Professional Documents
Culture Documents
Abstract˖Currently, ultra-high-voltage (UHV) systems are under development in many countries around the world in order
to accommodate the increasing levels in demand for electric power. In Korea, the commercialization of a 765kV ul-
tra-high-voltage system has been ongoing since 2002. We have developed a number of protection relays suitable for the UHV
system to enable us to make a contribution to the 765kV UHV projects in Korea. During the development of the protection
relays for the 765kV UHV system we encountered several technical issues of particular interest in relation to the transformer
protection relay.In this paper, we introduce a number of technical issues, such as a development undertaken in response to the
need for an increase in transformer capacity to overcome consequent transmission restrictions, the implementation of a CT
saturation countermeasure and the requirement for high-speed operation of the current differential elements. In order to pro-
vide solutions to these issues, we have undertaken several developments, which we explain in this paper. Furthermore, with
the development of this UHV transformer protection technology, we have been able to complete the commercialization of the
transformer protection relay for the 765kV UHV system.
1 Introduction
2011The International Conference on Advanced Power System Automation and Protection
scheme used for extra high voltage applications. For the UHV power transformer are connected to a one-and-a-half CB busbar.
transformer protection scheme a differential relay is used to detect According to the one-and-a-half CB busbar system and the pro-
each type of fault separately, and a current balance relay is used to tection scheme for the UHV system introduced earlier, the num-
observe the balance of the current between the two parallel trans- ber of current inputs from the CT to the transformer protection
formers. These protection functions are implemented as main relay are 36 (12 CTs3 phases) and the voltage inputs from the
functions within the UHV transformer protection scheme. In Ta- VT used for the transformer back up protection are 9 (3 VTs3
ble 1, the main protection functions of the 765kV transformer are phases). In total, the number of analog inputs is increased to 45.
indicated. In order to accommodate this large increase in the number of
analog inputs, 6 Bay Units (BU) are used for the current inputs
Primary side Secondary side and a single Central Unit (CU) is provided to serve as an arith-
CT-H1 CT-H2 CT-M1 CT-M2
metic unit in which the voltage inputs are introduced for the
whole system. Figure 3 shows the configuration of the system.
VT-H VT-M
CU
CT-HA CT-HB
BU BU
Series
winding
Tertiary side
CT-LA CT-L1
BU BU BU BU
CT-LB CT-L2
Common
winding VT-L
Tertiary
winding
CT-NA CT-NB
To next phase
Figure 3 Unit configuration.
CT Inputs
Figure 2 Single-line diagram of 2-tank transformer protection
Main function Dev Purpose (Figure 2: CT-
ƶ)
Detect all earth faults within the H1, H2, M1,
3 UHV Transformer Protection Scheme 87U
Primary and Secondary windings M2, NA, NB
Detect phase-to-phase faults in the NA, NB, LA,
To develop the transformer protection relay for the UHV system, 87T
Differential Tertiary winding LB, L1, L2
several development issues had to be considered when compared
Relay Detect phase-to-phase, earth and
with a standard transformer protection relay: 87MA HA, NA, LA
short-circuit faults in Tank-1
(1) Corresponding increase in the number of analog inputs
Detect phase-to-phase, earth and
(2) Configuration of the current balance relay 87MB HB, NB, LB
short-circuit faults in Tank-2
(3) Implementation of a CT- saturation countermeasure
Detect unbalance current between
(4) High-speed operation of the differential relay 61S HA, HB
Series windings
The four issues above are explained in detail in the following Current
Detect unbalance current between
sections of this paper. Balance 61C NA, NB
Common windings
Relay
Detect unbalance current between
3.1 Increase in analog inputs 61T LA, LB
Tertiary windings
In Korea, in general above 345kV the substation busbar configu-
ration is usually a one-and-a-half CB arrangement. Therefore,
both the 765kV primary side and the 345kV secondary side of the 3.2 Current Balance Relay
As introduced above, the current balance relay is an element for
2011The International Conference on Advanced Power System Automation and Protection
Id
2011The International Conference on Advanced Power System Automation and Protection
2TKOCT[
%WTTGPV Differential Relay
2TKOCT[
%WTTGPV Figure 9 Configuration of 2f block.
5GEQPFCT[
%WTTGPV
5GEQPFCT[
%WTTGPV DIF Current (Id)
6GTVKCT[
%WTTGPV
Equivalent to
inrush current
&KTTGTPVKCN (2f element is
%WTTGPV=+F? included)
&KH Output of 2f
&KH*1%
Figure 8 Verification test results for the response of transformer protection relay
to an external fault with CT saturation. In other words, it is necessary to make the 2f detection reset
time faster in order to meet the requirement that the transformer
protection operating time is less than 30ms. In order to solve this
3.4 High-speed operation problem, an arithmetic algorithm, based upon the characteristics
In order to minimize the electrical and mechanical stress to of a 765kV transformer, contained within the 2f element is uti-
equipment on the 765kV system when faults occur, high-speed lized so that resetting of the 2f detection function is faster. As a
operation of the protection is desirable. In this 765kV project, the result, a typical operating time of less than 26ms has been
operating time of the transformer protection differential relay achieved.
must be less than 30ms. In order to respond to this requirement,
the internal arithmetic algorithm has been optimized. In addition,
within the transformer percentage differential relay, a 2nd har- 4 Conclusion
monic detection function (2f block) has been implemented in
order to avoid unwanted operation when inrush current occurs. The commercialization of a transformer protection relay for the
An outline of the 2f block configuration is shown in Figure 9. In 765kV UHV system in Korea was completed in 2010. All of the
Figure 10 a current waveform during an internal fault is used to UHV protection relays have been designed taking into account
2011The International Conference on Advanced Power System Automation and Protection
References