2. On 3.35 pm power supply isolated from both ends. Permit No. 3788
and tag No. 79 applied at both ends with danger boards displayed at
sugar side panel as no provision of Lock Out is available at Sugar
electric panel.
3. Mr. Prashant Lole (Elect. Safety officer) issued a permit to work and
activity started. Mr. Chidanand Chougule (Electrician) & Mr. Sagar
Kamble (Eletrical helper) were cutting the cable. R Y B phase cable was
cut off but during cutting the neutral cable suddenly electrical flash over
occurred.
Immediate Causes:
1. Casual approach as no auxiliary power supply (DG) of sugar was
ensured.
2. Written communication with client was not made.
3. Permission / signature of clinet was not obtained being a common
supply of Sugar and Co-gen.
4. No provision is available for LOTO applicability and work started
without Lock Out.
5. Electrical SLD of Sugar plant not studied before work.
6. PPE did not used.
Root Causes:
1. LOTO Procedure (OCP 65) was not followed.
2. Casual approach by electrical team and bypass the safety norms.
3. Reverse power in neutral of sugar MCC (Neutral floating) due to
common neutral was not ensured.