STUDIO PERANCANGAN 1

PERHITUNGAN GORDING

DIMENSI PROFIL
 Jarak antar kuda kuda =4m
 Kemiringan atap = α = 30o
 Jarak antar gording = 1 m (Horizontal)
1,15 m (Diagonal)
 Mutu Baja = BJ 37 (fu = 370 Mpa; fy = 240 Mpa)
 Profil Gording = CNP 10
 `Dengan data profil :
o A = 13,5 cm2
o Ix = 206 cm4
o Iy = 29,3 cm4
o rx = 39,1 mm
o ry = 14,7 mm
o Sx = 41,2 cm3
o Sy = 8,49 cm3
o Zx = b . tf (H-tf) + ¼ tw (H-2tf)2 = 49,221 cm3
o Zy = ½ b2 tf + ¼ tw2 (H-2tf) = 11,372 cm3
o H = 100 mm
o B = 50 mm
o tw = 6 mm
o tf = 8,5 mm
o w = 10,6 kg/m

Gambar 1.1 Rencana gording


STUDIO PERANCANGAN 1

PEMBEBANAN

a) Beban Mati
Perletakan gording-gording 30° di asumsikan sendi-sendi
 Berat sendiri gording = 10,6 kg/m
 Berat Penutup Atap (PPIUG hal-12) = 50 kg/m2 x 1,15 m = 57,735 kg/m
68,335 kg/m
 Berat sambungan 10% x 66,375 kg/m = 6,8335 kg/m
q total = 75,169 kg/m
b) Beban Hidup
Beban hidup di tengah-tengah gording P = 100 kg (PPIUG 1983 pasal 3.2.1)

c) Beban Angin
Koefisien angin (α = 30o)
Menurut PPIUG 1983 pasal 4.2.1
Tekanan Angin minimum  P = 25 kg/m2 (untuk α < 65)
Koefisien angin tekan (Ct) = 0,02 α – 0,4
= 0,02 (30) – 0,4
= 0,2
Koefisien angin hisap (Ch) = -0,4
ω tekan = Ct x jarak gording x P
= 0,2 x 1,15 x 25
= 5,774 kg/m
ω hisap = -0,4 x jarak gording x P
= -0,4 x 1,15 x 25
= -11,547 kg/m
STUDIO PERANCANGAN 1

Gambar1.2 Gaya angin tekan dan angin hisap


d) Beban Air Hujan
Beban terbagi rata per m2 bidang datar berasal dari beban air hujan sebesar (40 -
0,8α) kg/m2 (PPIUG 1983 pasal 3.2.2.a)
Wh = 40 - 0,8α
= 40 – 0,8(30)
= 16 kg/m2

qh = Wh x jarak gording
= 16 x 1,15
= 18,48 kg/m
STUDIO PERANCANGAN 1

MOMEN PADA GORDING

qx

qy
q
a

qy
qy

dy

Ly

Mx

qx
qx

dx

Lx

My

MOMEN PADA GORDING


Pada arah sumbu lemah dipasang trekstang pada tengah bentang sehingga :
Bentang panjang (Ly) =4m
Bentang pendek (Lx) = ½ Ly
=½.4=2m
a) Beban mati
q = 75,169 kg/m
qy = 75,169 cos 30 qx = 75,169 sin 30
= 65,10 kg/m = 37,58 kg/m
STUDIO PERANCANGAN 1

1 1
Mx = 8 𝑞𝑦 𝐿𝑥 2 My = 8 𝑞𝑥 𝐿𝑦 2
1 1
= 8 (65,10) (2)2 = 8 (37,58) (4)2

= 130,20 kgm = 18,79 kgm

b) Beban hidup
P = 100 kg
Py = 100 cos 30 Px = 100 sin 30
= 86,603 kg = 50 kg
1 1
Mx = 4 Py Lx My = 4 Px Ly
1 1
= 4 (86,603)(2) = 4 (50)(4)

= 86,60 kgm = 25,00 kgm

c) Beban Angin
1 1
Mx = 8 (𝜔 𝑡𝑒𝑘𝑎𝑛) 𝐿𝑦 2 Mx = 8 (𝜔 ℎ𝑖𝑠𝑎𝑝)𝐿𝑥 2
1 1
= 8 (5,774) (4)2 = 8 (−11,547) (2)2

= 11,547 kgm = -23,094 kgm

d) Beban Air Hujan


qh = 18,48 kg/m2
1 1
Mx = 8 (𝑞ℎ) cos 𝛼 (𝐿𝑥)2 My = 8 (𝑞ℎ) sin 𝛼 (𝐿𝑦)2
1 1
= 8 (18,48) cos 30 (2)2 = 8 (28,48) sin 30 (4)2

= 32,00 kgm = 4,62 kgm


KOMBINASI PEMBEBANAN
Kombinasi pembebanan menurut SNI 03-1729-2002 sebagai berikut:
1. 1,4D
2. 1,2D + 1,6L +0,5(La atau H)
3. 1,2D + 1,6(La atau H) + 0,5W
4. 1,2D + W + L + 0,5 La
5. 1,2D + E + L + 0,2 S
STUDIO PERANCANGAN 1

6. 0,9D + W
7. 0,9D + E

Keterangan :
D = Beban mati
L = Beban hidup yang timbul akibat pengguna gedung
La = Beban hidup yang timbul selama perawatan oleh pekerja
H = Beban Hujan
W = Beban Angin
E = Beban Gempa
Dengan γL = 0,5 bila L< 5 kPa, dan γL = 1 bila L ≥ 5 kPa.
Beban angin hisap tidak diperhitungkan karena akan memperingan struktur dan selain itu
angin tidak selalu berembus.

Arah sumbu x Arah sumbu y


D = 130,20 kgm D = 18,79 kgm
La = 86,60 kgm La = 25,00 kgm
L =0 L =0
H = 32,00 kgm H = 4,62 kgm
W = 11,547 kgm W =0
E =0 E =0

Sumbu x Sumbu y
No Kombinasi Pembebanan
(kgm) (kgm)
1. 1,4D 182,27 26,31
2 1,2D + 1,6L +0,5(La atau H) 199,54 35,05
3 1,2D + 1,6(La atau H) + 0,5W 300,57 62,55
4 1,2D + W + L + 0,5 La 211,08 35,05
5 1,2D + E + L + 0,2 S 242,84 47,55
6 0,9D + W 128,72 16,91
7 0,9D + E 117,18 16,91
Kombinasi pembebanan maksimum arah sumbu x adalah kombinasi ke-3
Kombinasi pembebanan maksimum arah sumbu y adalah kombinasi ke-3
STUDIO PERANCANGAN 1

KONTROL PENAMPANG
Profil : CNP 8
H = 100 mm
B = 50 mm
t = 6 mm

Flens Web
𝑏 45 ℎ 80
λ = 𝑡𝑓 = = 7,5 λ = 𝑡𝑤 = = 13,3333
6 6

𝐸 2100000 𝐸 2100000
λp = 0,38 √𝐹𝑦 = 0,38 √ = 11,2406 λp = 3,76 √𝐹𝑦 = 3,76 √ = 111,2223
2400 2400

𝐸 2100000 𝐸 2100000
λr = 1,0 √𝐹𝑦 = 0,38 √ = 29,5804 λr = 5,7 √𝐹𝑦 = 5,7 √ = 168,6083
2400 2400

Karena flens λp < λ maka flens kompak.


Karena web λ < λp < λr maka web kompak.
Jadi disimpulkan bahwa penampang kompak, maka Mn = Mp

KONTROL MOMEN
 Terhadap Leleh
Mux = 300,57 kgm
Mpx = Zx . fy
= 300,57 . 2400
= 1181,30 kgm
Mnx = Mpx
= 1181,30 kgm

Muy = 62,55 kgm


Mpy = Zy . fy
= 62,55 . 2400
= 272,93 kgm
STUDIO PERANCANGAN 1

Mny = Mpy
= 272,93 kgm
 Terhadap Tekuk Torsi Lateral
Lb = Lx = 2 m
= 200 cm
𝐸 2100000
Lp = 1,76 𝑟𝑦 √𝐹𝑦 = 1,76 . 14,7 √ 2400

= 76,5 cm = 0,765 m

√𝐼𝑦.𝐶𝑤 29,3 . 3,976


rts2 =√ = √√ = 0,51 cm
𝑆𝑥 41,2
1
𝐼𝑓 𝑥 ℎ2 𝑥50𝑥6ᶾ𝑥100²
Cw = = 12
= 3,976 cm6
2 2
1 1
J = 3 x bt3 = 3 x (2 x 50 x 63) + ((100-2) x 6 ) x 63 = 1,354 cm4

ℎ 𝐼𝑦 100 29,3
C = 2 √𝐶𝑤 = √3,976 = 12,758
2

𝐸 𝐽𝑐 𝐽𝑐 0,7 𝐹𝑦 2
Lr = 1,95rts0,7 𝐹𝑦 √𝑆𝑥 ℎ + √(𝑆𝑥 ℎ)2 + 6,76 ( )
𝐸

2100000 1,354 . 12,758 1,354 . 10,943 2 0,7 2400


= 1,95 . 0,51 √ + √( ) + 6,76 (2100000)2
0,7 2400 41,2 . 100 41,2 . 100

= 372,6871 cm
= 3,7269 m
Dikarenakan Lp < L < Lr (0,765 < 2 < 3,7269) maka,

Diketahui : Mmaks = 300,57 kgm


1/4 bentang (MA) = 75,143 kgm
1/2 bentang (MB) = 150,29 kgm
3/4 bentang (MC) = 225,43 kgm
12,5 𝑀𝑚𝑎𝑘𝑠
Cb = 2,5 𝑀𝑚𝑎𝑘𝑠+3 𝑀𝐴+4 𝑀𝐵+3 𝑀𝐶
12,5 (300,57)
= 2,5 (300,57)+3 (75,143)+4 (150,29)+3 (225,43) = 1,67
2−0,765
Mn = 1,67(1181,30 – (1181,30 – 0,7 . 2400 . 41,2)(3,7269−0,765)
STUDIO PERANCANGAN 1

= 1628,9614 kgm
Dikarenakan Mn > Mp (1628,9614 > 1181,30), maka Mn = Mp = 1628,9614 kgm
Momen Nominal Pada Penampang
ϕ Mnx = 0,9 Mnx = 0,9 . 1181,30 = 1063,17 kgm
ϕ Mny = 0,9 Mny = 0,9 . 272,928 = 245,64 kgm

ϕ Mnx ≥ Mux
1063,17 kgm ≥ 300,57 kgm  OK

ϕ Mny ≥ Muy
245,64 kgm ≥ 62,55 kgm  OK

Untuk mengantisipasi masalah puntir maka Mny dapat dibagi 2

𝑀𝑢𝑥 𝑀𝑢𝑦
+1 ≤ 1,0
𝜑𝑏.𝑀𝑛𝑥 𝜑𝑏.𝑀𝑛𝑦
2

331,843 65,367
+1 ≤ 1,0
1583,579 . 338,118
2

0,792 ≤ 1,0  OK
Jadi profil CNP 8 aman terhadap lentur dan pengaruh tekuk local

KONTROL GESER (SNI 03-1729-2002 Pasal 8.8.1)


Vu/2 ≤ φ Vn
 φ Vn = 0,9 x 0,6 x fy x Aw
= 0,9 x 0,6 x 2400 x ((10 – 2x0,6) x 8) = 7776 kg
Beban terpusat = 100 Cos 30o = 86,603 kg
Beban merata = (beban mati + beban hujan + beban angin) Cos α
= (86,603 + 18,48 + 0) Cos 30o
= 81,097856 kg/m = 0,811 kg/cm
 Vu/2 = (86,603+81,097856*4)/2
= 205,4972 kg
 Vu/2 ≤ φ Vn = 205,4972 kg ≤ 7776 kg  OK
STUDIO PERANCANGAN 1

KONTROL LENDUTAN
Lendutan maksimum yang diijinkan :
Ly = 400 cm
Lx = 200 cm
𝐿
δ ijin = 240
𝐿𝑦
δy ijin = 240
400
= 240

= 1,667 cm
𝐿𝑥
δx ijin = 240
200
= 240

= 0,833 cm
Lendutan arah sumbu y
Beban terpusat = 100 Sin 30 = 50 kg
Beban merata = (beban mati + beban hujan + beban angin) Sin α
= (75,169 + 18,48 + 0) Sin 30o
= 42,821 kg/m = 0,428 kg/cm
5 𝑞𝑡𝑜𝑡𝑎𝑙. 𝐿𝑦4 1 𝑃 𝐿𝑦 3
δy = (384) ( ) +
𝐸 .𝐼𝑥 48 𝐸.𝐼𝑥
5 0,457.44 1 50 . 43
= (384) (2𝑥106 .106 ) + 48 2𝑥106 . 106

= 0,26 < 1,667 cm  OK

Lendutan arah sumbu x


Beban terpusat = 100 Cos 30o = 86,603 kg
Beban merata = (beban mati + beban hujan + beban angin) Cos α
= (86,603 + 18,48 + 0) Cos 30o
= 81,097856 kg/m = 0,811 kg/cm
5 𝑞𝑡𝑜𝑡𝑎𝑙. 𝐿𝑥4 1 𝑃 𝐿𝑥 3
δx = (384) ( ) +
𝐸 .𝐼𝑦 48 𝐸.𝐼𝑦

5 0,7923 . 24 1 86,603 . 23
= (384) (2𝑥106 .19,4 ) + 48 2𝑥106 . 19,4

= 0,1173 < 0,8333 cm  OK


STUDIO PERANCANGAN 1

Jadi profil CNP 8 aman terhadap lendutan.