ASHRAE 170
• Ventilation of Health Care Facilities (2008)
• First release of this standard
• Widely adopted in North America
ASHRAE 170
• Ventilation of Health Care Facilities (2008)
• First release of this standard
• Widely adopted in North America
2
9/16/2013
3
9/16/2013
Benefits
• Widely accepted design
• Supporting research
• Optional integrated filters
4
9/16/2013
Ceiling Space
• Diffusers consuming
valuable ceiling space
• 25 to 35 cfm/ft2 (fpm)
average face velocity
(ASHRAE 170 – 2008)
5
9/16/2013
Acceleration
• Result of ∆T between
supply and room air
• Archimedes principle
– ASHRAE RP-1397
Acceleration
• Tapering column of supply air
6
9/16/2013
7
9/16/2013
8
9/16/2013
“Primary”
Laminar Flow Diffuser
discharge velocity
9
9/16/2013
• 10 ft ceiling
10
9/16/2013
• Laminar flow
diffusers only in
“Primary Supply
Diffuser Array Area”
(per ASHRAE 170, 2008)
11
9/16/2013
• 25 to 35 cfm/ft2
(per ASHRAE 170, 2008)
• Diffuser layout
flexible if minimum
coverage satisfied
12
9/16/2013
• Inside perimeter of
air curtain diffusers:
• 2 ft offset from
Primary Diffuser
Array Area
• 3 ft offset from
surgical table
• 1000 cfm / 40 ft
= 25 cfm/ft
13
9/16/2013
14
9/16/2013
15
9/16/2013
16
9/16/2013
Draft potential
• Consider the locations of
staff in the O.R.
(i.e. Anesthesiologist)
Duct configuration
• Ensure laminar flow and
perimeter air curtain
diffusers are fed from
separate duct branches
17
9/16/2013
18
9/16/2013
19
9/16/2013
1920s 1960s
20
9/16/2013
2000s Now
21
9/16/2013
22
9/16/2013
Sheetrock
Sheetrock
Exception for
gasketed ceilings
23
9/16/2013
24
9/16/2013
Brushed
Aluminum
White
Powder
Coat
Clear Anodized
®
Unistrut Integration
• Mounting of C-Arm
support tracks
• Cath. labs
• Hybrid operating
rooms
25
9/16/2013
26
9/16/2013
Surface Mounting
Surface Mounting
Number of openings 38
Cut, finish, frame openings $14,700
27
9/16/2013
28
9/16/2013
29
9/16/2013
Questions?