Arc Suppression Coils

Introduction

The most common type of In this scheme the system By utilizing continuously
failure in an electrical power neutral is earthed through a variable arc suppression coils,
distribution network is a single high impedance reactor, a so ideal compensation of the
phase-to-earth fault. Many called arc suppression coil earthfault current, and there-
utilities are successfully (Petersen coil), which is fore optimal efficiency of the
mitigating the effects of this adjusted to the earth resonant earthing technique
type of fault by the use of capacitance of the network. can be achieved.
earthfault compensation
systems.

Fig. 1 20 kV Arc Suppression Coils


3
Arc Suppression Coil
(ASC)

Since the topology of an Based on years of achieved by connecting or


electrical power distribution experience in the disconnecting winding
network is subject to dynamic construction of arc segments, the core induction
changes, the inductance of suppression coils, the is practically constant within
the arc suppression coil used coil design concept was the whole regulation range
for neutral earthing must be thoroughly reviewed, and slightly below satur-
variable. resulting in a new and ation. As a consequence,
Two basic principles to vary improved series of ASCs overvoltages in the system
the inductance exist: which meet today’s are limited.
requirements for
• by performing switching earthfault • compact construction
operations on the reactor compensation. By
whereby coil sections are means of modern
connected or disconnected planning and
(step coil), or production processes
substantial cost savings
• by continuous variation of for plunger core coils
the reluctance of the were also achieved.
magnetic circuit by means of
a mechanical drive (plunger
core coil). The plunger core coil
approach provides the
The earthfault protection system following advantages:
developed by Trench Austria
favours the plunger core coil • continuously variable (in on-
compared to a reactor which is load condition) by means of
adjustable in finite steps, as variation of the air gap

• no switching operations for • the adjustment is accom-


inductance variation are plished by means of a motor
required (preferable since drive unit which may be
switching can easily lead to either locally or remotely
network perturbations controlled
during earthfault) and
• automatic tuning to the
• plunger core coils can be actual network condition via
tuned precisely to minimum an earthfault compensation
current at the fault location controller
due to their continuous
variability. • as current regulation is not

4
Principle Construction

Fig. 2 Principle construction of an arc suppression coil

5
Technical Data
power range 200 kVAr – 35 MVAr
voltage range up to 145/√3 kV
insulation level
rated voltage up to 36 kV fully insulated or graded insulated
rated voltage > 36 kV graded insulation
duty • 2 hours short time duty
• continuous duty
current regulation range 10 % – 100 %
rated frequency 50 Hz (60 Hz on request)
cooling method ONAN (self cooling)
installation indoor or outdoor

Fig. 3 20 kV Arc Suppression Coil


6
Standard Design / - mobile base with bi- Routine Tests
Equipment directional rollers
- measurement of winding
- porcelain bushings as per DIN; resistance
- iron cored, oil insulated coil for Um > 36 kV condenser
with continuously variable air bushings - measurement of current over
gap adjustment in on-load the whole adjustment range
condition by means of a - protective cap over low
plunger core voltage bushings - measurement of voltage ratio
between main winding and
- suitable for automatic - voltage measuring winding secondary windings
earthfault compensation via 100 V/3 A
the Trench Austria earthfault - separate-source power-
- power auxiliary winding frequency voltage test
compensation controller
(500 V, 5 % of coil power,
EFC50/EFC50i (see accessories)
30 s short time duty) for - induced overvoltage test
current injection used for the
- motor drive unit: Trench
Trench Austria earthfault - operation tests of core air
Austria model DMA,
protection system EPSY (for a gap mechanism
230/400 V, 50 Hz, (control-
detailed description refer to
voltage 230 V, 50 Hz), our brochure EPSY Earthfault
mounted on top of the tank, Protection System)
with hand-crank for emer-
Type Tests
gency service and potentio- - one additional pocket for oil
meter for remote position temperature indicator as per on request, as per agreement
indication, with separate DIN 42554
control cabinet mounted on
the side wall of the tank at - oil gauge without indicating
operational height contacts

- in oil-filled corrugated steel - dehydrating silicagel breather


tank with air cushion
- surface treatment with zinc
- oil-filling: mineral oil on primer and multiple coating,
naphthenic basis, PCB-free, top coat colour grey as per
accord. to IEC 60296 : 2003 RAL 7033

7
Special Designs /
Optional Equipment
- steel tank with flange
mounted radiators
- with detachable oil
conservator (OC)
- double float Buchholz relay
as per DIN 42566 (only with
OC)
- various insulating fluids
- current transformer
- power auxiliary winding
(with extended power rating,
continuous or short time
duty)
- devices for temperature
supervision
- minimum oil level indicator
with indicating contacts
(without OC)
- magnetic type oil level
indicator with/without
indicating contacts
(only with OC)
- plug-in cable termination
system
- surge arrester
- different motor drive types
- alternative motor voltages
- devices for remote indication
- supplementary resistor
mounting brackets/hardware
(only in connection with a
corresponding power auxiliary
winding)
Abb. 4 077/√3 kV, 31500 kVAr, short time duty 2h
8
Special ASC Designs

- air insulated resistor for Dry Type ASC/Neutral


resistive residual current Earthing Aggregat
increase (see accessories)
Design with epoxy resign
- skid base impregnated windings.
- hot galvanized

- paint/colour as per customer’s


specification

Sliding Core ASC

Simplified design for a power


range within 200-1250 kVAr,
current regulation range 1:5
with hand or motor drive.
Optional equipment as per
plunger core ASCs.

Neutral Earthing
Aggregate

Compact construction of an
arc suppression coil and a
corresponding earthing
transformer, housed in a
common oil-filled steel tank.
For a detailed description refer Fig. 5 Dry Type Neutral Earthing Aggregate 6 kV / 400 kVAR
to our brochure Neutral
Earthing Aggregates.
Technical Data
Fixed Core ASC
power range up to 1250 kVAR
Iron core coil with multiple voltage range up to 10 kV
sub-divided air gap for insulation level graded insulated to 1 kV
compensation of invariable max. BIL 60 kV
network sections, without duty • 2 hours short time duty
adjustment device.
• continuous duty
current regulation range 10 % – 100 %
rated frequency 50 Hz
cooling method AN
installation indoor

9
Accessories

Shunt Resistor One approach for detection of increase the residual earthfault
low-ohmic earthfaults is the current via a low voltage shunt
In order to eliminate earthfaults recognition by means of resistor connected to the
rapidly, the faulty feeder wattmetric directional relays. power auxiliary winding of the
has to be detected quickly and When this approach is used it is ASC.
selectively. sometimes necessary to

Fig. 6: air cooled resistor in stainless steel


enclosure, protection class IP23,
built on to the ASC base,
electrically connected to the power
auxiliary winding, including
contactor and thermal overload
protection.

10
Earthfault Compensation immediately adjusted to the of the ASC to the actual sys-
Controller EFC50 modified network. This task is tem earth capacitance. For a
achieved by the Trench Austria detailed description refer to
When changes occur in the earthfault compensation our brochure Earth-Fault
network topology the arc controller EFC50 through Compensation Controller
suppression coil must be adjustment of the inductance EFC50 / EFC50i.

Fig. 7 Earthfault Compensation Controller EFC50

Electronic
Resistor Control EZA3

The electronic resistor control


EZA3 is used for controlling a
low voltage shunt resistor
which is connected to the
power auxiliary winding of the
arc suppression coil. It also
protects the resistor and the
power auxiliary winding of the
ASC from thermal overload.

Fig. 8 Resistor control EZA3

11
Trench Austria GmbH
Paschinger Straße 49
AT-4060 Linz-Leonding/Austria
Phone +43.732.6793-0
Fax +43.732.67 13 41
email sales.at@trench-group.com
Trench Brasil LTDA
Via Expressa de Contagem, 2685
CEP 32370-485
Contagem, Minas Gerais/Brasil
Phone +55.31.391-5959
Fax +55.31.391-1828
email sales@trench.com.br
Trench China Limited
3658 Jiang Cheng Road
Minhang, Shanghai 200245
P.R. China
Phone +86.21.64630088
Fax +86.21.64637828
email sales.cn@trench-group.com
Trench France S.A.
16, rue du Général Cassagnou
B.P. 70
FR-68302 St-Louis/France
Phone +33.3.89 70 23 23
Fax +33.3.89 67 26 63
email sales.fr@trench-group.com
Trench Germany GmbH
Nürnberger Straße 199
DE-96050 Bamberg/Germany
Phone +49.951.1803-0
Fax +49.951.1803-224
email sales.de@trench-group.com
Trench Italia S.r.l.
Strada Curagnata 37
IT-17014 Cairo-Montenotte/Italy
Phone +39.019.5161.111
Fax +39.019.5161.401
email sales.it@trench-group.com
Trench Limited
Coil Product Division
71 Maybrook Drive, Scarborough
Ontario, Canada M1V 4B6
Phone +1.416.298-8108
Fax +1.416.298-2209
www.trenchgroup.com email sales.ca@trench-group.com
Trench Limited
Instrument Transformer Division
390 Midwest Road, Scarborough
Ontario, Canada M1P 3B5
Phone +1.416.751-8570
Fax +1.416.751-6952
email sales.ca@trench-group.com
Trench Switzerland AG
Lehenmattstraße 353
CH-4052 Basel/Switzerland
Phone +41.61.315 51 11
Fax +41.61.315 59 00
email sales.ch@trench-group.com