Comments on foundation stress

Regarding analysis of stress caused by external load and allowable stress I can give following
comments :
 Allowable stress for raft foundation in accordance with Geoemechanical Report
is 179 kN/m2 which is value for raft foundation B>6 m (See Par. 6.1 )
 In this case all stresses are under this limit.
 Allowable stress in Geomechanical Report are calculated using only result from
penetration test which are usually lower that result given by another methods.
Design bearing resistance is calculated in accordance EN 1997-1:2004 and attached
 Design bearing resistance is 1.57 times greater than design value of
action.

Conclusion
Stress caused by external loads and weight of structure are less than alowable stress.
All setlement which are calculated in accordance with strong requirments are inside
prescribed limits.

Attachment

Calculation of bearing resistance according to EN1997-1:2004

Foundation width
Foundation length

Page 1 of 3
Foundation depth
Angle of shearing resistance
Design effective weight density
Design bearing resistance

The bearing resistance

The inclination of the foundation base

The shape of foundation

The inclination of load

Design resistance value

Characteristic action pressure

Design value of action

Designed by :

Hadzialic Midhat, B.Sc.Civ.Eng.

Page 2 of 3
Siljak Enes, M.Sc.

NOTES ABOUT REINFORCEMENT OVERLAPING

1. Concrete grade C25/30 with where is the


strength at 28 days based on use of cylinder for compliance testing in accordance with
EN1992-1-1:2004. Maximum cement content to be not greater than .
Maximum water/cement ratio to be 0,45
2. Steel bar reinforcement shall conform to the following ASTM A615 grades: Grade
60,
3. Concrete cover
4. Minimum lap and anchorage lengths
X12 – 400
X16 – 560
X20 – 1000
X22 – 1100
X25 – 1300
5. Required soil bearing capacity