INTECONT PLUS
Solids Flow Meter
Operating Manual
BV-H2219 GB
Contacts, Copyright

Sales: Tel.: +49 (0)6151 32 - 10 28


Email: sales.process@schenck.net

Service: 24h Emergency hotline: +49 (0) 172 - 650 17 00 Discontinuous Weighing Technology
+49 (0) 171 - 255 11 95 Continuous Weighing Technology
Email: service.process@schenck.net

Business Segments:

Heavy Duty Weighing & Feeding


Service Tel.: +49 (0) 61 51 32 - 26 23
Service Fax: +49 (0) 61 51 32 - 32 70
E-Mail: bvh.process@schenck.net

Light Duty Weighing & Feeding


Service Tel.: +49 (0) 61 51 32 - 25 72
Service Fax: +49 (0) 61 51 32 - 20 72
E-Mail: bvl.process@schenck.net

Vibrating Machines
Service Tel.: +49 (0) 61 51 32 - 10 75
Service Fax: +49 (0) 61 51 32 - 30 96
E-Mail: bvs.process@schenck.net

Transport & Logistics


Service Tel.: +49 (0) 61 51 32 - 24 48
Service Fax: +49 (0) 61 51 32 - 13 69
E-Mail: bvt.process@schenck.net

Components & Spare Parts


Service Tel.: +49 (0) 61 51 32 - 17 58
Service Fax: +49 (0) 61 51 32 - 36 32
E-Mail: bvk.process@schenck.net

©Copyright 2004
SCHENCK PROCESS GmbH
Measuring and Process Systems
Landwehrstrasse 55, D-64293 Darmstadt
http://www.schenck-process.com

All rights reserved. Any reproduction of manual, regardless of method, without prior permission by
SCHENCK PROCESS GmbH in writing, even by excerpt, is prohibited.
Subject to change without prior notice.
INTECONT PLUS VDM

Contents
1. Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1

2. Control . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

Power ON · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 4

LEDs · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 4

Normal Displays · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 5

Operation in Normal Mode · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 5

Event Messages · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 6

Function Distributor · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 8

Display Check and Version Number · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 8

Keyboard Mode · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 9

START/STOP Feeder · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 9

EasyServe Active/Deactive · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 9

Batching Mode · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 10

Loading By Sight · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 13

Print Batch Report · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 13

Zero Setting · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 15

Read Parameters · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 17

3. Control Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

4. Technical Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

5. Characteristics. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25

6. Setting Programs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

Function Distributor · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 27

Calibrating Functions· · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 28

TW Tare · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 28

CW Weight Check · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 29
0405
Simulation Mode · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 31

Transmission to third parties and reproduction


of this documentation are not permitted. Technische Contents
SCHENCK PROCESS GmbH reserves all
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB I - 1
VDM INTECONT PLUS

Set Time · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 31

7. Service Values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

8. Parameterization . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35

Select Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Enter Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 36

Hardware Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Load Default Parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37

Parameter Overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

9. Event Messages . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

System Message S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Electrical System E . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 61

Calibration C . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

Maximum H . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

Minimum L . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 62

Material Flow (Batch) B . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

Signal Lamps. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 63

10. Commissioning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 65

Test Plug · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · · 65

11. Details . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Start Sources . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 67

Batching. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 69

Data Flow Charts: Signal Flow . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 71

Wiring Diagram . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

Base Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 73

Option Card . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 75

Printer Connection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77

12. Replacement Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79

Replacing INTECONT PLUS FIP —> INTECONT PLUS VEG . . . . . . . . . . . . . . . . . . . . . . . . . . . 79 0405

Transmission to third parties and reproduction


Contents Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB I-2 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

This manual applies to software version VDM 20600-00.

Edition : 0405

0405

Transmission to third parties and reproduction


of this documentation are not permitted. Technische Contents
SCHENCK PROCESS GmbH reserves all
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB I - 3
VDM INTECONT PLUS

This page left intentionally blank

0405

Transmission to third parties and reproduction


Contents Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB I-4 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

1. Overview
On INTECONT: For Further Reading:
Fieldbus manual BVH2220
INTECONT PLUS is designed as measuring and S5-RK512 (3964R) FH 458
evaluation system for Modbus (Comp) FH 525

Belt Weighers Display:


Solids Flow Meters
Mass Flow Meters 5 x 7 - dot matrix with 6 mm character height
Mass Flow Feeders
Weighfeeders Upper display left : running message
Loss-in-weight Feeders right : totalized amount in kg/h or
The system is supplied in 3 variants: t/h

1. Without option card (standard) Lower display left : event messages


right : selectable
2. With option card VFE 610V
flow rate, measured load,
for additional input/outputs and printer
etc.
3. With option card for fieldbus
VSS021V : Modbus/S5 Display can be changed over to American units.
VPB 020V: Profibus
VCB020V: DeviceNet

The present manual applies to solids flow meters with LEDs:


controlled material prefeeder.
2 green and 3 red LEDs
Task:
Green LEDs : Ready
A Solids Flow Meter is designed for continuous Red LEDs : Error or limit value messages
weighing of materials with free flowing or fluidizable
properties. Combined with a controlled material
prefeeder, preset material amounts can be batched.

O Z1 = 362.5 kg
E1 I = 1 0 0 0 kg/h

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Overview
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 1
VDM INTECONT PLUS

Keyboard: Measuring Technique:


n Precision AC voltage amplifier with continuous
Flexible membranes with tactile touch
correction of zero point and range.

gB Start/stop measurement
n Highly resolving analog-to-digital converter.
The integrated method is designed to efficiently

TU
suppress mains voltage interferences.
Preselect lower display n 16-bit microcontroller
Select functions
n
i
Unlimited storage of counter readings,
Reset counter configuration and calibration data.

G FUNC Call function distributor and


event texts

O DEL Acknowledge event message,


delete input

N ESC Abort function

f ENT Start function,


acknowledge input

P DAT Prepare input, e.g. of setpoint

B9 Enter parameters

KL Enter sign and decimal point

Some Definitions:

I = Feed rate in kg/h or t/h


Material amount per unit time
Z = Totalized amount in kg or t
Q = Measured load
Load on load cells in kg

Measuring Principle:

Material is guided to measuring chute S free from


whirls.
Deflection force acts on load cell L/C whose output
voltage is proportional to flow rate.
INTECONT evaluates signal and computes flow rate
and totalized amount.

0405

Transmission to third parties and reproduction


Overview Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 2 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

The schematic below shows all inputs and outputs. MIN = Relay output for MIN limit value

The sample mechanical equipment presents a system MAX = Relay output for MAX limit value
equipped with crossed flexure strip.
ACK = Acknowledge event messages

EXT INPUT = External interrupt input

ON = Relay output, scale started

START/STOP = Start and stop scale

Release = Release input

O Z1 = 362.5 kg
I = 1498 kg/h

S = Measuring chute

L/C = Load cell

M = Relay output for material prefeeder

F, G = Relay output for full feed/dribble


feed changeover

Z = External totalizing counter

A = Analog display for feed rate or


measured load

SERIAL = Serial interface for printer and host


computer

24 V = Power supply
0405
ALARM = Relay output for ALARM

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Overview
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 3
VDM INTECONT PLUS

2. Control
Power ON LEDs

During power failure

all counter readings


counter pulses still to be output
preselected normal displays,
Service values, e.g. ON-time
Z1 = 2 5 0 0 kg
are stored for an unlimited time.
E1 I = 0 kg/h
The internal clock continues running for approx. 5
days.

After power-up, an automatic display and lamp test is

a
performed, followed by the display version number,
then by normal displays. (green) POWER OK
lit if all power supplies are OK.

b
Message E1
(green) CPU OK
lit if microprocessor is ready to
operate.

E1
Z1 = 2 5 0 0 kg
I = 0 kg/h X (red) ALARM
flashes if an Alarm is available.
In addition, the event code is
shown in lower display line.

reports power failure . MIN (red) MIN LIMIT VALUE


Message can be configured as ALARM or WARNING. lit if feed rate limit value is

X and symbol E1 flash.


exceeded down.
ALARM: Red LED
MAX (red) MAX LIMIT VALUE
Acknowledge message before starting lit if feed rate limit value is

X
scale. exceeded up.
WARNING: LED remains dark, symbol E1 does
not flash.
No acknowledgement required. READY: The two green signal lamps light;
Start scale manually or automatically. no Alarm is available.

O Acknowledge event message.

0405

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 4 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Normal Displays Operation in Normal Mode

Upper Display
Left : Running message and operating modes. g Start totalization.
Condition : External Release signal
Rotating point indicates that totalization
and material prefeeder are active. available (selectable).
START_Source (B03) set
Right : Totalizing counter 1 to OP or Keyboard mode
active.

Operating Modes
Feature : Rotating point in left field
of upper display

B Stop totalization.
Feature: points stands still
Measured load continues being acquired.

i Reset totalizing counters.

1 Enter number of desired counter (1 or 2).


FMZ No. : _
Z1 = 5 0 0 0 kg Counter 3 cannot be reset. In case of
Z2 = 6 0 0 0 kg/h
overflow, counting resumes from 0.

f Acknowledge input.

Lower Display
N Delete faulty digits.
Left

Right
Event reported by alphanumeric code,
e.g. E1 for power failure.
Selectable
TU Select lower display
(see Normal Displays).

TU Select display
O Acknowledge event message.

Counter Z1 Z1 = 5000 kg G Call further functions, e.g. Display Event,


Calibration.
Counter Z2 Z2 = 6000 kg
Counter Z3
Feed rate
Z3 = 1000
I = 1000
kg
kg/h N Exit function distributor.
Feed rate Ir = 50,00 % 1)
Measured load Q = 10.000 kg
Measured load rel. Qr = 68,91% 2)
Batch Zb, ZI, Zd, Nb, Zbn, Zdn 3)

1) related to nominal feed rate


2) related to nominal measured load
3) see Batching Mode
0405
Display formats and units of Z1, Z2, Z3 and I can be
selected individually.

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Control
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 5
VDM INTECONT PLUS

n WARNING 2 Display permanent, not


Event Messages underscored.

Definitions Acknowledgement:
Not required.
All important scale functions are internally monitored.
Errors are reported by event message. n IGNORE No monitoring of events, save
MIN/MAX messages and deviation
For troubleshooting details, see chapter “Event via contact outputs and signal
Messages”. lamps.

If several events occur at the same time, the event


Z1 = 2 5 0 0 kg with the highest priority is displayed first.
E1 I = 0 kg/h Priority: Alarm, Warning 1, Warning 2.

Operation

Message E1 Power Failure


O Acknowledge all available events of
classes Alarm and Warning 1.
If several events are available,
Message is output in left field of lower display in form acknowledge same one after the other.
of a group letter (e.g. E) and a number (e.g. 1). In
addition, an explanatory text can be called up.
To display event texts:
The events are organized into 4 classes. The
assignment of event to class can be selected using
relevant parameter.
G Call function distributor.

n ALARM Display flashing and underscored. TU Scroll “Display Events” into lower display

X
field (normally not required).
In addition, red signal lamp
flashes. f Select function.
Totalization cuts off, scale is not
operable.

Start:
First remove cause of fault and
acknowledge message.

Acknowledgement:
If cause has not been removed
yet, flashing stops, underscores
are deleted, but message is still
available.
If fault is remedied after
acknowledgement, message
automatically effaces.

n WARNING 1 Display permanent and


underscored.
Totalization continues.

Acknowledgement:
If fault has not been remedied yet, 0405
underscore is faded out.

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 6 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

I = Feed rate
L/C = Load cell
1. Events S 2 = M06
No Release
* fault in device or cabling

Display shows: Contact Outputs

Name e.g. No Release General alarm available until


Code e.g. S2 acknowledgement
and hint e.g. Parameter M04
Min/Max outputs independent of event class,
of respective event. active also with IGNORE.
Limit values are reported as
The hint informs the service staff of the relevant long as event is available
parameter. The consecutive number relates to the provided that scale is active
priority sequence.

TU View several events.


Automatic Zero Setting Function

N Return to normal displays.


If automatic zero setting is selected and measurement
is cut off, zero point error is continuously acquired and
corrected.
List of Events Zero setting is reported by feature “Zero” independent
of measurement success.
The list is sorted by display priority.

System Message S S1 Memory Error * AUTOMATIC ON


S2 No Release
S3 Maint. Scale Run
S4 Maintenance Int. Elec 0o Z1 = 2 5 0 0 kg
S7 Simulation Active I = 0 kg/h
S9 Data Link Host

Batching B B1 Out of Tolerance


B9 Linearization

Electrical System E E1 Power Failure


E6 External Input

Calibration C C1 L/C Input*


C5 Tare Corr. > MAX

Maximum H H1 I >MAX
H4 L/C Input > MAX

Minimum L L1 I < MIN


0405 L4 L/C Input <MIN

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Control
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 7
VDM INTECONT PLUS

Programming” and “Calibrating Functions” lead to


Function Distributor further menus you can move through using cursor
keys.
The function distributor lets you call further functions
and/or dialogs. B = If batching mode is selected, additional
functions can be accessed in main
G Call function distributor.
If no event is available, display shows the
distributor.

Abort Batch
function selected last. If an event is Deselect Batch
available, the “Display Events” function is Batch Number
displayed. Print Batch
f Start function.
Reload

N Return to normal displays and/or


abort function.
S = Calibrating functions accessible after
password input.
Prompt is output after call of function
E = Only if an event is available

Function
With opposed functions, e.g. START/STOP, only the
Display Events one currently availabe can be reached.

Moving in function distributor does not limit any


scale-specific functions.

TU Move through function distributor. Display Check and Version Number


Display Events E This function lets you check displays and signal
Display Check lamps.
START/STOP Feeder

G
Service Values
START/STOP KEYB. MODE Call Display Check function.

TU
Select Batch B 1. All display elements rhythmically
EasyServe active/deactiv flash.
>0< Zero Set
f
2. Version number is displayed for
Programming approx. 10 s.
Calib.Functions S Test terminates automatically.
Print FMZ

Read Parameters
Enter Parameters S
Load Default Par. S INTECONT PLUS
Print Parameters VDM 20600-00 2063
Print Stat. Rep.

START/STOP Simulation
TW: Tare Example:
CW: Weight Check
Set Time VMD : Solids Flow Meter
20600-00 : Version number
0405

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 8 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Keyboard Mode EasyServe Active/Deactive

This function lets you shift the selected control source The “EasyServe Active/Deactive” functions let you
for START/STOP to the INTECONT keyboard. control your INTECONT using the EasyServe PC
After deselection of Keyboard mode, the former service tool.
source is active again.
Upon changeover from external source (e.g. serial) to
keyboard, START/STOP status is maintained. GT Call function distributor.
Select “EasyServe Active” function
In reverse direction, the external signals are active.

GT
To set communication parameters, use
Call function distributor. Block Q.
Select “START Keyboard Mode” or
“STOP Keyboard Mode” function.
Note: Upon power failure, the current status is
stored, i.e. “EasyServe Active” function
Display feature: needs not be re-called.
You will know Keyboard mode by the square in the left Connection to PC can also be made using a 9-pole
upper display field. SUB-D connector on X4 (RS 232 only) or a Phoenix
connector on X5 (RS232, RS422 or RS485).
See also Wiring Diagram in chapter DETAILS.
START/STOP Feeder

The “START/STOP Feeder” function lets you start and


stop material prefeeder.
In started state (ON), INTECONT controls prefeeder.
The normal Start/Stop commands cannot be used.
In Stop state, material flow is interrupted and scale
can be tared, etc.

GT Call function distributor.


Select “Start Feeder” or “Stop Feeder”
function.

f Start function.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Control
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 9
VDM INTECONT PLUS

1. Zb = Batch setpoint
Batching Mode
2. ZI = Batch actual value
Batching mode is used to feed a defined amount of (amount already
material. When batch setpoint is reached, batching discharged)
operation is complete.

0 Start batch, open prefeeder.


3. Zd = Batch residual value
1 Abort batch at any time
and (amount still to be
discharged)
2 resume.
3 Change over to dribble feed by reducing prefeeder
output. Zd = Zb-ZI
4 Cut off prefeeder.
5 Batch setpoint is reached.
4. Nb = Consecutive batch
number.
To set start value, use
“Batch Number“
function.

Before start of a batch, ZI and Zd indicate the


amounts fed out during previous batch.
Batching mode deselected (”Deselect Batch”
function), displays are disabled but can be used again
upon next selection.

Display format corresponds to the format of Counter


1.

Select Batching Mode


Additional Displays
Selection of Batching mode enables batching,
however, no batch is started yet.

EO Z1 = 2 5 0 0 kg Condition: Scale OFF


Z2 = 4 0 0 kg

G Call function distributor.

Upper display: If batching mode is selected, totals


TU Scroll “Select Batch” function into display
field.
sign G.

is displayed left of running


f Select function.
message.
The square indicating Keyboard
System prompts for input of batch setpoint.
mode is omitted.
If batch is selected from external PC, setpoint input is
omitted.

TU
Lower display:
Use cursor keys to scroll 3
additional values into display field. 0405

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 10 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Enter Setpoint Start and Abort

Prompt for setpoint input is output automatically upon


selection or can be started in manual when batch is g Start batch, process starts.
Display ZI : moves from 0 towards
complete (scale OFF).
If Batching mode is deselected or a batch is running, setpoint
no input is possible. Display Zd : moves from setpoint
If batch setpoint is preset via fieldbus (Parameter I07 towards 0
Batch Source=FB), no input is possible either. This
also applies to input of batch number and reload B Abort batch.
setpoint.
Batching continues upon next Start

P
command.
Prepare setpoint input.

Deselect Batch

19 Enter setpoint.
Max. 9 digits including decimal point.
Lets you deselect Batching mode, i.e. mode is removed
from available functions.
The unit is that of Counter 1. Totals sign Σ disappears from upper display, batching

f
values ZI, Zd, Zb and Nb are not longer available but
Acknowledge input. remain stored.

Conditions: Batch complete, or aborted using


EO Setpoint “Abort Batch” function, scale OFF.
Zb = - - - - - - kg

GT Call function distributor.

f
Select “Deselect Batch” function.

Acknowledge.

N Abort input; old setpoint is maintained.


The “Select Batch” function lets you reactivate

O
batching mode.
Delete faulty digits. The old ZI, Zd , Zb and Nb values can be viewed
again.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Control
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 11
VDM INTECONT PLUS

Abort Batch If reloaded batch is complete, next Start command


starts a normal batch.
Lets you abort a running batch, i.e. batching To repeat reloading, re-call function.
immediately stops. The “Abort Batch” function lets you also abort
Batching mode remains selected. reloading.

New batch starts upon next start command, old batch


is not resumed.
The “Reload” function lets you complete old batch. Batch Number Nb

GT Call function distributor and select “Abort


Batch” function.
Enter batch number. Number increments by 1 upon
start of every new batch.
Number is printed in batch report and can be viewed

f Acknowledge.
in lower display.
Reloading operations belong to previous batch and
are not counted.
You can also abort batch using contact O02.

Reloading GT Call function distributor.


Select “Batch Number” function.
Lets you add a specified amount to a complete batch.

Conditions : Running batch complete, scale f Acknowledge.


Prompt for input of
OFF. No batch report.
Nb = ——- is output.
Display ZI : Batch actual value increments from
value achieved. f Acknowledge input.

Display Zd : Batch residual value keeps value


achieved.
N Abort input.
Old number is maintained.
Display Zbn : Make-up setpoint
You can also change current number during batching.
Display Zdn : Batch residual value of make-up
amount.
Zdn = Zbn - make-up amount
reloaded

All displays can be scrolled into lower display field.


Zdn and Zbn are available only until start of next
batch.

GT Call function distributor.


Select “Reload” function.

f Acknowledge function.
System prompts for input of reload
setpoint in kg or t.
The unit is that of counter 1.

P Change setpoint Zbn before start of


reloading.

gB Start or abort reloading. 0405

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 12 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Loading By Sight Print Batch Report

Batch report can be printed only if a batch is complete The printing functions require an option card to be
(setpoint reached). present.

If you wish to batch an amount not previously


determined and print the result, follow these steps: Print Batch

1. Call “Select Batch” function. Start of printout disables the “Reload” function for the
2. Select very high batch setpoint, e.g. 999999999 kg. batch in question.
Function can be called only in Batching mode.
3. Scroll batch actual value ZI into lower display field.
4. Start scale. Printing can be started:
5. If amount ZI is reached, stop scale.
6. Call “Stop Batch” function. 1. Manually via function distributor
7. Start printing (see “Print Batch”). 2. Automatically, after each complete batch
(Parameter I 06).
The “Reload” function can be performed only before
print command. GT Call function distributor.
Select “Print Batch” function.
For next batch, follow steps 4...7.

f Start function.

N Abort printing.

Batch Report

07.07.03 11:45:10

Batch setpoint 0.150 t


Batch act.value 0.150 t
Counter 1 0.806 t
Counter 2 806.47 kg
Batch number 40

Events
E1 Power Failure M01

07.07.03 : Date and time


Batch setpoint: Preset batch amount
Batch act. value: Amount batched
Counter 1 : Totalizing counter 1
Counter 2 : Totalizing counter 2
Batch number : Consecutive number NB of scale
Events : Events available during printout

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Control
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 13
VDM INTECONT PLUS

Print Counter Readings (FMZ) Print Events

Identical with batch report; however, the title is


“Quantity Report”. Parameter J 02 lets you decide whether event
messages are to be printed or not.
Batch number, setpoint and actual value are printed
only if Batching mode is selected. Eligible settings :

To call: 1. No printout (NO)


2. Print events (Error)
1) Select “Print FMZ” function. 3. Print events and counter readings (YES)
Unlike “Print Batch”, report can also be printed during (see “Batching”)
batching.
2) Automatically upon each event printout
(Parameter J 02 = YES)
30.04.03 11:45:21 L1 W1 à I < MIN
30.04.03 11:59:01 L1 W1 ß I < MIN

Print Parameters

Lets you print out parameter list complete with current L1 : Event code
values. W1 : Message class, e.g. WARNING 1
Parameter values varying from default settings are
−> : Event has occurred
cross-marked (*).
As Appendix, a list of possible events and current <— : Cause removed; event
hardware assignment is printed. acknowledged, if required.
I < MIN : Explanation

GT Call function distributor.


Select “Print Parameters” function. Event is reported on INTECONT display as long as

f
available.
Start function.
For details, see “Event Messages”.
N Abort printing at any time.
Status Report
PRINT PARAMETERS
Printable at any time, the status report includes most
INTECONT PLUS VDM 20600-00 2063
significant status values and event messages output
03.06.03 7:39:25 after last printout. If status is printed for the first time,
counting starts from last power-on of INTECONT.
BLOCK A Scale Definitions

GT
01 Language ENGLISH
02 Units SI
Call function distributor.
BLOCK B Rated Data Select “Status Report”.

f
01 Feed Rate Unit ——— kg/h
02 Nominal Feed Rate * 1,000 t/h
usw.
Start function.

N Abort printing at any time.


0405

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 14 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Voltage ON-time
Total voltage ON-time
Zero Setting

Scale ON-Time The zero setting program lets you acquire the
Total ON-time of measurement and INTECONT measuring system’s zero point error over a settable
time.
Events after last status report The acquired value is used to correct the current
Number and type of events since last report printout. measuring result during operation.
If report is printed for the first time, counting starts
from power-On. Effects:

Counters 1, 2, 3 1. During zero setting, totalizing counters stop.


Totalizing counters 1-3 2. Analog value is set to elevation value.
3. Events continue being monitored.

STATUS REPORT INTECONT® PLUS Conditions:


03.06.03 13:37:12
Software : VMD 20600-00 2063 1. No material flow
Hardware version :1
Option card version :1 2. Scale turned off
Station address :1
------------------------------- (prefeeder, if present, closes).
Mode OP : NO
Mode Simulation : NO
Scale ON : NO Follow these steps:
Alarm : NO

G
Voltage ON-time : 35 h
Scale ON-time : 23 h
Counter 1 : 5635 kg
Counter 2 :6t Call function distributor.
Counter 3 :6t
-----------------------------------------------------------
Events after last status report

2 * S02 No Release
TU Scroll >0< (zero set) into lower display
field.

f Start function.

N Abort function at any time.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Control
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 15
VDM INTECONT PLUS

Program Running: Special Messages:

1. OFF INTECONT is still ON

0o >0< 70 % 2. ABORTED Zero setting result has not be


Tarkor 1.12 % accepted
3. VALUE TOO BIG Zero setting result has
exceeded specified limits
(Parameter H03).
Result is rejected.
Upper display : Residual run time in % of total run
time

Lower display : Zero point error related to nominal


measured load

N Abort program at any time.

0o Dev. 2.45%
Tarkor 3.50 %

Program Complete:

Upper display: Deviation of zero point from


previous zero setting operation
in % of nominal measured load

dev = + : error increased


dev = - : error decreased

Lower display: Mean value of total zero point in %


of nominal measured load

f Accept “Tarkor” result and enter into


Parameter D 05.

N Reject result, i.e. scale not tared.

0405

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 16 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Read Parameters

Parameters are defined as variable characteristics or


data used to match the INTECONT to the application.
Parameter input is protected by password.
The “Read Parameters” function lets you view all
parameters without jeopardizing the operating safety.

The parameters are organized into function blocks A ,


B... and consecutively numbered within a block.

GT Scroll “Programming” function into

f
display field and acknowledge.

Tf Select “Read Parameters” sub-function.

Display shows title of first parameter block.

Scale Definitions
Block: A

TU Move through parameter blocks A, B...

fT Move through parameters within a block.

Nominal Feed Rate


B02 1000.0 kg/h

N Return to blocks.

N Return to normal displays.

For details, see “Enter Parameters”.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Control
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 17
VDM INTECONT PLUS

This page left intentionally blank

0405

Transmission to third parties and reproduction


Control Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 18 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

3. Control Overview

O Z1 = 362.5 kg
-- I = 100 kg/h

Status Displays (Upper Display Field)

In normal mode, totalizing counter Z1 is displayed.

¦ Point rotates Scale (totalization) started

Control Keys:

gB Start/stop totalization (if selected)

U SCROLL Select lower display and functions.

T
1. Counters Z2, Z3 4. Measured load Q
2. Feed rate I 6. Batch displays Zb, ZI, Zd, Nb, Zbn, Zdn
3. Feed rate Ir in %

i RESET Reset totalizing counter.


1. Enter number of desired counter (1 or 2). Counter 3 cannot be reset.
2. Acknowledge input with ENTER key, or
3. Abort with ESCAPE key, or
4. Delete faulty input with DELETE key

G FUNCTION Call function distributor and event messages.


1. Select desired function using SCROLL keys.
If an event is available, “Display Events” function is already selected.
2. Activate function with ENTER key.
3. Pass through available event messages with SCROLL keys.
4. Return to normal display with ESCAPE key

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Control Overview
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 19
VDM INTECONT PLUS

O DELETE Acknowledge event message, delete input.

N ESCAPE Abort function, return to normal displays.

f ENTER Acknowledge input, e.g. parameter.


Start function, e.g. Display Events (see FUNCTION).

P DATA Prepare input, e.g. parameters

Lower display field shows event message, if any, e.g. symbol S2 = No Release.

List of Events

sorted by display priority.

System Messages S1 Memory Error *


S2 No Release
S3 Maint. Scale Run
S4 Maintenance Int. Elec
S7 Simulation Active
S9 Data Link Host

Batching B1 Out of Tolerance


B9 Linearization

Electrical System E1 Power Failure


E6 External Input

Calibration C1 L/C Input *


C5 Tare Corr. > MAX

Maximum H1 I >MAX
H4 L/C Input > MAX

Minimum L1 I < MIN


L7 WZ Eingang <MIN

I = Feed rate
L/C = Load cell

* fault in device or cabling

0405

Transmission to third parties and reproduction


Control Overview Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 20 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

4. Technical Data

n Panel-mounting unit: VEG 20600/20610 n Surface-mounting unit: with panel mounting unit
Front panel 96 x 288 mm: VEG 20...
Panel cut-outs : 88 x 282, wall thickness
max. 10 mm n Wall-mounting housing
Mounting depth : min. 225 mm
(including 50 mm for Measuring
connectors) systems : width x height x depth
Protected to : IP 20, front to IP 65 410x330x236mm
Material : plastic grey to RAL 7022 Feeding
systems : width x height x depth
Display : fluorescent, 2 lines of 20
500x600x300mm
characters, 6 mm high
Protected to : IP 65
Keyboard : flexible membranes with
tactile touch Material : steel sheet, 1.5 mm, grey
Voltage supply : 90...264V/50Hz...60Hz
Signal lamps : LEDs, 2 x green, 3 x red
Power supply : 24 V(DC) +50 % -25%, Extension : Feed unit controller
max. 1 A,
n Environment
no fuse, pole-reversal
protective circuit Temperature : -25 °C ... +45 °C,
Ext. power supply : 90...264V/ 50HZ...60HZ tested to -40°C
Humidity : Class F (DIN 40 040) *
Interference
immunity : to IEC 801
Interference
P = 100.00 kg/h suppression : to VDE 871, EN 55 011
I= 0 kg/h
Housing safety : to IEC 348
EC recommen-
dations : CE label

* Tropical version (class R) upon request

n Storage temperature

-40 °C ... +60 °C

n Connectors

Plug/screw connectors (Phoenix Combicon),


non-confusible

n Control outputs

Number :
8 N/O relay contacts
Base board 3:
Option card 5:
Load :
max. 230 V(AC)
8 A resistive load, 1 A
inductive
0405 If error message “CPU Not OK” is output, all contacts
open.

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Technical Data
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 21
VDM INTECONT PLUS

n Control inputs n Analog input

Number : 5 Number : 1
Base card : 3 Current : raise ...20 mA impressed
Option card : 2 Raise : 0... 20 mA
Type : 24 V(DC) +/-30 %, 5 mA, Load : 500 ohms
galvanically isolated Reference : 0 V internal,
galvanically non isolated
Resolution : 10 bits +/- 1/2 d
n Control inputs (NAMUR) Acuracy: <0.4% over entire
temperature range
Number : 2
Type : NAMUR (DIN 19234),
short-circuit and cable n External totalizing pulse counter
breakage monitoring
Frequency : max. 10 Hz
Pulse length : selectable 50...1000 ms
Output : 24 V, max. 100 mA
optionally active low or
active high,
galvanically isolated,
n Analog output
short-circuit-proof, limited to
Number : 2 apr. 350 mA,
Base card : 1 negative amounts are stored
Option card : 1 internally and must be
compensated by positive
Current : raise ...20 mA impressed
amounts before new pulse is
Raise : 0... <20 mA
output.
Load : max. 500 ohms
This ensures integral
Reference : 0 V by user, accuracy also with minimal
galvanically isolated belt load.
Resolution : 12 bits +/- 1 d

If error message “CPU Not OK” is output, output


signal turn 0 mA. n Serial printer interface

Number : 1 (option card)


Type : RS 232 (V24), max. 38400
baud
Data format : 8 data bits, 1 stop bit, no
parity
Isolation : galvanically non-isolated
Connectors : Phoenix MSTB, contat
spacing 3.5 mm, max. 1.5
mm2

0405

Transmission to third parties and reproduction


Technical Data Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 22 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

n Load cell connection

Voltage supply : +/- 6 V AC (+/-3 %)


(apr. 66 Hz),
short-circuit-proof
Measuring cycle : 100ms
Resolution : 24 Bit
Load : R (load cell) = min. 80 ohms
Cable length : max. 30 % voltage drop,
max. 500 m
Measuring range : -20mV....+50mV
with VLW:
-1.6mV...min. 32mV

n Serial interface for service PC

Number : 1
Type : RS232; RS422 or RS 485
max. 19200 baud
Data format : 8 data bits, 1 stop bit, odd
parity changeable to even or
no
Isolation : galvanically non-isolated
Connectors : Phoenix MSTB, contact
spacing 3.5 mm, max. 1.5
mm2 or 9-pole D-Sub HD20

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Technical Data
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 23
VDM INTECONT PLUS

This page left intentionally blank

0405

Transmission to third parties and reproduction


Technical Data Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 24 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

5. Characteristics

n Power Failure n Displays

Scale data, calibration values, counter readings and Upper display : Totalizing counter 1
pulses pending remain stored after power failure for Lower display: Totalizing counters 2...3
an unlimited period of time. The internal clock Feed rate absolute I
continues running for approx. 5 days. Feed rate relative Ir
Measured load absolute
Measured load relative
Batch data
n Dialog Language
for error messages, operation, and service Select lower display using cursor keys.
programs.

Eligible : DEUTSCH
ENGLISH n Signal Lamps (top down)
FRANCAIS
ESPANOL VOLTAGE OK (green)
ITALIANO PROCESSOR OK (green)
ALARM (red)
MIN (red) feed rate MIN limit
MAX (red) feed rate MAX limit
n Units (selectable)

SI units : kg, kg/h n Event Messages


t , t/h
m, cm Events and faults are displayed in form of an
NON-SI units : lb , lb/h alphanumeric code.
t , t/h Call clear text of events via keyboard.
f , inch Events are organized into Alarms, and Warnings
(see Parameter Shortlist) with and without acknowledgement. Alarms stop
scale, warnings don’t.

All alarms are additionally reported via relay


n Start/Stop Totalizing Counter outputs.

Select using Parameter B03.


n Operating Philosophy

Operator prompting through multi-level menus.


n Release, Emergency Stop Important configuration and calibration functions
are protected by password.
Functions are realized using a digital input O01.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Characteristics
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 25
VDM INTECONT PLUS

n Zero Setting n Calibration

Zero setting is performed by an automatic program. Calibration as such is not required. All you have to
No material is required. do is enter some constructional data of load cells,
Program can be started speed transducer, belt inclination, etc. INTECONT
uses these data to compute all requisite display
1. manually via keyboard normalisations.
2. automatically with closed prefeeder Check, or recalibration, can be effected in two ways:

Max. admissible zero setting amount is monitored. a) Using material

Enter check result into INTECONT, and


measurement value will be corrected.

n Taring b) Using check weight


Designed to zero the basic tare load, the taring A special check program lets you check
program on principle has the same function as the normalizations, and correct them if technical
zero setting program. However, tare elevation is not data or not exactly known. In later operation,
monitored, and the call is protected by password. program can also be used to show technical
modifications.
n Zero Drop Out
n Digital Inputs
Suppresses totalization upon measurements
around zero point, so that counter stops with small
feed rates. Number Name Default
Deselect function if not desired. O03 DI Ackn. Events DI1
O01 Release DI2
n Display Filters
B03 START Source —-(OP)
O02 DI Stop Batch —-
can be defined individually for feed rate and
O02 DI Ext. Event —-
measured load.

n Digital Outputs
n Maintenance Hints
Nummer Name Default
through display of event s
P04 DO I-MIN D01
1. Voltage ON-time P05 DO I-MAX DO2
2. Scale ON-time P01 DO ALARM D03
P02 DO Prefeeder ON D06
P03 DO Feeder ON D05
n Adaptions P07 Full Feed —-
P08 Dribble Feed —-
The electrical system needs not be redesigned nor P06 DO Batch Active —-
adapted.

0405

Transmission to third parties and reproduction


Characteristics Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 26 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

6. Setting Programs
Function Distributor Programming and Calibration functions lead to further
menus you can move through using cursor keys.
The function distributor lets you call further functions
and/or dialogs. B = If Batching mode is selected, additional
functions can be accessed in main

G
distributor.
Call function distributor.
If an event is available, “Display Events” Abort Batch
is displayed; if no event has occurred, Deselect Batch
display shows function selected last. Batch Number

f
Print Batch
Start function. Reload

N
S = Calibrating functions protected by
Return to normal displays, or abort password. Prompt for password input is
function. output after call of function.

E = If an event is available.

F u nc t i o n With opposed functions, e.g. START/STOP, only the


DisplayEvents one currently accessible can be called.

Moving through function distributor has no effect on


weighing functions.

TU Move through function distributor.

Display Events E
Display Check
START/STOP Feeder
Service Values
START/STOP Keyb. Mode
Select Batch B
EasyServe active/deactiv
>0< Zero Set
Programming
Calib.Functions S
Print FMZ

Read Parameters
Enter Parameters S
Load Default Par. S
Print Parameters
Print Stat. Rep

START/STOP Simulation
Tare
CW: Weigh Check
0405
Set Time

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Setting Programs
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 27
VDM INTECONT PLUS

Calibrating Functions TW Tare

Menu item “Calibration Functions” lets you access 3 The taring program acquires zero point error of
functions: complete measuring system over a settable time
(Parameter C 01, default = 30 s).
1. TW Tare INTECONT uses this value to correct measuring
2. CW: Weight Check result during operation.
2. Set Time In contrast to zero setting program, zero setting range
is not monitored nor limited.
All functions are protected from unauthorized use by Taring program deletes the zero setting result.
password.
The operating sequence is the same for all programs.

G Call function distributor.


Effects: 1. During taring, no totalization
takes place.

TUf
2. Analog output is set to
Scroll CALIBRATION elevation value.
FUNCTIONS into lower display 3. Events continue being
field and acknowledge. monitored.

...... f Enter password 07734.


Conditions: 1. No material flow.
2. Scale cut off
(prefeeder closed, if present).

Display shows one of the setting programs, e.g. TW: Follow these steps:
Tare.
Gf Function distributor, Calibration functions,
password (see “Calibration Functions”).

TU
CALIBRATION FUNCTIONS
TW: Tare
Scroll “TW: Tare” function into lower
display field.

f Start function.

f Start setting program.


N Abort at any time

N Return to normal displays.


For apr. 2 min., Calibration
menu can be recalled without
password input.

0405

Transmission to third parties and reproduction


Setting Programs Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 28 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Program running:
CW Weight Check

This program lets you check the INTECONT


>0< TW: 9 0. 2 % measuring range.
>. Tare 5 2. 3 5 Load measuring system with a known check weight
and acquire load cell load mean value over a certain
time.
INTECONT compares result with specified setpoint
Upper display: Residual run time in % of total run and displays value.
time No automatic correction takes place.

Lower display: Continuously meaned tare in % of Effects:


nominal measured load
1. During run time, no totalization takes place.
Program complete:
2. Analog output is set to elevation value.
3. Events continue being monitored.

Conditions:
>0< Dev. 2.45 %
Tare 3.50%
1. Taring or zero setting performed
2. Effective check weight entered into Parameter C 05
3. Check weight applied in provided point
4. Scale cut off
Upper display : Deviation of tare value from
previous taring operation
in % of nominal measured load Sequence:

dev = +: tare increased Gf Function distributor, Calibration function,


password (see “Calibration Functions”)
dev = - : tare decreased

Lower display : Mean value of total tare TU Scroll “CW: Weight Check” into lower
display field.
in % of nominal measured load
f
f
Start program.
Accept taring result and enter value into
Parameter D 04.
Tare correction (D05) is set to zero.
N Abort at any time

N Reject result, i.e. scale not tared.

Special Messages:

1. STOP if INTECONT is still started


2. ABORTED if taring result is not acquired
yet

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Setting Programs
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 29
VDM INTECONT PLUS

Program running Evaluating result:

Error < 1 % : COR = 0.99...1.01


Scale OK, no further action
required.
>. CW 51.4%
SET/ACT 0.9842% Error < 5 % : COR = 0.95...1.05
Enter KOR value into Parameter D
02 .
This makes good sense only if
Upper display : Residual run time in % of total run parameter has not yet considered
time result of check using material.

Lower display : Continuously meaned SET/ACT Error > 5 % : COR < 0.95 or COR > 1.05
measuring result Multi-percent deviations suggest
wrong data input (e.g. belt
inclination not exactly known, lever
arms) and/or mechanical faults
Program complete (misalignment, distorsions).

Check does not consider Parameter “Weight


Correction" D 02, so that check program will
>. CW 5.325 % indicate same error quotient COR after check.
COR 0.9915%

Feed rate display for check weight:

C05
I = D02
Upper display : ACTUAL measured load in kg C04
Lower display : Mean value COR of SET/ACT over
total run time
I = Feed rate in t/h
C05 = Check Weight in kg
C04 = Device Constant in kg/(t/h)
D02 = Weight Correction

fN Exit program.
Since result is not acquired automatically,
the two keys are equivalent.

Special hints:

1. STOP if INTECONT is still ON


2. ABORTED after exit of program

* Lets you check scale zero point without check weight


Display format: xxxxxxx,yy kg

0405

Transmission to third parties and reproduction


Setting Programs Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 30 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Simulation Mode Set Time

Simulation Mode lets you check all scale functions Unlike the other programs, date and time can be
without material at the time of commissioning. changed in Start and Stop states of scale and be read
During simulation, scale is cannot operate in normal off under SERVICE VALUES.
mode.

Gf Function distributor, Calibration functions,


Gf Function distributor, calibration functions,
password (see “Calibration Functions”).

TU
password (see “Calibration Functions”).
TU Scroll “Set Time” into lower display field.

f
Scroll “Start Simulation” into lower display
field. Call menu.

f Start program. N Abort at any time.

Display :
Event message S7
In upper line, “=” symbol
0 3 Enter year, e.g. 03, month, day, hour,
minute, and second.
flashes.
Function can be cut off in the same way (STOP
Simulation). f Acknowledge every input.
When seconds have been
acknowledged, new date is acquired.

Complete date is displayed for some seconds.


Features:

1. All operating functions can be performed.


O Delete digit entered last.

2. Feed rate actual value is set to nominal rate.


3. Measured load measurement is active.
After power failure, time remains stored for min. 5
4. All control inputs and outputs operate in normal days.
fashion.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Setting Programs
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 31
VDM INTECONT PLUS

This page left intentionally blank

0405

Transmission to third parties and reproduction


Setting Programs Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 32 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

7. Service Values
The Service table includes detailed system 6. Inputs switching conditions
information. Call does not affect weighing functions.
I+ : DI = 1 1 1 1 1 + 0

GTf Call SERVICE VALUES


function and start.
“1” = Contact closed
“0” = Contact open
Inputs 4 + 5 on option card
“N” = No option card

TU Move through service values. Inputs 6 + 7 are designed as Namur inputs


(external input)

N Return to normal displays.


“+” short-circuit; “-” cable breakage;
“1” = sensor covered; “0” = sensor free

Displays: 7. EL = 22 h

1. VMD 20600-00 2063 Version number Voltage ON-time


2. HW = 1 Hardware version
3. Opt.K: 0 (no option card) Monitoring: Parameter K 01, Message S4
1 option card available)
8. ED = 19 h

Scale On-time
O Z1 = 1500100 kg
Opt..IND : 1
Condition : Totalization ON
Monitoring : Parameter K 03, Message
S3

4. Date and time


9. aw = 30.988 %
5. Relay outputs switching conditions
Load on load cells related to total of load cell
rated capacities.
I +: DO = 1 1 1 0 0 0 0 0 If value exceeds 100%, load cells are
overloaded.
“1” = Contact closed From 110 % onward, Message H4:
“0” = Contact open “L/C Input > MAX” is output.
Inputs 4-8 on option card
“N” = No option card
10 wz = 1.383257 mV/V

Unnormalised output value of load cell


amplifier (Gross)

11. R_wz = 300 ohms

Load cell resistance value

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Service Values
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 33
VDM INTECONT PLUS

12. AO1 = 4.15 mA

Analog output 1 output current

13. AO2 = 10.00 mA

Analog output 2 output current


(on option card)

14. ZE = 53

Pulses output across pulse output for external


totalizing counter, counted after command
“Reset Counter 1".

15. ZO = 1
Pulses still to be output.
If value keeps exceeding zero, pulse
frequency is higher than 10 Hz.
Increase weighting of smallest display digit of
Counter 1 (Parameter B 10).

16. AI = 12.54 mA

Analog input input current .

17. CS = 10851

Scale software check sum

18. CS_b = 10851

Check sum cyclically recomputed. If value


“CS_b” is unequal to “CS”, a serious fault is
given. Contact the Schenck Service.

19. Iun = 4876 kg/h

Unlinearized feed rate

0405

Transmission to third parties and reproduction


Service Values Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 34 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

8. Parameterization

General Information There are two types of parameter:

Parameters are variable characteristics or data used Selection parameters


to match INTECONT to the application.

Display units and format Let you select from various options, e.g. WARNING,
Limit values ALARM.
Nominal and calibration data, etc.
Numeric parameters
Some parameters can be set in accordance with
requirements (e.g. display formats), others have to be
taken from Spec Sheet supplied. Enter numeric value, e.g. nominal feed rate.
During parameter input, all functions are maintained.
However, during operation, only parameters with no
influence on measurement, e.g. display filters, should
be changed.
Call Parameter Menu

Default Values G Call function distributor.


All parameters are preset with default values. These
are proven suggestions and can normally used as
TUf Scroll PROGRAMMING into
lower display field and
defined.
acknowledge.
The default values can be loaded using sub-function
“Load Default Parameters”. TUf Select ENTER PARAMETER
function.

Bf
Identification
Enter password 07734.
The parameters are organised into function blocks A,
B, ... and, within a block, described by

name Display shows title of first parameter block.


number 1, 2, 3 ..
and
value.
Values differing from default are identified by a *
before the block letter.
Dialog Behaviour
Block: A

Nominal Feed Rate


B02 1000.0 kg/h

N Return to normal display.


For apr. 2 min., Parameter
menu can be recalled without
password input.
0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 35
VDM INTECONT PLUS

Select Parameters Enter Parameters


1. Block Letter
P Prepare input.

TU Selection parameter:
value flashes.
Rated Data Scroll desired value into lower
Block: B display field.

46 Go to the left (4) or to the right


(6); see “Hardware
Configuration”.

B9 Numeric parameters:
TU Move through blocks A, B ... up
and down.
Feature - - - - - - - - - - - - - - - -
Enter value using number keys.

f
Block letter flashes.

f Select block.
Acknowledge input.
Next parameter is displayed.

O
Display shows parameter
selected last. Delete digits.

2. Parameter Number N Abort input.

OFF key “0" is always active; ON key ”I" only if


parameter input is complete.
Nominal Feed Rate
B02 10000.0 kg/H

TU Move through parameter


numbers within a block.
Parameter number flashes.

f Move through parameter


numbers independent of block
(UP only).

NN Return to block titles.


Return to normal mode.

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 36 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Hardware Configuration Load Default Parameters


When parameterising the hardware, the source Lets you load the default setting.
determines whether unit, channel and level must be Function is protected by password and YES/NO
indicated or not. The table below will assist you in prompt.
configuring the hardware.
Attention!
Source Unit Channel Level All changes to parameters and calibration values
get lost.
FB

OP
G Select PROGRAMMING function,
call DEFAULT PARAMETERS.
v


B1 YES = 1
NO = 0
DI I+ DI1-DI7 HI, LO

DO I+ DO1-DO8 HI, LO f Acknowledge selection.

AI I+
Power Failure
As you can see, with “Fieldbus” (FB), “Operator
Panel” (OP), “Speed” (v) and “Not Assigned” (—) no Parameters remain stored for an unlimited period of
additional input is required. time.
“Digital Inputs” (DI) and “Digital Outputs” (DO) require
unit, channel and level to be indicated.
With “Analog Input” (AI), the unit is firmly set to I+.

Sample:

Parameter B06 “START Source" determines from


where the scale is started.

Description Source
B06 START Source OP
Alternatives FB, DI

On standard the scale is started from the INTECONT


keyboard.
Alternatively, fieldbus or digital input (DI) can be
selected. If DI is the desired source, additionally
indicate channel and level (see table above). The unit
is firmly set to I+.

4 Keys 4 (go to the left) and 6 (go to the

6
right) let you shift between source,
channel and level.
0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 37
VDM INTECONT PLUS

Parameter Overview BLOCK F Limit Values

This list applies to software: VDM 20600-00 01 Value for I-MIN 5.0 % Io
02 Event Class I-MIN W1 (L 01)
BLOCK A Scale Definitions 03 Value for I-MAX 120.0 % Io
04 Event Class I MAX W1 (H 01)
01 Language * ENGLISH
02 Units SI
BLOCK G Filter Setting

BLOCK B Rated Data 01 I Display 3.0 s


02 I Analog Output 3.0 s
01 Feed Rate Unit ——— kg/h 03 Q Display 3.0 s
02 Nominal Feed Rate 0200.000 t/h 04 L/C FILTER 1.0 s
03 START Source OP 05 Afterfl. Time 5.0 s
04 FMZ1 Unit ———- t
05 FMZ 1 Pulse Dur. 0 ms
06 FMZ 2 Unit ———- t BLOCK H Additional device
07 FMZ 3 Unit ———- t
01 AUTO Zero Active NO
02 Autom. Zero Limit 1.00 % Io
BLOCK C Calibrating Data 03 Zero Set Limit 5.00 % Io
04 Tare Corr. MAX W1 (C 05)
01 Calibration Time 30.0 s 05 ZDO Active NO
02 L/C Charac. Value 2.0000 mV/V 06 ZDO Limit 1.00 % Io
03 L/C Rated Cap. 60.000 kg
04 Device Constant 0.0400 kg/h
05 Check Weight 1.000 kg BLOCK I Batch Mode

01 Batch Dribble FD 100.000 kg


BLOCK D Calibrat. Results 02 Batch End 0.000 kg
03 Adaption fact. 0.5
01 Nominal Platf. Load 8.00 kg 04 Batch Tolerance 100000.000 kg
02 Span Correction 1.0000 05 Out of Tolerance W1 (B 01)
03 Total Tare 0.00 kg/h 06 AUTO Print NO
04 Basic Tare N 0.00 kg/h 07 Batch Source OP
05 Tare Correction T 0.00 kg/h
06 Material Corr. 1.00
BLOCK J Printer Setting

BLOCK E Analog Output 01 Baud Rate 9600


02 Print Subtotal Error
01 Source AO 1 I 03 Print Page Length 72
02 Elevation AO 1 4.00 mA
03 Limit Value AO 1 20.00 mA
04 Source AO 2 Q BLOCK K Maintenance Int.
05 Elevation AO 2 4.00 mA
06 Limit Value AO 2 20.00 mA 01 Maintenance Elec. 3000 h
02 Event Maint. EL. W1 (S 04)
03 Maint. Scale Run. 3000 h
04 Event Maint. Run. W1 (S 03)

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 38 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

BLOCK L Comm. Fieldbus BLOCK O Digital Inputs

01 Protocol Type NO 01 Release DI I+.DI2 HI


02 Host timeout 10 s 02 DI Stop batch —
03 Comm.-Error Host IGNORE (S 09) 03 DI Ackn. Events DI I+.DI1 HI
04 Address 1 05 DI Ext. Event —
05 Resolution 4096
06 Word sequence I:std/L:std
07 Physics RS485 BLOCK P Digital Outputs
08 Baud Rate 9600 01 DO ALARM DO I+.DO3 LO
09 Format Data 8-E-1 02 DO Prefeeder ON DO I+.DO5 HI
10 FLOAT-format SIEMENS-KG 03 DO Feeder ON DO I+.DO6 HI
11 Physics RS422 04 DO I-MIN DO I+.DO1 LO
12 Baud Rate 9600 05 DO I-MAX DO I+.DO2 LO
13 Format Data 8-E-1 06 DO Batch active —
14 Address 16 07 DO Full feed —
15 FLOAT-format IEEE 08 DO Dribble feed —
16 Configuration FIXED-1
17 Address 16
18 Baud Rate 125K BLOCK Q Comm. EasyServe
19 Configuration FIXED-1
20 Byte sequence Low - High 01 Station address 1
21 Word sequence I:std/L:std 02 Physics RS232
03 EasyServe Baudr. 19200
04 Format Data 8-O-1
BLOCK M Events

01 Power Failure A (E 01)


02 Memory Error A (S 01)
03 L/C Input A (C 01)
04 No Release W1 (S 02)
05 L/C Input MAX A (H 04)
06 L/C <MIN A (L 04)
07 Simulation aktiv W2 (S 07)
08 Error Ext. Event A (E 06)

BLOCK N Linearization

01 Linearization ON NO
02 Lin.-S1 25.00 % Io
03 Lin.-I1 25.00 % Io
04 Lin.-S2 50.00 % Io
05 Lin.-I2 50.00 % Io
06 Lin.-S3 75.00 % Io
07 Lin.-I3 75.00 % Io
08 Lin.-S4 100.00 % Io
09 Lin.-I4 100.00 % Io
10 Lineariz. error W2 (B 09)

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 39
VDM INTECONT PLUS

Block A : Scale Definitions

A 01 Language A 02 Units
Range: SI Default: SI
Range: DEUTSCH Default: DEUTSCH
NON-SI
ENGLISH*
AMERICAN ENG*
FRANCAIS Lets you change over displays and parameter inputs
ESPANOL from SI units to American units.
ITALIANO
Selection holds for all displays, event messages and
American Unit SI Unit Conversion *
parameters. lb kg 1 lb = 0.453593 kg
t t 1 t = 0.907185 t = 2000 lb
* identical f m 1 f = 0.3048 m
inch cm 1 inch = 2.54 cm

*also applicable to compound units, e.g. kg/h

Block B : Rated Data

B 01 Feed Rate Unit B 02 Nominal Feed Rate


Range: ------ t/h Default: Range: 0.0001..230000.0 t/h Default:
----.- t/h - - - - - - kg/h 200.0 t/h
---.-- t/h
--.--- t/h Reference for limit values and service displays
------ kg/h
----.- kg/h
- - -. - - kg/h
- -.- - - kg/h
Determines feed rate display format

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 40 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Dialog function “Keyboard Mode” lets you change over


B 03 START Source from selected source to keyboard, and vice versa.
Range: OP Default: OP
FB
DI
To start/stop totalization, there is no single solution:

OP : From INTECONT keyboard


FB : Via fieldbus interface
DI : Using digital input. Default value is DI3.
You can also use any other free digital
input. Digital input operates
edge-controlled, i.e. if scale fails after
Alarm, remove START signal and re-apply.

Note

G05 defines the totalizing counter tracking time.


If Parameter O01 “Release” is set to “- -”,
no release is required.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 41
VDM INTECONT PLUS

B 04 FMZ1 Unit B 06 FMZ 2 Unit


Range: ------- t Default: - - - - - - - t
As with B04; however, for counter 2
-----.- t
----.-- t
---.--- t
- - - - - - t *10
----- t *100
- - - - - - - kg
- - - - - . - kg B 07 FMZ 3 Unit
- - - - . - - kg
- - - . - - - kg As with B04; however, for counter 3

B10 determines the display format for counter 1,


batching values and pulse weighting for external
counter. If no external counter is present, set
Parameter B11 to 0.

B 05 FMZ 1 Pulse Dur.


Range: 0....1000 ms Default: 0 ms

Length of external counter output pulse. Pulse


weighting corresponds to the smallest display digit of
counter 1 (Parameter B04).

B05 < 10 ms : Pulse output is blocked.


All pulses not yet output are
deleted.

Output frequency at nominal feed rate:

PNENN = nominal
n feed rate in kg/h or t/h
Zmin = smallest display digit of counter 1
(B 04) in kg or t

Select Zmin (B 04) so that f does not exceed 10 Hz.


Furthermore, pulse duration B05 should be smaller
than 1/f .

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 42 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Block C : Calibrating Data

C 01 Calibration Time C 06 Check Weight


Range: 1...9999 s Default: 30 s Range: 0.010...22 000.0 kg Default: 1 kg

Measuring time for taring and zero settings programs The check weight is used to check weighing system
using calibration program “CW: Weight Check”.

Enter weight acting on load cell through check weight.


C 02 L/C Charac. Value
Range: 0.01...9.9999 mV/V Default: 2 mV/V

Load cell characteristic value (transmission factor)

C 03 L/C Rated Cap.


Range: 0.5000...220000.0 kg Default: 60 kg

Total of load cells rated capacities

C 04 Device Constant
Range: 0.00100...1.0 kgh/t Default:
0.04 kgh/t

Unit: kg h/t = kg / (t/h)

The device constant indicates the correlation of


measured load and feed rate, i.e. load on load cell in
kg / t/h.

Q kg
GK = in
I t/h

Q = Measured load on load cell in kg


I = Feed rate in t/h

GK determines calibration accuracy. For value, see


technical Spec Sheet.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 43
VDM INTECONT PLUS

Block D : Calibrat. Results

D 01 Nom. Platform Load D 04 Basic Tare N


No input Default: 8000 kg No input Default: 0.00 kg/h
max. 10000 kg/h
Computed from rated data B 02 and C 04

Nominal measured load serves as reference for limit Result of taring program
values and zero setting programs.

For computation, see DETAILS chapter.


D 05 Tare Correction T
No input Default: 0.00 kg/h
D 02 Weight Correction max. +- 1000 kg/h

Range: 0.5000...2,0000 Default: 1,0000


Result of manual or automatic zero setting.
Proportionally influences feed rate I measurement
Every taring operation sets D 05 to 0.
I(corrected) = I(measured) ∗ D 02

Function: Correct measuring system through


check using material and
calibration program CW: Weight
Check D 06 Material Corr.
Range: 0.5000...2,0000 Default: 1

Proportionally influences measurement of linearized


D 03 Total Tare
feed rate I.
No input Default: 0.00 kg/h
I(corrected) = I(measured) ∗ D 06
Total tare = basic tare + tare correction
= D04 + D05 Function: Correct feed rate through check using
material

Attention!
If you enter Parameters D 02 ... D 05 in manual, enter
D 02 first.

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 44 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Block E : Analog Output

E 01 Source AO 1
Range: I (feed rate) Default: I
Q (measured load)
X = I, Q Xnom = nominal value

Note:
One of these values can be output in analog fashion.
1) Maximum output current is 20 mA.
Filters: Parameters G 02, G 04 2) Minimum output current corresponds to elevation E
02.
3) In Stop state of scale, output for I is set to elevation
value; for Q, measurement value is output.
E 02 Elevation AO 1
Range: 0.00...20.00 mA Default: 4.00 mA E 04 Source A02
Output current of 0% value I, or Q. Range: I (feed rate) Default: Q
Q (measured load)
E 03 Limit Value AO 1
See Parameter E01
Range: 0.00...1000.00 mA Default: 20.00 mA

Output current of 100% value I, or Q.

E 05 Elevation A02
Range: 0.00...20.0 mA Default: 4.00 mA

See Parameter E02

E 06 Limit Value A02


Range: 0.00...1000.00 mA Default: 20.00mA

See Parameter E03

X
i = ELEV + (END - ELEV)
Xnom

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 45
VDM INTECONT PLUS

Block F : Limit Values

F 01 Value for I MIN F 03 Value for I MAX


Range: -10...200.0 % Io Default: 5.0 % Io Range: -10...200.0 % Io Default: 120.0 %
Io
Related to nominal feed rate B 02
Related to nominal feed rate B 02
If measurement value exceeds MIN limit, event
message L1 is output. If measurement value exceeds MAX limit, event
message H1 is output.
Monitoring starts 10 s after start-up.

F 04 Event Class I MAX H1


Range: WARNING 2 Default:
WARNING 1 WARNING 1
F 02 Event Class I MIN L1 IGNORE
ALARM
Range: WARNING 2 Default:
WARNING 1 WARNING 1
IGNORE
ALARM

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 46 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Block G : Filter Settings

I = feed rate Q = measured load

G 01 I Display G 05 Afterfl. Time


Range: 0.0...600.0 s Default: 3.0 s Range: 0.0...2000.0 s Default: 3.0 s

Feed rate display During specified time, totalization goes on after scale
stop.

All filters are of the first-order type


G 02 I Analog Output (exponential), i.e. upon abrupt
change of signal, approx. 2/3
Range: 0.0...600.0 s Default. 3.0 s of full scale are reached
after set time.
Feed rate analog output
Long times lead to a stable
but slowly refreshing display.

G 03 Q Display
Range: 0.0...600.0 s Default: 3.0 s

Measured load display

G 04 L/C Filter
Range: 0.0...600.0s Default: 1.0 s

Applies to all functions and displays depending on


measured load

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 47
VDM INTECONT PLUS

Block H : Additional Device

H 01 AUTO Zero Active H 03 Zero Set Limit


Range: NO Range: 0.00...100.00 %Io Default: 5.00 %Io
YES Default: NO
Bezug: Nom. Platf. Load D01
Lets you select automatic zero setting.
Max. admissible amount of the total of all manual and
NO : No automatic zero setting zero setting operations.
If limits are exceeded, correction value is not
YES : Automatic is running, if acquired.
1. Measurement is cut off
2. No other setting program is running Monitoring : Parameter H 04, message C5
3. No parameters are input.
Start delay is 60s.

Measuring time : Parameter C 01 H 04 Tare Corr. > MAX C5


Monitorings: Parameters H 02...H04 Range: WARNING 1 Default:
WARNING 2 WARNING 1
Display feature : “0” in upper display field ALARM
IGNORE
Automatic zero setting result exceeds limit H 03.
Value is not acquired.

H 02 Autom. Zero Limit

Range: 0.00...10.00%Q Default: 1%Q H 05 ZDO Active


Related to: Nom. Platform Load D01 Range: NO
YES Default: NO
If mean value measured by automatic zero setting
function falls below H 02 and H03 over time C01, zero Active Zero Drop Out (see H 06).
point is corrected.
H 06 ZDO Limit
Result: Parameter
: D 05
Range: 0.0...10.00 %Io Default: 1.00 %Io

Related to: Nominal Feed Rate B 02

If Zero Drop Out is active and feed rate exceeds set


limit, value is set to 0.

No display feature.

Conditions: Totalization ON or Afterfl. Time


G 05.

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 48 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Block I : Batch Mode

For detailed batching sequence, see DETAILS chapter.

I 01 Batch Dribble FD I 03 Adaption Fact.


Range: 0.00...220 000 kg Default: 100.000 kg Range: 0.0...1.0 Default: 0.5

If batch setpoint (I 01-I 02) is reached, dribble feed Pre-cut-off amounts I 01 and I 02 are adapted
output (P08) is set. automatically so that the system better fits the
Signal can be used, e.g. to reduce prefeeder rate. situation upon next batch.

The two values are adapted by value


“batch error * I 03".
I 02 Batch End I 03 = 0 : no adaption
I 03 = 1 : full adaption
Range: 0.00...220 000 kg Default: 0.000 kg

If batch setpoint has reached pre-cut-off amount I 02, Intermediate values cause a filtered adaption which is
batching terminates and prefeeder stops. preferable in plants with unprecise repeatability
behaviour.

I 04 Batch Tolerance
Range: 0.0...2200000.0 kg Default:
100000.000 kg
I 02 considers material afterflow, if any.
Related to batch setpoint

Admissible deviation from setpoint. Check takes place


after completion of batch.

I 05 Out of Tolerance B1
Range: WARNING 1 Default:
WARNING 2 WARNING 1
ALARM
IGNORE

If limit value I 04 is exceeded, event message B1 is


output .
0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 49
VDM INTECONT PLUS

I 06 AUTO Print
Range: NO Default: NO
YES

YES : Automatic printout after every complete


batch
NO: Batch report can be printed only using
control menu.

06.03.03 16:20:16
Batch Setpoint 200 kg
Batch Actual Val. 205 kg
Counter 1 31779 kg
Counter 2 32 t
Batch-Number 6

Events B1 Out of Tolerance I05

I 07 Batch Source
Range: OP
FB Default: OP

OP : Enter batch and make-up setpoints from


INTECONT keyboard
FB : Values are set via fieldbus.

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 50 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Block J : Printer Settings

J 01 Baud Rate J 03 Print Page Length


Range: 2400 Default: 9600 Range: 9...127 lines Default: 72 lines
4800
9600
19200
38400 Page length for Quantity Report

Speed of transmission to printer Line spacing is always 1/6 inch.

Printer initializes upon change of parameter or


power-up.
J 02 Print Subtotal
Range: Error Default: Error
YES Quantity Report
NO
28.01.04 11:45:10
Error : Every event is printed automatically as
soon as occurred Counter 1 [kg] 12000
YES : See above, but complete with totalizing Counter 2 [kg] 90000
counter (FMZ) sub-totals Zero set before [h] 3.00
NO : No printout
Event
L1 I<MIN F2
Printing takes place in Normal and Batching modes.

30.09.03 11:45:21 L1 W1 --> I < MIN


30.09.03 11:59:01 L1 W1 <-- I < MIN

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 51
VDM INTECONT PLUS

Block K : Maintenance Int.

K 01 Maintenance Elec. K 04 Event Maint. Run. S3


Range: 0...10000 h Default: 3000 h Range: WARNING 1 Default:
Message: S4 WARNING 2 WARNING 1
(K 02) IGNORE

Alerts you on maintenance work to be effected as a


function of voltage ON-time.
Total measuring times exceeds time K 03.
If a time interval has elapsed, message S3 is output.

K 02 Event Maint. EL. S4


Range: WARNING 1 Default:
WARNING 2 WARNING 1
IGNORE

The total of power ON-times exceeds time K 01.


If a time interval has elapsed, message S4 is output.

K 03 Maint. Scale Run.


Range: 0...10000 h Default: 3000 h
Message: S3
(K 04)

Alerts you on maintenance work to be effected as a


function of scale run time.

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 52 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Block L : Comm. Fieldbus

L 01 Protocol Type L 05 Resolution


Range: NO Default: NO Range: 1...32767 Default: 4096
MODBUS COMP.
S5-BCC COMP. Resolution of data for nominal value in Modbus
MODBUS protocol (integer format).
PROFIBUS DP
DEVICENET

Eligible protocol variants. L 06 Word Sequence


Every protocol requires an optional interface card to
Range: I: std/L:std Default: I: std/L: std
be present.
I: swp/L: std
“COMP” identifies the compatible protocols.
I: std/L: swp
I: swp/L: swp

Determines the word sequence within a data double


L 02 Host Timeout
word in the Modbus protocol.
Range: 0...600s Default: 10s “I” stands for IEEE-754 values (floating point values)
“L” stands for 4-byte integer values
If timeout value exceeds zero, a message from host “std” does not swap the word sequence; “swp” does.
system is expected to arrive during set time.

L 07 Physics
L 03 Comm. Error Host S9
Range: RS232 Default: RS 485
Range: IGNORE Default: IGNORE RS 422
W1 (WARNING 1) RS 485
W2 (WARNING 2)
A (Alarm) Sets interface physics for Modbus

If no message is received during the time set by


Parameter L02, event message S9 “Data Link Host” is
output. L 08 Baud Rate
Range: 2400 Default: 9600
4800
9600
L 04 Address 19200
38400
Range: 1...254 Default: 1
Modbus baud rate
Slave address for Modbus protocol

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 53
VDM INTECONT PLUS

L 09 Format Data L 14 Address


Range: 8-E-1 Default: 8-E-1 Range: 0...126 Default: 16
8-0-1
8-N-2 Profibus DP slave address
8-N-1

Modbus data format (data bits - parity bit - stop bits)


L 15 FLOAT-format
L 10 FLOAT-format Range: SIEMENS-KG Default: IEEE
IEEE
Range: SIEMENS-KG Default:
IEEE SIEMENS-KG
Determines representation of floating point values for
Profibus DP protocol

Determines representation of floating point values for


S5 protocol

L 11 Physics L 16 Configuration
Range: RS 232 Default: RS 422 Range: FIXED-1 Default: FIXED-1
RS 422 FIXED-2
NO-PARA-ID
PARA-ID
Sets interface physics for S5 protocol

Determines structure and size of process image


(Profibus DP)
L 12 Baud Rate
Range: 2400 Default: 9600
4800
9600 L 17 Address
19200
38400 Range: 0...63 Default: 16

Baud rate for S5 protocol DeviceNet slave address

L 13 Format Data L 18 Baud Rate


Range: 8-E-1 Default: 8-E-1 Range: 125k Default: 125k
8-0-1 250k
8-N-2 500k
8-N-1
DeviceNet baud rates

S5 data format (data bits - parity bit - stop bits)

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 54 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

L 19 Configuration
Range: FIXED-1 Default: FIXED-1
FIXED-2
NO-PARA-ID
PARA-ID

Determines structure and size of process image


(DeviceNet)

L 20 Byte Sequence
Range: LOW-High Default: LOW-High
High-LOW

Determines byte sequence within a data word

L 21 Word Sequence
Range: I: std/L:std Default: I: std/L: std
I: swp/L: std
I: std/L: swp
I: swp/L: swp

Determines the word sequence within a data double


word in the DeviceNet protocol.
“I” stands for IEEE-754 values (floating point values)
“L” stands for 4-byte integer values
“std” does not swap the word sequence; “swp” does.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 55
VDM INTECONT PLUS

Block M: Events

M 01 Power Failure E1 M 05 L/C Input > MAX H4


Range: ALARM Default: ALARM Range: ALARM Default: ALARM
WARNING 1 WARNING 1
WARNING 2 WARNING 2
IGNORE
Load on load cell exceeds 110 % of the total of load
cell rated capacities (C 03).
Scale does not start automatically regardless of event
class. Full scale: approx. 115 % with CSD load cells
160% with HBM load cells
M 02 Memory Error S1

ALARM: No changes possible M 06 L/C Input < MIN L4

Scale no longer operable Range: ALARM


WARNING 1
WARNING 2 Default: ALARM

Load on load cells is smaller than 1% of total load


M 03 L/C Input C1 cells rated capacities (C 03)

Range: ALARM Default: ALARM Meldung: L4


WARNING 1
WARNING 2
M 07 Simulation Active S7
Range: WARNING 1 Default:
1. Load cell not (or improperly) connected. WARNING 2 WARNING 2
2. Analog-to-digital converter of measuring amplifier is ALARM
in saturation (see Service Value wz). IGNORE
3. Supply voltage is below 19V.
Simulation Mode is active.
Error must be available for at least 3 s.
M 08 Error Ext. Event E6
Range: IGNORE Default: ALARM
WARNING 1
M 04 No Release S2 WARNING 2
ALARM
Range: WARNING 1 Default:
WARNING 2 WARNING 1
IGNORE Event is output if external digital input (Parameter
ALARM O04) is set.
No RELEASE input signal

Exception:
IGNORE always releases scale.
0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 56 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Block N: Linearization

N 01 Linearization ON N 06 Lin.-S3
Range: NO Default: NO Range: 0.10...1000.00%Io Default: 75%Io
YES
Linearization point 3:
This function lets you linearize feed rate
measurement. See N 02
The 4 linearization points can be determined through
checks using material. Place points not needed, or
measured, outside the measuring range or interpolate.
N 07 Lin.-I3
N 02 Lin.-S1
Range: 0.1...1000.0%Io Default: 75%Io
Range: 0.10...1000.00%Io Default: 25%Io
Linearization point 3:
Related to nominal feed rate B02
See N 03
Linearization point 1:

Material amount fed out divided by measuring time


N 08 Lin.-S4
Range: 0.10...1000.0%Io Default: 100%Io
N 03 Lin.-I1 Linearization point 4:
Range: 0.1...1000.0%Io Default: 25%Io
See N 02
Related to nominal feed rate B02

Linearization point 1: N 09 Lin.-I4


Check amount displayed on INTECONT divided by Range: 0.1...1000.0%Io Default: 100%Io
measuring time
Linearization point 4:

N 04 Lin.-S2 See N03


Range: 0.10...1000.00%Io Default: 50%Io
N 10 Lineariz. Error B9
Linearization point 2:
Range: WARNING 1 Default:
See N 02 WARNING 2 WARNING 2
ALARM
IGNORE
N 05 Lin.-I2 Monitoring for monotonously rising compensation
Range: 0.1...1000.0%Io Default: 50%Io takes place only if linearization is active.

Linearization point 2: 1. Upon start of linearization


2. Upon change to parameter
See N03
0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 57
VDM INTECONT PLUS

Block O: Digital Inputs

O 01 Release
Range: DI Default: DI (DI2)

Determines digital input used to release scale.

Setting “- - ” means that no release is required.

Default is DI2; however, any other free digital input


can be used as well.

O 02 DI Stop batch
Range: DI Default: —

Digital input signal used to stop a running batch

O 03 DI Ackn. Events
Range: DI Default: DI (DI1)

Determines digital input used to acknowledge events

O 05 DI Ext. Event
Range: DI Default: - -

Digital input used to output external fault signal

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 58 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Block P: Digital Outputs

P 01 DO Alarm Q 06 DO I-MAX
Range: DO Default: DO (DO3) Range: DO Default: DO (D02)
— —

Digital output used to report general alarm Digital output signal used to report that maximum feed
rate (F03) is exceeded up.
Contact output is independent of event class (F04).

P 02 DO Prefeeder ON
Range: DO Default: DO (DO6) P 06 DO Batch Active

Range: DO Default: —
Digital output used to START/STOP prefeeder —

Digital output signal used to report that a batch is


running.
Signal becomes active upon start of batch, and is
reset after batch complete. If batch is stopped, signal
P 03 DO Feeder ON
continues being available.
Range: DO Default: DO (DO5)

Digital output signal used to report START/STOP P 07 DO Full Feed


states of scale
Range: DO Default: —

P 04 DO I-MIN
Range: DO Default: DO (DO1) Full feed signal is available from start of batch until
— amount batched = batch setpoint - I01-I02 is
reached. Feeding continues in dribble feed.

Digital output signal used to report that minimum feed


rate (F01) is exceeded down.
Contact output is independent of event class (F02).
P 08 DO Dribble Feed
Range: DO Default: —

Dribble feed signal is output when full feed phase is


complete (see P07).

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Parameterization
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 59
VDM INTECONT PLUS

Block Q: Comm. EasyServe

Q 01 Station Address Q 04 Format Data


Range: 1...254 Default: 1 Range: 8-0-1 Default: 8-0-1
8-E-1
Make sure station address and baud rate of scale and 8-N-2
EasyServe are identical. 8-N-1
EasyServe lets you search for proper setting including
COM interface (menu: Tools/Options/Communication).
The station address is specially designed for plants EasyServe uses either a 10- or 11-bit character frame.
using a service bus. If the latter is not available,
select 1.
Connection to PC can also be made using a 9-pole Example:
SUB-D connector on X4 (RS 232 only) or a Phoenix
connector on X5 (RS232, RS422 or RS485). 8-0-1 means:
See also Wiring Diagram in chapter DETAILS.
1 start bit, 8 data bits, odd parity, 1 stop bit
(N = No Parity, E = Even Parity)

Q 02 Physics
Range: RS 232 Default: RS 232
RS 422
RS 485
Physics of data transmission protocol

Q 03 EasyServe Baudr.
Range: 9600 Default: 19200
19200

Data transmission rate

0405

Transmission to third parties and reproduction


Parameterization Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 60 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

9. Event Messages

System Message S S7 : Simulation Active

Operating in Simulation Mode, scale is not


S1 : Memory Error prepared for normal operation.
In Simulation Mode, all scale functions can
Program and parameter memories are be tested without material at the time of
checked in cycles. If an error is detected, commissioning.
scale is normally inoperable. Action : Stop “Simulation” function.
Action : Contact the SCHENCK Parameter : M 07
Service.
Parameter: M02 S9 : DATA LINK HOST

Serial communication interrupted for longer


S2 : No Release than timeout period.
Action : Check cable connections.
No external RELEASE signal. Parameter : L 03
Scale cannot start.
Parameter : M 04

S3 : Maint. Scale Run.

Total ON-time of totalization exceeds set Electrical System E


limit.
Perform requisite service work, if
necessary. E1 : Power Failure
Acknowledgement of message does not
influence time intervals. Power failed or cut off.
Parameters : K 03, K 04 It is possible that totalization has stopped
during this time.
Action : Acknowledge message.
Parameter : M 01
S4 : Maintenance Int.Elec

The INTECONT power supply has been E6 : External Input


switched on for a set time.
Perform requisite service work, if External fault signal available across fault
necessary. input.
Acknowledgement of message does not Parameter : M08
influence time intervals.
Parameters : K 01, K 02

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Event Messages
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 61
VDM INTECONT PLUS

Calibration C Maximum H

C1 : L/C Input H1 : I > MAX


1. Load cell cable broken, not (or
improperly) connected. Current feed rate exceeds set limit value.
2. Supply voltage smaller than 19V Action : Normally none, unless
Action : Check cabling. message H4 is additionally
If OK, check load cell available or system-
amplifier. specific limits have to be
Parameter : M05 observed.
Parameters : F 03, F 04

H4 : L/C Input > MAX


C5 : Tare Corr. > MAX
Scale overloaded. Errors in measurement
Automatic zero setting result exceeds can occur.
zeroing limit. No correction takes place. Action : Check material infeed.
Action: Retare device. Parameter : M 05
Parameters: H 03, H 04

Minimum L

L1 : I < MIN

Current feed rate has fallen below set limit


value.
Action : System-specific
Parameters : F 01, F 02

L4 : L/C Input < MIN

Weighing system is underloaded, or not


positively tied. Measurement can fail.
Action : Check mechanical scale
system and cabling.
Parameter : Q 06

0405

Transmission to third parties and reproduction


Event Messages Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 62 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Material Flow (Batch) B Signal Lamps

B1 : Out of Tolerance a (green) POWER OK


LED not lit:
Batch not completed with preset accuracy. 1. No power supply
Tolerance : Parameter I04 2. Device defective
Event : Parameter I05 3. All other functions OK, LED
Cause : Automatic adaption probably defective. Call
connected (Parameter display test.
I 03)?
Material infeed faulty ? b (green) CPU OK
If display is pending or flashing,
processor system is faulty,
Scale is inoperable.
B9 : Linearization

Linearisation for feed rate measurement


X (red) ALARM
flashes if an Alarm is available.
improperly set. Display additionally shows
Message is output only if linearization is event code.
active.
Action : Check relevant parameters Action:
to see if preset curve see relevant event code.
features plateaus or
turning points. MIN (red) MIN LIMIT VALUE
Parameters : N 01...N 10 lit if feed rate limit value is
exceeded down.

Action:
see L1: I<MIN

MAX (red) MAX LIMIT VALUE


lit if feed rate limit value is
exceeded up.

Action:
see H1: I>MAX.

No power supply:

Upon short circuit on the secondary side of the power


supply, internal overload protection responds.
Disconnect power for approx. 1 min., and it is ready to
operate again.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Event Messages
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 63
VDM INTECONT PLUS

This page left intentionally blank

0405

Transmission to third parties and reproduction


Event Messages Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 64 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

10. Commissioning

Test Plug

Almost any possible error in operation is reported by


event message. For interpretation, see Chapter 10.

Check INTECONT for proper operation by using a


simple test plug. This helps to see whether the fault is
with load cell, cabling or electrical equipment.

1. Switch plug as shown in drawing.


2. Withdraw load cell connector X7 and replace by test
plug.

At the indicated resistance values, the following


service values result:

1. wz apr. 1.1mV/V
2. Load cell apr. 50 % (C02 =2mV/V)
utilization aw apr. 35% (C02 =2.85mV/V)

If wz is in specified range, measuring amplifier


operates properly.

Note:
With different R1 and R2 resistance values, the
following raw measured value results:

Raw measured value ~ 500 * R2 / R1 [mV/V].

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Commissioning
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 65
VDM INTECONT PLUS

This page left intentionally blank

0405

Transmission to third parties and reproduction


Commissioning Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 66 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

11. Details
Start Sources

Fig.: START Sources

Sources
START/STOP Synchronization
The “Start/Stop” functions can be started from different
control sources preselected via parameters. Upon changeover from external setpoint source or
The “Keyboard Mode” dialog function lets you shift keyboard, external setpoint is acquired. In reverse
from preselected sources to keyboard and vice versa. direction, the external source is active.

Parameter:

B 03 START Source FB (fieldbus)


OP (keyboard)
DI (contact)

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Details
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 67
VDM INTECONT PLUS

Control Inputs/Outputs

Fig.: Control Inputs/Outputs

Operating Sequence

1 As long as no Release signal is available (contact


open), no start command is effective.
2 Scale is released.
3 L-H edge of Start input or Start command from
another source starts measurement and prefeeder.
4 Cut-off command
Prefeeder immediately stops, measurement and
totalization continue for time G 05.
5 Feed rate acquisition and totalization complete.

Measured load is acquired and displayed also in Stop


state of scale.
Running display (rotating point) reports all phases
during which totalization is active.
Cut-off after alarm is identical with normal cut-off
sequence.

0405

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 68 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Batching

Principle: Sequence:
When batch is complete, material prefeeder cuts off. 0 Start batch using Start command.
Changeover from full feed to dribble feed can be Prefeeder and totalizing counter start operating.
effected using prefeeder speed or opening angle. . 1 Stop batch using Stop command.
Measurement continues for time G 05.
Output signals (Batch Running, Full Feed, Dribble 2 Continue batch using Start command.
Feed) can be placed on free output contacts, if
required.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Details
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 69
VDM INTECONT PLUS

3 Dribble feed changeover point Alarm:


FM = SET - A - F is reached. Dribble Feed signal
changes its level. Batch stops (measuring wheel and prefeeder
A and F are the cut-off amounts defined by immediately cut off) and can be resumed after
parameters I 01 and I 02. removal of cause and acknowledgement of event
message.
4 Cut-off point
AM = SET - A is reached and batch is complete.
Prefeeder stops.

5 Material afterflow
Power OFF:
If parameters A and F are properly set, defined
setpoint is exactly reached.
Batch aborts, batching mode remains selected.
If note, see “Adaption”.
All counter readings and amounts batched are stored
for an unlimited period of time.
Next Start command starts new batch.

Adaption:

After every complete batch, INTECONT uses the


missing material amount to compute a correction
value (I02). Dribble feed changeover point is adapted
automatically.

Error = SETPOINT - amount batched

Cut-off point for next batch is computed from error and


an evaluation factor.

A(new) = A(old) + FAK * error

A(new) = Batch cut-off point I02


FAK = Adaption factor I03

Errors smaller than smallest display digit are not


corrected.

DI Complete Batch:

The Complete Batch contact acts like a Stop


command with additional abort of batch. Next Start
command starts new batch.

0405

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 70 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Data Flow Charts: Signal Flow

Fig.: Simplified Signal Flow Chart

Note: Code Meaning


WZ Load cell
In normal INTECONT operation, the data flow charts D Cross-flexure strip for chute and check weight
Qwz Measured load on load cell
need not be known.
QPRF Measured load on load cell C05
In special cases, they can be used to trace internal
LWZ Load cell lever arm
normalizations relevant for precalibration (theoretical LPG Check weight lever arm
calibration). QP Check weight
GK Device constant C04
GEWKOR Weight correctionr D02
TARA Basic tare D04
TARKOR Tare correction D05
MATKOR Material correction D06
WZF0 Load cell rated capacity C03
WZKENN Load cell characteristic value C02
Q Measured load
P Flow rate

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Details
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 71
VDM INTECONT PLUS

Device Constant GK C04 in kg/(t/h) Calibration CW

GK indicates the correlation of load cell load and feed The CW calibration program compares the effective
rate and thus determines calibration accuracy. check weight entered (load on load cell through check
weight) with measured load cell load.
GK = QNOM / PNOM

QNOM = Spec Sheet value; does not refer to


Parameter L/C Rated Cap. (C 03)!

L/C Rated Cap. WZF0 C03 in kg

Enter total of load cells rated capacities.

WZF0 influences calibration accuracy.

L/C Charac. Value WZKENN C02 in mV/V

Load cell transmission coefficient WZKENN is an


important calibration value.

Ua = Ue x WZKENN x (F / WZF0)

Ua Output voltage in mV
Ue Input voltage in V

CSD load cells WZKENN 2.85mV/V


HBM load cells WZKENN 2 mV/V 1)

1) With certain types, WZKENN is not calibrated.

For exact value, see type plate.

Effective Check Weight QPRFC05 in kg

Enter the force the check weight exerts on load cell.

Effective check weight QPRF = U2 x check weight

U2 = LPG / LWZ (see Fig.)

Feed rate is P = QPRF / GK in kg/h

(MATKOR = 1, TARKOR = 0, LIN on Linear)

0405

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 72 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Wiring Diagram
Base Card

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Details
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 73
VDM INTECONT PLUS

0405

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 74 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Option Card

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Details
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 75
VDM INTECONT PLUS

Namur Inputs: n Cable fastening

> 8 mA = short circuit


1.65...8 mA = level 0
0.1...1.65 mA = level 1 (sensor covered)
< 0.1 mA =cable breakage

Option Card:

The option card is affixed to the INTECONT cover.


Signal exchange with base card is via a pluggable flat
cable connector.
If pulled off, system behaves as if no option card was
present and only the operating functions and In the rear wall of the INTECONT, under each
parameters of the base card can be used. connector, several slots are provided. The upper slot
pair is reserved for the cable clamp which presses the
Cabling Hints:
shielded cable against the rear wall. The shield needs
not be separately connected. The lower cut-out serves
n All cables are led to the device from the rear
for accommodation of a pull relief, e.g. by cable
(front-of-panel mounting housing) or from below
(flush mounting housing) and connected with binders.
special connectors. Connectors cannot be
confused. Attention!
n The INTECONT is isolated from the mounting
surface by its plastic housing. Connectors to base card require to be plugged-in
The rear earthing connector is internally connected with screwed connections up; connectors to option
with the electronics zero potential. card, with screwed connections down.
The protective ground used requires to be hum- and
transient-free. n Connectors on INTECONT rear wall:
The power supply zero potential (0V ext.) is not
connected to the earthing connector. Normally no
earthing is required..
n Make sure no leakage currents are conducted over
cable shields. Therefore shields are applied to one
side of INTECONT. The load cell housing is not
connected with shields.
Shields of data cables to host computer are
connected to ground on either side.
n The consumers connected to the relay and pulse
outputs require to be radioshielded, e.g. by
suppressor diodes or RC elements.
n Analog outputs
Long cables, particularly to frequency transducers,
can interact on analog outputs. We suggest to use
an isolating amplifier..
n Make sure the space between power and
measuring cables, if run in parallel, is min. 0.30 m.
If this is not possible lay measuring cable in steel
conduit. The same holds if the measuring cable is
laid over free stretches or close to powerful
transmitters (e.g. broadcasting stations). 0405

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 76 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Printer Connection
Interface : Serial, see “Technical Data”. Switch
Cable : The connection diagram refers to 1-1 : OFF 8-bit message
EPSON and CITIZEN printers. 1-2 : OFF No parity bit
1-3 : egal Even/odd
1-4 : OFF Postive edge
1-5...8 : OFF, ON, OFF, OFF 9600 baud
2-1...6 : ON, ON, OFF, OFF, OFF, OFF
(default)

Use Parameter J 01 to set baud rate to 9600. On the


right side of printer, there are two additional DIP
switches. Diagram view corresponds to top of printer.

Fig. Printer Cable Fig. EPSON Printer

Switch
EPSON printer: LX 850 1-1 : OFF 10 CPI character spacing
1-2 : OFF Zero without backslash
1-3 : ON Graphics character set
1-4 : OFF AUTO hyphenation activated
1-5 : ON Normal sprint speed .
1-6...8 : ON, ON, ON USA
2-1 : ON 12" page length
2-2 : OFF No single sheet
2-3 : OFF Jump over performation
2-4 : OFF No AUTO line feed

Information on switch position can be printed using


the printer self-test function. (Press line feed key while
starting printer).

CITIZEN Printer: 120D

Fig. EPSON Interface

The interface board is equipped with 2 DIP switches


used for selection of serial message base data.

To initialize:
Fig. Serial Interface
Printer is initialised via serial interface, 5s after
power-up of INTECONT PLUS.

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Details
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 77
VDM INTECONT PLUS

This page left intentionally blank

0405

Transmission to third parties and reproduction


Details Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 78 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

12. Replacement Instructions

Replacing INTECONT PLUS FIP —> INTECONT PLUS VEG

FIP base card wiring diagram

The VEG digital inputs and outputs can be configured,


i.e. the logical signals can be freely distributed on
physical signals.

0405 FIP option card wiring diagram

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Replacement Instructions
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 79
VDM INTECONT PLUS

The FIP base and option cards connection diagrams Load Cell
indicate for every digital input and output the relevant
INTECONT VEG parameter numbers used for FIP Physical Signal VEG
distribution on physical signals.
X5 3 OUT1 X7 3
The tables below compares the connector X5 4 REF1 X7 4
assignments of FIP and VEG for all physical signals. X5 5 IN2 X7 6
X5 6 IN1 X7 5
Digital Outputs X5 7 REF2 X7 7
X5 8 OUT2 X7 8
FIP Physical Signal VEG

X1 1,2 DA1 X1 1,2 Attention:


X1 3,4 DA2 X1 3,4 Signals IN1 and IN2 are swapped between FIP and
X1 5,6 DA3 X1 5,6 VEG. (VEG is compatible to DISOCONT).
X6 1,2 DA4 X8 1,2
X6 3,4 DA5 X8 3,4
X6 5,6 DA6 X8 5,6
X6 7,8 DA7 X8 7,8 Power Supply
X6 9,10 DA8 X8 9,10
FIP Physical Signal VEG
Digital Inputs X2 1 24V ext X2 1
X2 2 0V ext X2 2
FIP Physical Signal VEG X2 3 ext. supply 0V X2 3
X2 4 ext. supply 24V X2 4
X3 1,2 DE1 X3 1,2
X9 1,2 DE2 X3 3,4
X9 3,4 DE3 X6 6,7 Printer
—- DE4 X9 1,2
—- DE5 X9 3,4 FIP Physical Signal VEG
X3 5,6 Ext. input X3 5,6
X8 1 Screen X10 1
X8 2 TX X10 2
Analog Inputs/Outputs X8 3 RX X10 3

FIP Physical Signal VEG


Pulse Output
X9 9,10 A01 X6 4,5
—- A02 X9 5,6 FIP Physical Signal VEG

—- AI X6 1,2,3 X9 5 24V X6 8
X9 6 Open collector X6 9
X9 7 Open emitter X6 10
X9 8 0V X6 11

With VEG, fieldbus is connected via separate fieldbus


cards (FIP: Connector X7). See Fieldbus Manual
BVH2220.

0405

Transmission to third parties and reproduction


Replacement Instructions Technische of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
BV-H2219 GB 80 Redaktion BVED rights of ownership and copyrights.
INTECONT PLUS VDM

Connector Size

FIP

X1 Phoenix contact spacing 5mm : 6 pins


X2 Phoenix contact spacing 5mm : 4 pins
X3 Phoenix contact spacing 5mm : 7 pins
X5 Phoenix contact spacing 5mm : 8 pins
X6 Phönix Raster 5mm : 8 or 10 pins
X7 SUB-D : 9 pins
X8 SUB-D : 9 pins
X9 Phoenix contact spacing 5mm : 12 pins
X11 Phoenix contact spacing 5mm : 3 pins

VEG

X1 Phoenix contact spacing 5mm : 6 pins


X2 Phoenix contact spacing 5mm : 4 pins
X3 Phoenix contact spacing 3.5mm: 6 pins
X4 SUB-D : 9 pins
X5 Phoenix contact spacing 3.5mm: 7 pins
X6 Phoenix contact spacing 3.5mm: 11 pins
X7 Phoenix contact spacing 3.5mm: 8 pins
X8 Phoenix contact spacing 5mm : 10 pins
X9 Phoenix contact spacing 3.5mm: 9 pins
X10 Phoenix contact spacing 3.5mm: 7 pins

0405

Transmission to third parties and reproduction


of this documentation are not permitted.
SCHENCK PROCESS GmbH reserves all
Technische Replacement Instructions
rights of ownership and copyrights. Redaktion BVED BV-H2219 GB 81