom Car is a battery-powered shuttle car,
also with an AC-VFD system. Therefore, although there is some DC equipment in
coal mines, the emphasis in this chapter will be on AC power systems and modeling
AC loads. It is assumed that the reader is familiar with basic DC and AC circuit
analysis techniques; however, a brief review of some of the more commonly used
AC circuit analysis techniques and also AC power are provided in this section.
5. Mine Electrical Power
MINE CABLES
Mine power cables carry electricity from the substation to the electrical loads. As
such, cables are an integral part of the distribution and utilization systems.
Probably no other industry subjects cables to the wide range of conditions as does
the mining industry. In many cases, cables are connected directly to mobile
equipment and are subjected to harsh mining conditions such as extreme
temperatures, abrasion, flexure, tension, and so forth.
(1) Cable Types
There are several cable types, and the type selected depends on the application. For
example, some utilization cables that are connected to portable or mobile mining
equipment are moved very frequently and subjected to physical stress. Other cables
supply power to equipment such as shuttle cars or roof bolters that have cable reels
to automatically wind and unwind the cable. These cables must be flexible and able
to withstand the mechanical and thermal stresses associated with being wound onto
a reel. Distribution cables may be moved infrequently and not subjected to much
physical stress; however, these cables are subjected to higher voltage stress
compared with utilization cables. Finally, some cables are suspended vertically in a
borehole while others are exposed to extreme temperatures and/or ultraviolet (UV)
radiation. Three broad categories of cables are:
5. Mine Electrical Power
MINE CABLES
(3) Conductors
Conductors are the current-carrying component of a cable. Conductors include the
power conductors, grounding conductors, and, in some cables, a ground-check
conductor. Conductors may be copper or aluminum. Copper has higher conductivity
and is more flexible than aluminum, but it is also heavier and more expensive. Each
conductor is composed of numerous small wires bound together in strands to improve
conductor flexibility.
(4) Insulation
Insulation is used to separate conductors and keep current within its intended path.
Insulation surrounds each power conductor and also the groundcheck conductor, if
present in a cable. Grounding conductors are generally not insulated. Insulation must
withstand electrical, physical, and thermal stresses, and be relatively flexible for
certain applications.
5. Mine Electrical Power
MINE CABLES
(5) Shielding
In general, shielding helps to reduce voltage stress on the insulation and confine the
electric field to the insulation. Two types of shielding are used in cables. The first is
called the conductor (or strand) shield. The strand shield surrounds the conductor and
is firmly bonded to the insulation. Its purpose is to reduce or eliminate the voltage
stress in any voids that may be between the conductor and insulation.
The second type of shielding is the insulation shield. For situations where the
insulation shield is placed directly over the conductor insulation, it serves to confine
the electric field to the conductor insulation. The conductor shield also serves to
produce a symmetrical and radial voltage stress within the insulation, which reduces
the possibility of partial discharges.
(4) Fuses
Fuses are the oldest and simplest devices for sensing overloads or shorts circuits and
opening a circuit. Because fuses can be constructed with a wide variety of time-
current characteristics, they can be applied in many special situations. However, one
disadvantage of a fuse is that it is a one-shot device (i.e., when a fuse blows, it must
be replaced). For this reason, fuses are used primarily for transformer protection in
mining applications (see fuse location in Figure 5.27). Fuses are ideal for this
application because they are excellent at limiting the energy tothe transformer during
a short circuit, thereby limiting thermal and mechanical stress on the transformer
caused by high fault current.
Disconnect switches are used on the input and output primary and secondary to
disconnect power to or from the substation. Disconnect switches are constructed to
provide visual assurance that the circuit or device is disconnected from the source.
This visual assurance is essential to the safety of maintenance personnel who may be
working on substation components.
5. Mine Electrical Power
SUBSTATIONS
35kV
(6) Surge Arresters
Surge arresters are used to protect equipment from voltage transients due to
switching and lightning. They are connected from line to ground and exhibit high
resistance to normal operating voltages but low resistance to high voltages. This
characteristic causes surge arresters to divert abnormal surges to ground and
protect equipment from damaging voltages.
Surge arresters may be either gapped arresters with resistors made of silicon
carbide or metal oxide arresters without gaps. The silicon carbide arresters have an
air gap (or a series of gaps) in series with the silicon carbide. There is also a shunt
resistorconnected in parallel with each gap. During an overvoltage, the gaps spark
over and current is conducted through the silicon carbide. Silicon carbide arresters
are (reportedly) susceptible to moisture entry that can contaminate the gaps,
causing the arrester to fail because it sparks over at reduced voltage levels. Metal
oxide arresters use zinc oxide blocks with no gaps. It is believed that the failure
rate of metal oxide arresters is lower compared with silicon carbide arresters
because of the absence of spark gaps. Although there are many silicon carbide
arresters in service, most new applications utilize metal oxide arresters.
5. Mine Electrical Power
SUBSTATIONS
(7) Ground Beds and Neutral Grounding Resistor
The ground bed establishes the earth as the ground reference and the neutral
grounding resistor limits the fault current during a ground fault. A detailed description
of the ground bed(s) and neutral grounding resistor (NGR) are given later in the
“Grounding” section of this chapter.
(8) SWITCHHOUSES
A switchhouse is used to provide protective relaying to the distribution system and to
allow the system to branch. Switchhouses are typically single, double, or triple. As the
names imply, a single switchhouse has one protected outgoing circuit, whereas double
and triple switchhouses have two and three protected outgoing circuits, respectively.
Switchhouses with more than three protected outgoing circuits exist, but because of
space limitations underground, the use of switchhouses with more than three protected
outgoing circuits is probably limited to surface mines. In addition to the protected
circuits, it is common for a switchhouse to have a feed-through circuit, which is an
unprotected outgoing circuit, essentially a continuation of the incoming circuit.
5. Mine Electrical Power
SUBSTATIONS
(8) SWITCHHOUSES
(8) SWITCHHOUSES
(3) Fuses
As with a substation, fuses are used principally to protect the transformer. Fuse
selection is primarily based on having the fuse blow before damaging levels of fault
current flow but still permit transformer inrush currents without damaging the fuse
element. Based on these considerations, fuses should be able to withstand 12 times
the transformer rated current for 0.10 seconds without any element damage. In
addition, the fuse element should also be able to withstand 25 times the transformer
rated current for one half cycle without damage.
5. Mine Electrical Power
POWER CENTERS
(4) Surge Arresters
Surge arresters are typically located at the transformer primary terminals to protect
the transformer from damaging surges. Unlike surge arresters at the substation,
however, power center surge arresters. are connected from the power conductors to
the frame of the power center instead of the station ground bed. Surge arrester
selection is primarily based on the transformer basic impulse insulation level (BIL),
which is the transformer’s ability to withstand a voltage surge without damage. BIL
is referenced to a transient voltage that reaches its peak in 1.5 μs and decays to one
half of its peak value in 40 μs. (This characteristic is typical of the shape of surges
caused by lightning or switching.) The surge arrester should spark over well below
the transformer BIL to protect the transformer.
(5) Transformer
Power center transformers are typically dry-type transformers, unlike the oil-filled
transformers usually found in substations. Dry-type transformers used in power
centers are almost exclusively air cooled (although some may be sealed, gas-filled
units). The transformers may be two- or three-winding transformers. Three-winding
transformers are built to provide two utilization voltages and are common in
underground coal mining applications. For example, a typical power center may have
a 12,470-V primary, a 995-V (or 2,400-V) secondary for the continuous miner, and a
480-V tertiary for other equipment.
5. Mine Electrical Power
POWER CENTERS (6) Neutral Grounding Resistor
(5) Transformer The neutral grounding resistor is used to limit fault
current during a ground fault. A detailed discussion
of the neutral grounding resistor is given later in the
“Grounding” section of this chapter.
Molded-case circuit breakers are normally used to protect each outgoing circuit.
Unlike oil-filled or vacuum breakers, molded-case circuit breakers have their
contacts in air and they must extinguish the arc that forms when the breaker contacts
separate. This is done through the use of specially designed arc chutes that break the
arc into a series of smaller arcs that are lengthened and cooled to extinguish the arc.
Figure 5.34 shows arc chutes in a circuit breaker.
The molded-case breakers often have both overload and short-circuit elements in
them instead of having separate relays that send a trip signal to the circuit breaker.
Short-circuit protection is achieved by having a solenoid in series with the load
current. The circuit breaker contacts are held closed by a latch; and when the latch is
released, the contacts open rapidly by spring action. When a short occurs, the high
current increases the magnetic pull of the solenoid, causing the latch to be released
and opening the circuit breaker contacts.
Each outgoing circuit also has ground-fault protection provided by a zero-
sequence relay. When a ground fault occurs and is detected, the zerosequence relay
sends a trip signal to the molded-case breaker. Ground wire monitoring is also
included on each outgoing circuit, as described later in the “Grounding” section.
Figure 5.35 shows two underground power centers.
5. Mine Electrical Power
POWER CENTERS
Although not listed by the NEC, another important purpose of grounding is to reduce
electrical noise that can interfere with electronic equipment. Poor grounding practices could
affect communication and automation equipment.
An important function of equipment grounding is to maintain all metal equipment frames
at, or near, ground potential to minimize shock hazards to mine personnel. If done properly,
equipment will also be protected.
5. Mine Electrical Power
GROUNDING
Adequate grounding has historically been difficult to achieve in the mining industry.
Problems arise because the mine is constantly expanding; therefore, the equipment
must be moved frequently. In addition, much of the mining machinery is portable,
making it difficult to establish a suitable ground near each machine. This situation is
further complicated because mine personnel are required to regularly come in
contact with portable machinery, thereby increasing shock hazards. Because of these
shock hazards and the difficulties in trying to establish local ground beds, the U.S.
Bureau of Mines recommended, in 1916, that the frames of mining equipment be
connected to a permanent ground bed located near the main substation.
The most important factor in establishing an adequate ground bed is the soil
resistivity. Because of its importance to ground beds, resistivity will be briefly
reviewed before discussing ground bed design.
5. Mine Electrical Power GROUNDING
Thank You !
49
02:09:52 AM 49