EXPERIMENT NO. 10: To provide hot, cold, humid or dry condition under which
article may be placed.
PROCEDURE: First of all Switch on Recirculating Air Conditioning Unit apparatus after taking
care of all necessary precautions. Then, allow running of the apparatus for a while so that the
readings shown become stable. Switch on the component which is desired as per requirement
and take out the readings. Insert the values in the table of observations.
OBSERVATIONS TABLE:
1 19.5 18.6 37 23.8 19 15.8 36.8 24 11.75 2 5 --- 4.7 2.3 4.4
--
2 28 25 53.1 35.6 30.4 27.2 41.3 32.1 9 2.4 5.1 --- 4.6 2.4 4.7
--
3 26.7 27.2 53 40.3 22.9 22.3 46.4 39.5 13.5 2.4 5.2 --- 4.6 2.63 4.8
--
Intake Orifice Fan Ref Temp at Ref Temp Cond. Press. (KN Evap. Press (KN
Diff. Current Ex Valve Inlet at m )-2 m-2)
mmH2O (℃) Evap
(A) outlet
(℃)
z If T11 T13 Pc Pe
4.7 0.7 35.7 13.2 950 460
4.7 0.7 39.4 18.4 1150 525
4.6 0.7 42.1 16.2 1125 540
SPECIMEN CALCULATIONS:
Heating B-C:
Draw the points ‘B’ and ‘C’ on psychrometric chart and read out specific volume of air
So
𝒎𝒂 = 𝟎. 𝟎𝟕𝟓𝟕 √𝒛⁄𝒗𝒂
= 𝟐𝟑𝟎 × 𝟓
= 𝟏𝟏𝟓𝟎 𝑾
Draw the points ‘B’ and ‘C’ on psychometric chart and read out specific volume of air
So
𝒎𝒂 = 𝟎. 𝟎𝟕𝟓𝟕 √𝒛⁄𝒗𝒂
= 𝟐𝟑𝟎 × 𝟓
= 𝟏𝟏𝟓𝟎 𝑾
Increase of moisture = 𝒎𝒂 (𝑾𝑪 − 𝑾𝑩 )
= 𝟎. 𝟎𝟎𝟎𝟎𝟓𝟖𝟏 𝒌𝒈/𝒔𝒆𝒄
Draw the points ‘C’ and ‘D’ on psychrometric chart and read out specific volume of air
So
𝒎𝒂 = 𝟎. 𝟎𝟕𝟓𝟕 √𝒛⁄𝒗𝒂
= 𝟎. 𝟏𝟖𝟑𝟏𝟔 𝒌𝒈/𝒔𝒆𝒄
= 𝟎. 𝟎𝟎𝟎𝟓𝟗𝟐𝟖 𝒌𝒈/𝒔𝒆𝒄
COMMENTS:
DEPARTMENT OF MECHANICAL ENGINEERING, UET LAHORE
Name: Syed Tauqeer haider Regd. No: 2015-Me-81 Date: December 2, 2018
CALCULATIONS:
OBSERVATIONS TABLE:
Dry bulb Dry bulb Dry bulb Wet bulb Orifice Pre- Specific Specifi Enthal Mass
heat c
Temperatu Temperatu Temperatu Temperatu Differenti heat py flow
capacity volume
al
re before re after re’ before re’ before er of air rate
Pressure (kjkg_1k_ (kj/kg)
Preheater Preheater Orifice Orifice inpu of air
(mm t
1)
(m^3/k
H2O) g) Kg/s
(kW)
SPECIMEN CALCULATION:
Draw the point on psychometric chart at TDd and TDw = and read out Specific volume
of air at orifice = 𝟎. 𝟖𝟓𝟔 𝒎𝟑 𝒌𝒈−𝟏
Air mass flow rate (from orifice constant)
𝒎𝒂 = 𝟎. 𝟎𝟓𝟎𝟒 √𝒉/𝑽𝑫
𝑚𝑎 = 0.0504 × √4.8/0.856
𝒎𝒂 = 𝟎. 𝟏𝟐𝟖𝟗𝟗 𝒌𝒈/𝒔𝒆𝒄
Applying steady flow equation between A&B and ignoring the Fan power input,
𝑄𝑝 = 𝑚(ℎ𝐶 − ℎ𝐵)
𝑄𝑝 = 𝑚𝐶𝑝(𝑇𝐶𝑑 − 𝑇𝐵𝑑)
𝑪𝒑 = 𝑸𝑨−𝑩 /𝒎(𝑻𝒄𝒅 − 𝑻𝑩𝒅)
𝐶𝑝 = 1.5⁄0.12899(42 − 23.6)
𝒌𝑱
= 𝟎. 𝟔𝟑𝟐𝟎𝟎 ⁄𝒌𝒈. 𝑲𝒆𝒍𝒗𝒊𝒏
COMMENTS:
Name: Syed Tauqeer Haider Regd. No: 2015-Me-81 Date: December 2, 2018
PROCEDURE: Remove the stop from the slot from the damper of air Recirculating unit
and set the damper to give 100% recirculation. Switch on the Air Recirculating Unit
Apparatus after taking care of all necessary precautions. Switch on the 0.5kW pre-heater
and adjust the fan at a moderately high speed. Allow the unit to run until the temperature
of the air circulating in the duct stabilizes. Insert the values in the table of observations.
CALCULATIONS:
TABLE/OBSERVATIONS:
SPECIMEN CALCULATIONS:
When the temperature stabilizes, the heat loss from the duct is equal to the
energy input to the heater and fan. So
U (Td - Ta) L= V (I - If)
U= 𝟖𝟐. 𝟏𝟓 𝑾⁄𝒎 𝑲
COMMENTS: