You are on page 1of 1

Table S3.

2 Point Source emissions to water (other than sewer) – emission limits and monitoring
requirements
Emission Parameter Source Limit Reference Monitoring Monitoring
point ref. & (incl. period frequency standard or
location unit) method
W1 on site plan Purge pit Weekly –
in schedule 2 outfall analysed
Monthly
SE 5850 2510 Total weekly and
No limit average of
emission to suspended reported BS EN 872
set weekly spot
River Aire solids monthly as
sample
monthly
average
Continuous
Reported
BS EN ISO
pH 6-9 Instantaneous monthly as
10523
min max and
average pH
Continuous
Reported
Traceable to
monthly as
Temperature 30°C Instantaneous national
min max and
standards
average
temperature
Continuous
24 hour Reported
Traceable to
126 000 period monthly as
Flow 3 national
m /day beginning min max and
standards
00.01 average daily
flow
Weekly –
analysed As per
Monthly
weekly and current
average of
Total copper 0.2 mg/l reported version of
weekly spot
monthly as M18
samples
monthly guidance
average
Weekly –
analysed As per
Monthly
weekly and current
Copper (on 0.1 mg/l average of
reported version of
filtered sample) weekly spot
monthly as M18
samples
monthly guidance
average
Mercury and its
compounds,
0.005 Monthly spot
expressed as Monthly
mg/l sample BS EN13506
mercury (Total
Hg)
Cadmium and As per
its compounds, current
0.01 Monthly spot
expressed as Monthly version of
mg/l sample
cadmium (Total M18
Cd) guidance
W2 FGD waste Outlet from Continuous
water treatment FGD waste 24 hour Reported
plant outlet water 3,000 period monthly as
Flow 3 BS 3680
treatment m /day beginning min max and
00.01 average daily
flow

Permit number
EPR/AB1234CD 28