Ansi/Amca Standard 500-L-07: Laboratory Methods of Testing Louvers For Rating

You might also like

You are on page 1of 59

ANSI/AMCA

Standard 500-L-07
Laboratory Methods of
Testing Louvers for Rating

An American National Standard


Approved by ANSI on January 17, 2006

AIR MOVEMENT AND CONTROL


ASSOCIATION INTERNATIONAL, INC.

The International Authority on Air System Components


ANSI/AMCA STANDARD 500-L-07

Laboratory Methods of Testing


Louvers for Rating

Air Movement and Control Association International, Inc.


30 West University Drive
Arlington Heights, IL 60004-1893
© 2007 by Air Movement and Control Association International, Inc.

All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections 107 and
108 of the United States Copyright Act without the permission of the copyright owner is unlawful. Requests for
permission or further information should be addressed to the Chief Staff Executive, Air Movement and Control
Association International, Inc. at 30 West University Drive, Arlington Heights, IL 60004-1893 U.S.A.
Authority

AMCA Standard 500-L-07 was adopted by the membership of the Air Movement and Control Association
International, Inc. on 19 October, 2006. It was approved as an American National Standard by the American
National Standards Institute (ANSI) and became effective on 11 January 2007.

ANSI/AMCA 500-L Review Committee

Robert Van Becelaere, Chairman Ruskin Manufacturing Co.

Larry Carnahan Airline Products

Sharyn I. Blanchard The Airolite Company

Roger Lichtenwald American Warming & Ventilation

Vincent Kreglewicz Arrow United Industries

Rich Niemela Cesco Products

Bill Vincent Construction Specialties, Inc.

Arnold Druda Farr, Inc.

Terry Horvat Greenheck Fan Corporation

Wendell Simmons Hart and Cooley, Inc.

James Sterriker Industrial Louvers, Inc.

Dane Carey NCA Manufacturing

James Tatum NCA Manufacturing

Mike Beaver P.C.I. Industries, Inc.

Tim Orris AMCA International, Inc.

Disclaimer

AMCA uses its best efforts to produce standards for the benefit of the industry and the public in light of available
information and accepted industry practices. However, AMCA does not guarantee, certify or assure the safety or
performance of any products, components or systems tested, designed, installed or operated in accordance with
AMCA standards or that any tests conducted under its standards will be non-hazardous or free from risk.
Objections to AMCA Standards and Certifications Programs

Air Movement and Control Association International, Inc. will consider and decide all written complaints regarding
its standards, certification programs, or interpretations thereof. For information on procedures for submitting and
handling complaints, write to:

Air Movement and Control Association International


30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.

or

AMCA International, Incorporated


c/o Federation of Environmental Trade Associations
2 Waltham Court, Milley Lane, Hare Hatch
Reading, Berkshire
RG10 9TH United Kingdom

Related AMCA Standards and Publications

AMCA Publication 501 Application Manual for Air Louvers

AMCA Publication 511 Certified Ratings Program for Air Control Devices
TABLE OF CONTENTS

1. Purpose . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

2. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3. Units of Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3.1 System of units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3.2 Basic units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3.3 Airflow rate and velocity . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3.4 Water flow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3.5 Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3.6 Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3.7 Gas properties . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3.8 Dimensionless groups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

3.9 Physical constants . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

4. Symbols and Subscripts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

4.1 Symbols and subscripted symbols . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

4.2 Additional measurements (planes of measurement) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

5. Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

5.1 Louver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

5.2 Air control louver . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

5.3 Free area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

5.4 Face area and core area . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

5.5 Psychrometrics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

5.6 Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

5.7 Performance variables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

5.8 Miscellanious . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

6. Instruments and Methods of Measurement . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

6.1 Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5
6.2 Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .5

6.3 Airflow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .6

6.4 Water flow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

6.5 Torque . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

6.6 Air density . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

6.7 Voltage . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

6.8 Meters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

6.9 Pneumatic actuator supply air pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

6.10 Pressure gauges . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

6.11 Chronometers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

6.12 Rain gauge . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

7. Equipment and Setups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

7.1 Setups . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

7.2 Ducts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

7.3 Chambers . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

7.4 Variable supply and exhaust systems . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

7.5 Wind driven rain simulation equipment . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

8. Objective, Observations, and Conduct of Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

8.1 Air performance-pressure drop test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

8.2 Air leakage flow rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

8.3 Water penetration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

9. Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

9.1 Calibration correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

9.2 Density and viscosity of air . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

9.3 Louver flow rate at test conditions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

9.4 Density correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

9.5 Air leakage-system leakage correction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

Annex A. Presentation of Air Performance Results for Rating Purposes . . . . . . . . . . . . . . . . . . . .44

Annex B. Water Penetration Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .45


Annex C. References . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .46

Annex D. Simulated Rain Spray Nozzles . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .47

Annex E. Water Eliminator Performance Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .48

Annex F. Wind Driven Rain Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .49


AMCA INTERNATIONAL, INC. ANSI/AMCA 500-L-07

Laboratory Methods of Testing 3.2 Basic units

Louvers for Rating The unit of length is the meter (m) or millimeter (mm);
I-P units are the foot (ft.) or the inch (in.). The unit of
mass is the kilogram (kg); the I-P unit is the
1. Purpose
poundmass (lbm). The unit of time is either the
The purpose of this standard is to establish uniform minute (min) or the second (s). The unit of
laboratory test methods for louvers. The temperature is either the degree Celsius (°C) or
characteristics to be determined include air leakage, kelvin (K). I-P units are either the degree Fahrenheit
pressure drop, water penetration, wind driven rain, (°F) or the degree Rankine (°R). The unit of force is
and operational torque. the newton (N); the I-P unit is the pound (lb).

It is not the purpose of this standard to establish 3.3 Airflow rate and velocity
minimum or maximum performance ratings.
3.3.1 Airflow rate. The unit of volumetric airflow rate
2. Scope is the cubic meter per second (m3/s); the I-P unit is
the cubic foot per minute (cfm).
This standard may be used as a basis for testing
louvers with air used as the test gas. 3.3.2 Airflow velocity. The unit of airflow velocity is
the meter per second (m/s); the I-P unit is the foot per
Tests conducted in accordance with the requirements minute (fpm).
of this standard are intended to demonstrate the
performance of a louver and are not intended to 3.4 Water flow rate
determine acceptability level of performance. It is not
the scope of this standard to indicate actual The unit of liquid volume is the liter (L); the I-P unit is
sequences of testing, nor is it in its scope to specify the gallon (gal). The unit of liquid flow rate is the liter
minimum or maximum criteria for testing. per second (L/s); the I-P unit is the gallon per minute
(gpm).
The parties to a test for guarantee purposes may
agree to exceptions to this standard in writing, prior to 3.5 Pressure
the test. However, only a test which does not violate
any mandatory requirement of this standard shall be The unit of pressure is the pascal (Pa) or the
designated as a test conducted in accordance with millimeter of mercury (mm Hg); the I-P unit is either
this standard. the inch water gauge (in. wg), or the inch mercury
column (in. Hg). Values in mm Hg or in in. Hg shall
3. Units of Measurement be used only for barometric pressure measurements.
The in. wg shall be based on a one inch column of
distilled water at 68°F under standard gravity and a
3.1 System of units
gas column balancing effect based on standard air.
The in. Hg shall be based on a one inch column of
SI units (The International System of Units, Le
mercury at 32°F under standard gravity in a vacuum.
Systéme International d'Unités) [1] are the primary
The mm Hg shall be based on a one mm column of
units employed in this standard, with I-P units (Inch-
mercury at 0°C under standard gravity in a vacuum.
Pound) given as the secondary reference. SI units
are based on the fundamental values of the
International Bureau of Weights and Measures [1],
3.6 Torque
and I-P values are based on the values of the
National Institute of Standards and Technology which The unit of torque is the newton-meter (N-m); the I-P
are, in turn, based on the values of the International unit is the pound-inch,(lb-in.).
Bureau. Annex A provides conversion factors and
coefficients for SI and other metric systems. 3.7 Gas properties

The unit of density is the kilogram per cubic meter


(kg/m3); the I-P unit is the pound mass per cubic foot

1
ANSI/AMCA 500-L-07

(lbm/ft3). The unit of viscosity is the Pascal-second, 3.9 Physical constants


(Pa-s); the I-P unit is the pound mass per foot-second
(lbm/ft-s). The SI unit of gas constant is the joule per The value of standard gravitational acceleration shall
kilogram-kelvin (J/kg-K); the I-P unit is the foot-pound be taken as 9.80665 m/s2 (32.174 ft/s2) at mean sea
per pound mass-degree Rankine, (ft-lbf/lbm-°R). level at 45° latitude [2]. The density of distilled water
at saturation pressure shall be taken as 998.278
3.8 Dimensionless groups kg/m3 (62.3205 lbm/ft3) at 20°C (68°F) [3]. The
density of mercury at saturation pressure shall be
Various dimensionless quantities appear in the text. taken at 13595.1 kg/m3 (848.714 lbm/ft3) at 0°C
Any consistent system of units may be employed to (32°F) [3]. The specific weights in kg/m3 (lbm/ft3) of
evaluate these quantities unless a numerical factor is these fluids under standard gravity in a vacuum are
included, in which case units must be as specified. numerically equal to their densities at corresponding
temperatures.

4. Symbols and Subscripts

4.1 Symbols and subscripted symbols

SYMBOL DESCRIPTION SI UNIT I-P UNIT

A Area of Cross-Section m2 ft2


Ac Louver Core Area/Area of hole in Calibration Plate m2 ft2
C Nozzle Discharge Coefficient dimensionless
D Diameter and Equivalent Diameter m ft
Dh Hydraulic Diameter m ft
E Energy Factor dimensionless
E Effectiveness %
F Beam Load N lb
g Acceleration due to gravity m/s2 ft/s2
G Water Volume Flow Rate L/s gpm
Kp Compressibility Coefficient dimensionless
l Length of Moment Arm m in
L Nozzle Throat Dimension m ft
Le Equivalent Length of Straightener m ft
Lx,xN Length of Duct Between Planes x and xN m ft
M Chamber Dimension m ft
n Number of Readings dimensionless
N Speed of Rotation rpm rpm
Ps Static Pressure Pa in. wg
Psx Static Pressure at Plane x Pa in. wg
Pt Total Pressure Pa in. wg
Ptx Total Pressure at Plane x Pa in. wg
Pv Velocity Pressure Pa in. wg
Pvx Velocity Pressure at Plane x Pa in. wg
pb Corrected Barometric Pressure Pa in. Hg
pe Saturated Vapor Pressure at tw Pa in. Hg
pp Partial Vapor Pressure Pa in. Hg
Q Louver Airflow Rate m3/s cfm
Qx Airflow Rate at Plane x m3/s cfm
qd Water Penetration Rate Collected Downstream
of the Test Louver L/h gpm
qs Water Supply Rate to Nozzles L/h gpm
qu Water Rejection Rate Collected Upstream
of the Test Louver L/h gpm
Qv Volume rate of Airflow at Flow Meter m3/s cfm
2
ANSI/AMCA 500-L-07

Qw/a Rainfall rate through the calibration plate L/h/m2 gpm/ft2


R Gas Constant J/kg-K ft-lb/lbm-°R
Re Reynolds Number dimensionless
T Torque N-m lb- in.
td Dry-Bulb Temperature °C °F
ts Static Temperature °C °F
tt Total Temperature °C °F
tw Wet-Bulb Temperature °C °F
V Velocity m/s fpm
vw Wind Velocity m/s fpm
vc Core Velocity m/s fpm
w Weight of water g oz.
W Rainfall Rate mm/hr. in./hr.
y Thickness of Straightener Element m ft
Y Nozzle Expansion Factor dimensionless
z Function Used to Determine Kp dimensionless
α Static Pressure Ratio for Nozzles dimensionless
β Diameter Ratio for Nozzles dimensionless
γ Ratio of Specific Heats dimensionless
ΔP Pressure Differential Pa in. wg
ΔPn Pressure Differential Across Nozzle Pa in. wg
Δpx,x' Pressure Differential Between Planes x and x' Pa in. wg
μ Air Viscosity Pa- s lbm/ft-s
ρ Air Density kg/m3 lbm/ft3
ρx Air Density at Plane x kg/m3 lbm/ft3

4.2 Additional subscripts (planes of measurement)

SUBSCRIPT DESCRIPTION

c Converted parameter
DS Louver and system
l Outlet of Louver under Test
m Measuring Point at the Airflow Meter
n Value at Selected Point of Airflow Rate/Static Pressure Curve
o Measured value with Calibration Plate
r Reading
s System
x Plane 0, 1, 2, ..., as appropriate
0 Plane 0 (general test area)
1 Plane of inlet of louver being tested
2 Plane of outlet of louver being tested
3 Plane of Pitot traverse
4 Plane of duct Ps measurement downstream of louver being tested
5 Plane of nozzle inlet Ps measurement
6 Plane of nozzle discharge station
7 Plane of Ps measurement in chamber downstream of louver being tested
8 Plane of Ps measurement in chamber upstream of louver being tested
9 Plane of duct Ps measurement of upstream louver being tested (used to show correct values
against references values)

3
ANSI/AMCA 500-L-07

5. Definitions 5.5 Psychrometrics

5.1 Louver 5.5.1 Dry-bulb. The air temperature measured by a


dry temperature sensor.
A louver is a device comprised of multiple blades
which, when mounted in an opening, permits the flow 5.5.2 Wet-bulb. The temperature measured by a
of air but inhibits the entrance of other elements. temperature sensor covered by a water-moistened
wick and exposed to air in motion. When properly
5.1.1 Fixed blade louver. A louver in which the measured, it is a close approximation of the
blades do not move. temperature of adiabatic saturation.

5.1.2 Adjustable blade louver. A louver in which 5.5.3 Wet-bulb depression. The difference between
the blades may be operated either manually or by dry-bulb and wet-bulb temperatures at the same
mechanical means. location.

5.2 Air control louver 5.5.4 Stagnation (total) temperature. The


temperature that exists by virtue of the internal and
A mechanical device which does not fit the definition kinetic energy of the air. If the air is at rest, the
of a louver and which, when placed in a duct or stagnation (total) temperature will equal the static
opening, is used to regulate airflow. temperature.

5.3 Free area 5.5.5 Static temperature. The temperature which


exists by virtue of the internal energy of the air only.
The minimum area through which air can pass. It is If a portion of the internal energy is converted into
determined by multiplying the sum of the minimum kinetic energy, the static temperature will be
distances between intermediate blades, top blade decreased accordingly.
and head and bottom blade and sill, by the minimum
distance between jambs. The percent of free area is 5.5.6 Air density. The mass per unit volume of air.
the free area thus calculated, divided by the gross
area of the air control louver × 100. See louver 5.5.7 Standard air. Standard air is air with a density
cross-sections (Figure 1). of 1.2 kg/m3 (0.075 lbm/ft3), a ratio of specific heats of
1.4, a viscosity of 1.8185 × 10-5 Pa-s (1.222 ×10-5
5.3.1 Free area velocity. Airflow through a louver lbm/ft-s). Air at 20°C (68°F) temperature, 50% relative
divided by its free area. humidity, and 101.3207 kPa (29.92 in. Hg) barometric
pressure has these properties, approximately.
5.4 Face area and core area
5.6 Pressure
5.4.1 Face area. The total cross sectional area of a
louver, duct or wall opening. 5.6.1 Pressure. Force per unit area. This
corresponds to energy per unit volume of fluid.
5.4.1.1 Face area velocity. Airflow through a louver
divided by its face area. 5.6.2 Absolute pressure. The value of a pressure
when the datum pressure is absolute zero. It is
5.4.2 Core area. The product of the minimum height always positive.
H and minimum width W of the front opening in the
louver assembly with the louver blades removed (see 5.6.3 Barometric pressure. The absolute pressure
Fig. 12). exerted by the atmosphere at the location of
measurement.
5.4.2.1 Louver calibration plate. The louver
calibration plate is a plate having an opening of the 5.6.4 Gauge pressure. The value of a pressure
same geometric shape and dimensions as the core when the reference pressure is the barometric
area of the test specimen. pressure at the point of measurement. It may be
negative or positive.
5.4.2.2 Core area velocity. The airflow rate through
the louver divided by the core area. 5.6.5 Velocity pressure. That portion of the air
pressure which exists by virtue of the rate of motion
5.4.2.3 Core ventilation rate. The airflow rate only. It is always positive.
through the core area of the louver.
4
ANSI/AMCA 500-L-07

5.6.6 Static pressure. That portion of the air operation of the test louver. The measurements must
pressure which exists by virtue of the degree of be sufficient to determine all appropriate
compression only. If expressed as gauge pressure, it performance variables as defined in Section 5.7.
may be negative or positive.
5.8.3 Test. A series of determinations for various
5.6.7 Total pressure. The air pressure which exists points of operation of a louver.
by virtue of the degree of compression and the rate
of motion. It is the algebraic sum of the velocity 5.8.4 Energy factor. Energy factor is the ratio of the
pressure and the static pressure at a point. Thus, if total kinetic energy of the airflow to the kinetic energy
the air is at rest, the total pressure will equal the static corresponding to the average velocity of air.
pressure.
6. Instruments and Methods of Measurement
5.6.8 Pressure differential. The change in static
pressure across a louver. 6.1 Accuracy [4]
5.7 Performance variables The specifications for instruments and methods of
measurement which follow include both accuracy
5.7.1 Pressure drop. The difference in pressure requirements and specific examples of equipment
between two points in a flow system, usually caused that are capable of meeting those requirements.
by frictional resistance to fluid flow through an Equipment other than the examples cited may be
opening, in a duct or other flow system. used provided the accuracy requirements are met or
exceeded.
Pressure drop is a measure of the resistance to
airflow across a louver. It is expressed as the 6.2 Pressure
difference in static pressure across the louver for a
specific rate of airflow. The total pressure at a point shall be measured on an
indicator, such as a manometer, with one leg open to
5.7.2 Air leakage. The amount of air passing atmosphere and the other leg connected to a total
through a louver when it is in the closed position and pressure sensor, such as a total pressure tube or the
at a specific pressure differential. It is expressed as impact tap of a Pitot-static tube. The static pressure
the volumetric rate of air passing through the louver at a point shall be measured on an indicator, such as
divided by the face area. a manometer, with one leg open to the atmosphere
and the other leg connected to a static pressure
5.7.3 Water penetration. The amount of water sensor, such as a static pressure tap or the static tap
passing through a louver while air is flowing through of a Pitot-static tube. The velocity pressure at a point
it at a specific free area velocity. It is expressed as shall be measured on an indicator, such as a
the weight of water passing through the louver manometer, with one leg connected to a total
divided by the free area, at a specified free area pressure sensor, such as the impact tap of a Pitot-
velocity. static tube, and the other leg connected to a static
pressure sensor, such as the static tap of the same
5.7.3.1 Insertion loss. The difference in simulated Pitot-static tube. The differential pressure between
rain penetration between the test specimen and the two points shall be measured on an indicator, such as
calibration plate at the same test conditions. a manometer, with one leg connected to the
upstream sensor, such as a static pressure tap, and
5.7.3.2 Louver effectiveness. The effectiveness of the other leg connected to the downstream sensor,
a louver at any core area velocity through the louver such as a static pressure tap.
is the insertion loss of the louver assembly divided by
the water penetration of the calibration plate at that 6.2.1 Manometers and other pressure indicating
velocity. instruments. Pressure shall be measured on
manometers of the liquid column type using inclined
5.8 Miscellaneous or vertical legs or other instruments which provide a
maximum uncertainty of 1% of the maximum
5.8.1 Shall and should. The word shall is to be observed test reading during the test or 3 Pa (0.01 in.
understood as mandatory; the word should as wg) whichever is larger.
advisory.
6.2.1.1 Calibration. Each pressure indicating
5.8.2 Determination. A determination is a complete instrument shall be calibrated at both ends of the
set of measurements for a particular point of scale and at least nine equally spaced intermediate

5
ANSI/AMCA 500-L-07

points in accordance with the following: specified in Figure 3 within 1.2 mm (0.05 in.) or
0.25% of the duct diameter, whichever is larger.
(1) When the pressure to be indicated falls in the Straighteners are specified so that flow lines will be
range of 0 to 0.5 kPa (0 to 2 in. wg), calibration approximately parallel to the duct axis.
shall be against a water-filled hook gauge of the
micrometer type or a precision micromanometer. 6.2.3 Static pressure taps. The static pressure at a
point may be sensed with a pressure tap of the
(2) When the pressure to be indicated is above 0.5 proportions shown in Figure 2. The pressure signal
kPa ( 2 in. wg), calibration shall be against a can then be transmitted to an indicator.
water-filled hook gauge of the micrometer type, a
precision micromanometer, or a water-filled U- 6.2.3.1 Calibration. Pressure taps having the
tube. proportions shown in Figure 2 are considered primary
instruments and need not be calibrated provided they
6.2.1.2 Averaging. Since the airflow and pressures are maintained in the specified condition.
through a louver in a typical system are never strictly
steady, the pressure indicated on any instrument will 6.2.3.2 Averaging. An individual pressure tap is
fluctuate with time. In order to obtain a representative sensitive only to the pressure in the immediate
reading, either the instrument must be damped or the vicinity of the hole. In order to obtain an average, at
readings must be averaged in a suitable manner. least four identical taps shall be manifolded into a
Multi-point or continuous record averaging can be piezometer ring. The manifold shall have an inside
accomplished with instruments and analyzers area at least four times that of each tap.
designed for this purpose.
6.2.3.3 Piezometer rings. Piezometer rings are
6.2.1.3 Corrections. Manometer readings shall be specified for upstream and downstream nozzle taps
corrected for any difference in specific weight of and for outlet duct or chamber measurements unless
gauge fluid from standard, any difference in gas Pitot traverse is specified. Measuring planes shall be
column balancing effect from standard, or any located as shown in the figure for the appropriate
change in length of the graduated scale due to setup.
temperature. However, corrections may be omitted
for temperatures between 14°C and 26°C (58°F and 6.2.4 Other pressure indicating instruments.
78°F), latitudes between 30° and 60°, and elevations Pressure measuring systems consisting of indicators
up to 1500m (5000 ft.). and sensors other than manometers and Pitot-static
tubes, or static pressure taps may be used if the
6.2.2 Pitot-static tubes [5] [6]. The total pressure or combined uncertainty of the system including any
the static pressure at a point may be sensed with a transducers does not exceed the combined
Pitot-static tube of the proportions shown in Figure 4. uncertainty for an appropriate combination of
Either or both of these pressure signals can then be manometers and Pitot-static tubes, or static pressure
transmitted to a manometer or other indicator. If both taps.
pressure signals are transmitted to the same
indicator, the differential shall be considered the 6.3 Airflow rate
velocity pressure at the point of the impact opening.
An airflow rate shall be calculated either from
6.2.2.1 Calibration. Pitot-static tubes having the measurements of velocity pressure obtained by Pitot
proportions shown in Figure 4 are considered primary traverse or from measurements of pressure
instruments and need not be calibrated provided they differential across a flow nozzle. Airflow rates less
are maintained in the specified condition. than 10 cfm may be measured directly using a airflow
meter.
6.2.2.2 Size. The Pitot-static tube shall be of
sufficient size and strength to withstand the pressure 6.3.1 Pitot traverse [7]. Airflow rate may be
forces exerted upon it. The outside diameter of the calculated from the velocity pressures obtained by
tube shall not exceed 1/30 of the test duct diameter traverses of a duct with a Pitot-static tube for any
except that when the length of the supporting stem point of operation provided the average velocity
exceeds 24 tube diameters, the stem may be corresponding to the airflow rate is at least 6.35 m/s
progressively increased beyond this distance. The (1250 fpm).
minimum practical tube diameter is 2.5 mm (0.10 in.).
6.3.1.1 Traverse point. The number and locations
6.2.2.3 Support. Rigid support shall be provided to of the measuring stations on each diameter and the
hold the Pitot-static tube axis parallel to the axis of number of diameters shall be as specified in Figure 3.
the duct within 1 degree and at the head locations
6
ANSI/AMCA 500-L-07

6.3.1.2 Averaging. The stations shown in Figure 3 6.3.4 Other airflow measurement methods.
are located on each diameter according to the log- Airflow measurement methods that utilize a meter or
linear rule [8]. The arithmetic mean of the individual a traverse other than flow nozzles or Pitot-static tube
velocity measurements made at these stations will be traverse described herein may be used if the
the mean velocity through the measuring section for uncertainty introduced by the method does not
a wide variety of profiles [9]. exceed that introduced by an appropriate flow nozzle
or Pitot-static tube traverse method. The contribution
6.3.2 Nozzles. Airflow rate may be calculated from to the combined uncertainty in the airflow rate
the pressure differential measured across an airflow measurement shall not exceed that corresponding to
nozzle or bank of nozzles for any point of operation 1.2% of the discharge coefficient for a flow nozzle
provided the pressure differential across the nozzle [11].
bank is at least 25 Pa (0.1 in. wg). The uncertainty of
the airflow rate measurement can be reduced by 6.4 Water flow rate
changing to a smaller nozzle or combination of
nozzles for low airflow rates. A calibrated flow meter capable of indicating flow in
increments of 0.5 liter per minute (0.1 gallon per
6.3.2.1 Size. The nozzle or nozzles shall conform to minute) or less, per unit of time or less shall be used.
Figure 8A. Nozzles may be of any convenient size. Measurement accuracy shall be within 0.5% of the
However, when a duct is connected to the inlet of the indicated flow rate.
nozzle, the ratio of nozzle throat diameter to the
diameter of the inlet duct shall not exceed 0.525. Water flow meters shall be calibrated against a
known weight of water flowing for a measurement
6.3.2.2 Calibration. The standard nozzle is time period or factory calibrated.
considered a primary instrument and need not be
calibrated if maintained in the specified condition. 6.5 Torque
Reliable coefficients have been established for throat
dimensions L = 0.5D and L = 0.6D, shown in Figure A torque meter having a demonstrated accuracy of
8A [10]. Throat dimension L = 0.6D is recommended ±2% of observed reading may be used to determine
for new construction. power.

6.3.2.3 Chamber nozzles. Nozzles without integral 6.5.1 Calibration. A torque meter shall have a static
throat taps may be used for multiple nozzle chambers calibration and may have a running calibration
in which case upstream and downstream pressure through its range of usage. The static calibration
taps shall be located as shown in the figure for the shall be made by suspending weights from a torque
appropriate setup. Alternatively, nozzles with throat arm. The weights shall have certified accuracies of
taps may be used in which case the throat taps ±0.2%. The length of the torque arm shall be
located as shown in Figure 8A shall be used in place determined to an accuracy of ±0.2%.
of the downstream pressure taps shown in the figure
for the setup and the piezometer for each nozzle 6.5.2 Tare. The zero torque equilibrium (tare) and
shall be connected to its own indicator. the span of the readout system shall be checked
before and after each test. In each case, the
6.3.2.4 Ducted nozzles. Nozzles with integral throat difference shall be within 0.5% of the maximum value
taps shall be used for ducted nozzle setups. measured during the test.
Upstream pressure taps shall be located as shown in
the figure for the appropriate setup. Downstream taps 6.6 Air density
are the integral throat taps and shall be located as
shown in Figure 8A. Air density shall be calculated from measurements of
wet-bulb temperature, dry-bulb temperature, and
6.3.2.5 Taps. All pressure taps shall conform to the barometric pressure. Other parameters may be
specification in Section 6.2.3 regarding geometry, measured and used if the maximum error in the
number, and manifolding into piezometer rings. calculated density does not exceed 0.5%.

6.3.3 Airflow meter. An airlow rate may be 6.6.1 Thermometers. Both wet and dry-bulb
measured directly using a calibrated airflow meter temperatures shall be measured with thermometers
capable of measuring airflow in increments of 0.2 L/s or other instruments with demonstrated accuracies of
(25 cubic feet per hour) or less. A direct-reading ±1°C (±2°F) and readability of 0.5°C (1°F) or finer.
airflow meter may be used if the airflow is below 4.7
L/s (10 cfm).

7
ANSI/AMCA 500-L-07

6.6.1.1 Calibration. Thermometers shall be 6.10 Pressure guages


calibrated over the range of temperatures to be
encountered during test against a thermometer with Supply air pressure for pneumatic actuator shall be
a calibration that is traceable to the National Institute measured with a pressure gauge or other instrument
of Standards and Technology (NIST) or other national with a demonstrated accuracy of ±10 kPa (1 psi) and
physical measures recognized as equivalent by a readability of 10 kPa (1 psi) or less.
NIST.
6.11 Chronometers
6.6.1.2 Wet-bulb. The wet-bulb thermometer shall
have an air velocity over the water-moistened wick- Time measurements shall be made with a watch
covered bulb of 3.5 to 10 m/s (700 to 2000 fpm) [12]. having minimum accuracy of ± 0.2% per day.
The dry-bulb thermometer shall be mounted
upstream of the wet-bulb thermometer so its reading 6.12 Rain guage
will not be depressed.
Rain gauge shall have an accuracy of ± 2% of reading.
6.6.2 Barometers. The barometric pressure shall
be measured with a mercury column barometer or
7. Equipment and Setups
other instrument with a demonstrated accuracy of
±170 Pa (± 0.05 in. Hg) and readable to 34 Pa (0.01
in. Hg) or finer.
7.1 Setups

6.6.2.1 Calibration. Barometers shall be calibrated Six test louver setups are diagramed in Figures 5.1,
against a mercury column barometer with a 5.2, 5.4, 5.5, 5.6, and 5.11. Six airflow measurement
calibration that is traceable to the National Institute of setups are diagramed in Figures 6.1, 6.2, 6.3, 6.4,
Standards and Technology (NIST) or other national 6.5 and 6.6.
physical measures recognized as equivalent by
NIST. A convenient method of doing this is to use an 7.1.1 Installation Types. There are three categories
aneroid barometer as a transfer instrument and carry of installation types which can be used with louvers.
it back and forth to the Weather Bureau Station for The installation types and the corresponding test
comparison. A permanently mounted mercury louver setup figures are:
column barometer should hold its calibration well
enough so that comparisons every three months Figure 5.1 - Free Inlet, Ducted Outlet
should be sufficient. Transducer type barometers Figure 5.2 - Ducted Inlet, Free Outlet
shall be calibrated for each test. Barometers shall be Figures 5.4, 5.5, 5.6, 5.11 - Free Inlet, Free Outlet
maintained in good condition.
7.1.2 Leakage. The ducts, chambers and other
6.6.2.2 Corrections. Barometric readings shall be equipment utilized should be designed to withstand
corrected for any difference in mercury density from the pressure and other forces to be encountered. All
standard or any change in length of the graduated joints between the louver and the measuring plane
scale due to temperature. Refer to manufacturer's should be designed for minimum leakage.
instructions.
7.2 Duct
6.7 Voltage
A duct may be incorporated in a laboratory setup to
Actuator input voltage during the test shall be within provide a measuring plane or to simulate the
1% of the voltage shown on the actuator nameplate. conditions the louver is expected to encounter in
service or both. The dimension D in the test louver
setup figure is the inside diameter of a circular cross-
6.8 Meters
section duct or equivalent diameter of a rectangular
cross-section duct with inside transverse dimensions
Electrical meters shall have certified accuracies of
a and b where:
±1.0% of observed reading. It is preferable that the
same meters shall be used for the test as for the D = 4ab / π Eq. 7.1
calibration.
7.2.1 Transformation Pieces (Figure 10)
6.9 Pneumatic actuator supply air pressure
7.2.1.1 Transformation pieces used to connect a
Pneumatic actuator supply air pressure during a test louver being tested and a duct with a measuring
shall be within 5% of the desired test pressure. plane shall not contain any converging element that

8
ANSI/AMCA 500-L-07

makes an angle with the duct axis greater than 7.5° 7.3.3 Airflow Settling Means. Airflow settling means
or a diverging element that makes an angle with the shall be installed in a chamber where indicated on
duct greater than 3.5°. the test setup figure to provide proper airflow
patterns.
7.2.1.2 Transformation pieces used to connect a
variable exhaust system to a flow measuring nozzle Where a measuring plane is located downstream of
shall have a maximum included angle of 7°. the settling means, the settling means is provided to
ensure a substantially uniform flow ahead of the
7.2.1.3 Transformation pieces used to connect a measuring plane. In this case, the maximum local
duct containing a louver being tested and a flow velocity at a distance 0.1M downstream of the screen
measuring duct shall not contain any converging or shall not exceed the average velocity by more than
diverging element that makes an angle with the duct 25% unless the maximum local velocity is less than 2
axis greater than 30°. m/s (400 fpm).

7.2.1.4 Transformation pieces used to connect a Where a measuring plane is located upstream of the
duct which provides a measuring plane to a variable settling means, the purpose of the settling screen is
supply system or a chamber shall not be restricted as to absorb the kinetic energy of the upstream jet, and
to size or shape. allow its normal expansion as if in an unconfined
space. This requires some backflow to supply the air
7.2.2 Roundness. The portion of a Pitot traverse to mix at the jet boundaries, but the maximum
duct within one-half duct diameter of either side of reverse velocity shall not exceed 10% of the
the plane of measurement shall be round within 0.5% calculated Plane 2 or Plane 6 mean jet velocity.
of the duct diameter. The remainder of the duct shall
be round within 1% of the duct diameter. The area of Where measuring planes are located on both sides of
the plane of measurement shall be determined from the settling means within the chamber, the
the average of four diameters measured at 45° requirements for each side as outlined above shall be
increments. The diameter measurements shall be met.
accurate to 0.2%.
Any combination of screens or perforated plates that
7.2.3 Straighteners. Straighteners or star will meet these requirements may be used, but in
straighteners shall be used where indicated in the general a reasonable chamber length for the settling
figures. The downstream plane of the straightener or means is necessary to meet both requirements.
star straightener shall be located between 5 and 5.25 Screens of square mesh round wire with open areas
duct diameters upstream of the plane of the Pitot of 50% to 60% are suggested and several will usually
traverse or piezometer station. The form of the be needed to meet the above performance
straightener or star straightener shall be as specified specifications. A performance check will be
in Figure 9A or 9B [14]. necessary to verify the airflow settling means are
providing proper flow patterns.
7.3 Chamber
7.3.4 Multiple nozzles. Multiple nozzles shall be
A chamber may be incorporated in a laboratory setup located as symmetrically as possible. The centerline
to provide a measuring station or to simulate the of each nozzle shall be at least 1.5 nozzle throat
conditions the louver is expected to encounter in diameters from the chamber wall. The minimum
service or both. A chamber may have a circular or distance between centers of any two nozzles in
rectangular cross-sectional shape. The dimension M simultaneous use shall be three times the throat
in the airflow measurement setup diagram is the diameter of the larger nozzle.
inside diameter of a circular chamber or the
equivalent diameter of dimensions a and b where 7.4 Variable supply and exhaust systems
M = ( 4ab / π ) Eq. 7.2
A means of varying the points of operation shall be
provided in a laboratory setup.
7.3.1 Outlet chamber. An outlet chamber (Figure
5.4) shall have a cross-sectional area at least fifteen 7.4.1 Throttling device. A throttling device may be
times the free area of the louver being tested. used to control the point of operation. The device
shall be located on the end of the duct or chamber
7.3.2 Inlet chamber. An Inlet chamber (Figure 5.5) and shall be symmetrical about the duct or chamber
shall have a cross-sectional area at least three times axis.
the free area of the louver being tested.

9
ANSI/AMCA 500-L-07

7.4.2 Supply or exhaust fan. A fan may be used to 7.5.4 Test specimen calibration plate
control the point of operation of the test louver. The
fan shall provide sufficient pressure at the desired 7.5.4.1 For the purpose of calibration tests, a
airflow rate to overcome losses through the test calibration plate shall be fabricated which will fit over
setup. Airflow adjustment means, such as a damper, the test plane and have an opening of the same
pitch control, or speed control may be required. A dimensions as the core area of the louver to be
supply fan shall not surge or pulsate during a test. tested. This plate is used in the determination of the
rain penetration insertion loss of the louver.
7.5 Wind driven rain simulation equipment
7.5.5 Wind simulation equipment
7.5.1 Wind simulation weather section
7.5.5.1 An external fan shall direct air perpendicular
7.5.1.1 The louver or calibration plate shall be to the louver test plane, as illustrated in Figure 5.11.
mounted and fixed in the center of a 3m x 3m (9.75 ft
x 9.75 ft) square wall located at the rear of the 7.5.5.2 The air outlet of the fan and any silencing or
weather section (see Figure 5.11). straightening section shall not be less than 1m (3.25
ft) diameter.
7.5.1.2 The louver or the calibration plate shall be
sealed to the wall. 7.5.5.3 The fan shall be capable of producing the
prescribed air velocity at 1m (3.25 ft) in front of the
7.5.1.3 The outside face of the louver shall face the test plane of the louver.
wind and rain simulation test apparatus.
7.5.5.4 A fan air straightener section shall be
7.5.2 Rain simulation equipment assembled to the outlet of the fan to avoid swirling air
currents.
7.5.2.1 The simulated rain shall be produced by at
least 4 nozzles in an array close to the discharge of 8. Objective, Observations and Conduct
the wind effect fan to suit the spread of rain required. of Test
A typical spray can be achieved by using the nozzles
and control system as shown in Figure 5.11 and 8.1 Air performance-pressure drop test
Annex E.
The objective of this test is to determine the
7.5.2.2 Simulated rain performance. The rain relationship between the airflow rate and the
simulation equipment shall have the following pressure drop of a louver.
performance capabilities with the calibration plate
mounted in the test opening: 8.1.1 General requirements.

(1) Produce a simulated rain penetration through the 8.1.1.1 Test. A test shall consist of five or more
calibration plate at the specified rate (+10%, -0%) determinations taken at approximately equal
per square meter (10.76 ft2) of opening increments of airflow rate covering the range desired.

(2) The simulated rainfall rate measured using a rain 8.1.1.2 Equilibrium. Equilibrium conditions shall be
gauge in the positions specified shall not deviate established before each determination. To test for
from the mean rainfall rate by more than 15% equilibrium, trial observations shall be made until
steady readings are obtained.
7.5.3 Collection duct
8.1.1.3 Test area ambient air measurements.
7.5.3.1 The collection duct (see Figure 5.11) shall be Once during each test the dry-bulb temperature of the
sealed against the back of the weather section. air flowing in the general test area, wet-bulb
temperature, the barometric pressure and the ambient
7.5.3.2 The collection duct shall have a water droplet temperature at the barometer shall be recorded.
elimination section at the downstream end to prevent
carry over of airborne water droplets from the 8.1.1.4 Airflow measurement. Airflow at the plane
collection duct. See Annex F for details. of measurement when, determined by using a Pitot-
static tube measurement of velocity pressure, shall
7.5.3.3 The collection duct shall have an airtight not be less than 6.35 m/s (1250 fpm). When nozzles
connection to the airflow measurement plenum. are used the minimum ΔPn shall be 25 Pa (0.1 in. wg)
at the minimum airflow rate of the test.
10
ANSI/AMCA 500-L-07

8.1.2 Data to be recorded 8.1.2.5.2 Louver with inlet duct (Figure 5.2). One
reading per determination of inlet duct static pressure
8.1.2.1 Test unit. The description of the test unit, (Ps9) shall be recorded.
including the model, the louver type, (i.e., fixed blade
louver, adjustable blade louver, combination blade 8.1.2.5.3 Louver with discharge chamber (Figure
louver, etc.) size and free area shall be recorded. 5.4). One reading per determination of discharge
chamber static pressure (Ps7) shall be recorded.
8.1.2.2 Test setup. The description of the test setup
including specific dimensions shall be recorded. 8.1.2.5.4 Louver with inlet chamber (Figure 5.5).
Reference shall be made to the figures in this One reading per determination of inlet chamber static
standard. Alternatively, a drawing or annotated pressure (Ps8) shall be recorded.
photograph of the setup shall be attached to the data.
8.1.3 Conduct of test
8.1.2.3 Instruments. The instruments and apparatus
used in the test shall be listed. Names, model 8.1.3.1 General requirements. Tests shall be
numbers, serial numbers, scale ranges, and conducted at ambient temperatures between 10°C
calibration information shall be recorded. and 40°C (50°F and 104°F). A test determination is
a complete set of measurements for one setting of
8.1.2.4 Airflow measurement test data. Test data airflow and pressure drop. The louver shall be tested
for each determination shall be recorded. Readings with airflow in both directions (except products
shall be made simultaneously whenever possible. specifically labeled for airflow in only one direction).
For all types of tests, readings of ambient dry-bulb
temperature (two), ambient wet-bulb temperature (tdo), 8.1.3.1.1 Combination louver backdraft damper.
ambient barometric pressure (pb) shall be recorded. A test shall begin with the lowest airflow value, the
damper being allowed to seek its own equilibrium
8.1.2.4.1 Pitot traverse test (Figure 6.1). For a Pitot position with respect to pressure differential. If
traverse test, one reading each of velocity pressure desired, the blade angle may be measured (degrees
(Pv3r) and static pressure (Ps3r) shall be recorded for from closed) at each test point. To determine the
each Pitot station. In addition, readings for traverse- differences in mechanical forces within the damper
plane dry-bulb temperature (td3) shall be recorded. while opening vs. closing, the test may be repeated,
beginning with the maximum airflow value.
8.1.2.4.2 Duct nozzle test (Figure 6.2). For a duct
nozzle test, one reading each of pressure drop (ΔPn), 8.1.4 Presentation of results. The report and
approach dry-bulb temperature (td5) and approach presentation of results shall include all the data as
static pressure (Ps5) shall be recorded. outlined in Section 8.1.2

8.1.2.4.3 Chamber nozzle test (Figures 6.3 and 8.1.5 In addition, the following shall be recorded as
6.5). For a chamber nozzle test, the nozzle appropriate:
combinations and one reading each of pressure drop
(ΔPn), approach dry-bulb temperature (td5), and Blade orientation
Blade action
approach static pressure (Ps5), shall be recorded.
Blade position (open or closed)
Airflow direction
8.1.2.4.4 Outlet chamber test (Figure 6.4). For an
Personnel
outlet chamber test, one reading each of outlet
Date
chamber dry-bulb temperature (td5), pressure drop
Test ID#
(ΔPn), and outlet chamber static pressure (Ps5), shall Lab name
be recorded. Lab location
Reference to ANSI/AMCA Standard 500-L
8.1.2.5 Test louver setup. Each louver should be Test figure
tested in a setup which simulates its intended field
installation (see Section 7.1.1). Table 1 shown below 8.2 Airflow leakage rate
displays allowable combinations of airflow rate
measurement and test louver setups. The purpose of this test is to determine the
relationship between airflow leakage rate and static
8.1.2.5.1 Louver with outlet duct (Figure 5.1). pressure for a louver mounted on a chamber.
One reading per determination of outlet duct static
pressure (Ps4) shall be recorded.

11
ANSI/AMCA 500-L-07

8.2.1 General requirements 8.2.1.5 Seating torque measurement

8.2.1.1 Test. A test shall consist of five or more 8.2.1.5.1 Seating torque. Seating torque is the
determinations taken at approximately equal torque specified to properly seal the test louver.
increments of pressure differential covering the range
desired. 8.2.1.5.2 Torque measurement. Calibrated weights
and a distance measuring device having divisions of
8.2.1.2 Equilibrium. Equilibrium conditions shall be 1.0 mm (1/32 in.) or smaller are to be used. The
established before each determination. To test for torque arm is considered to be the minimum of
equilibrium, trial observations shall be made until distance from the vertical centerline of the weights to
steady readings are obtained. the centerline of the point of blade rotation. Direct
torque measuring instrumentation with a tolerance of
8.2.1.3 Test area ambient air measurements. .5 N m (+5 in. lb.) may be used as an alternative.
Once during each test the dry-bulb temperature of Applied torque does not have to be measured if an
the air flowing in the general test area, wet-bulb actuator is installed.
temperature, the barometric pressure and the
ambient temperature at the barometer shall be 8.2.1.5.3 Application of torque. The torque shall
recorded. be applied with zero ΔP across the louver with its
blades at the full open position. The corresponding
8.2.1.4 Airflow measurement. Airflow at the plane weight shall be lowered gradually, without impact
of measurement when using a Pitot-static tube shall loading, until the louver reaches its closed position
not be less than 6.35 m/s (1250 fpm). When nozzles and without additional applied force or with the
are used, the minimum ΔPn shall be 25 Pa (0.1 in wg) normal pressure or voltage of the actuator.
at the minimum airflow rate of test. A direct-reading
meter may be used if the airflow is below 17 m3/h (10
cfm).

Table 1

Airflow Leakage Rate


Louver Test Setups
Measurement Setups
Figure Connection Plane Figure Connections Plane
6.1 B
6.2 B
5.1 Z
6.3 A
6.4 A
6.1 C
Y
5.2 6.2 C
X 6.5 B
6.1 B
Y
6.2 B
5.4
6.3 B
X
6.4 B
6.1 C
X
5.5 6.2 C
Y 6.5 A

12
ANSI/AMCA 500-L-07

8.2.2 Data to be recorded flow in increments of 0.2 L/s (.33 cfm), or less, shall
be used. Flow measurements per this louver shall be
8.2.2.1 Test unit. The description of the test unit, limited to a maximum of 5 L/s (10 cfm).
including the model, the louver type (i.e., adjustable
blade louver, combination blade louver, etc.) size and 8.2.2.5 Test louver setup. Table 2 displays
face area shall be recorded. allowable combinations of airflow rate measurement
and test louver setups.
8.2.2.2 Test setup. The description of the test setup
including specific dimensions shall be recorded. 8.2.2.5.1 Louver with discharge chamber (Figure
Reference shall be made to the figures in this 5.4). One reading of discharge chamber static
standard. Alternatively, a drawing or annotated pressure (Ps7) shall be recorded per determination.
photograph of the setup shall be attached to the data.
8.2.2.5.2 Louver with inlet chamber (Figure 5.5).
8.2.2.3 Instruments. The instruments and apparatus One reading of inlet chamber static pressure (Ps8)
used in the test shall be listed. Names, model shall be recorded per determination.
numbers, serial numbers, scale ranges, and
calibration information shall be recorded. 8.2.3 Conduct of test

8.2.2.4 Airflow measurement using pitot 8.2.3.1 General requirements. Tests shall be
traverse. Test data for each determination shall be conducted at ambient temperature between 10°C
recorded. Readings shall be made simultaneously and 40°C (50°F and 104°F). A test determination is a
whenever possible. Three readings of ambient dry- complete set of measurements for one setting of
bulb temperature (tdo), ambient wet-bulb temperature airflow leakage rate and pressure drop.
(two), and ambient barometric pressure (pb) shall be
recorded unless the readings are steady in which 8.2.3.1.1 Combination louver-backdraft damper.
case only one need be recorded. A combination louver-backdraft damper shall be
mounted in its normal operating position and in such
8.2.2.4.1 Pitot traverse test (Figure 6.1). For a a manner that airflow leakage will force the damper
Pitot traverse test, one reading each of velocity blades to the closed position.
pressure (Pv3r) and static pressure (Ps3r) shall be
recorded for each Pitot station. In addition, three 8.2.3.2 Test using airflow meter. Mount louver as
readings of traverse-plane dry-bulb temperature (td3) shown in Figure 6.6. Perform test as described in
shall be recorded unless the readings are steady in Section 8.2.2.4.5.
which case only one need be recorded.
8.2.3.3 Louver mounted on chamber (Figure 5.4
8.2.2.4.2 Duct nozzle test (Figure 6.2). For a duct or 5.5). This test consists of two parts, a Device and
nozzle test, one reading each of pressure drop (ΔPn), System Test, and a System Test. Both tests shall be
approach dry-bulb temperature (td5) and approach conducted at approximately the same pressure
static pressure (Ps5) shall be recorded. increments. The louver shall be mounted on the
chamber as shown in either Figure 5.4 or 5.5, as
appropriate.
8.2.2.4.3 Chamber nozzle test (Figures 6.3 and 6.5)
For a chamber nozzle test, the nozzle combinations and
8.2.3.3.1 The following chamber criteria are to be
one reading each of pressure drop (ΔPn), approach dry-
met for a Figure 5.5 leakage test to be valid:
bulb temperature (td5), approach static pressure (Ps5),
shall be recorded. When using a chamber for leakage Reference: Upstream is referenced as being on the
testing, criteria for velocity profile downstream of the inlet (fan side) of the nozzles. System Leakage is
nozzles, and area ratio criteria may be ignored. defined as the volume of air leaking into or out of the
chamber with the louver blanked off or the opening
8.2.2.4.4 Outlet chamber test (Figure 6.4). For an covered. Louver Leakage is defined as the volume of
outlet chamber test, one reading each of outlet chamber air leaking across the plane of the louver with the
dry-bulb temperature (td5), pressure drop (ΔPn), and blades closed and torque applied per section 8.2.1.5.
outlet chamber static pressure (Ps5) shall be recorded.
(1) Close all nozzles and install the leakage chamber
8.2.2.4.5 Flow meter test (Figure 6.6). For a flow (Figure 6.6C) on the downstream side of
meter test, airflow shall be recorded as indicated on chamber with the 13mm (0.5 in.) nozzle open.
the meter and inlet static pressure (Ps9) shall be Increase the pressure upstream of the nozzles in
recorded. A calibrated flowmeter capable of indicating a minimum of five (5) approximately equal

13
ANSI/AMCA 500-L-07

increments, to a minimum of 995 Pa (4 in. wg) 8.2.3.3.3 Pressure drop across the nozzle(s) for the
static pressure or the maximum fan pressure. If system leakage test must be the SAME or HIGHER
the calculated airflow is greater than 4.47×10-5 × than the pressure drop across nozzle(s) for the
(Ps)0.5 m3/s (1.5 × (Ps)0.5 cfm), then the nozzle corresponding louver leakage test when the system
wall has excessive leakage and must be leakage test is equal to or more than 9.44×10-4 m3/s
resealed and retested until the leakage value is (2 cfm) total. When system leakage is less than
less than 4.47×10-5 × (Ps)0.5 m3/s (1.5 × (Ps)0.5 cfm). 9.44×10-4 m3/s (2 cfm) the pressure drop restriction
does not apply.
(2) Blank off exiting end of chamber (location where
the leakage chamber (Figure 6.6C) is in Step 1 8.2.3.3.4 For chambers other than Figure 5.5, an
above). Open 13mm (0.5 in.) or 19mm (0.75 in.) equivalent method of determining nozzle wall and
nozzle. Increase the pressure upstream of chamber leakage shall be used.
nozzles in a minimum of five (5) approximately
equal increments, to a minimum of 995 Pa (4 in. 8.2.3.3.5 Device and system test. Test
wg) static pressure or the maximum fan determinations shall be carried out with the louver
pressure. If the calculated leakage is greater mounted on the chamber and airflow unobstructed.
than 4.47×10-5 × (Ps)0.5 m3/s (1.5 × (Ps)0.5 cfm), System Test: The louver shall remain mounted on
the chamber but shall be covered with a suitable solid
then the chamber downstream of the nozzles has
board or other appropriate material to prevent air
excessive leakage and must be resealed and
from flowing. Test determinations shall then be
retested until the leakage value is less than
carried out with the airflow obstructed. For each
4.47×10-5 × (Ps)0.5 m3/s (1.5 × (Ps)0.5 cfm).
determination the device leakage shall be the
leakage with the device in place (device and system)
(3) Repeat test step 1 to insure leakage values were minus the system leakage at the identical pressure.
not affected by downstream leakage values. If Refer to Section 9.5 if device and system pressures
airflow across downstream tail end piece (Figure and system pressures are not identical.
6.6C) is greater than 4.47×10-5 × (Ps)0.5 m3/s
(1.5 × (Ps)0.5 cfm), then repeat steps 1 and 2 8.2.4 Presentation of results. The report and
above. presentation of results shall include all the data as
outlined in Section 8.2.2. In addition, the following
This procedure shall have been checked and shall be recorded:
documented no greater than 6 months before any
AMCA certified Figure 5.5 leakage test. Method of closure
Blade orientation
8.2.3.3.2 The maximum system leakage that can be Blade action
deducted is 4.47×10-5 × (Ps)0.5 m3/s (1.5 × (Ps)0.5 Airflow direction
cfm) or 2% of louver leakage (whichever is higher), if Personnel
system leakage is measured higher than the Date
maximum allowed. Test ID#
Lab name
If system leakage is measured less than maximum Lab location
allowed, then actual system leakage becomes Reference to ANSI/AMCA Standard 500-L
allowable system leakage. Test figure

14
ANSI/AMCA 500-L-07

Table 2

Louver Test Setups Airflow Leakage Rate Measurement Setups

Connection
Figure Figure Connection Plane
Plane

6.1 B
Y
6.2 B
5.4
6.3 B
X
6.4 B

6.1 C
X
5.5 6.2 C

Y 6.5 A

---- 6.6 Flow Meter Test

8.3 Water penetration equilibrium, trial observations shall be made until


steady readings are obtained.
8.3.1 Water penetration test
8.3.1.1.3 Water flow meter. A calibrated water flow
The objective of this test is to define the point of meter shall be used to determine the rate of water
beginning water penetration, by finding the intake air flow in each water system.
velocity at which water begins to penetrate a louver.
It is not intended to provide information on the 8.3.1.1.4 Water flow rate. Water flow rate shall be
amount of water that will penetrate the louver under held within 5% of the prescribed flow rates.
service conditions (e.g., wind driven rain). The
purpose of the test is to provide a basis for comparing 8.3.1.1.5 Water collecting surface. The length of
different louver designs, not to provide design data. the water collecting surface inside the test plenum
shall be a minimum of 150% of the vertical distance
8.3.1.1 General requirements from the top of the louver to the water collecting
surface below the louver. The width of the water
8.3.1.1.1 Determinations. A test shall consist of 4 collecting surface shall extend at least 300 mm (12
or more determinations taken at approximately equal in.) beyond each side of the test louver.
increments of airflow rate covering the range desired.
Each test determination shall be of equal duration for 8.3.1.1.6 Water drop manifold. Droplet flow from
the prescribed length of time (minimum, 15 minutes) the water drop manifold shall be maintained at the
at a selected constant air flow rate though the test prescribed per hour rate (minimum, 100 mm (4 in.))
louver. during the test period and shall extend 150 mm (6 in.)
beyond each side of the louver wall opening (see
8.3.1.1.2 Equilibrium. Equilibrium conditions shall Figure 5.6).
be established before each determination. To test for

15
ANSI/AMCA 500-L-07

8.3.1.1.7 Wetted wall. Water flow rate on the wetted 8.3.1.2.4.4 Airflow measurement using outlet
wall shall be maintained at the prescribed rate per chamber (Figure 6.4). For outlet chamber tests, one
meter (foot) of wetted wall (minimum, 3.28 L/m (0.25 reading each of outlet chamber dry-bulb temperature
gpm)) and shall extend 150 mm (6 in.) beyond each (td5) and pressure drop (ΔPn) shall be recorded.
side of the louver wall opening (see Figure 5.6).
8.3.1.2.5 Test setup. Each louver shall be tested in
8.3.1.2 Data to be recorded accordance with one of the test figure combinations
shown below in Table 3.
8.3.1.2.1 Test unit. The description of the test unit
including the model, the louver type (i.e. fixed blade 8.3.1.2.5.1 Water carryover measurement (Figure
louver, adjustable blade louver or combination blade 5.6). Collected water carry-over shall be weighed on
louver, etc.), size and free area shall be recorded. a scale with an accuracy of at least 1%. The weight
shall be recorded in grams (ounces) for each
8.3.1.2.2 Test setup. The description of the test determination.
setup including specific dimensions shall be
recorded. Reference shall be made to the figures in 8.3.1.3 Conduct of test. The louver to be tested
this standard. Alternatively, a drawing or annotated shall be 1.2 m × 1.2 m (48” × 48”). There are to be no
photograph of the setup shall be attached to the data. appurtenances attached (screens). There will be no
finish applied to the louver although the surfaces can
8.3.1.2.3 Instruments. The instruments and be cleaned. The louver blades shall extend to within
apparatus used in the test shall be listed. Names, 12 mm (0.5 inches) of the exterior and interior face of
model numbers, serial numbers, scale ranges, and the louver frame. No portion of the louver shall
calibration information should be recorded. extend beyond the face of the louver frame. Either
the head and sill, jamb frames, or both shall be flush
8.3.1.2.4 Airflow measurement test data. Test with the wetted wall.
data for each determination shall be recorded.
Readings shall be made simultaneously whenever Mount the louver in the chamber with the forward
possible. For all types of tests, readings of ambient most portion of the air intake side of the frame flush
dry-bulb temperature (tdo), ambient wet-bulb with the face of the wetted wall. Use a drain pan
temperature (two), and ambient barometric pressure under the louver so that the rear flange of the drain
(pb) shall be recorded. pan is butted against the rear of the test louver. Tape
the joint between the test setup and the louver using
8.3.1.2.4.1 Airflow measurement using pitot smooth wrinkle free tape. If an operating louver is
(Figure 6.1). For Pitot traverse tests, one reading being tested adjust the blades so that they are fully
each of velocity pressure (Pv3r) and static pressure open.
(Ps3r) shall be recorded for each Pitot station. In
addition, three readings of traverse-plane dry-bulb The water drop flow shall be set at a minimum rate of
temperature (td3) shall be recorded unless the 102 mm/hour (4 in. per hour) over the area of the pan
readings are steady in which case only one need be .33 m2 (5 square feet).
recorded.
Tests are conducted at airflow values that exceed the
8.3.1.2.4.2 Airflow measurement using duct water carry-over point. Water carry-over is mopped
nozzle (Figure 6.2). For duct nozzle tests, one dry from all wetted surfaces inside the plenum by any
reading each of pressure drop (ΔPn), approach dry- suitable method and the weight determined for each
test point. A minimum test point shall be run at
bulb temperature (td5) and approach static pressure
conditions where the weight of the water carried over
(Ps5) shall be recorded.
shall not exceed 3 g/m2 (0.01 oz./ft2) of free area or
30 g (1 oz.) per determination, whichever is
8.3.1.2.4.3 Airflow measurement using chamber
minimum. The maximum test point shall be run with
nozzle (Figures 6.3 and 6.5). For chamber nozzle
a free area velocity sufficient to cause between 60-75
tests, the nozzle combinations and one reading each
g (2-2.25 oz.) of water carry-over per m2 (ft2) of free
of pressure drop (ΔPn), approach dry-bulb
area or at an air velocity through the free area of 6.35
temperature (td5), and approach static pressure (Ps5)
m/s (1250 fpm), whichever air velocity is lower or
shall be recorded. when water is observed passing over the collection
point.

16
ANSI/AMCA 500-L-07

8.3.1.4 Presentation of results. The report and 8.3.2.1.3 The rate of water and airflow shall be held
presentation of results shall include all the data as to the tolerances given below:
outlined in Section 8.3.1.2. In addition, the following
shall be recorded: Water supply rate (Figure 13) ± 2%

Personnel Water collection rate ± 10%


Date
Test ID# Ventilation airflow rate ± 5%
Lab name
Lab location Wind velocity ± 10%
Reference to ANSI/AMCA Standard 500-L
Test figure 8.3.2.1.4 Determinations. Test values shall be
noted at regular intervals not more than 10 minutes
The weight in grams (ounces) of water carry-over per apart and the test period shall be complete when a
determination shall be plotted versus air flow velocity minimum of four consecutive reading of values within
through the free area and a smooth curve drawn the steady state tolerance have been noted.
through the test points. Minimum test period is 30 minutes.

8.3.2 Wind driven rain test 8.3.2.2 Conduct of test

The objective of this test is to specify a method for 8.3.2.2.1 Calibration plate test.
measuring the water rejection performance of louvers
subject to simulated rain and wind pressure, both (1) Mount the calibration plate in the test position
with and without air flow through the louver under (see Figure 5.11).
test. The test incorporated in this section establishes
louver effectiveness when subjected to wind (2) Mount the spray nozzles as illustrated on
pressure at various air flow rates. Figure 5.11.

8.3.2.1 General requirements (3) Adjust the ventilation air flow rate qv to zero
and set the wind speed to the specified
8.3.2.1.1 The louver to be tested shall be mounted value.
and sealed to the 3m x 3m (9.7 ft x 9.7 ft) wall at the
rear of the weather section as recommended by the (4) Set up the rain pattern as described in
manufacturer, to prevent any ingress of water other Section 7.5.2.
than through the louver blades.
(5) Adjust the water supply rate qs so that the
8.3.2.1.2 All tests shall be carried out at a simulated penetration rate qdo lies between (+10%-0%)
wind speed measured by means of a velocity meter of the specified rainfall rate through the
(i.e., vane anemometer or Pitot tube) on the center calibration plate.
line of the fan and 1 m. (3.25 ft) in front of the face of
the louver. The velocity meter shall be removed (6) For the test period, the following values shall
before the rain simulation nozzles are turned on. be measured and recorded:

The water flow rates shall be measured with a flow a. the water supply rate qso
meter and set to the desired rates for each test.
Water shall be collected from behind the louver. b. the water rejection rate quo

At the collection duct. Water shall be collected at the c. the water penetration rate qdo
drain from the collection duct so that the penetration
for the test period can be measured, and d. air flow rate through plate qvo
(except for no air flow test)
In front of the louver. Water shall be collected in the
section at the base in front of calibration plate so that e. wind velocityvw
the water rejection during the period of the test can (at the start and end of test period)
be measured.
(7) Adjust the air flow qv through the plate to the
next value in the test schedule and repeat (5)
to (6).

17
ANSI/AMCA 500-L-07

(8) When a test has been made at each of t h e The corrected water penetration rate qd corr is
values of qvo the test results shall be the water penetration rate that would be
summarized and the penetration rate achieved if the water supply rate were to be
corrected by calculation if the water supply equal to the nominal water supply rate qs nom
rate has varied from the nominal value of qso. at the test ventilation air flow rate.

The nominal water supply rate qs nom is the supply rate qd corr = (qs nom) × (qd) × (qs-1)
to the nozzles that will produce a penetration of the
specified rainfall rate through the calibration plate at 8.3.2.3 Presentation of results. The report and
the test air flow rate. presentation of results shall include all the data as
outlined in Section 8.3.2.2. In addition, the following
qs nom = (Rainfall Rate) × (qso) × (qdo-1) × (A) shall be recorded:

8.3.2.2.2 Louver test Personnel


Date
(1) Install the Louver in the test opening (see Test ID#
Figure 5.11). Lab name
Lab location
(2) Install the spray nozzles as illustrated on Reference to ANSI/AMCA Standard 500-L
Figure 5.11. Test figure

(3) Adjust the airflow rate qvo to zero and the


wind speed to the specified value. 8.3.2.3.1 Prepare a graph of the test results of the
rain penetration through the calibration plate by
(4) The rain pattern shall be as established plotting:
during the testing of the calibration plate.
qs nom vs. vc and
(5) Adjust the water supply rate as close as
possible to qs nom as established during the qd0 vs. vc
testing of the calibration plate.
8.3.2.3.2 Prepare a graph of the test results of the
(6) During the test period the following values rain penetration through the louver by plotting:
shall be measured and recorded:
qs nom vs. vc and
a. the water supply rate qs
qd corr vs. vc
b. the water penetration rate qd
8.3.2.3.3 Prepare a graph of the effectiveness of the
c. airflow rate through louver qv louver at different velocities by plotting the velocity
(except for no airflow test) calculated from qvA-1 against the effectiveness E
calculated from:
(7) Adjust the air flow rate qv through the louver
to the next value in the test schedule and E = [qwA - qd corr] 100 [qwA]-1 at each of the test
repeat steps 5 and 6. airflow rates.

Note: Airflow rates should be as established Note:


during calibration plate test ± 5%.
1) Louver effectiveness is defined in Section
(8) When a test has been made at each of the 5.7.3.2
values of qv the test results shall be
summarized and the penetration rate 2) qwA is the product of the required calibration
corrected by calculation if the water supply plate specified water penetration rate (qw) and
rate has varied from the nominal value of the area of the calibration plate hole (AC).
qs nom.

18
ANSI/AMCA 500-L-07

9. Calculations ⎛ t + 459.67 ⎞ ⎛ Psx + 13.63 pb ⎞


ρ x = ρ0 ⎜ d 0 ⎟⎜ ⎟ Eq. 9.4 I-P
9.1 Calibration correction ⎝ tdx + 459.67 ⎠ ⎝ 13.63 pb ⎠

Calibration corrections, when required, shall be If Psx is numerically less than 1000 Pa, (4 in. wg), ρx
applied to individual readings before averaging or may be considered equal to ρ0.
other calculations. Calibration corrections need not
be made if the correction is smaller than one half the 9.2.3 Air viscosity. The viscosity (μ) shall be
maximum allowable error as specified in Section 6. calculated from:

9.2 Density and viscosity of air μ = (17.23 + 0.048ta ) × 10 −6 Eq. 9.5 SI


9.2.1 Atmospheric air density. The density of
atmospheric air (ρ0) shall be determined from μ = (11.00 + 0.018ta ) × 10 −6 Eq. 9.5 I-P
measurements, taken in the general test area, of dry-
bulb temperature (td0), wet-bulb temperature (tw0), The value for 20°C (68°F) air, which is 1.819 × 10-5
and barometric pressure (pb) using Equations 9.1, 9.2 Pa•s (1.222E-5 lbm/ft•s), may be used for
and 9.3 [12]. temperatures ranging between 4 °C (40 °F) and 40
°C (100 °F) [14].
pe = 3.25tw2 0 + 18.6tw 0 + 692 Eq. 9.1 SI
9.3 Louver airflow rate at test conditions
pe = 2.96 × 10 −4 tw2 0 − 1.59 × 10 −2 tw 0 + 0.41 9.3.1 Velocity traverse. The louver airflow rate may
Eq. 9.1 I-P be calculated from velocity pressure measurements
(Pv3) taken by Pitot traverse.
⎛t −t ⎞
pp = pe − pb ⎜ d 0 w 0 ⎟
⎝ 1500 ⎠ Eq. 9.2 SI
9.3.1.1 Velocity pressure. The velocity pressure
(Pv3) corresponding to the average velocity shall be
⎛t −t ⎞ obtained by taking the square roots of the individual
pp = pe − pb ⎜ d 0 w 0 ⎟ measurements (Pv3r) (see Figure 3), summing the
⎝ 2700 ⎠ Eq. 9.2 I-P
roots, dividing the sum by the number of
measurement (n), and squaring the quotient as
pb − 0.378 pp indicated by:
ρ0 =
R(td 0 + 273.15) Eq. 9.3 SI
2
⎛ Σ Pv 3 r ⎞
Pv 3 = ⎜ ⎟ Eq. 9.6
70.73( pb − 0.378 pp ) ⎜ n ⎟
ρ0 = ⎝ ⎠
R(td 0 + 459.67) Eq. 9.3 I-P
9.3.1.2 Velocity. The average velocity (V3) shall be
Equation 9.1 is approximately correct for pe for a obtained from the density at the plane of traverse (ρ3)
range of tw0 between 4 °C and 32°C (40°F and 90°F). and the corresponding velocity pressure (Pv3) using
More precise values of pe can be obtained from the
ASHRAE Handbook of Fundamentals [13]. The gas
2Pv 3
constant (R) may be taken as 287 J/kg•K (53.35 V3 = Eq. 9.7 SI
ft•lb/lbm•°R) for air. ρ3

9.2.2 Duct or chamber air density. The density of


Pv 3
air in a chamber at Plane x (ρx) may be calculated by V3 = 1097 Eq. 9.7 I-P
correcting the density of atmospheric air (ρ0) for the ρ3
pressure (Psx) and temperature (tdx) at Plane x using:

9.3.1.3 Airflow rate. The airflow rate (Q3) at the


⎛ t + 273.15 ⎞ ⎛ Psx + pb ⎞
ρ x = ρ0 ⎜ d 0 ⎟⎜ ⎟ Eq. 9.4 SI Pitot traverse plane shall be obtained from the
⎝ tdx + 273.15 ⎠ ⎝ pb ⎠ velocity (V3) and the area (A3) using:

19
ANSI/AMCA 500-L-07

Q3 = V3 A3 Eq. 9.8 The ratio of specific heats (γ) may be taken as 1.4 for
air. Alternatively, the expansion factor for air may be
approximated with sufficient accuracy under this
9.3.1.4 Louver airflow rate. The louver airflow rate standard using:
at test conditions (Q) shall be obtained from the
equation of continuity.
Y = 1 − (0.548 + 0.71β 4 )(1 − α ) Eq. 9.14
Q = Q3 ( ρ3 / ρ ) Eq. 9.9
9.3.2.4 Energy factor. The energy factor (E) may
be determined by measuring velocity pressures (Pvr)
9.3.2 Nozzle. The louver airflow rate may be
upstream of the nozzle at standard traverse stations
calculated from the pressure differential (ΔP)
and calculating.
measured across a single nozzle or bank of multiple
nozzles. [18]
⎛ ∑(Pvr3 / 2 ) ⎞
9.3.2.1 Alpha ratio. The ratio (α) of absolute nozzle ⎜ ⎟
n
exit pressure to absolute approach pressure shall be E= ⎝ ⎠
3 Eq. 9.15
calculated from: ⎛ ∑(Pvr ) ⎞
1/ 2

⎜ ⎟
⎝ n ⎠
Ps 6 + pb
α= Eq. 9.10 SI
Psx + pb Sufficient accuracy can be obtained for setups
qualifying under this standard by setting E = 1.0 for
chamber approach or E = 1.043 for duct approach
Ps 6 + 13.63 pb [10].
α= Eq. 9.10 I-P
Psx + 13.63 pb
9.3.2.5 Reynolds number. The Reynolds number
(Re) based on nozzle exit diameter (D6) in m (ft) shall
or
be calculated from:

ΔP
α = 1− Eq. 9.11 SI D6V6 ρ6
ρ x R(tdx + 273.15) Re = Eq. 9.16 SI
μ6

5.187ΔP
α = 1− Eq. 9.11 I-P D6V6 ρ6
ρ x R(tdx + 459.67) Re =
60 μ6 Eq. 9.16 I-P

The gas constant (R) may be taken as 287 J/kg•K


(53.35 ft•lb/lbm•°R) for air. Plane x is Plane 4 for duct using properties of air as determined in Section 9.2
and the appropriate velocity (V6) in m/s (fpm). Since
approach or Plane 5 for chamber approach.
the velocity determination depends on Reynolds
9.3.2.2 Beta ratio. The ratio (β) of nozzle exit number an approximation must be employed. It can
diameter (D5) to approach duct diameter (Dx) shall be be shown that:
calculated from:
2 ΔP ρ x
β = D6 / Dx Eq. 9.12 Re = CD6Y Eq. 9.17 SI
μ 1− β 4

For a duct approach Dx = D4. For a chamber


approach, Dx = D5, and β may be taken as zero. 1097 ΔP ρ x
Re = CD6Y Eq. 9.17 I-P
60 μ 1− β 4
9.3.2.3 Expansion factor. The expansion factor (Y)
may be obtained from:
For duct approach ρx = ρ4. For chamber approach
1/ 2 1/ 2
ρx = ρ5, and β may be taken as zero.
⎡ γ 1 − α (γ −1) / Y ⎤ ⎡ 1− β 4 ⎤
Y =⎢ α 2/γ ⎥ ⎢ 4 2/γ ⎥
⎣γ − 1 1− α ⎦ ⎣1 − β α ⎦ 9.3.2.6 Discharge coefficient. The nozzle discharge
coefficient (C) shall be determined from
Eq. 9.13

20
ANSI/AMCA 500-L-07

7.006 134.6 9.4 Density correction


C = 0.9986 − + Eq. 9.18
Re Re
The resistance of a duct system or pressure drop of
L a louver is dependent upon the density of the air
for = 0 .6
D flowing through the system or louver. At constant
volume airflow rate the pressure drop varies in direct
6.688 131.5 proportion to the density, for example, a 10%
C = 0.9986 − + Eq. 9.19 increase in density would cause a 10% increase in
Re Re pressure drop. A correction shall be made to adjust
L the pressure drop measured at test conditions to the
for = 0 .6
D pressure drop which would be measured at the same
airflow rate with standard air density (0.075 lbm/ft3).
for Re of 12,000 and above [10].
The correction shall be calculated from Q = Q1.
9.3.2.7 Airflow rate for ducted nozzles. The volume
airflow rate (Q4) at the entrance to a ducted nozzle
⎛ 0.075 ⎞
shall be calculated from: ΔP = ΔP1,2 ⎜ ⎟
⎝ ρ1 ⎠
CA6 2ΔP / ρ 4
Q4 = Eq. 9.20 SI 9.5 Air leakage-system leakage correction
1− E β4
For the purpose of establishing louver air leakage the
“system” air leakage must be subtracted from the
1097CA6 ΔP / ρ 4
Q4 = Eq. 9.20 I-P “louver and system” air leakage. Since it is not
1− E β4 practical to set up and test the exact pressure
differential corrected to standard air for each pair of
The area (A6) is measured at the plane of the throat determinations, the subtraction may be
taps. accomplished by one of the methods below.

9.3.2.8 Airflow rate for chamber nozzles. The 9.5.1 Subtraction by chart. The data from both
volume airflow rate (Q5) at the entrance to a nozzle or tests shall be plotted on logarithmic graph paper. A
straight line shall then be drawn through each set of
multiple nozzles with chamber approach shall be
data points. The louver air leakage airflow rate for
calculated from:
any given pressure differential is the airflow rate
difference between the plotted lines at that pressure
2ΔP differential.
Q5 = Y Σ(CA6 ) Eq. 9.21 SI
ρ5
9.5.2 Subtraction by data points. The air leakage
airflow rates for a given set of pressure differential
ΔP data may be subtracted directly provided the
Q5 = 1097Y Σ(CA6 ) Eq. 9.21 I-P “system” air leakage airflow rate is corrected to the
ρ5
identical pressure differential as the “louver and
system” pressure differential. The converted airflow
The coefficient (C) and area (A6) must be determined rate (subscript c) is determined by adjusting the
for each nozzle and their products summed as tested airflow rate (subscript t) by the square root of
indicated. The area (A6) is measured at the plane of the pressure ratio required to make the pressure
the throat taps or the nozzle exit for nozzles without differentials identical.
throat taps.
0 .5
9.3.2.9 Louver airflow rate. The louver airflow rate ⎛ ΔP ⎞
Qc = Q1 ⎜ DS ⎟
(Q) at test conditions shall be obtained from the ⎝ ΔPS ⎠
equation of continuity,
where:
Q = Qx ( ρ x / ρ ) Eq. 9.22
ΔPDS = louver and system test pressure differential

ΔPS = system test pressure differentia

21
ANSI/AMCA 500-L-07

Free Area = L[ A + B + (N × C )]

L[ A + B + (N × C )]100
PercentFree Area =
W ×H

Where:

A* = Minimum distance between the head and top blade.


Note: Where the top blade dimension C is less than A, use the value for C.
B* = Minimum distance between the sill and bottom blade.
C* = Minimum distance between adjacent blades. Note that in louver Type 2, C may not be equal to C1.
N = Number of “C” openings in the louver.
L = Minimum distance between louver jambs.
W = Actual louver width.
H = Actual louver height.

* The A, B & C spaces shall be measured within one inch from each jamb and averaged.

Figure 1 - Typical Louver and Frame Cross - Section Showing Minimum Distance Formulae

22
ANSI/AMCA 500-L-07

Surface shall be smooth and free


from irregularities within 20D of
hole. Edge of hole shall be square
and free from burrs.

D = 2 mm (0.07 in.) preferred


2.5D Minimum
D = 3 mm (0.125 in.) max

2D Minimum

To Pressure Indicator

Note: A 2 mm (0.07 in.) hole is the maximum size which will allow space for a smooth surface 20D from the hole
when installed 38 mm (1.5 in.) from a partition, such as in Figures 6.3 and 6.5.

Figure 2 - Static Pressure Taps

0.184D
0.117D
0.021D
60° ±1°
0.345D

D
ALL PITOT POSITIONS
±0.0025D RELATIVE TO
INSIDE DUCT WALLS.

Note: D is the average of four measurements at traverse plane at 45° angles measured to accuracy of 0.2% D.
Traverse duct shall be round within 0.5% D at traverse plane and for a distance on either side of traverse plane.

Figure 3 - Traverse Points in a Round Duct

23
ANSI/AMCA 500-L-07

16D 8D

0.8D 0.5D Radius

0.4D
3D Radius D

Head shall be free from nicks and burrs.


90° ± 0.1°
All dimensions shall be within ±2%.

SECTION A-A 8 holes - 0.15D, not to exceed 1mm (0.04 in.),


diameter equally spaced and free from burrs.
Hole depth shall not be less than the hole
diameter.

Static Pressure
Note: Surface finish shall be 0.8 micrometer (32 micro-
in.) or better. The static orifices may not exceed 1 mm
(0.04 in.) diameter. The minimum Pitot tube stem diameter
recognized under this standard shall be 2.5 mm (0.10 in.)
Total Pressure in no case shall the stem diameter exceed 1/30 of the test
duct diameter.
All other dimensions are the same X/D V/D X/D V/D
as for spherical head pitot-static 0.000 0.500 1.602 0.314
tubes. 0.237 0.496 1.657 0.295
8D 0.336 0.494 1.698 0.279
0.474 0.487 1.730 0.266
0.622 0.477 1.762 0.250
0.741 0.468 1.796 0.231
0.936 0.449 1.830 0.211
D 1.025 0.436 1.858 0.192
X 1.134 0.420 1.875 0.176
1.223 0.404 1.888 0.163
1.313 0.388 1.900 0.147
1.390 0.371 1.910 0.131
0.2D Diameter 1.442 0.357 1.918 0.118
1.506 0.343 1.920 0.109
V 1.538 0.333 1.921 0.100
1.570 0.323

Figure 4 - Pitot Static Tubes

24
ANSI/AMCA 500-L-07

PL-1 PL-2 PL-4 PL-Z


10D minimum

D ± 0.02D
To Exhaust System and
Flow Measuring Section
Louver being tested

Ps4

D = 4ab / π for rectangular ducts

where:

a = duct width
b = duct height
D = duct diameter for round ducts.

Figure 5.1 - Louver Test Setup with Outlet Duct

PL-X PL-Y PL-9 PL-1 PL-2


L9,1
6D minimum
D9 ± 0.02 D9

To Supply System and


Louver being tested
Flow Measuring Section

Inlet cone required


Ps9
if attached to plenum

D = 4ab / π for rectangular ducts

where:

a = duct width
b = duct height
D = duct diameter for round ducts.

Figure 5.2 - Louver Test Setup with Inlet Duct

25
ANSI/AMCA 500-L-07

PL-1 PL-7 PL-X PL-Y

M/2 min. M/2 min.


75 mm ±6 mm
(3 in. ±0.25 in.)

Device M
W×H AIRFLOW
being tested

Blank off plate.


Seal airtight to
Device damper flange.
being tested

100 mm (4 in.) minimum

PL-7 PL-Y

ALTERNATE
(Leakage Test Only)

Note: For pressure drop testing an outlet chamber shall have a cross sectional area at least fifteen times the free
area of the louver being tested.

Figure 5.4 - Louver Test Setup with Outlet Chamber

26
ANSI/AMCA 500-L-07

PL-X PL-Y PL-8 PL-2

M/2 min. M/2 min. PL-2


75 mm ±6 mm
(3 in. ±0.25 in.)

Device
AIRFLOW WXH being
WXH
tested

100 mm
(4 in.) min.

Blank off plate.


Seal airtight to
PL-Y PL-8 damper flange.

ALTERNATE
(Leakage Test Only)

Note: For pressure drop testing an inlet chamber shall have a cross sectional area at least three times the free
area of the louver being tested.

Figure 5.5 - Louver Test Setup with Inlet Chamber

27
ANSI/AMCA 500-L-07

200

Plenum size shall be larger than the test louver by a minimum of 300 mm (12 in.) on all four sides.

Water drop manifold

Rainfall pattern holes located on 75 mm (3 in.) staggered spacing. The first row of holes will be 38 mm ± 3.8 mm
( 1½ ± ⅛ in.) distance from the wetted wall. Size holes to maintain required rainfall rate in droplets. Louvers such
as nails, pointed wire or other means to develop raindrop formations are acceptable. Airflow from each hole shall
be in individual drops.

Wetted wall manifold

Manifold sizing shall not interfere with the first row of raindrops from the water drop manifold. Water discharge
holes in the manifold shall not exceed 50 mm (2 in.) spacing and extend a minimum of 150 mm (6 in.) beyond the
louver wall opening. The manifold shall be mounted flush against the wetted wall surface with the water discharge
holes directed 15° downward towards the wetted wall.

Figure 5.6 - Louver Test Setup with Water Penetration Chamber

28
ANSI/AMCA 500-L-07

This figure reproduced from


HEVAC Technical Specification,
Laboratory testing and rating of
weather louvres when subjected
to simulated rainfall, courtesy of
Heating Ventilating and Air
Conditioning Manufacturers
Association (HEVAC)

Figure 5.11 - Louver Test Setup with Wind Driven Rain Water Penetration Chamber

29
ANSI/AMCA 500-L-07

2
⎡ P ⎤
Pv 3 = ⎢Σ v 3 r ⎥
⎢⎣ n ⎥⎦

2Pv 3
V3 = SI Q3 = V3 A3
ρ3

Pv 3 ⎛ρ ⎞
V3 = 1097 I-P Q = Q3 ⎜ 3 ⎟
ρ3 ⎝ ρ ⎠

Figure 6.1 - Airflow Rate Measurement Setup, Pitot Traverse in Duct

30
ANSI/AMCA 500-L-07

CA6Y 2ΔP / ρ5
Q5 = SI
1− E β 4

1097CA6Y ΔP / ρ5
Q5 = I-P
1− E β 4

⎛ ρ ⎞
Q = Q5 ⎜ ⎟
⎝ ρ5 ⎠

Figure 6.2 - Airflow Rate Measurement Setup, Nozzle on End of Duct

31
ANSI/AMCA 500-L-07

Q5 = ⎡Y 2ΔP / ρ5 ⎤ Σ(CA6 ) SI
⎣ ⎦

Q5 = ⎡1097Y ΔP / ρ5 ⎤ Σ(CA6 ) I-P


⎣ ⎦

⎛ρ ⎞
Q = Q5 ⎜ 5 ⎟
⎝ ρ ⎠

Figure 6.3 - Airflow Rate Measurement Setup, Multiple Nozzles Intake Chamber

32
ANSI/AMCA 500-L-07

Q5 = CA6Y 2ΔP / ρ5 SI

Q5 = 1097CA6Y ΔP / ρ5 I-P

⎛ρ ⎞
Q = Q5 ⎜ 5 ⎟
⎝ ρ ⎠

Figure 6.4 - Airflow Rate Measurement Setup, Single Nozzle Intake Chamber

33
ANSI/AMCA 500-L-07

Q5 = ⎡⎣Y 2ΔP / ρ5 ⎤⎦ Σ(CA6 ) SI

Q5 = ⎡⎣1097Y ΔP / ρ5 ⎤⎦ Σ(CA6 ) I-P

⎛ρ ⎞
Q = Q5 ⎜ 5 ⎟
⎝ ρ ⎠

Figure 6.5 - Airflow Rate Measurement Setup, Multiple Nozzle Discharge Chamber

34
ANSI/AMCA 500-L-07

Figure 6.6A - Test Louver Setup - Leakage Test with Louver under Positive Pressure

Figure 6.6B - Test Louver Setup - Leakage Test with Louver under Negative Pressure

35
ANSI/AMCA 500-L-07

2ΔPn
Q5 = Y Σ(CA6 ) SI formula
ρ5

ΔPn
Q5 = 1097Y Σ(CA6 ) I-P formula
ρ5

⎛ρ ⎞
Q = Q5 ⎜ 5 ⎟
⎝ ρ ⎠

Figure 6.6C - Leakage Chamber

36
ANSI/AMCA 500-L-07

Figure 7 – Coefficients of Discharge for Flow Nozzles

37
ANSI/AMCA 500-L-07

Notes:

1. The nozzle shall have a cross-section consisting of elliptical and cylindrical portions, as shown. The cylindrcal
portion is defined as the nozzle throat.

2. The cross-section of the elliptical portion is one quarter of an ellipse, having the large axis D and the small axis
0.667D. A three-radii approximation to the elliptical form that does not differ at any point in the normal direction
more than 1.5% from the elliptical form shall be used. The adjacent arcs, as well as the last arc, shall smoothly
meet and blend with the nozzle throat. The recommended approximation which meets these requirements is
shown in Figure 7B by Cermak, J., Memorandum Report to AMCA 210/ASHRAE 51P Committee, June 16, 1992.

3. The nozzle throat dimension L shall be either 0.6D ± 0.005D (recommended), or 0.5D ± 0.005D.

4. The nozzle throat dimension D shall be measured (to an accuracy of 0.001D) at the minor axis of the ellipse
and at the nozzle exit. At each place, four diameters – approximately 45° apart must be within ± 0.002D
greater, but no less than, the mean at the nozzle exit.

5. The nozzle surface in the direction of airflow from the nozzle inlet towards the nozzle exit shall fair smoothly
so that a straight-edge may be rocked over the surface without clicking. The macro-pattern of the surface shall
not exceed 0.001D, peak-to-peak. The edge of the nozzle exit shall be square, sharp, and free of burrs, nicks
or roundings.

6. In a chamber, the use of either of the nozzle types shown above is permitted. A nozzle with throat taps shall
be used when the discharge is direct into a duct, and the nozzle outlet should be flanged.

7. A nozzle with throat taps shall have four such taps conforming to Figure 4, located 90° ± 2° apart. All four taps
shall be connected to a piezometer ring.

Figure 8A - Elliptical Nozzles

38
ANSI/AMCA 500-L-07

Figure 8B - Three Arc Approximation of Elliptical Nozzles

39
ANSI/AMCA 500-L-07

Figure 9A - Flow Straightener

Figure 9B - Star Straightener

Airflow Straighteners
Note: The devices shown are the primary airflow straighteners for Section 7.2.3.

40
ANSI/AMCA 500-L-07

Figure 10 - Transformation Pieces

41
ANSI/AMCA 500-L-07

This figure reproduced from HEVAC Technical


Specification, Laboratory testing and rating of
weather louvres when subjected to simulated
rainfall, courtesy of Heating Ventilating and Air
Conditioning Manufacturers Association (HEVAC)

Figure 11 - Schematic Diagram of Nozzle Control System

42
ANSI/AMCA 500-L-07

This figure reproduced from HEVAC Technical


Specification, Laboratory testing and rating of
weather louvres when subjected to simulated
rainfall, courtesy of Heating Ventilating and Air
Conditioning Manufacturers Association (HEVAC)

Figure 12 - Core Area and Rainfall Coverage

43
ANSI/AMCA 500-L-07

Annex A. Presentation of Air Performance Results for Rating Purposes

[This annex is not a part of ANSI/AMCA Standard 500-L but is included for information purposes only. See
Publication 511, Certified Ratings Program for Air Control Louvers, for complete information on rating.]

A.1 Rating air performance - pressure drop

For the purpose of publishing ratings, extrapolation from test data is permissible. The portion of the curve obtained
by extrapolation shall be charted with a broken line and must be a smooth continuation of the adjacent portion of
the curve. The static pressure drop shall not be extrapolated more than 50 percent of the range of the test either
upwards or downwards.

A.1.1 Louver. The results of an air performance test shall be presented as a statement of the pressure drop
across the louver (Pa) versus the free area velocity (m/s) at standard air density.

A.2 Rating air leakage

A.2.1 For in-duct or in-wall mounting. The results of an air leakage test shall be presented as a statement of
the pressure differential across the louver (Pa) versus airflow rate per square foot of louver or damper area
(m3/s/sq. ft area) at standard air density. The area is determined by the installation method as shown in the
sketches below. Results shall include a statement of the specific seating torque holding the louver closed, and
direction of airflow.

44
ANSI/AMCA 500-L-07

Annex B. Water Penetration Performance

This annex is not a part of ANSI/AMCA Standard 500-L but is included for information purposes only.

For purposes of published ratings the curve of water carryover per determination versus free area velocity may be
extended to intersect the line of weight of water carryover specified in AMCA Publication 511. This intersection may
be considered the free area velocity at the point of beginning of water penetration. In addition, the results shall
include: the louver test size, a specific time duration and at standard air.

45
ANSI/AMCA 500-L

Annex C. References
This annex is not a part of ANSI/AMCA Standard 500-L but is included for information purposes only.

[1] PAGE, C. H. and VIGOUREUX, P., The International System of Units (SI), National Bureau of Standards, NBS
Special Publication 330, 1972. (Now known as NIST.) AMCA #1140

[2] ibid, p19. AMCA #1140

[3] ASME Steam Tables, p 283, American Society of Mechanical Engineers, 1967. AMCA #2312

[4] Standard Measurement Guide. Engineering Analysis of Experiemental Data, ASHRAE, Inc., ASHRAE Standard
41.5-75 (1975) AMCA #1142

[5] FOLSOM, R. G., Review of the Pitot Tube, University of Michigan, IP-142, 1955. AMCA #1144

[6] Supplementary Notes on Pressure Tappings, International Organization for Standardization, ISO/TC 117/SC
1/WG 2 (U.K. 4) 1969. AMCA #1145

[7] Bohanon, H.R., Air Flow Measurement Velocities, Memorandum Reports to AMCA 210/ASHRAE 51.P
Committee, April 18, 1973 AMCA #1146

[8] Winternitz, F.A.L. and Fischal, S.F., A Simplified Integration Technique for Pipe Flow Measurement, Water
Power, Vol. 9, No. 6, June, 1957, pp. 225-234 AMCA #1147

[9] Brown, N., A Mathematical Evaluation of Pitot Tube Traverse Methods. ASHRAE, Inc., ASHRAE Technical
Paper No. 2335, 1975 AMCA #1003

[10] BOHANON, H. R., Fan Test Chamber-Nozzle Coefficients. American Society of Heating, Refrigerating and
Air-Conditioning Engineers, Inc., ASHRAE Technical Paper No. 2334, 1975. AMCA #1038

[11] Bohanon, H.R., Laboratory Fan Test: Error Analysis. ASHRAE, Inc., ASHRAE Technical Paper No. 2332,
1975 AMCA #1034

[12] Instruments and Apparatus, Pressure Measurement, American Society of Mechanical Engineers, ASME PTC
19.2-1987. AMCA #2093

[13] Report on Measurements Made on the Downstream Side of a Fan with Duct Connection. International
Organization for Standardization, ISO/TC 117 SC1/WG 1 (Denmark-4) 46E, 1971. AMCA #1152

[14] Whitaker, J., Bean, P.G., and Hay, E., Measurement of Losses Across Multi-Cell Flow Straighteners, National
Engineering Laboratory, NEL Report No. 46 1, July, 1970 AMCA #1153

[15] HELANDER, L., Psychrometric Equations for the Partial Vapor Pressure and the Density of Moist Air, Report
to AMCA 210/ASHRAE 51P Committee, November 1, 1974. AMCA #1156

[16] Handbook of Fundamentals, Weight of Air Tables, Chapter 6, American Society of Heating, Refrigerating and
Air-Conditioning, 1993

[17] HELANDER, L., Viscosity of Air, Memorandum Report to AMCA 210/ASHRAE 51P Committee, January 11.
1973. AMCA #1158

[18] Measurement of Fluid Flow by Means of Orifice Plates and Nozzles, International Organization for
Standardization, ISO/R 541-1967E. AMCA #1162

[19] Metric Practice Guide, American Society for Testing Materials, ASTM E 380-92, ANSI Z 210.1-1973. AMCA #1160

[20] Laboratory testing and rating of weather louvres when subjected to simulated rain, Heating, Ventilating and
Air Conditioning Manufacturers Association (HEVAC), 4th Edition, January 1995.
46
ANSI/AMCA 500-L-07

Annex D. Simulated Rain Spray Nozzles

The general arrangement for the simulated rain spray nozzles shall be as indicated in Figures 5.11 and 5.12.

The overall required effect is to cover the area of the louver and calibration plate in a uniform manner.

In order to achieve a satisfactory trajectory, water flow rate and droplet size from the nozzles it is necessary to spray
water from the nozzles in short bursts with only one of the 4 nozzles spraying at any instant for 75 mm/h (3 in./h)
rainfall rates, more nozzles for greater than 75 mm/h (3 in./h) rainfall rates.

This is achieved by connecting each nozzle array to an electrically or mechanically operated timer valve as shown
in Figure 11.

The total airflow rate to the nozzle array shall be maintained constant and the water flow sufficient to ensure that
the droplet size is significant.

The nozzles used shall be of the wide spray type featuring a solid cone-shaped spray pattern with a square impact
area, and a spray angle of 93° to 115° with the specified capacity at 30 kPa (4.35 psi) pressure.

47
ANSI/AMCA 500-L-07

Annex E. Water Eliminator Performance Test

E.1 The following installation and procedures shall be used to check the effectiveness of the water eliminators in
the water collection duct as shown in Figure 5.11. The test shall be carried out for the extremes of the louver test
conditions ie,

Rainfall rate = 75 mm/h (3 in./h)

simulated wind=13 m/s (29 mph) ventilation rate = Maximum chamber airflow rate not to exceed
3.5 m/s. (7.8 mph)

simulated wind=13 m/s (29 mph) no ventilation rate

For extended range, the test shall be carried out for the following extremes of the louver test conditions:

Rainfall rate = 200 mm/h (8 in./h)

simulated wind = 22.4 m/s (50 mph) ventilation rate = Maximum chamber airflow rate not to exceed
3.5 m/s (7.8 mph)

simulated wind = 22.4 m/s (50 mph) no ventilation rate

E.2 With the test conditions spelled out above, the maximum water leakage through the water eliminator shall be
less than 3% of the water flow rate through the nozzle.

48
ANSI/AMCA 500-L-07

Annex F. Wind Driven Rain Performance

F.1 Penetration classification

Louvers shall be classified by their ability to reject simulated rain. The following table shows different classifications
based on the maximum simulated rain penetration per square meter (square feet) of louver. Water penetration
rating at a given louver face velocity is determined by the water penetration while the louver is subjected to a
selected simulated rainfall rate and wind velocity.

Class Effectiveness Maximum allowed penetration of simulated rain l/h/m2 (gal/h/ft2)

75 mm/h (3 in./hr) rainfall & 13 m/s 200 mm/h (8 in./hr) rainfall & 22 m/s
(29 mph) wind velocity (50 mph) wind velocity

A 1 to 0.99 0.75 (0.018) 2 (0.049)

B 0.989 to 0.95 3.75 (0.092) 10 (0.245)

C 0.949 to 0.80 15.0 (0.368) 40 (0.982)

D Below 0.8 Greater than 15.0 (0.368) Greater than 40 (0.982)

These classification apply at various core velocities.

F.2 Discharge loss coefficient

The discharge loss coefficient given in the following table is determined in accordance with this standard.

Class Discharge Loss Coefficient

1 0.4 and above

2 0.3 to 0.399

3 0.2 to 0.299

4 0.199 and below

The water penetration class letter should precede the coefficient of discharge class letter followed by the limiting
core velocity such as:

A 2 up to 1 m/s
B 2 up to 2 m/s
C 2 up to 3 m/s

49
AIR MOVEMENT AND CONTROL
ASSOCIATION INTERNATIONAL, INC.
30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.
Tel: (847) 394-0150 Fax: (847) 253-0088
E-Mail : info@amca.org Web: www.amca.org

The Air Movement and control Association International, Inc. is a not-for-profit international association of the
world’s manufacturers of related air system equipment primarily, but limited to: fans, louvers, dampers, air
curtains, airflow measurement stations, acoustic attenuators, and other air system components for the industrial,
commercial and residential markets.

You might also like