Project

The Concrete Centre


Client Made by Date Page
Location rc 16-Mar-2019 134
RETAINING WALL design to IS Checked Revision Job No
- R68

IDEALISED STRUCTURE and FORCE DIAGRAMS DESIGN STATUS: VALID

WARNING :
Passive pressure should
only be considered if it
can be guaranteed that
there will be no future
excavation in front of
the wall.

DIMENSIONS (mm)
H= 3250 B= 4000 Tw = 300
Hw = 1500 BI = 1200 Tb = 300
Hp = 300 BN = 0 TN = 0
Hn = 0
MATERIAL PROPERTIES steel class A
fcu = 35 N/mm² gm = 1.5 concrete
fy = 500 N/mm² gm = 1.15 steel
cover to tension steel = 50 mm
Max allowable design surface crack width (W) = 0.3 mm (0.2 or 0.3
mm only)
Concrete density = 24 kN/m³
SOIL PROPERTIES Wall Geometry
Design angle of int'l friction of retained mat'l (Ø) = 30 degree
Design cohesion of retained mat'l (C ) = 0 kN/m² (Only granular backfil considered, "C" = zero)
Density of retained mat'l (q ) = 20 kN/m³
Submerged Density of retained mat'l (qs ) = 5.00 kN/m³ [default=2/3*q (only apply when 13.33
Design angle of int'l friction of base mat'l (Øb) = 20 degree ASSUMPTIONS
Design cohesion of base material (Cb ) = 10 kN/m² a) Wall friction is zero
Density of base material (qb ) = 10 kN/m³ b) Minimum active earth pressure = 0.25qH
Allowable gross ground bearing pressure (GBP) = 200 kN/m² c) Granular backfill
d)Does not include check of rotational slide/slope failure
LOADINGS Surcharge load -- live (SQK) = 10 kN/m² e)Does not include effect of seepage of ground
Surcharge load -- dead (SGK) = 10 water beneath the wall.
Line load -- live (LQK) = 10.3 kN/m f)Does not include deflection check of wall due to
Line load -- dead (LGK) = 43 kN/m lateral earth pressures
Distance of line load from wall (X) = 0 mm h) Design not intended for walls over 3.0 m high
i) Does not include check for temp. or shrinkage effects
LATERAL FORCES (unfactored) Ka = 0.33 [ default ka = (1-SIN Ø)/(1+SIN Ø)0.33
Kp = 2.04 [ default kp = (1+SIN Øb)/(1-SIN Ø2.04
Kpc = 2.86 [ default kpc = 2kp0.5 ] = 2.86
Kac = 1.15 [ 2ka0.5 ]

Force Lever arm Moment about TOE gf Fult Mult


(kN) (m) (kNm) (kN) (kNm)
PE = 29.58 LE = 1.194 35.33 1.40 41.42 49.46
PS(GK) = 10.83 LS = 1.63 17.60 1.40 15.17 24.65
PS(QK) = 10.83 LS = 1.63 17.60 1.60 17.33 28.17
PL(GK) = 0.00 LL = 3.25 0.00 1.40 0.00 0.00
PL(QK) = 0.00 LL = 3.25 0.00 1.60 0.00 0.00
PW = 11.25 LW = 0.50 5.63 1.40 15.75 7.88
Total 62.50 76.16 89.67 110.15
PP = -9.49 (LP-HN) = 0.15 -1.38 1.00 -9.49 -1.38
Project 0 The Concrete Centre
Client 0 Made by Date Page

Location 0 rc 16-Mar-2019 135


RETAINING WALL design to IS Checked Revision Job No
0 - R68

EXTERNAL STABILITY STABILITY CHECKS : OK

OVERTURNING about TOE F.O.S = 1.50


(using overall factor of safety instead of partial safety factor) LOADING OPTION
Overturning Lateral FORCE (kN) Lever arm (m) Moment (kNm) (select critical load combination)
Moments PE = 29.58 LE = 1.08 32.05 EARTH
PS(GK) = 10.83 LS = 1.63 17.60 ✘ PS(GK) Warning:
PS(QK) = 10.83 LS = 1.63 17.60 ✘ PS(QK)
PL(GK) = 0.00 LL = 3.25 0.00 ✘ PL(GK)
PL(QK) = 0.00 LL = 3.25 0.00 ✘ PL(QK)
PW = 11.25 LW = 0.50 5.63 ✘ PW
åP = 62.50
Pp = -9.49 (LP-HN) = 0.15 -1.38
å Mo = 71.50

Restoring Vertical FORCE (kN) Lever arm (m) Moment (kNm)


Moments Wall = 17.64 1.35 23.81
Base = 16.80 2.00 33.60 Warning:
Nib = 0.00 0.00 0.00
Earth = 102.50 2.75 281.88 ✘ ALLOW BUOYANCY OF BASE
Water = 30.00 2.75 82.50
Surcharge = 50.00 2.75 137.50
Line load = 53.30 1.50 79.95
åV = 270.24 å Mr = 639.24

Factor of Safety, Mr / Mo = 8.94 > 1.50 OK

SLIDING (using overall factor of safety instead of partial safety factor) F.O.S = 1.50

Sum of LATERAL FORCES, P = 62.50 kN

PASSIVE FORCE, Pp x Reduction factor (1) = -9.49 kN Red'n factor for passive force = 1.00
BASE FRICTION ( å V TANØb + 0.75 B Cb ) = -128.36 kN
Sum of FORCES RESISTING SLIDING, Pr = -137.85 kN

Factor of Safety, Pr / P = 2.21 > 1.50 OK

GROUND BEARING FAI Taking moments about centre of base (anticlockwise "+") :

Vertical FORCES (kN) Lever arm (m) Moment (kNm) BEARING PRESSURE (KN/m²)
Wall = 21.24 0.65 13.81 0 0 44 8 8 32 7 6 20 6 4 08
4. 3. 2. 2. 1. 1. 0. 0.
Base = 28.80 0.00 0.00 0.000

Nib = 0.00 2.00 0.00


Earth = 102.50 -0.75 -76.88
Water = 30.00 -0.75 -22.50
Surcharge= 50.00 -0.75 -37.50 50.000
Line load = 53.30 0.50 26.65
åV= 285.84 å Mv = -96.42

Moment due to LATERAL FORCES, Mo = 71.50 kNm


100.000

Resultant Moment, M = Mv + Mo = -24.91 kNm

Eccentricity from base centre, M / V = -0.09 m


Therefore, MAXIMUM Gross Bearing Pressure (GRP) = 77 kN/m² < 200 OK
Project 0 The Concrete Centre
Client 0 Made by Date Page

Location 0 rc 16-Mar-2019 137


RETAINING WALL design to IS Checked Revision Job No
0 - R68

BASE - unloaded side ( per metre length ) BS8110


gf = 1.45 (default = ult mt / non-factored m1.45 reference
V ult = 97.94 kN
M ult = 48.62 kNm ( '+' TENSION AT BOTTOM FACE)

BOTTOM REINFORCEMENT : Min. As = 390 mm2 Table 3.25


f= 16 mm
centres = 150 mm < 558 OK 3.12.11.2.7(b)
Asprov = 1340 mm2 > 390 OK

MOMENT of RESISTANCE : d= 242 mm


z= 223.36 mm 3.4.4.4
As' = 0 mm2
Mres = 130.17 kNm > 48.62 OK

SHEAR RESISTANCE: 100 As/bd = 0.55%


vc = 0.66 N/mm2 Table 3.8
Vres = 159.32 kN > 97.94 OK 3.5.5.2

CHECK CRACK WIDTH TO BS8110/BS8007 (:Temperature and shrinkage effects not included)
X= 80.69 mm em = 0.000236 BS8007
Acr = 86.81 mm W= 0.05 mm < 0.30 OK App. B.2

BASE - loaded side ( per metre length )


V ult = 96.20 kN
M ult = 23.89 kNm (TENSION - TOP FACE)

TOP REINFORCEMENT : Min. As = 390 mm2 Table 3.25


f= 16 mm
centres = 150 mm < 558 OK 3.12.11.2.7(b)
Asprov = 1340 mm2 > 390 OK

MOMENT RESISTANCE : d= 242 mm


z= 223.36 mm 3.4.4.4
As' = 0 mm2
Mres = 130.17 kNm > 23.89 OK

SHEAR RESISTANCE: 100 As/bd = 0.55%


vc = 0.66 N/mm2 Table 3.8
Vres = 159.32 kN > 96.20 OK 3.5.5.2

CHECK CRACK WIDTH to BS8100/ BS8007 (: Temperature and shrinkage effects not included)
X= 80.69 mm em = -0.000167 BS8007
Acr = 86.81 mm W= -0.03 mm < 0.30 OK App. B.2

REINFORCEMENT SUMMARY for BASE

Type f Centers As Min. As


mm mm mm2 mm2
TOP (DESIGN) H 16 150 1340 390 OK
BOTTOM (DESIGN) H 16 150 1340 390 OK
TRANSVERSE H 12 200 565 390 OK
Project 0 The Concrete Centre
Client 0 Made by Date Page

Location 0 rc 16-Mar-2019 138


RETAINING WALL design to IS Checked Revision Job No
0 - R68

APPROXIMATE WEIGHT OF REINFORCEMENT

No. Type Dia Length Unit Wt Weight

WALL VERTICAL - External face 7 H 12 3046 0.888 18.93


VERTICAL - Internal face 7 H 20 3110 2.466 53.69
TRANSVERSE (Ext.& Int.) 40 H 12 1000 0.888 35.51

BASE TOP (MAIN) 7 H 16 4128 1.578 45.61


BOTTOM (MAIN) 7 H 16 4128 1.578 45.61
TRANSVERSE ( T & B ) 42 H 12 1000 0.888 37.29
WALL STARTERS (Ext.) 7 H 12 1155 0.888 7.18
WALL STARTERS (Int.) 7 H 20 1475 2.466 25.46

NIB (assume same reinforcement as wall)


INTERNAL FACE (MAIN) 7 H 12 96 0.888 0.60
EXTERNAL FACE (MAIN) 7 H 20 160 2.466 2.76
TRANSVERSE (EXT.+ INT.) 2 H 12 1000 0.888 1.78

SUMMARY Approx total reinforcement per metre length of wall (kg) 274.4
Diagrams

Project 0
Location 0 DATA FOR DIAGRAMS I
RETAINING WALL design to IS sheet 1 of 2 Made by rc Job No R

DESIGN STATUS: VALID

IF(ABS(ECCY)>B/1000/2,"BEARING FAIL",IF(ABS(ECCY)>(B/1000)/6,(2*VL)/(3*((B/1000)/2-ABS(ECCY))),(VL/(B/1000)*(1+(6*ABS(ECCY))/(B/1000)))))

IF(ECCY>(B/1000)/6,IF(XX>(B/1000/2-ECCY)*3,0,(((B/1000/2-ECCY)*3-XX)/((B/1000/2-ECCY)*3))*BP),((VL/(B/1000)*(1-(6*ECCY)/(B/1000))))+(B/1000-XX)/(B/1000)*(BP-(VL/(B/1000)*(
(6*ECCY)/(B/1000)))))
4

1 76.90
0 76.90 3
BEARING PRESSURE DIAGRAM
0.4 76.90 3
0.8 76.90 3
1.2 76.90 3
1.6 76.90 3 0 1 2 3 4 5
KN/M^2

0
2 76.90 3
2.4 76.90 3
2.8 76.90 3 50
3.2 76.90 3
3.6 76.90 3 100 M
4 76.90 3
4 0.00 0
IF(ECCY<0,B/1000-B/1000/50*B24,B/1000/50*B24)
72.23
0 4.00 58.217 0 58.217 0.080 4.657 6.101 0.080 4.657
1 3.92 58.591 BEARING PRESSURE DIAGRAM 1 58.591 0.080 4.687 5.765 0.080 4.687
2 3.84 58.965 .0
0
.5
2
.0
4
.5
6
.0
8
.6
0
.1
2
.6
4
.1
6 2 58.965 0.080 4.717 5.425 0.080 4.717
4 3 3 2 2 1 1 0 0
3 3.76 59.338 3 59.338 0.080 4.747 5.079 0.080 4.747
0.000
4 3.68 59.712 4 59.712 0.080 4.777 4.729 0.080 4.777
10.000
5 3.60 60.086 5 60.086 0.080 4.807 4.374 0.080 4.807
KN/M^2

6 3.52 60.459 20.000 6 60.459 0.080 4.837 4.015 0.080 4.837


7 3.44 60.833 30.000 7 60.833 0.080 4.867 3.650 0.080 4.867
8 3.36 61.207 40.000 8 61.207 0.080 4.897 3.281 0.080 4.897
9 3.28 61.581 50.000 9 61.581 0.080 4.926 2.907 0.080 4.926
10 3.20 61.954 60.000
10 61.954 0.080 4.956 2.528 0.080 4.956
11 3.12 62.328 11 62.328 0.080 4.986 2.144 0.080 4.986
70.000
12 3.04 62.702 12 62.702 0.080 5.016 1.756 0.080 5.016
80.000
13 2.96 63.075 13 63.075 0.080 5.046 1.362 0.080 5.046
14 2.88 63.449 90.000
M
14 63.449 0.000 0.000 0.000 0.000 0.000
15 2.80 63.823 15 63.823 0.000 0.000 0.000 0.000 0.000
16 2.72 64.197 76.90 16 64.197 0.000 0.000 0.000 0.000 0.000
17 2.64 64.570 BP 0 76.903 17 64.570 0.000 0.000 0.000 0.000 0.000
18 2.56 64.944 BPE 1.2 76.903 18 64.944 0.000 0.000 0.000 0.000 0.000
19 2.48 65.318 BPI 1.5 76.903 19 65.318 0.000 0.000 0.000 0.000 0.000
20 2.40 65.691 BPZ 4 76.903 20 65.691 0.000 0.000 0.000 0.000 0.000
21 2.32 66.065 21 66.065 0.000 0.000 0.000 0.000 0.000
22 2.24 66.439 22 66.439 0.000 0.000 0.000 0.000 0.000
23 2.16 66.813 23 66.813 0.000 0.000 0.000 0.000 0.000
24 2.08 67.186 24 67.186 0.000 0.000 0.000 0.000 0.000
25 2.00 67.560 25 67.560 0.000 0.000 0.000 0.000 0.000
26 1.92 67.934 26 67.934 0.000 0.000 0.000 0.000 0.000
27 1.84 68.307 27 68.307 0.000 0.000 0.000 0.000 0.000
28 1.76 68.681 28 68.681 0.000 0.000 0.000 0.000 0.000
29 1.68 69.055 29 69.055 0.000 0.000 0.000 0.000 0.000
30 1.60 69.429 30 69.429 0.000 0.000 0.000 0.000 0.000
31 1.52 69.802 31 69.802 0.000 0.000 0.000 0.000 0.000
32 1.44 70.176 32 70.176 0.000 0.000 0.000 0.000 0.000
33 1.36 70.550 33 70.550 0.000 0.000 0.000 0.000 0.000
34 1.28 70.923 34 70.923 0.000 0.000 0.000 0.000 0.000
35 1.20 71.297 35 71.297 0.000 0.000 0.000 0.000 0.000
36 1.12 71.671 36 71.671 0.000 0.000 0.000 0.000 0.000
37 1.04 72.045 37 72.045 0.000 0.000 0.000 0.000 0.000
38 0.96 72.418 38 72.418 0.000 0.000 0.000 0.000 0.000
39 0.88 72.792 39 72.792 0.000 0.000 0.000 0.000 0.000
40 0.80 73.166 40 73.166 0.000 0.000 0.000 0.000 0.000
41 0.72 73.539 41 73.539 0.000 0.000 0.000 0.000 0.000
42 0.64 73.913 42 73.913 0.000 0.000 0.000 0.000 0.000
43 0.56 74.287 43 74.287 0.000 0.000 0.000 0.000 0.000
44 0.48 74.661 44 74.661 0.000 0.000 0.000 0.000 0.000
45 0.40 75.034 45 75.034 0.000 0.000 0.000 0.000 0.000
46 0.32 75.408 46 75.408 0.000 0.000 0.000 0.000 0.000
47 0.24 75.782 47 75.782 0.000 0.000 0.000 0.000 0.000
48 0.16 76.155 48 76.155 0.000 0.000 0.000 0.000 0.000
49 0.08 76.529 49 76.529 0.000 0.000 0.000 0.000 0.000
50 0.00 76.9029 50 76.903 0.000 0.000 0.000 0.000 0.000
67.924 53.116 67.924

Page 5
Diagrams

Project 0
Location 0 DATA FOR DIAGRAMS II
RETAINING WALL design to IS sheet 1 of 2 Made by rc Job No R

YY= 2.95 MTE= 24.98


MTLG= 0.00
MTLQ= 0.00
MTSG= 14.504
MTSQ= 14.50
MTW= 2.88

UTM= 82.52
82.52
0 0.00 0 0.00
1 0.06 0.0255 0.06 0 10 MOMENT
20 30 40DIAGRAM
50 60 70 80 90
2 0.12 0.1021 0.12
3 0.18 0.2297 0.18

0 0
0.
4 0.24 0.4084 0.24
5 0.30 0.6382 0.30

3 0
0.
6 0.35 0.919 0.35
7 0.41 1.2508 0.41

5 9
0.
8 0.47 1.6337 0.47
9 0.53 2.0677 0.53 89
WALL (M)
0.

10 0.59 2.5527 0.59


11 0.65 3.0888 0.65
18
1.

12 0.71 3.6759 0.71


13 0.77 4.3141 0.77
4 8
1.

14 0.83 5.0033 0.83


15 0.89 5.7436 0.89
7 7
1.

16 0.94 6.535 0.94


17 1.00 7.3774 1.00
0 7
2.

18 1.06 8.2708 1.06


19 1.12 9.2153 1.12
3 6
2.

20 1.18 10.211 1.18


21 1.24 11.258 1.24
6 6
2.

22 1.30 12.355 1.30


23 1.36 13.504 1.36 ULT. MT (KNM)
9 5
2.

24 1.42 14.704 1.42


25 1.48 15.955 1.48
26 1.53 17.381 1.53
27 1.59 18.976 1.59
28 1.65 20.659 1.65
29 1.71 22.429 1.71
30 1.77 24.29 1.77
31 1.83 26.232 1.83
32 1.89 28.255 1.89
33 1.95 30.365 1.95
34 2.01 32.563 2.01
35 2.07 34.853 2.07
36 2.12 37.238 2.12
37 2.18 39.722 2.18
38 2.24 42.308 2.24
39 2.30 44.999 2.30
40 2.36 47.8 2.36
41 2.42 50.712 2.42
42 2.48 53.74 2.48
43 2.54 56.887 2.54
44 2.60 60.156 2.60
45 2.66 63.55 2.66
46 2.71 67.073 2.71
47 2.77 70.729 2.77
48 2.83 74.52 2.83
49 2.89 78.451 2.89
50 2.95 82.523 2.95

0 0
0 300 WALL GEOMETRY
1200 300 4000
WALL (mm)

1200 3250
3500
1500 3250
1500 300 3000

4000 300 2500

4000 0 2000
0 0 1500
0 0
1000
0 0
500
0 0
0 0 0
0

1000

2000

4000
3000

3250 4000 BASE ( mm)

Page 6
Diagrams

ade by rc Job No R68


Date 16-Mar-19

000)*(BP-(VL/(B/1000)*(1-

0.08 4.657
0.08 4.687
0.08 4.717
0.08 4.747
0.08 4.777
0.08 4.807
0.08 4.837
0.08 4.867
0.08 4.897
0.08 4.926
0.08 4.956
0.08 4.986
0.08 5.016
0.08 5.046
0.08 5.076
0.08 5.106
0.08 5.136
0.08 5.166
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
0 0.000
88.407

Page 7
Diagrams

ade by rc Job No R68


Date 16-Mar-19

Page 8
Project 0
Location 0 CRACK WIDTH CALCULATIONS
RETAINING WALL design to IS Made by rc Job No R68
Date 16-Mar-19

WALL
MR= 15.06 MIN SPACING= 364 ASreq = 932.14 fs = 148.35Asprov%= 0.8727
As/bd= 0.009 MSBB= 558 ASBBreq 0.01 fs = 0.0025Asprov%= 0.5539
X= 95.47 MSBT= 558 ASBTreq 246.03 fs = 61.184Asprov%= 0.5539
Ic= 948749705
STS= 0.0007 Charles:
ST1= 0.0010 Charles: The last cell reference in the formaula
ST2= 0.0003455 Minor point - the formula should be DESIGN!G74 not DESIGN!
Acr= 86.046864 label given for the cell G740. Since cell G740 is blank the
W= 0.12 should be AsBT/bd not calculation currently always results in a
em= 0.0006 AsBB/bd. value of 0.01 rather than the correct
figure.
MR= 15.06 MR= 15.06
AsBB/bd= 0.0055 AsBB/bd= 0.0055 Charles:
X= 80.69 X= 80.69 The comparison in these three cells highlighted
Ic= 700256021 Ic= 700256021 in orange should be W>0.1 not W>1. Since the
STS= 0.0006 STS= 0.0003 maximum value of W is 0.3 the current
ST1= 0.0008 ST1= 0.0004 comparison results in the wrong formula being
ST2= 0.0005561 ST2= 0.0005561 used in many cases resulting in a crack width
Acr= 86.810337 Acr= 86.810337 estimate that is lower than it should be.
W= 0.05 W= -0.0325
em= 0.0002 em= -0.0002