You are on page 1of 1

Codes For Design for Container Data Centre Remarks

1、Codes Used in Design:IS875、IS802、IS800、IS1893、IS456

2. Load
1)Wind Load: IS875-2015.
Basic wind speed Vb = 170 kmph (47.2m/s)
Terrain category “2”
Importance factor =1.15
Risk coefficient = 1
Topography = 1

2. Earthquake Load:IS1893-2016
Seismic Zone factor (Z) = 0.36
Importance factor I = 1.5
Soil type = Ⅱ
Response reduction R= 5

3)Snow Load:Not Considered

4)Temperature Load: Not Considered

5) Load combination:IS875-2015、IS800

4) Calculation Software:SAP2000

5) The first line to provide a model for the calculation of


building structure January 25 Luo Hai offers