Professional Documents
Culture Documents
25635-220-3DR-M11-00001-000
.
Source
Code.
TABLE OF CONTENTS
ATTACHMENTS
ATTACHMENT 1: Wilson Nomogram for Limit Settling Velocity (ANSI/HI 12.1-12.6, 2005)
ATTACHMENT 3: Effect of average particle size and impeller diameter on Hr and Rh (ANSI/HI
12.1/12.6, 2005)
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 2 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
1.0. GENERAL
These criteria will govern the design of In-Plant Fluid and Slurry Handling for Las
Bambas Project for Xstrata Tintaya S.A. These criteria will be applied in conjunction
with site conditions and mechanical specifications governing specific elements of
individual projects.
The source code letters listed for each criterion refer to the origin of that criterion value.
In certain cases, two source codes may be referenced. The following letter code
designators are used:
Code Description
A Criteria provided by the client
B Standard industry practice
C Bechtel recommendation
D Vendor originated criteria
E Criterion from calculations
F Engineering handbook data
G Assumed data
H Criteria provided by “Technology Supplier”.
Unless specifically stated otherwise, the design of all mechanical systems will be
B
based on the current standards and/or codes that concern to the specific system as
issued by the following organizations:
In addition to the applicable codes and standards, the design will comply with all laws
or regulations of local authorities. In the event of conflicting requirements between
codes and standards, the most stringent will apply.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 3 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
4.0. REFERENCE DOCUMENTS
This Design Criteria shall apply in conjunction with the Project Documents, Drawings
C
and Bechtel Standard Documents listed below.
This Hydraulic Design Criteria shall be used in conjunction with the following project
documents:
25635-220-3DR-V01-00001 DESIGN CRITERIA FOR PROCESS
25635-220-3DR-H01-00001 DESIGN CRITERIA FOR ENVIRONMENTAL
25635-220-3DR-M10-00001 DESIGN CRITERIA FOR MECHANICAL DESIGN
25635-220-3DR-M85-00001 DESIGN CRITERIA FOR MATERIAL HANDLING.
4.2. Drawings
• “Engineering Design Guide for Fluid Flow in Piping Systems”, Doc. No. 3DG-
M11-00001 – Rev. 003.
• “Engineering Design Guide for Pipeline Orifice Sizing”, Doc. No. 3DG-M47-
00001 – Rev. 001.
• “Mechanical Engineering Design Aid for Materials Handling Seminar 1967
Liquids”, Doc. No. 3DZ-G04H-00002, Rev. 000.
• “Engineering Department Procedure, Design Criteria”, 3DP-G04-00001,
Revision 001.
• “Design Guide for Hydraulics for Slurry Flow”, 3DG-K04-00007, Revision 000.
Page 4 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
at the AIME Annual Meeting.
• Karassik, I.J., Messina, J.P., Cooper, P., and Heald, C.C., Editors (2008).
“”Pump Handbook”, 4th Edition, McGraw-Hill, 2008. Available on Knovel
(www.knovel.com).
• Mayerle, R., Nalluri, C. and Novak, P. (1991). “Sediment transport in rigid bed
conveyances”, IAHR Journal of Hydraulic Research, Vol. 29, 1991, No. 4.
• Mays, L.W. (1999). “Hydraulic Design Handbook”, McGraw-Hill, 1999.
Available on Knovel (www.knovel.com).
• MOP (2001). “Manual de Carreteras”, Dirección de Vialidad, Dirección
General de Obras Públicas, Ministerio de Obras Públicas, República de Chile.
• Nalluri, C. and Kithsiri, M.M.A.U. (1992). “Extended data on sediment
transport in rigid bed rectangular channels”, IAHR Journal of Hydraulic
Research, Vol. 30, 1992, No. 6.
• Warman (2009). “Slurry Pumping Manual”, 5th Edition, Weir Slurry Group,
Warman International Ltd., 2009.
• Wilson, K.C., Addie, G.R., Sellgren, A., and Clift, R. (2006). “Slurry transport
using centrifugal pumps”, 3rd Edition, Springer.
Dimensioning of slurry transport system shall consider the flow fluctuation over the C
metallurgical balance, as indicated in the Process Design Criteria and Process Flow
Diagrams. Special consideration shall be given to streams where the maximum
instantaneous flow rates can be significantly higher than the balance value.
Design flow requirements for maintenance conditions (where certain equipment may
be offline due to maintenance) shall be evaluated on a case-by-case basis for each
system.
Minimum flow rates, based on the expected fluctuation below the balance value, shall
also be evaluated.
Froth factors for maximum flow shall be applied as indicated in this document. In
addition, a realistic minimum value of froth factors shall be evaluated on a case-by-
case basis to determine the minimum volumetric flow rate.
6.1. Water B
Standard charts or tables, such as those in the “Hydraulic Design Handbook (Mays,
1999), shall be used for aqueous systems. Parameters shall be adjusted for design
temperature and plant elevation, where applicable.
The chemical properties of water, in particular reclaim water, shall be evaluated to
determine whether allowances for reduction in pipe internal diameter due to scaling
should be included in calculations.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 5 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
6.2. Slurry Viscosity C
Slurry yield stress is not considered to be significant within in-plant slurry transport
systems due to the high turbulence in these systems, and use of an apparent viscosity
is considered to be sufficient for system design.
Apparent viscosities according to the percent solids by volume of the slurry shall be as
follows (Green et al., 1978).
This section outlines the criteria to be used for design of in-plant slurry transport
gravity flow systems in pipes and open channels.
7.1 General B
Gravity transport systems shall avoid full flow through closed pipelines where feasible,
and especially the formation of siphons.
Calculations shall be carried out according to the method described in “A New
Launder Design Procedure” (Green et. al., 1978).
8 Rgi B
V =
λ
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 6 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
Where:
i = Launder slope [m/m]
λ = Darcy-Weisbach Friction factor [non dimensional]
R = Flow hydraulic radius [m]
= S/P
S = Flow cross-sectional area [m2]
P = Flow wetted perimeter [m]
V = Average velocity in the launder [m/s]
g = Gravitational acceleration [m/s2].
Colebrook-White equation:
1 ⎛ ks 2.51 ⎞
= −2 ⋅ log⎜⎜ + ⎟⎟
λ ⎝ 3.7(4 R) Re⋅ λ ⎠
4 RV
Re =
υ
Where:
ks = Boundary roughness [m]
Re = Reynolds number [non-dimensional]
υ = Slurry kinematic viscosity [m2/s].
Due to effect of high velocity free surface flows typical in slurry launders, the
roughness values given above are higher than those typically used for pipe full flow,
and are consistent with the Manning n values quoted below.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 7 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
1 2 / 3 1/ 2
V = R i
n
Where:
V = Average velocity in the launder [m/s]
n = Manning roughness coefficient
i = Launder slope [m/m]
R = Flow hydraulic radius
= S/P [m]
S = Flow cross-sectional area [m2]
P = Flow wetted perimeter [m].
In order to avoid solids settling, the limit settling velocity shall be evaluated based on
the method in Green et. al. (1978).
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 8 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
Where:
VL = Limit Settling Velocity [m/s].
FL = Function of solid particle size and concentration of solids (see
McElvain and Cave Limit Settling Velocity Parameter Diagram,
Attachment 2).
g = Gravitational acceleration [m/s2].
R = Hydraulic radius of launder [m].
Ss = Relative density of the solid particles with respect to the
conveying fluid [non-dimensional].
In order to avoid solids settling, the minimum flow velocity shall be at least 10% higher
than the limit settling velocity.
To prevent excessive wear the maximum flow velocity shall be limited to 5 m/s where
possible.
Where feasible, flow depth in open or pipe launders shall be restricted to the following:
h h
h
D B W
h = [ 0.15 - 0.5 ] h > 0.15 h > 0.3
D B W
h = Flow depth
D = Pipe diameter
B = U-shaped launder width
W = Rectangular launder width
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 9 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
7.7 Froude Number
The flow depth for design flow range shall be outside the critical flow condition, as
C
determined by Froude number (Fr) = 1.0. Where feasible, Froude numbers less than
1.4 shall be avoided (Abulnaga, 2002). The following formula shall be used to
calculate Froude number:
V
Fr =
gS
T
Where:
V = Flow velocity [m/s]
g = Gravitational acceleration [m/s2]
S = Flow cross-sectional area [m2]
T = Flow stream surface top width [m].
Maximum depth and minimum freeboard (clear height between the top of the launder
sidewall and the surface of the flow stream) calculations shall be performed at the
maximum flow rate including froth.
Where feasible, dimensioning criteria for launder height and freeboard of open
launders shall consider the following:
a) Launder heights shall be at least three times the flow depth.
b) For flow in pipes, diameter shall be at least two times the flow depth.
c) Freeboard shall be at least 0.5 m.
d) In runs with fittings, elbows, bends or restrictions (transfer boxes), freeboard
shall be at least 1.0 times the velocity head (V2/2g).
Hydraulic conditions in launder shall be computed based the slurry flow without froth,
as described in previously. Where applicable, the depth of flow in the launder shall be
increased using a froth factor, as follows:
hf = FF x h
Where:
hf = Depth including froth
FF = Froth factor
h = Depth based on slurry flow without froth.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 10 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
The following froth factors shall be used for computing the maximum depth of flow for
sizing of launders:
In addition to the above criteria, for bulk, cooper, and molybdenum launders minimum
slopes must be 4%, depending particulary on process considerations for each case.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 11 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
8.0. JUNCTION BOXES, SAMPLING BOXES AND DISTRIBUTORS
8.1. General B
Junction boxes shall be used at changes of direction and for joining flows. A junction
box that collects either the process stream for sampling or the sample reject will be
called a sampling box.
A distributor will be used where it is necessary to divide a slurry stream into two or
more streams of specified proportions having approximately the same solids
concentration, size distribution and composition as the original stream.
Junction boxes shall be designed so that the entering stream will fall on a body of
slurry based on the free fall stream trajectory and not on the bottom or walls of the
box. The volume shall be sufficient to absorb and dissipate the excessive kinetic
energy whilst avoiding solids deposition and or particle separation.
Design slurry levels in chambers upstream of free discharge overflow weirs shall be
determined assuming critical conditions at the weir, allowing for end contractions at
the sides of the outlet (Mays, 1999):
Q = 0.385 2 g ⋅ (L − 0.2 ⋅ H c ) ⋅ H c
3/ 2
The design slurry level upstream of the outlet is computed as follows, allowing for high
turbulence in slurry boxes:
Where:
Q = Flow [m3/s]
L = Width of rectangular outlet [m]
Hc = Critical energy head above outlet/weir invert [m]
Hd = Design slurry level above outlet/weir invert [m].
Where required for design optimization, sharp- or broad-crested weir equations can be
used based on weir geometry.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 12 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
8.3. Outlets to Launders F
Design slurry levels in chambers upstream of circular or rectangular lateral outlets into
open channel or pipe launders shall be determined using culvert inlet-control design
charts or equations, such as those given in the Manual de Carreteras (MOP, 2001). A
turbulence design factor shall be included in determining the design slurry level.
The head loss across submerged orifices, such as dart valves, rectangular underflow
baffles, or bottom outlets shall be estimated according to the following formula:
2
⎛ Q ⎞ 1
ΔH = ⎜⎜ ⎟⎟
⎝ Cd ⋅ S ⎠ 2g
Where:
ΔH = Loss of head through orifice [m]
Q = Flow [m3/s]
S = Orifice cross-section area [m2]
Cd = Coefficient of discharge, for sharp edged orifices C = 0.61
g = Gravitational acceleration [m/s2].
For dart valves orifice, flow velocity shall be less than 2.5 m/s. This value shall be
reviewed case by case in terms of the wear, lead loss and the particular conditions of
each design.
When fully open, dart valves should be raised above the slurry in the box.
Therefore, hydraulic calculations should estimate the maximum depth of fluid above
a dart valve outlet, to provide input to minimum required travel height for the dart
valve.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 13 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
8.6. Dimensioning of Transfer Boxes B, C
Transfer boxes shall be dimensioned to avoid overflow and splashing. For this
purpose, the following guide shall be followed (Refer to Figure 1).
^2
R > V /2g
Lc>2Lp
Lp
>1.2Hd
Hd
B
D≥h
Figure 1
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 14 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
• EITHER the vertical clearance of the outlet must be at least 20% more than the
design depth, Hd, defined for maximum flow, OR a vent pipe shall be located
no further than 5 diameters and no less than 2 diameters from the outlet and
the discharge shall be designed so that the flow reaches free surface flow
before venting. Vent pipe diameter shall be at least a quarter of the diameter of
the discharge, with a minimum of 6”. The choice between both alternatives
shall be made considering such factors as costs and/or space availability for
the box.
• The discharge section shall be arranged for a smooth transition downstream to
normal flow depth.
• Where feasible, transfer boxes shall be designed with a bed or buffering
cushion, bottom drainage (quick opening and full flow) and covers to prevent
overflowing. For boxes below ground level, the bottom of the box shall be
sloped to a pit in one corner so that the box can be easily pumped out.
• Layout of slurry outlets shall consider a transition piece with a flat bottom or a
transition area with a variable section, to provide an excess discharge area to
absorb flow turbulences and fluctuations. The use of expansion nozzles shall
be considered in the design of some inlets to the transfer boxes in order to
reduce drop speed.
Pump boxes shall be sized and arranged to avoid overflow, splashes, and sharp
variations in static pressure of slurry at the pump inlet.
Pump boxes shall be sized for not less than 60 seconds retention time at design flow
rates. Retention time will be based on the volume of the sump between the minimum
level above the top of the pump suction nozzle and the lip of the sump overflow weir.
For froth slurries, the flow rate used to size the pump box volume shall be increased
by the froth factor in Section 8.9.
Slurry level with respect to pump inlet level shall be adequate to avoid pump
cavitations at maximum flow rate, (need to exceed NPSHr and minimum submergence
for pump).
The recommended minimum submergence S of the outlet fitting below the free
surface of the liquid, given the outlet diameter D, may be obtained from the
relationship, according with ANSI/HI9.8:
S/D=1.0+2.3FD
Where:
S = minimum submergence of the outlet fitting below the free surface of the liquid [m]
D = Outlet fitting internal diameter [m]
V
FD = Froude number =
gD
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 15 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
Pipe Centerline
Freeboard shall be not less than 300 mm above the top of the overflow. The overflow
shall be at least one pipe size larger than the pump suction outlet or main flow inlet
pipe.
Concrete pump box outlet nozzles shall include a sacrificial flanged wear spool piece
as required for abrasive service, and the inclusion of such a spool for lined steel pump
boxes will be dependent on the service conditions.
The slurry levels inside vendor provided sampler boxes shall be checked against
the depth and flow of the incoming launder to ensure acceptable hydraulic
conditions at the inlet to the sampler.
The following flow factors shall be used for computing the maximum flow rate for
design of transfer, distribution and pump boxes:
Q = FF x QS
Where:
Q = Flow rate including froth
FF = Froth factor
QS = Slurry flow rate.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 16 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
When determining minimum flow, froth factor value shall be reviewed in a case by
case basis.
In addition to the froth factor applied to flow rate as presented above, pump,
distribution and transfer boxes should consider a froth freeboard to allow for froth that
will collect in the box and float on top of the slurry surface. Froth freeboard values
shall be as specified in the Process design criteria.
Slurry boxes shall be provided with emergency overflows. As a general rule, the
design flow for the emergency overflow shall be based on the following conditions:
For boxes with 1 or 2 outlets Maximum design inflow with all outlets closed.
For boxes with 3 or more outlets Maximum design inflow with at least half the
outlets closed.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 17 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
9.0. PRESSURE PIPELINES
9.1. General
VD
Re =
υ
Where:
Re = Reynolds number [non-dimensional]
υ = Slurry kinematic viscosity [m2/s]
ks = Pipe wall equivalent sand grain roughness [m].
Where:
HL = Pipe fittings losses [m].
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 18 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
Typical values of K, applicable for Reynolds numbers > 2 x 105, are given below.
Description K
Close radius bends (R/D = 1)
22.5° 0.15
45° 0.3
90° 0.75
Long radius bends (R/D = 2 to 6)
22.5° 0.1
45° 0.2
90° 0.4
Tees (90o equal offtake)
Flow through 0.2
Full flow to branch 1.9
Full flow from branch 1.6
Valve
Full open sluice or gate valve 0.2
Full open globe valve 10.0
Typical values of K can be taken from standard references such as “Pump Handbook”
(Karassik et. al., 2008) or “Hydraulic Design Handbook” (Mays, 1999). Fittings losses
for non-standard components should be obtained from suppliers.
It may be necessary to adjust fittings loss coefficients for high viscosity or non-
Newtonian fluids.
This section summarizes criteria for design of Fresh Water, Potable Water, Seal and
Cooling Water, Process Water and Solution storage and distribution systems.
9.2.1 Type of Flow B
Transport and distribution piping for water and solution systems shall be designed for
full pipe flow.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 19 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
Fresh water, such as water for dust suppression, pump seal water and cooling water
shall be sized according to the flow and the pressure recommended by the equipment
supplier.
This section outlines the criteria to be used for design of pressurized in-plant slurry
pipelines.
The limit settling velocity shall be determined in accordance with the Wilson
nomogram given in the ANSI/HI slurry pump standard (see Attachment 1).
Alternatively, the limit settling velocity may be calculated according to the Durand-
Rayo formula:
Where:
Page 20 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
g = Gravitational acceleration [m/s2].
D = Inside diameter of pipeline [m].
Ss = Relative density of the solid particles with respect to the
conveying fluid [non-dimensional].
10.0. PUMPS
10.1. General
Page 21 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
rate at the maximum/design operating point shall be at least 10% below the maximum
flow on the supplier’s pump curve, to avoid operating beyond the pump curve.
Special attention shall be paid to filter feed pumps, that the above criteria be applied to
initial conditions that have low back pressure and high flow rates, to avoid pump run-
out under this condition.
B
10.1.2 Pump speed
Slurry pumps shall be selected at a maximum operating speed at least 10 percent
below the recommended maximum by the pump supplier.
Where:
Q = Flow rate including froth
FF = Froth factor
QS = Slurry flow rate.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 22 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
FROTH FACTOR FOR PUMPS
FF
Concentrator Plant
Regrind pumps 1.1
Vertical mill recirculation 1.1
Column cells feed 1.1
Molybdenite Plant
Final concentrate 1.5
Column cells feed 1.2
Rougher tailings 1.1
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 23 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
Where:
Hatm = Absolute atmospheric (barometric) pressure at the liquid supply level, in
meters of water.
Hvap = Absolute vapor pressure of liquid at pumping temperature, in meters of
water.
Zs = Static pressure developed by height of slurry above (+) or below (-) the
centerline of the pump suction inlet, in meters of slurry.
Hi = Suction line losses including entrance loss, friction loss and pressure
drop across valves, in meters of slurry.
Sm = Slurry Specific Gravity [t/m3]
NPSHa values computed using the above formula shall be compared directly with
NPSH required (NPSHr) values given on curves provided by the pump supplier
developed from water tests, without adjusting for specific gravity. The pump supplier
shall be consulted when pumping highly viscous slurries, or slurries with entrained air,
since NPSHr values can be greater.
NPSHa shall be at least 1m greater than the NPSH required (NPSHr) by the pump as
indicated by the pump Supplier, at 40 % sump level minimum.
10.2.6 Seals B
Where feasible, slurry pumps shall have gland shaft seals flushed with pressurized
seal water. For slurry pumps in remote locations (such as booster pump stations)
without adequate supply of gland seal water, mechanical seals may be considered.
Milk of lime pumps shall have mechanical seals if possible; otherwise minimum water
flow gland seals may be utilized.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 24 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
ATTACHMENT 1: Wilson Nomogram for Limit Settling Velocity (ANSI/HI 12.1-12.6, 2005)
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 25 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
ATTACHMENT 2: Modified Durand’s Limiting Settling Velocity Parameter Diagram
(Warman, 2009)
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 26 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
This chart is valid for solids concentration volume, Cv = 15%, with solids Ss=2.65 and a
negligible amount of fine particles. Impeller diameters are given in mm and inches.
For different solids concentration volume and Ss or slurries with fine particles, head reduction
factor shall be multiplied concurrently by the correction factors Cs, Cfp and Ccv.
0.65
⎛ ( Ss − 1) ⎞
Cs = ⎜ ⎟
⎝ 1.65 ⎠
Cfp = (1 − fractional content of particles by weigh < 75μm )
2
⎛ Cv ⎞
Ccv = ⎜ ⎟
⎝ 15% ⎠
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 27 of 28
Design Criteria for Fluid and Slurry Handling
25635-220-3DR-M11-00001-000
.
Source
Code.
Electronic documents, once printed, are uncontrolled and may become outdated.
Refer to the electronic documents in Project InfoWorks stobambas for current revision.
BECHTEL Confidential © BECHTEL 2010. All rights reserved
Page 28 of 28