1. General
1.1. Geberit HDPE Soil and Waste Drainage Pipe
1.1.1. Pipe Characteristics
1.2. Geberit HDPE Fittings
2. Physical Characteristics
2.1. Mechanical Characteristics
2.2. Thermal Characteristics
2.3. Electrical Properties
2.4. Chemical Resistance
3. Installation
3.1. Cutting and Preparation
3.2. Tooling
3.2.1. Butt Welding
3.2.2. Electro-Welding
3.4. Brackets
3.5. Fire Protection
4. Testing
5. Storage of HDPE pipes
6. Contact Details
Geberit Sales Ltd · Geberit House · Academy Drive · Warwick · Warwickshire · CV34 6QZ
Telephone + 44 (0)1926 516 800 · Fax +44 (0)1926 516 815 · technical@geberit.co.uk · www.geberit.co.uk
1. General
For relevant approvals, please contact Geberit Product Management – Piping, or alternatively
refer to the Geberit Drainage Systems Installation Guide.
2. Physical Characteristics
Geberit Sales Ltd · Geberit House · Academy Drive · Warwick · Warwickshire · CV34 6QZ
Telephone + 44 (0)1926 516 800 · Fax +44 (0)1926 516 815 · technical@geberit.co.uk · www.geberit.co.uk
2.3. Electrical Properties
Measured under standard climatic conditions of 23ºC, 50% relative air humidity.
3. Installation
The system shall be installed all in accordance with Geberit’s installation recommendations,
and be compliant with current building regulations.
For further information, refer to the Geberit Drainage Systems Installation Guide.
3.2. Tooling
3.2.2. Electro-Welding
ESG 40/200 240V 40mm - 160mm
ESG 40/200 110V 40mm - 160mm
ESG – T2 Starter Switch 240V 200mm - 315mm
(Advanced Welding machine to be announced)
Prior to Electro-welding, the pipe end must be prepared. Refer to the Geberit
Drainage Systems Installation Guide for details.
3.3. Expansion
Expansion joints must be provided at a maximum of 6 metre intervals and/or changes in
direction more than a metre apart, unless bending legs are positioned to allow thermal
movement. For further information refer to the Geberit Drainage Systems Installation
Guide.
Geberit Sales Ltd · Geberit House · Academy Drive · Warwick · Warwickshire · CV34 6QZ
Telephone + 44 (0)1926 516 800 · Fax +44 (0)1926 516 815 · technical@geberit.co.uk · www.geberit.co.uk
3.3.1.Rigid Installation
Thermal expansion can be contained within the material itself due to its high elasticity
when buried into a solid medium such as concrete. For further information please
refer to the Geberit Drainage Systems Installation Guide.
3.4. Brackets
Brackets should be provided to allow support and to control the directional movement of
thermal expansion.
Brackets shall not inadvertently anchor a system that is designed to expand.
Refer to the Geberit Drainage Systems Installation Guide for full details.
4. Testing
The work shall be inspected and tested during installation. All work which will be concealed
shall be tested before it is finally enclosed. A final test shall be made upon completion for
soundness and performance in accordance with BS EN 12056 Code of Practice for Sanitary
pipe-work.
All completed Soil & Waste systems to be air tested to a minimum of 38mm water gauge over
3 minutes with no pressure drop.
6. Contact Details
Geberit Sales Ltd Telephone: 01926 516800
Geberit House Fax: 01926 516809
Academy Drive E-mail: technical@geberit.co.uk
Warwick
Warwickshire
CV34 6QZ
Geberit Sales Ltd · Geberit House · Academy Drive · Warwick · Warwickshire · CV34 6QZ
Telephone + 44 (0)1926 516 800 · Fax +44 (0)1926 516 815 · technical@geberit.co.uk · www.geberit.co.uk