Professional Documents
Culture Documents
Protection Coordination
4 3.0
Phase-fault relays
2.0
The pick-up values of phase o/c relays are
normally set 30% above the maximum 1.0
load current, provided that sufficient short-
5 circuit current is available. 2 10 100 400
This practice is recommmended in particu- Rated transformer power [MVA]
lar for mechanical relays with reset ratios
of 0.8 to 0.85.
Time constant of inrush current
Numerical relays have high reset ratios
near 0.95 and allow therefore about 10%
6 lower setting. Nominal power 0.5 . . . 1.0 1.0 . . . 10 >10
Feeders with high transformer and/or [MVA]
motor load require special consideration.
Time constant 0.16 . . . 0.2 0.2 . . . 1.2 1.2 . . . 720
Transformer feeders [s]
7 The energizing of transformers causes
inrush currents that may last for seconds,
depending on their size (Fig. 113).
Fig. 113: Transformer inrush currents, typical data
Selection of the pickup current and as-
signed time delay have to be coordinated
so that the rush current decreases below High-resistance grounding requires much An even more sensitive setting is applied
8 the relay o/c reset value before the set more sensitive setting in the order of in isolated or Peterson-coil-grounded net-
operating time has elapsed. some amperes primary. works where very low ground currents occur
The rush current typically contains only The ground-fault current of motors and with single-phase-to-ground faults.
about 50% fundamental frequency compo- generators, for example, should be limited Settings of 20 mA and less may then be
nent. to values below 10 A in order to avoid iron required depending on the minimum
burning. ground-fault current.
9 Numerical relays that filter out harmonics
Sensitive directional ground-fault relays
and the DC component of the rush current Residual-current relays in the star point
can therefore be set more sensitive. The connection of CTs can in this case not be (integrated in the relays 7SJ512, 7SJ55
inrush current peak values of Fig. 113 will used, in particular with rated CT primary and 7SA511) allow settings as low as 5 mA.
be nearly reduced to one half in this case. currents higher than 200 A. The pickup
value of the zero-sequence relay would
10 Ground-fault relays
in this case be in the order of the error
currents of the CTs.
Residual-current relays enable a much A special zero-sequence CT is therefore
more sensitive setting, as load currents do used in this case as ground current sensor.
not have to be considered (except 4-wire The window-type current transformer
circuits with single-phase load). In solidly 7XR96 is designed for a ratio of 60/1 A.
and low-resistance grounded systems a The detection of 6 A primary would then
setting of 10 to 20% rated load current is require a relay pickup setting of 0.1 A
generally applied. secondary.
6/62 Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition
WWW.EECM.MIHANBLOG.COM
Power System Protection
Protection Coordination
Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition 6/63
WWW.EECM.MIHANBLOG.COM
Power System Protection
Protection Coordination
1 Operating time
52 M
51
2 M
52 F 52 F
51 51
3 F F
0.2–0.4
Time grading
4
Fault Fault Interruption of
inception detection fault current
6 Overshoot*
tOS
I> Margin tM
t51M
Example 1
9
Mechanical relays: tOS = 0.15 s
Oil circuit-breaker t52F = 0.10 s tTG = 0.10 + 0.15 + 0.15 = 0.40 s
Safety margin for measuring errors,
etc.: tM = 0.15
10
Example 2
6/64 Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition
WWW.EECM.MIHANBLOG.COM
Power System Protection
Protection Coordination
Calculation example
The feeder configuration of Fig. 117 and Example: Time grading of inverse-time relays for a radial feeder
the assigned load and short-circuit currents 1
are given. Load
Numerical o/c relays 7SJ60 with normal A F4 B F3 C F2 13.8 kV/ Fuse: D F1
inverse-time characteristic are applied. 0.4 kV 160 A
The relay operating times dependent on Load
13.8 kV
current can be taken from the diagram or
1.0 MVA
L.V. 75. 2
derived from the formula given in Fig. 118.
51 7SJ60 51 7SJ60 51 7SJ60 5.0%
The IP /IN settings shown in Fig. 117 have Load
been chosen to get pickup values safely
above maximum load current. Station Max. Load Iscc. max.* CT ratio Ip/IN ** Iprim*** Iscc. max.
I /Ip =
This current setting shall be lowest for [A] [A] [A] Iprim
the relay farthest downstream. The relays 3
further upstream shall each have equal or A 300 4500 400/5 1.0 400 11.25
higher current setting. 2690 200/5 1.1 220 12.23
B 170
The time multiplier settings can now be
calculated as follows: C 50 1395 100/5 0.7 70 19.93
Station C: D – 523 – – – – 4
*) Iscc.max. = Maximum short-circuit current
■ For coordination with the fuses, we
** Ip/IN = Relay current multiplier setting
consider the fault in location F1. *** Iprim = Primary setting current corresponding to Ip/IN
The short-circuit current related to
13.8 kV is 523 A. Fig. 117
This results in 7.47 for I/IP at the o/c 5
relay in location C.
■ With this value and TP = 0.05 The setting values for the relay at station B
are herewith t [s]
we derive from Fig. 118
an operating time of tA = 0.17 s ■ Current tap: IP /IN = 1.1 100
This setting was selected for the o/c relay ■ Time multiplier TP = 0.11 6
to get a safe grading time over the fuse on Given these settings, we can also check 50
the transformer low-voltage side. the operating time of the relay in B for a 40
The setting values for the relay at station C close-in fault in F3: 30
are therefore: The short-circuit current increases in this Tp [s]
20
■ Current tap: IP /IN = 0.7 case to 2690 A (see Fig. 117). The corre-
sponding I/IP value is 12.23.
7
■ Time multipler: TP = 0.05 10
■ With this value and the set value of 3.2
Station B: TP = 0.11 5
The relay in B has a back-up function for we obtain again from Fig. 118 4
the relay in C. an operating time of 0.3 s. 1.6
3
The maximum through-fault current of 8
1.395 A becomes effective for a fault in Station A: 2 0.8
location F2. ■ We add the time grading interval of
For the relay in C, we obtain an operating 0.3 s and find the desired operating time 1 0.4
time of 0.11 s (I/IP = 19.9). tA = 0.3 + 0.3 = 0.6 s.
We assume that no special requirements
for short operating times exist and can
Following the same procedure as for the 0.50
0.4 0.2 9
relay in station B we obtain the following
therefore choose an average time grading values for the relay in station A: 0.3
interval of 0.3 s. The operating time of the 0.1
■ Current tap: IP /IN = 1.0 0.2
relay in B can then be calculated:
■ Time multiplier: TP = 0.17
■ tB = 0.11 + 0.3 = 0.41 s 0.05
■ Value of IP /IN = 1395 A = 6.34
■ For the close-in fault at location F4 we 0.1 10
obtain an operating time of 0.48 s.
220 A
0.05
see Fig. 117.
■ With the operating time 0.41 s
2 4 6 8 10 20
and IP /IN = 6.34, Normal inverse I/Ip [A]
we can now derive TP = 0.11 0.14
from Fig. 118. t= . Tp [s]
(I/Ip)0.02 – 1
Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition 6/65
WWW.EECM.MIHANBLOG.COM
Power System Protection
Protection Coordination
1
= 16.000 kA
Iscc = 1395 A
Iscc = 2690 A
Imax = 4500 A
I – 0.4 kVmax
8
Fig. 119: O/c time grading diagram
6/66 Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition
WWW.EECM.MIHANBLOG.COM
Power System Protection
Protection Coordination
Secondary I2>, t2 n
a
breaker
0.2 seconds LV bus 7
I>>
b)
Fig. 120: Coordination of an o/c relay with an MV fuse and a low-voltage breaker trip device
9
10
Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition 6/67
WWW.EECM.MIHANBLOG.COM
Power System Protection
Protection Coordination
X Fig. 123
D
5
X3A ■ Typical settings of the ratio R/X are:
C
– Short lines and cables (≤ 10 km):
X2A R/X = 2 to 10
B – Medium line lengths < 25 km: R/X = 2
6 – Longer lines 25 to 50 km: R/X = 1
X1A
6/68 Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition
WWW.EECM.MIHANBLOG.COM
Power System Protection
Protection Coordination
(9~) [15~]
8
Fig. 126
10
Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition 6/69
WWW.EECM.MIHANBLOG.COM
Power System Protection
Protection Coordination
protection: Verification of design The differential relay must be a high- This check is made by assuming an exter-
1 impedance relay designed as sensitive nal fault with maximum through-fault
current relay (7VH80/83: 20 mA) with current and full saturation of the CT in the
The following design series resistor. If the series resistor is faulted feeder. The saturated CT ist then
data must be established: integrated in the relay, the setting values only effective with its secondary winding
may be directly calibrated in volts, as with resistance RCT, and the appearing relay volt-
2 CT data the relays 7VH80/83 (6 to 60 V or 24 to age VR corresponds to the voltage drop of
The CTs must all have the same ratio and 240 V). the infeeding currents (through-fault
should be of low leakage flux design ac- current) at RCT and RL. The current at the
Sensitivity
cording to Class TPS of IEC 44-6 (Class X relay must under this condition safely stay
of BS 3938). The excitation characteristic For the relay to operate in case of an inter- below the relay pickup value.
and the secondary winding resistance are nal fault, the primary current must reach a In practice, the wiring resistances RL may
3 to be provided by the manufacturer. minimum value to supply the set relay not be equal. In this case, the worst
The knee-point voltage of the CT is required pickup current (IR-set), the varistor leakage condition with the highest relay voltage
to be designed at least for two times the current (Ivar) and the magnetizing currents (corresponding to the highest relay current)
relay pick-up voltage to assure dependable of all parallel-connected CTs (n·ImR). must be sought by considering all possible
operation with internal faults. Low relay voltage setting and CTs with low external feeder faults.
magnetizing demand therefore increase
4 the protection sensitivity.
Setting
The setting is always a trade-off between
1 2 3 n sensitivity and stability. A higher voltage
Voltage limitation by a varistor setting leads to enhanced through-fault
is required if: stability, but, also to higher CT magnetizing
5 RCT RCT RCT RCT
and varistor leakage currents resulting con-
sequently in a higher primary pickup cur-
VRmax = 2 2VKN (VF –VKN) > 2kV
rent.
RL RL RL RL IFmax Through A higher voltage setting also requires a
with VF = (RCT + 2·RL + RR) higher knee-point voltage of the CTs and
N
therefore greater size of the CTs.
6 Fig. 129 A sensitivity of 10 to 20% IN is normal for
motor and transformer differential protec-
RR tion, or for restricted ground-fault protection.
Varistor
With busbar protection a pickup value
87B Calculation example: ≥ 50 % IN is normally applied.
An increased pickup value can be achie-
7 Given: n = 8 feeders
ved by connecting a resistor in parallel to
Fig. 127 N = 600/1 A the relay.
VKN = 500 V
Varistor
RCT = 4 Ohm
Sensitivity: ImR = 30 mA (at relay setpoint) Voltage limitation by a varistor is needed if
8 peak voltages near or above the insulation
IFmin = N·(IRset + Ivar + n·ImR) RL = 3 Ohm (max.) voltage (2 kV) are to be expected. A limita-
Stability: IRset = 20 mA tion to 1500 V rms is then recommended.
RR RR = 10 kOhm This can be checked for the maximum in-
IFThrough max < N· ·I ternal fault current by applying the formula
RL + RCT Rset IVar = 50 mA (at relay setpoint)
shown for VR-max.
N = CT ratio
9 Sensitivity: A restricted ground-fault protection may
IRset = Set relay pickup current normally not require a varistor, but, a bus-
IVar = Varistor spill current IFmin = N·(IRset + Ivar + n·ImR) bar protection in general does.
ImR = CT magnetizing current at The electrical varistor characteristic can be
IFmin = 600 ·(0.02 + 0.05 + 8·0.03) expressed as V=K·IB. K and B are the varis-
relay pickup voltage 1
tor constants.
10 V IFmin = 186 A (31% IN)
VKN Stability:
VKN =CT knee
point voltage RR Relay K B Varistor
IFmaxThrough < N· ·I
RL + RCT Rset setting type
VR =RR·IRset
VR VKN ≥ 2·VR IFmax Through < 600 · 10,000 ·0.02 V rms
1 3+4
≤125 450 0.25 600A/S1/S256
IFmax Through < 17 kA (28·IN)
ImR Im 125–240 900 0.25 600A/S1/S1088
6/70 Siemens Power Engineering Guide · Transmission and Distribution · 4th Edition
WWW.EECM.MIHANBLOG.COM