21 AIR CONDITIONING
This document must be used for training purpose only
EFFECTIVITY Page i
ALL 21 CONTENTS Dec 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 AIR CONDITIONING
UF90100 TABLE OF CONTENTS Page
EFFECTIVITY Page ii
ALL 21 CONTENTS Dec 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
21-00-00 GENERAL -
SYSTEM PRESENTATION
CONTENTS:
Introduction
Presentation
TMUAIR604 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page 1
1
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
INTRODUCTION
EFFECTIVITY
EFFECTIVITY Page
Page 2
2
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUAIR604-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page 3
3
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
PRESENTATION
EFFECTIVITY
EFFECTIVITY Page
Page 4
4
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUAIR604-P02 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page 5
5
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page 6
6
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
21-00-00 GENERAL -
SYSTEM CONTROLS AND INDICATING
CONTENTS:
Overhead Panel
Main Instrument Panel
TMUAIR80B LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page 7
1
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
OVERHEAD PANEL
EFFECTIVITY
EFFECTIVITY Page
Page 8
2
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUAIR80B-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page 9
3
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page10
4
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUAIR80B-P02 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page11
5
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page12
6
ALL 21-00-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
CONTENTS:
Basic Principle
Pack Units
Mixer Unit
Hot Air Pressure Regulating Valve (PRV)
Hot Trim Air
Air Distribution
Lavatory And Galley Ventilation
Temperature Regulation
Pack Controllers
Zone Controller
Self Examination
TMUAIR109 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page13
1
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
Hot air coming from the air bleed system is flow Hot air tapped upstream of the packs supplies the trim
regulated before entering the packs in order to be air valves through a hot air pressure regulating valve.
temperature regulated. This valve regulates the downstream pressure above the
Hot air pressure is maintained above the cabin pressure cabin pressure.
allowing the hot air flow to join the pack air supply
when necessary. HOT TRIM AIR
A part of cabin air is recirculated to decrease air
supply demand. A trim air valve associated with each zone optimizes
the temperature by adding hot air, if necessary, to
Note: the lavatories and galleys are ventilated with the cold air coming from the mixer unit.
air coming from zones and main distribution
ducts. AIR DISTRIBUTION
The mixer unit mixes regulated temperature air from The lavatory and galley ventilation system uses air
the packs with part of the cabin air supplied by from the cabin zones. A fan extracts this air through
TMUAIR109-T01 LEVEL 1
EFFECTIVITY
EFFECTIVITY Page
Page14
2
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUAIR109-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page15
3
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TEMPERATURE REGULATION
PACK CONTROLLERS
ZONE CONTROLLER
EFFECTIVITY
EFFECTIVITY Page
Page16
4
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
SELF EXAMINATION
EFFECTIVITY
EFFECTIVITY Page
Page17
5
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page18
6
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
CONTENTS:
Pack Flow Control Valve
Exchangers - Compressor
Turbine
Anti-Ice Valve
RAM Air Inlet Flap and ByPass Valve
Self Examination
TMUAIR20A LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page19
1
ALL 21-50-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
Each pack flow control valve is pneumatically operated The air expands in the turbine section which results
and electrically controlled. The flow regulation is in a very low turbine discharge air temperature. The
achieved by a torque motor under pack controller turbine drives the compressor and the cooling air fan.
control.
In case of pack compressor overheat, (230ºC = 446ºF), ANTI-ICE VALVE
the pack Flow Control Valve starts to close
pneumatically. The pack controller controls the anti-ice valve to
pneumatically open in order to stop ice formation
Note: Part of the hot air, downstream of the pack Flow across the pack condenser.
Control Valve, is sent to the hot air Pressure In case of complete pack controller failure, the
Regulating Valve anti-ice valve is signalled to pneumatically control
Each pack Flow Control Valve is automatically the pack outlet temperature (to the mixer unit) to
closed during either a same side engine start 15ºC(59ºF).
sequence or an opposite side engine start
sequence(provided the crossbleed valve is RAM AIR INLET FLAP AND BYPASS VALVE
detected open)
It reopens 30 seconds after the end of any engine The ByPass Valve and the RAM air inlet flap are
start sequence. simultaneously controlled by the pack controller.
The ByPass Valve is electrically controlled to modulate
EXCHANGERS - COMPRESSOR the pack discharge temperature by adding hot air.
The RAM air inlet flap modulates the air flow through
Bleed air is ducted to the primary heat exchanger, the exchangers.
then to the compressor. - To increase cooling, the RAM air inlet flap
The air is cooled in the main heat exchanger. Then it opens more and the ByPass Valve closes more.
passes through the reheater, the condenser and the - To increase heating, the RAM air inlet flap
TMUAIR20A-T01 LEVEL 1
water extractor in order to remove water particles closes more and the ByPass Valve opens more.
from the turbine air. During take-off and landing, the RAM air Inlet flap
is fully closed to prevent ingestion of foreign
objects.
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page20
2
ALL 21-50-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUAIR20A-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page21
3
ALL 21-50-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
SELF EXAMINATION
EFFECTIVITY
EFFECTIVITY Page
Page22
4
ALL 21-50-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
CONTENTS:
Pack Flow Control Valve Pushbutton
Pack Flow Selector
Hot Air Valve Pushbutton
Temperature Selectors
Ram Air Pushbutton
Fan Pushbutton
Self Examination
TMUAIR30A LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page23
1
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
When pack 1 (or pack 2) pushbutton is pressed in, the The PACK FLOW selector permits selection of pack valve
pack Flow Control Valve electro-pneumatically flow according to number of passengers and ambient
regulates the pack inlet air flow. conditions.
When set to OFF, the pack Flow Control Valve is Select:
maintained closed electrically. - "LO": if number of passengers is below 81,
The pack Flow Control Valve is electrically controlled - "HI": for abnormal hot and humid conditions
to close for:
- Same side engine start, Note: When "LO" is selected and cooling or heating
- Opposite side engine start provided the cannot be carried out, the zone controller
crossbleed valve is open, automatically provides a normal flow and if
- Engine fire pushbutton released out, necessary increases the engine power.Whatever
- Ditching pushbutton set to ON. the selection, the zone controller automatically
provides high flow in case of bleed air taken
and pneumatically controlled to close for: from the APU or single pack operation.
- pack overheat,
HOT AIR VALVE PUSHBUTTON
- lack of air pressure.
When the HOT AIR pushbutton is pressed in, the hot air
Pressure Regulating Valve opens and pneumatically
regulates hot air pressure above the cabin pressure.
When set to OFF, the valve closes electrically as well
as the Trim Air Valves.
Without air pressure the hot air Pressure Regulating
Valve is springloaded closed.
In case of duct temperature above 88oC (190.4oF) it is
TMUAIR30A-T01 LEVEL 1
EFFECTIVITY
EFFECTIVITY Page
Page24
2
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUAIR30A-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page25
3
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TEMPERATURE SELECTORS
FAN PUSHBUTTON
EFFECTIVITY
EFFECTIVITY Page
Page26
4
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
SELF EXAMINATION
EFFECTIVITY
EFFECTIVITY Page
Page27
5
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page28
6
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
CONTENTS:
Pack Flow Control Valve Pushbutton
ECON FLOW Pushbutton
Hot Air Valve Pushbutton
Temperature Selectors
Ram Air Pushbutton
Fan Pushbutton
Self Examination
TMUAIR30B LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page29
1
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
When the pack 1 (or pack 2) pushbutton is pressed in, When the hot air pushbutton is pressed in, the hot air
the pack Flow Control Valve electro-pneumatically Pressure Regulating Valve opens and pneumatically
regulates the pack inlet air flow. regulates hot air pressure above the cabin pressure.
When set to OFF, the pack Flow Control Valve is When set to OFF, the valve closes electrically as well
maintained closed electrically. as the Trim Air Valves.
The Pack Flow Control valve is electrically controlled Without air pressure, the hot air pressure regulating
to close for: valve is spring loaded closed.
- Same side engine start, In case of duct temperature above 88ºC(190.40ºF), it
- Opposite side engine start provided the is automatically electrically closed.
crossbleed valve is open, When it is electrically closed, the cockpit FWD and
- Engine fire pushbutton released out, AFT Trim Air Valves are also closed.
- Ditching pushbutton set to ON.
TEMPERATURE SELECTORS
and pneumatically controlled to close for:
The COCKPIT, FWD CABIN, AFT CABIN selectors enable the
- pack overheat,
selection of the desired ambient temperature in the
- lack of air pressure. corresponding zone.
The zone controller takes into account the Mixer Unit
ECON FLOW PUSHBUTTON temperature (recircultated air influence) to generate
a Pack temperature demand to satisfy the lowest
The ECON FLOW pushbutton permits economic or normal selected zone temperature. It also controls Trim Air
pack flow according to the number of passengers and Valves to add hot air for other zone fine temperature
ambient conditions (smoke removal, hot or wet adjustment.
conditions).
- ON: ECON FLOW is selected,
TMUAIR30B-T01 LEVEL 1
EFFECTIVITY
EFFECTIVITY Page
Page30
2
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUAIR30B-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page31
3
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
FAN PUSHBUTTON
EFFECTIVITY
EFFECTIVITY Page
Page32
4
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
SELF EXAMINATION
EFFECTIVITY
EFFECTIVITY Page
Page33
5
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page34
6
ALL 21-60-00 Jun 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
CONTENTS:
Pack Flow Control Valve
Pack Flow Indication
Pack Compressor Outlet Temperature
Turbine Bypass Valve Position
Pack Outlet Temperature
Emergency Ram Air Inlet Flap Position
Duct Supply
Hot Air Pressure Regulating Valve
Zone Controller Fault Indication
Cabin Fan Fault Indication
Trim Air Valves Position
Zone Duct Temperature
Zone Temperature
Temperature Unit
TMUAIR508 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page35
1
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
The pack flow control valve indication is normally The pack outlet temperature indication is green.
green. It becomes amber if the valve is not in agreement Amber if temperature is above 90ºC (194ºF).
with the demanded position. XX: invalid signal.
Normally, the pack flow indication is given by a green The emergency ram air inlet flap position indication
pointer on a white scale. is green when closed.
PACK FLOW: LO: LOW FLOW
HI: HIGH FLOW DUCT SUPPLY
Note: The flow control indication is amber if the pack Normally, the duct supply indication is green.
flow control valve is closed. Amber if both pack valves are closed.
EFFECTIVITY
EFFECTIVITY Page
Page36
2
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUAIR508-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page37
3
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
The Hot Air pressure regulating valve indication is Normally, the zone duct temperature indication is
green when open or closed, amber when faulty. green.
Amber if higher than 80ºC (176ºF).
ZONE CONTROLLER FAULT INDICATION
ZONE TEMPERATURE
The zone controller fault indication appears in case
of controller fault. The zone temperature indication is green.
- ALTN MODE: Primary zone controller fault XX: Invalid signal.
- PACK REG: Zone controller fault (basic
regulation by packs only) The cockpit and cabin compartment temperature is also
- No indication: Zone controller normal displayed on the CRUISE ECAM page.
operation. Zone temperature is normally displayed in green.
XX(amber): Temperature data is not available.
CABIN FAN FAULT INDICATION
TEMPERATURE UNIT
The cabin fan fault indication appears amber if a
fault is detected. The temperature unit of measure is indicated in cyan.
No indication if no fault. ºC: Degrees Celcius.
EFFECTIVITY
EFFECTIVITY Page
Page38
4
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUAIR508-P02 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page39
5
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page40
6
ALL 21-60-00 Nov 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
21-31-00 PRESSURIZATION -
SYSTEM DESIGN PHILOSOPHY
CONTENTS:
General
Design Philosophy
Self Examination
TMUPRE702 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page41
1
ALL 21-31-00 Oct 30/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
GENERAL
DESIGN PHILOSOPHY
EFFECTIVITY
EFFECTIVITY Page
Page42
2
ALL 21-31-00 Oct 30/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUPRE702-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page43
3
ALL 21-31-00 Oct 30/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
SELF EXAMINATION
EFFECTIVITY
EFFECTIVITY Page
Page44
4
ALL 21-31-00 Oct 30/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
21-31-00 PRESSURIZATION -
SYSTEM CONTROLS AND INDICATING
CONTENTS:
Landing Elevation Selector
Control MODE SEL Pushbutton And MAN V/S Toggle SW
Ditching Pushbutton
Self Examination
TMUPRE40A LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page45
1
ALL 21-31-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
LANDING ELEVATION SELECTOR Note 1: In MANual mode, CPC1 has a backup system with
a pressure sensor which ensures excessive
When the LDG ELEV selector is in AUTO position, the cabin altitude warning generation and pressure
system is in normal operation conditions. The landing outputs for the indication on the EIS.
elevation comes from the Flight Management & Guidance
System (automatic operation). Note 2: The MANual mode can only be selected a maximum
In other positions the selected landing elevation is of two times in a single flight. On the third
used (semi-automatic operation). selection, the auto system previously in
When not set to AUTO and as the scale on the LDG ELEV control will remain in the latched state.
rotary selector is inaccurate, use the ECAM CAB PRESS
page to correctly set the landing elevation (if QNH DITCHING PUSHBUTTON
used) or zero (if QFE used).
When the DITCHING pushbutton is selected ON, the
CONTROL MODE SEL PUSHBUTTON AND MAN V/S TOGGLE SW operating controller sends a closure signal to the
outflow valve.
When the MODE SEL pushbutton is in the AUTO position,
the outflow valve is automatically controlled by the DITCHING
active system. The CPCs use the data from the Flight When ON: The outflow valve closes, and in addition,
Management and Guidance System (FMGS) and the Air the emergency ram air inlet, avionics ventilation
Inertial/Reference System (ADIRS). extract valve and pack flow control valves close.
When in MAN position, the outflow valve is controlled
by the MANual Vertical Speed control switch. Note:
When the MANual mode is selected, it overrides the If MANual mode has been selected, the outflow valve
automatic pressure control system. Normally, this mode does not close automatically.
is only used in the event of the failure of both
automatic systems.
The MANUAL Vertical Speed control switch is spring
TMUPRE40A-T01 LEVEL 1
EFFECTIVITY
EFFECTIVITY Page
Page46
2
ALL 21-31-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUPRE40A-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page47
3
ALL 21-31-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
SELF EXAMINATION
EFFECTIVITY
EFFECTIVITY Page
Page48
4
ALL 21-31-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
21-31-00 PRESSURIZATION -
ECAM PAGE PRESENTATION
CONTENTS:
Outflow Valve
Safety Valves
System: SYS 1 Or SYS 2
Cabin Differential Pressure
Cabin Vertical Speed (V/S)
Manual Mode (MAN)
Cabin Altitude (CAB ALT)
Landing Elevation
TMUPRE503 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page49
1
ALL 21-31-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
The outflow valve position is normally displayed in The cabin vertical speed is normally displayed in
green. If fully open in flight it changes to amber. green. It changes to amber when out of normal range.
It is also displayed on the cruise page.
SAFETY VALVES - Indicated values in green when in normal range,
- and amber when V/S greater than 2000ft/mn up
The safety valve position is displayed in green when or down.
the two safety valves are closed. It becomes amber if - Pulsing advisory when V/S greater than
either safety valve is not closed. 1200 ft/mn.
EFFECTIVITY
EFFECTIVITY Page
Page50
2
ALL 21-31-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUPRE503-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page51
3
ALL 21-31-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
CABIN ALTITUDE
on MAN.
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page52
4
ALL 21-31-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUPRE503-P02 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page53
5
ALL 21-31-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page54
6
ALL 21-31-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
CONTENTS:
Avionics
Lav & Galleys
Cargo (Option)
Controllers
TMUVEN301 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page55
1
ALL 21-20-00 Dec 31/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
AVIONICS
CARGO (Option)
CONTROLLERS
TMUVEN301-T01 LEVEL 1
EFFECTIVITY
EFFECTIVITY Page
Page56
2
ALL 21-20-00 Dec 31/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUVEN301-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page57
3
ALL 21-20-00 Dec 31/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
SELF EXAMINATION
EFFECTIVITY
EFFECTIVITY Page
Page58
4
ALL 21-20-00 Dec 31/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
CONTENTS:
Blower Pushbutton
Extract Pushbutton
Skin Air Inlet Valve
Vent Indication
Skin Air Outlet Valve (extract Valve)
TMUVEN903 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page59
1
ALL 21-26-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page60
2
ALL 21-26-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUVEN903-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page61
3
ALL 21-26-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page62
4
ALL 21-26-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
CONTENTS
General
Pressure Regulating Valve (PRV)
Trim Air Valve
Inlet Isolation Valve
Extraction Fan
Outlet Isolation Valve
Pressure Switch
Ventilation Controller
Heating Controller
TMUVE110A LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page63
1
ALL 21-43-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
The FWD cargo compartment ventilation system operates The suction of the air is caused by the extraction fan
in two different modes. when it is running.
The first mode operates with the aircraft on the ground The extraction fan runs, when the aircraft is on
and in flight. the ground or in flight, when both isolation valves
The second mode operates in flight only. are open with a ∆P ≤ 1 psi.
- First mode: On the ground and in flight with Note that, in flight only, when ∆P > 1 psi,the fan
∆P ≤ 1 psi. stops.
- Second mode: Only in flight with ∆P > 1 psi.
OUTLET ISOLATION VALVE
PRESSURE REGULATING VALVE
The outlet isolation valve permits the FWD cargo
The hot air is pressure regulated by the cockpit and compartment air to be discharged overboard at a skin
cabin hot air pressure regulating valve above the cabin mounted venturi.
pressure.
The Pressure Regulating Valve regulates pressure of PRESSURE SWITCH
the hot air (4 psi above the cabin pressure) to the
Trim Air Valve. The pressure switch detects a differential pressure
and sends a signal to the ventilation controller.
TRIM AIR VALVE In flight only, when a ∆P > 1 psi is detected by the
pressure switch, the ventilation controller stops
The trim air valve regulates the hot air flow. The hot the extraction fan.
air is then mixed with the cabin ambient air to obtain Note that when the ∆P decreases below 1 psi, the
the desired temperature. controller starts the fan.
The inlet isolation valve permits the air which has The cargo ventilation system part is controlled by the
been mixed to enter into the FWD cargo compartment. ventilation controller. It controls and monitors the
isolation valves and the extraction fan.
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page64
2
ALL 21-43-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUVE110A-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page65
3
ALL 21-43-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
HEATING CONTROLLER
EFFECTIVITY
EFFECTIVITY Page
Page66
4
ALL 21-43-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
CONTENTS:
General
Cargo Compartment Temperature
Zone Indication
Duct Inlet Temperature
Trim Air Valve
Inlet Isolation Valve
Outlet Isolation Valve
TMUVE1305 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page67
1
ALL 21-43-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
The FWD cargo compartment can be optionally equipped The outlet isolation valve is displayed in green when
with Ventilation and heating systems. The AFT open or closed and amber when faulty.
ventilation and heating systems are also optional.
ZONE INDICATION
EFFECTIVITY
EFFECTIVITY Page
Page68
2
ALL 21-43-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUVE1305-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page69
3
ALL 21-43-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page70
4
ALL 21-43-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
CONTENTS:
Pressure Regulating Valve (PRV)
Trim Air Valve
Inlet Isolation Valve
Extraction Fan
Outlet Isolation Valve
Ventilation Controller
Heating Controller
TMUVE170A LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page71
1
ALL 21-43-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
The hot air is tapped from the bleed air duct and The cargo ventilation system part is controlled by the
pressure regulated by the cargo HOT AIR Pressure ventilation controller.
Regulating Valve above the cabin pressure. The cargo ventilation controller controls the
The cargo HOT AIR Pressure Regulating Valve regulates isolation valves and the extract fan. In normal
the HOT AIR pressure (4 psi above the cabin pressure) operation they are open and the fan runs continuously
going to the Trim Air Valve.
HEATING CONTROLLER
TRIM AIR VALVE
The cargo heating system part is controlled by the
The trim air valve regulates the hot air flow, the hot cargo heating controller.
air is then mixed with the cabin ambient air to obtain The heat controller receives temperature indications
the desired temperature. from two temperature sensors and controls the Trim Air
Valve in order to regulate the amount of hot air added
INLET ISOLATION VALVE to cabin ambient air.
It closes the Trim Air Valve when:
The inlet isolation valve permits the air which has - the isolation valve is closed,
been mixed to enter into the aft cargo compartment. - the cargo HOT AIR Pressure Regulating Valve is
closed,
EXTRACTION FAN - the extract fan has failed,
- the cargo door is not closed and locked.
The suction of the air is caused by the extraction fan
when it is running.
It also determines the Trim Air Valve position by means
The extract fan runs only if both isolation valves are
of a step counter (it counts the steps of the TAV
open.
stepper motor).
TMUVE170A-T01 LEVEL 1
outflow valve.
EFFECTIVITY
EFFECTIVITY Page
Page72
2
ALL 21-43-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUVE170A-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page73
3
ALL 21-43-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page74
4
ALL 21-43-00 Jul 31/00
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
21 - AIR CONDITIONING
CONTENTS:
General
Cargo Compartment Temperature
Zone Indication
Duct Inlet Temperature
Trim Air Valve
Pressure Regulating Valve
Inlet Isolation Valve
Outlet Isolation Valve
TMUVE1906 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page75
1
ALL 21-43-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
The AFT cargo compartment can be optionally equipped The inlet isolation valve is displayed in green when
with ventilation and heating systems. The FWD open or closed and amber when faulty.
ventilation and heating systems are also optional.
OUTLET ISOLATION VALVE
CARGO COMPARTMENT TEMPERATURE
The outlet isolation valve is displayed in green when
The cargo compartment temperature is indicated in green open or closed and amber when faulty.
and given by the cargo temperature sensor.
ZONE INDICATION
EFFECTIVITY
EFFECTIVITY Page
Page76
2
ALL 21-43-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
TMUVE1906-P01 LEVEL 1
UF90100
EFFECTIVITY
EFFECTIVITY Page
Page77
3
ALL 21-43-00 Sep 30/99
_A319/A320/A321 TECHNICAL TRAINING MANUAL
GENERAL FAMILIARIZATION COURSE 21 AIR CONDITIONING
EFFECTIVITY
EFFECTIVITY Page
Page78
4
ALL 21-43-00 Sep 30/99