This Sizing Guide provides a Note: This is a guide and the 2. The graphs on pages 3 and 4
simple method of accurately system designer should consider provide various combinations
determining the correct heater/ all load demands and heat losses available based on the
storage tank combination for carefully. information from Step 1. Graphs
apartment and condominium 1, 2 and 3 are for interior and
Useful sizing equation: Boiler
complexes, hotels and motels. By exterior installations.
Output (BTU/hr) = 500 x GPM flow
providing a variety of heater and
tank combinations, the Sizing through boiler x temperature rise 3. The system designer can
(F) through boiler. combine the information from
Guide allows the system designer
Steps 1 and 2 with the
to optimally utilize existing Selecting the appropriate water
equipment and boiler room floor performance and dimensional
heater/storage tank combination is data from documents 2044,
space. Sizing is based on service a three-step procedure:
2045 and 2046 to select the
water heating recommendations of
the American Society of Heating, 1. Use the table on this page to optimal water heater and storage
determine the total number of tank to complete the installation.
Refrigeration and Air Conditioning
Engineers. sizing increments in the
installation.
Hotel — Examples
Total Sizing Increments = Number of Hotel Units x TF x FR x CW Total Sizing Increments = Number of Hotel Units x
= 145 Hotel Units x 1.3 x 1.3 x 1 TF x FR x CW
= 245 = 315 Hotel Units x 1.3 x 1.3 x 0.9
= 479.1
NOTE: Any combination of water heater and storage tank can be used as long as they cross the sizing
unit line. Whenever the combination falls on the size line, the larger unit should be installed.
Graph 1
SIZING INCREMENTS 1 - 45 STORAGE TANK CAPACITY (IN GALLONS)
82
500
INDOOR AND OUTDOOR SIZES
119
400
325 230
250
175
0 5 10 15 20 25 30 35 40 45
SIZING INCREMENTS
Graph 2
SIZING INCREMENTS 45 - 300 STORAGE TANK CAPACITY (IN GALLONS)
230 535 650
IW* 119 380 800 1000 1500 2000
1825
1670
INDOOR AND OUTDOOR SIZES
1430
1200
1010
850 82
715
600
500
MODEL
5000 I
4500 I
4500 E
INDOOR AND OUTDOOR SIZES
4050 I
4000 E
3500 I
3600 E
3050 I
3200 E
2450 I
2800 E
2000 I
2200 E
150 200 250 300 350 400 450 500 550 600
SIZING INCREMENTS
I = Indoor E = Outdoor
*(IW) Instantaneous heaters with no tank