You are on page 1of 8

International Review of Electrical Engineering (I.R.E.E.), Vol. 7, N.

2
ISSN 1827- 6660 March-April 2012

A New Approach of Under-Frequency Load Shedding Technique


in an Islanded Distribution Network

M. Karimi1, 2, H. Mohamad2, 3, H. Mokhlis1, 2, A. H. A. Bakar2

Abstract – Under-frequency load shedding is a common technique to maintain the power system
stability by removing the overload in some part of the system. The existing under-frequency load
shedding schemes operate successfully in the interconnected grid system. A particular approach
of under-frequency load shedding scheme is required for an islanded system which is known to be
not as strong as the grid. This paper presents a new approach of load shedding scheme in an
islanded distribution system incorporating distribution state estimation. The scheme is based on
an intelligent technique to reduce the effect of power deficiency in an islanded network. The
disturbance magnitude is calculated based on rate of change of frequency by using the simplest
expression of the generator swing equation. Moreover, the process for assessing the power
consumption of the customer can be achieved by state estimation method. In this paper, state
estimation for a distribution network is developed and enhanced by composite load model to
obtain the most practical value of the system state variables. Finally, the calculated value of the
disturbance magnitude will be shed according to the estimated value of loads in each bus.
Copyright © 2012 Praise Worthy Prize S.r.l. - All rights reserved.

Keywords: Distribution State Estimation, Under-Frequency Load Shedding, Distribution


Network, Distributed Generation, Islanding

Nomenclature I. Introduction
H Generator inertia constant Nowadays, islanding operation of a distribution
fc Frequency of the center of inertia network is a topic of interests to improve security and
Pi Real power injection reliability of a network. Implementing an intentional
Qi Reactive power injection islanding operation of Distributed Generation (DG) will
Pij Real power flow establish continuity of supply in the customer side [1]-
Qij Reactive power flow [2]. Accordingly, IEEE 1547 group has produced a
hi(x) Measurement matrix of the nonlinear standard which serve as a guide for practicing an
function intentional islanding operation in an electric power
H(x) Jacobian matrix of the measurement system [3]. However, the operation of a DG in an
function islanded brings up some concerns.
P Imbalance power The most critical concern is to maintain the power
DG Distributed generation quality of the islanded system. A sudden change in
UFLS Under-frequency load shedding generation and load immediately after system is islanded
SE State estimation poses a challenge in controlling the frequency response.
EMS Energy management system A large excess of load over local generation in the
DSE Distribution state estimation islanded system could result in a rapid frequency drop.
WLS Weighted least square The smaller system inertia tends to cause a quick
AUFLS Adaptive Under-frequency load shedding frequency drop. It also has a limited spinning reserve to
ROCOF Rate of change of frequency cover for the shortfall of the generation. For such an
FCM Frequency calculator module imbalance power, DG would not be able to stabilize the
LSCM Load shedding controller module frequency response. The only way to stabilize the
DSEM Distribution state estimation module frequency to its nominal value is to reject several loads.
COI Center of inertia It is a common practice among the power utilities to
employ a conventional Under-Frequency Load Shedding
(UFLS) scheme. The UFLS relay is set to shed certain
amount of loads based on a specified frequency
threshold. Although the scheme is simple, it is widely

Manuscript received and revised March 2012, accepted April 2012 Copyright © 2012 Praise Worthy Prize S.r.l. - All rights reserved

4155
M. Karimi, H. Mohamad, H. Mokhlis, A. H. A. Bakar

known to be unreliable in shedding the right amount of an islanded distribution system. The strategy utilizes an
load [4]-[7]. In an adaptive UFLS scheme, the amount of adaptive UFLS scheme incorporating an intelligent
load to be shed is determined based on the estimated technique using state estimation for distribution network
magnitude of the disturbance (power imbalance). The application. A composite load model is utilized in state
magnitude is normally estimated using the swing estimation to compute an accurate value of active and
equation which requires an estimated value of the rate of reactive power of various types of loads such as
change of frequency (df/dt) in the system [8]-[10]. industrial, commercial and domestic. The proposed
Different aspects of intelligent load shedding scheme Distribution State Estimation (DSE) is based on
have been reported in the literature [11]-[14]. Intelligent Weighted Least Square (WLS) method to find and
scheme utilized power system automation, two-way high capture a network operation point. It would be able to
speed communication system, fast and accurate intelligently shed the load in accordance to the load
measurement units and other modern facilities to acquire priority. The proposed scheme is implemented to an
knowledge and information regarding the network for intentional islanding operation considering Malaysia’s
intelligently and optimally shedding the load [15]-[18]. existing distribution network that consists of two small
Therefore, the intelligent load shedding scheme for an units of hydro generation connected in parallel to the
islanded distribution network can be achieved by grid.
implementing a real-time monitoring of the network.
However in practice, measurement devices are very
few due to high cost of these devices. Only selected II. Proposed Under-Frequency Load
locations are being monitored, mainly at the critical area Shedding Scheme
and main substations. The problem of limitation number
In this paper a new approach of UFLS Scheme for an
of measurement equipment can be found in many
islanded distribution network is proposed. The proposed
conventional distribution systems. Very often distribution
method combined an Adaptive Under-Frequency Load
network is monitored only at the primary substation. One
Shedding (AUFLS) and DSE for islanded distribution
way to address this issue is by determining the state
network.
condition of a distribution network using State
As reported in the literature, AUFLS technique
Estimation (SE). State estimator could approximate and
executes the load curtailment in two steps. In the first
estimate the power flow (active and reactive power) and
step, it clarifies and calculates the rate of change of
voltage at a bus which measurement are not available.
frequency (ROCOF) in the system immediately after the
SE is a data processing scheme which is used to find
occurrence of the disturbance, at t = 0+ s. Then, it
the best possible values of the state. In the modern
determines and computes the power imbalance (that
Energy Management System (EMS), SE program
causes the frequency drop) in the system based on simple
processes a set of raw measurement data and provides a
expression of the generator swing equation. The scheme
real-time solution which is the basis of the advanced
will always try to shed right amount of load which is
functions for system security monitoring and control
close to the calculated power imbalance.
[19]. The ability of the state estimator to achieve a high
In general, the proposed scheme adopted the AUFLS
level of efficiency and numerical robustness is very
strategy which using ROCOF to determine the amount of
importance in today’s electric utility industry that heavily
load to be shed. It is designed to compute the value of
interconnected with loads. Pseudo measurement is
unbalanced power based on AUFLS. Therefore, to shed
commonly applied in SE due to address the limitation
the right amount of load, the proposed method utilizes
number of measurements. Customer load pseudo
DSE to estimate the online value of power for load at
measurements are obtained from the historical data, load
each bus. DSE program perform as a real-time
forecasting or other similar approximation methods in
monitoring device in the distribution network. This is
customer side. Hence, a few numbers of real-time
therefore solved the lacking of real time measurement in
measurements in a system is acceptable when using SE.
the distribution network.
Various techniques have been used to obtain an SE
Another presetting step of the load shedding scheme is
solution. Excellent surveys on SE algorithms can be
to clarify the load priority. The load shedding is
found in [20]-[22]. Two types of data are required for
performed according to the load priority in the network.
SE; the network data and measurement data. A real-time
The loads are classified into 3 categories; vital, semi-
central control system can be used to improve the
vital and non-vital. The non-vital load will be the first
security and reliability of electrical power system [23]. A
priority to be shed, followed by the semi-vital and lastly
SE algorithm based on forward-backward propagation
the vital load. Fig. 1 illustrates the overall concept of
with higher R/X ratio of lines has been presented in [24]-
load shedding scheme for an islanded distribution
[25]. A branch estimation based on SE method, suitable
network connected with Mini Hydro power plants.
for real-time monitoring of distribution network is
The scheme consists of three main modules; (a)
presented in [26].
Frequency Calculator Module (FCM), (b) Load
This paper proposes a new conceptual strategy of a
Shedding Controller Module (LSCM) and (c)
load shedding scheme which will provide a solution for
Distribution State Estimation Module (DSEM).

Copyright © 2012 Praise Worthy Prize S.r.l. - All rights reserved International Review of Electrical Engineering, Vol. 7, N. 2

4156
M. Karimi, H. Mohamad, H. Mokhlis, A. H. A. Bakar

II.1. Frequency Calculator Module - H is the generator inertia constant in seconds


- fc is the frequency, Hertz
The FCM will continuously calculate the frequency of
- fn is the rated value of frequency, Hertz
the distribution network. It monitors the voltage of the
- N is the number of generators
network then, calculates the system frequency based on
- P is the imbalance power, per-unit.
the zero crossing technique.
In (1), the magnitude of ROCOF (dfc/dt) is utilized to
estimate the power imbalance. If ROCOF is less than
zero and the system frequency fall less than 49.5 Hz then
the decision is made to shed some of the loads. In this
case, the LSCM will estimate the amount of load needed
to be shed by using the swing equation. However, the
magnitude of ROCOF is valid immediately after the
occurrence of the disturbance due to the dynamic
response of the control elements such as turbine,
governor, load and generator. Consequently, the
unknown value of P is estimated by solving (1).

II.3. Distribution State Estimation Module


A typical algorithm for SE uses the WLS algorithm
that minimizes the sum of the squared weighted errors
between the estimated and actual measurements. This
Fig. 1. Concept of proposed load shedding scheme method is popular among commercial state estimators. In
this method, weights are selected as proportional to the
During system disturbances, the generators are accuracy of the measurements.
disturbed by inter generator oscillations and their Hence, measurement with high accuracy will has high
deceleration or acceleration rates are not the same. weight.
Therefore, for the power imbalance calculation, the In a power system including distribution and
frequency of the Center of Inertia (COI) is considered transmission system, the global measurement vector is
[27]-[30]. This frequency is then compared to the indicated by Z. For an N-bus power system with m
frequency protection setting of each generator. If the measurements, assume r is an error vector with standard
frequency lies outside this range, both generators will be Gaussian that has a zero mean and covariance . Let i be
tripped off by an under or over frequency relay, which in the index of the measurements.
practice is available to protect the generator. The system The measurement equation is formulated in (2):
frequency which is captured by the FCM will be
transmitted to the LSCM. Zi hi x ri , i 1, 2,...,m (2)

where:
II.2. Load Shedding Controller Module
- Zi is the vector of measurements
In the LSCM, the amount of loads that are needed to - X is the state vector
be shed is determined and calculated. A certain delay - hi(x) is the measurement matrix of the nonlinear
time equal to 100ms which comprises communication, function
calculation and circuit breaker opening time is being - ri is the measurement errors vector.
considered in this module. The LSCM will have to Then, the measurement residual vector can be defined
decide the power imbalanced value based on the and formulated in (3) as follow:
ROCOF. This strategy is to address the changes of
frequency due to sudden increment of load in an islanded ri Zi hi x , i 1, 2,...,m (3)
system. In this strategy, the amount of load to be shed
depends on the disturbance magnitude. It is estimated By applying the WLS method, it will minimize the
based on the amount of power imbalance following objective function as describe in (4):
frequency deviation in the system. The amount of power
imbalance is estimated by using the ith generators swing m 2
Zi hi x
equation which is expressed in (1): J x (4)
i 1 Ri
N
2 Hi df c
P i 1
(1) - Ri diagonal matrix of [1/ 12, 1/ 22, …, 1/ m2]
fn dt 2
- m is the covariance of the mth measurement error.
The best solution of the state vector X can be achieved
where: by the solution of the following equation. It is calculated

Copyright © 2012 Praise Worthy Prize S.r.l. - All rights reserved International Review of Electrical Engineering, Vol. 7, N. 2

4157
M. Karimi, H. Mohamad, H. Mokhlis, A. H. A. Bakar

to reflect the expected accuracy of the corresponding estimator cannot attain convergence. Therefore, pseudo
meter used: measurements are needed to assist convergence of the
state estimator for distribution network.
T 1
G x xk 1 H xk R Z h xk (5)
III. Validation of the Proposed Load
where: Shedding
- H(x) is the Jacobian matrix of the measurement
function The test system consists of 30 buses, 27 lumped loads
- h(x) which is mentioned in (2) with 2 mini hydro generators. The mini hydro generators
- G(x) is called the Gain matrix; it can be defined and rated at 2MVA with 2.5 s of constant inertia are operated
formulated in (6) as follow: at 3.3kV. Two parallel units of 2MVA generator
transformer were connected to the DGs to step up the
T 1
voltage level to 11kV. The transmission grid is
G x H xk R H xk (6) connected to the distribution network via steps down
transformers (132kV/11kV). As indicated in Fig. 2, a
By solving the (5) to minimize such errors and find an Normal off Point (NOP) for 11kV network is located at
optimal estimate, system state will be solved, iteratively. the intersection of two buses 21 and 22. Each load is
In this paper, WLS state estimation, as a mathematical connected with motorized switchgear that can be
analysis tools and an iterative solution, is presented to remotely controlled for load shedding purposes. Non-
filter out such errors and find an optimal estimate of Elastic Water Column without Surge Tank and PID
system states in distribution network. The measurement Controls including Pilot and Servo Dynamics model are
matrix can be of a variety of most commonly used used as a hydro turbine and governor model,
measurements in the practical system. The line power respectively. IEEE Alternator Supplied Rectifier
flows, bus power injections, bus voltage magnitudes and Excitation System is also chosen as an excitation model.
line current flows are common measurements in real The model parameters are shown in Table I, II and III
power system. The proposed DSEM is used the line respectively. The system state variable measurement (i.e.
power flows, bus power injections and bus voltage active power, reactive power and voltage) are monitored
magnitudes in order to construct the measurement by the DSEM. The system frequency is also calculated
matrix. Real and reactive power injection, Pi and Qi, by FCM to prepare the system information for LSCM.
equations at bus i can be expressed by below: The LSCM collect the data from FCM and DSEM to
determine or estimate the amount of power imbalance
m and accordance load need to be shed based on DSE
Pi Vi Gij cos ij Bij sin ij Vj (7) values.
j 1
TABLE I
HYDRAULIC TURBINE PARAMETERS
m
Parameter Value Parameter Value
Qi Vi Gij sin ij Bij cos ij Vj (8)
TW 1.2 Initial output power 0.7
j 1
fP 0.02 Initial operating head 1.0
D 0.5 Rated output power 1.0
where:
Gij is a line conductance from bus i to bus j in Siemens TABLE II
GOVERNOR PARAMETERS
(real part of admittance matrix),
Parameter Value Parameter Value
Bij is a line susceptance from bus i to bus j in Siemens KP 2.25 TC 0.2
(imaginary part of admittance matrix). KI 0.37 TD 0.2
Real and reactive power flow, Pij and Qij, equations KD 0.9 Max gate opening 0.16
from bus i to bus j can be expressed as follow: TA 0.05 Max gate closing 0.16
RP 0.04 Dead band value 0
Max gate position 1.0 Min gate position 0
Pij Vi 2 Gij Gi 0 ViV j Gij cos ij Bij sin ij (9)
TABLE III
EXCITATION PARAMETERS
2
Qij Vi Bij Bi 0 ViV j Gij sin ij Bij cos ij (10) Parameter Value Parameter Value
TC 0 KF 0.03
TB 0 TF 1
The proposed DSEM is based on voltage KA 400 TE 0.8
measurements. The power injection and power flow is TA 0.02 KE 1
computed by using (7), (8), (9) and (10) at each buses of VAMAX 14.5 KC 0.2
the distribution network. Finally, the calculated values VAMIN -14.5 KD 0.38
VRMAX 6.03 VRMIN -5.43
are used to construct the measurement matrix (hi) in SE(VE1) 0.1 SE(VE2) 0.03
order to solve (5). Since real-time information is very VE1 4.18 VE2 3.14
limited in a conventional distribution system, the state

Copyright © 2012 Praise Worthy Prize S.r.l. - All rights reserved International Review of Electrical Engineering, Vol. 7, N. 2

4158
M. Karimi, H. Mohamad, H. Mokhlis, A. H. A. Bakar

Fig. 2. Concept of proposed load shedding scheme for an islanded network

IV. Simulation Results versus system frequency is illustrated in Fig. 5. In


response to the event and to stabilize the islanded system,
In order to test the proposed scheme, an intentional the LSCM would immediately trip significant numbers
islanding is performed to the test system. In this case, the of load feeders. Optimum load shedding value for
distribution network is disconnected from grid to operate proposed method is presented in Table IV. The total
in an islanding mode. Two scenarios are considered, base loads shedding for both scenarios are observed.
and peak load. The total load demand for base and peak As shown in Fig. 3, system frequency for base and
load is 2.42MW and 3.16MW respectively. peak load drop to 48.156 Hz and 47.958 Hz,
Various events are simulated to justify the respectively; then slowly restores to its nominal value.
effectiveness of the proposed load shedding scheme. The
events such as trip the generator number 2 and sudden 50.5
connection of load are selected as the disturbance. These
events are applied in the test system at time t = 5 50

seconds. The scheme should be able to cope with the


different range of power imbalances between load and 49.5

generation following the events. Trip the generator


49
number 2 is considered in case I and the sudden
connection of load is simulated in case II.
48.5

IV.1. Case I: Trip of the Generator 2 48


Base Load
Peak Load
In this case, loss of the generator number 2 is 47.5
0 5 10 15 20 25 30 35 40 45
simulated. Frequency responses for base and peak load Time (s)

scenarios are shown in Fig. 3. Since the loads in the


islanded system are supplied with two small hydro DGs, Fig. 3. Frequency response of the network for case I
loss of one DG will give a great impact to the island. As
a result of losing half of the island generation (1.58MW TABLE IV
AMOUNT OF LOAD SHEDDING BY LSCM IN CASE I
in peak load case), the system frequency has dropped,
Load Case Power Imbalance (MW) Load Shed (MW)
tremendously. Fig. 4 presents the active power generated Base Load 1.21 1.009
for base and peak load cases. Aberration of the df/dt Peak Load 1.58 1.468

Copyright © 2012 Praise Worthy Prize S.r.l. - All rights reserved International Review of Electrical Engineering, Vol. 7, N. 2

4159
M. Karimi, H. Mohamad, H. Mokhlis, A. H. A. Bakar

TABLE V
AMOUNT OF LOAD SHEDDING FOR BASE LOAD IN CASE II
Load Case Power Imbalance (MW) Load Shed (MW)
Base Load 0.30 0.227
Base Load 0.45 0.290

TABLE VI
AMOUNT OF LOAD SHEDDING FOR PEAK LOAD IN CASE II
Load Case Power Imbalance (MW) Load Shed (MW)
Peak Load 0.30 0.113
Peak Load 0.45 0.284

Fig. 4. Active power of the DGs for case I

2
Peak Load
1 Base Load

-1

-2

-3

-4

-5

-6
47.5 48 48.5 49 49.5 50 50.5 Fig. 6. Frequency response of the overload for case II
Frequency (Hz)

0.4
Fig. 5. df/dt versus frequency response in case I 0.45MW Overload
0.2 0.30MW Overload

0
IV.2. Case II: Sudden Connection of a Load
-0.2

In this case, the sudden connection of load in the -0.4


islanded system for base and peak load is simulated. To -0.6
create the overload disturbances, various loads are
-0.8
connected to the bus number 12 at simulation time, t=5s.
These rated values are 0.30MW and 0.45MW. System -1

frequency responses for base load demand are illustrated -1.2


in Fig. 6. Following 0.3MW and 0.45MW overload -1.4
49.2 49.4 49.6 49.8 50
disturbances the frequency is dropped to 49.327 Hz and Frequency (Hz)
49.092 Hz, respectively. The LSCM is compute the
amount of load need to be shed based on estimated value Fig. 7. Frequency response versus df/dt in case I
of AUFLS. These values are presented in Table V. The
50.4
total powers of load shedding for both scenarios are 0.45MW Overload
0.30MW Overload
observed in this table. The difference value is supplied 50.2
by spinning reserve of the generators and other
50
frequency controller devices. Fig. 7 is demonstrated the
frequency response versus the df/dt of the network. It is 49.8
observed that the system frequency could be converged
and restored back to the normal value after applying the 49.6

load shedding.
49.4
For peak load case, the LSCM is also compute the
amount of load need to be shed based on AUFLS and 49.2
DSE. Fig. 8 shows the frequency response of the system
49
in this case. The amount values of load shedding are 0 5 10 15 20 25 30 35 40 45
Time (s)
presented in Table VI. Fig. 9 is illustrated the df/dt
versus the frequency response of the network. It is Fig. 8. Frequency response of peak load for case II
observed that the system frequency could be converged
and restored back to the normal value after applying the
load shedding.

Copyright © 2012 Praise Worthy Prize S.r.l. - All rights reserved International Review of Electrical Engineering, Vol. 7, N. 2

4160
M. Karimi, H. Mohamad, H. Mokhlis, A. H. A. Bakar

0.4 [4] "IEEE Recommended Practice for Utility Interface of


0.45MW Overload
0.2 0.30MW Overload Photovoltaic (PV) Systems," IEEE Std 929-2000, p. i, 2000.
[5] "IEEE Standard for Interconnecting Distributed Resources With
0 Electric Power Systems," IEEE Std 1547-2003, pp. 1-16, 2003.
-0.2 [6] V. V. Terzija and H. J. Koglin, "Adaptive underfrequency load
shedding integrated with a frequency estimation numerical
-0.4 algorithm," Generation, Transmission and Distribution, IEE
-0.6 Proceedings, vol. 149, pp. 713-718, 2002.
[7] X. Ding and A. A. Girgis, "Optimal load shedding strategy in
-0.8 power systems with distributed generation," in Power
-1 Engineering Society Winter Meeting, IEEE, pp. 788-793 vol.2,
2001.
-1.2 [8] V. Terzija, "Adaptive underfrequency load shedding based on the
-1.4 magnitude of the disturbance estimation," IEEE Transactions on
49 49.2 49.4 49.6 49.8 50
Frequency (Hz) Power Systems, vol. 21, pp. 1260-1266, 2006.
[9] Rasha M. EL Azab, E. H. Shehab Eldin, P. Lataire, M. M.
Sallam, "Power Measurement for the AUFL," International
Fig. 9. df/dt versus frequency response of peak load in case II Review on Modelling and Simulations (IREMOS), Vol. 4. N. 5,
pp. 2285-2290, 2011.
[10] S. Ramesh, A. Krishnan, "Fuzzy Logic Based Frequency
V. Conclusion Stabilization in a Parallel AC-DC Multi Area Non Reheat
Thermal Power Systems," International Review on Modelling
This research developed a new load shedding scheme and Simulations (IREMOS), Vol. 3. N. 4, pp. 590-597, 2010.
based on frequency and rate of change of frequency in [11] F. Shokooh, et al., "Intelligent Load Shedding," Industry
the system with coordination of the state estimation Applications Magazine, IEEE, vol. 17, pp. 44-53, 2011.
[12] J. Jung, et al., "Adaptation in load shedding under vulnerable
technique. It used an adaptive under frequency load operating conditions," IEEE Transactions on Power Systems,
shedding method to improve the estimation of vol. 17, pp. 1199-1205, 2002.
disturbance magnitude in the system. According to the [13] F. Shokooh, et al., "An intelligent load shedding (ILS) system
conventional distribution network with very few application in a large industrial facility," Industry Applications
Conference, Fourtieth IAS Annual Meeting. Conference Record
numbers of measurements, system state variable is of the 2005, pp. 417-425 Vol. 1, 2005.
obtained by incorporating State Estimation. The [14] D. Andersson, et al., "Intelligent load shedding to counteract
possibility of an intelligent load shedding technique is power system instability," Transmission and Distribution
achieved by combination of an Adaptive Under- Conference and Exposition: Latin America, 2004 IEEE/PES, pp.
570-574, 2004.
Frequency Load Shedding and Distribution State [15] D. Hazarika and A. K. Sinha, "Method for optimal load shedding
Estimation. in case of generation deficiency in a power system,"
It is observed that the proposed scheme manages to International Journal of Electrical Power & Energy Systems,
immediately perform the load shedding in distribution vol. 20, pp. 411-420, 1998.
[16] P. Wang and R. Billinton, "Optimum load-shedding technique to
network. Simulation results show that optimal amounts reduce the total customer interruption cost in a distribution
of load can be shed according to the well-estimation of system," Generation, Transmission and Distribution, IEE
the system state. Of significance is that the scheme has Proceedings, vol. 147, pp. 51-56, 2000.
proved to be an essential tool for a successful islanding [17] W. P. Luan, et al., "Genetic algorithm for supply restoration and
optimal load shedding in power system distribution networks,"
operation. The power quality of the island can be Generation, Transmission and Distribution, IEE Proceedings,
sustained thus allowing the island to persist. vol. 149, pp. 145-151, 2002.
[18] Aliakbar Mohammadi, "A Novel Approach to Power System
Controller Design," International Review on Modelling and
Acknowledgements Simulations (IREMOS), Vol. 4. N. 5, pp. 2348-2354, 2011.
[19] C. Lu, et al., "Distribution system state estimation," IEEE
This work was supported by Malaysian Government Transactions on Power Systems, vol. 10, pp. 229-240, 1995.
and University of Malaya, Kuala Lumpur under [20] F. F. Wu, "Power system state estimation: a survey,"
International Journal of Electrical Power & Energy Systems,
HIR/MOHE research Grant (Grant code: D000004- vol. 12, pp. 80-87, 1990.
16001). [21] A. da Silva and D. Falcao, "Bibliography on power system state
estimation (1968-1989)," IEEE Transactions on Power Systems,
vol. 5, pp. 950-961, 1990.
References [22] A. Bose and K. A. Clements, "Real-time modeling of power
networks," Proceedings of the IEEE, vol. 75, pp. 1607-1622,
[1] M. R. Aghamohammadi and A. Shahmohammadi, "Intentional 1987.
islanding using a new algorithm based on ant search [23] F. C. Schweppe, "Power system static-state estimation, Part III:
mechanism," International Journal of Electrical Power & Implementation," IEEE Transactions on Power Apparatus and
Energy Systems, 2011. Systems, pp. 130-135, 1970.
[2] Hasmaini Mohamad, Hazlie Mokhlis, Ab Halim Abu Bakar, Hew [24] D. Thukaram, et al., "A robust three-phase state estimation
Wooi Ping, " A review on islanding operation and control for algorithm for distribution networks," Electric Power Systems
distribution network connected with small hydro power plant," Research, vol. 55, pp. 191-200, 2000.
Renewable and Sustainable Energy Reviews, Vol. 15, pp. 3952- [25] A. Shahriari, H. Mokhlis, A. H. A. Bakar, H. A. Illias, "Proposed
3962, 2011. Optimal Multiplier Load Flow Method for the Maximum
[3] D. G. Photovoltaics and E. Storage, "IEEE Guide for Design, Loading Point Search in Ill Conditioned System," International
Operation, and Integration of Distributed Resource Island Review on Modelling and Simulations (IREMOS), Vol. 4. N. 6,
Systems with Electric Power Systems," 2011. pp. 3155-3162, 2011.

Copyright © 2012 Praise Worthy Prize S.r.l. - All rights reserved International Review of Electrical Engineering, Vol. 7, N. 2

4161
M. Karimi, H. Mohamad, H. Mokhlis, A. H. A. Bakar

[26] Y. Deng, et al., "A branch-estimation-based state estimation H. Mokhlis received his B. Eng in Electrical
method for radial distribution systems," IEEE Transactions on Engineering in 1999 and M. Eng. Sc in 2002
Power Delivery, vol. 17, pp. 1057-1062, 2002. from University of Malaya, Malaysia. His
[27] J. J. Ford, et al., "Adaptive load shedding and regional obtained PhD degree from the University of
protection," International Journal of Electrical Power & Energy Manchester, UK in 2009. Currently he is a
Systems, vol. 31, pp. 611-618, 2009. Senior Lecturer in the Department of Electrical
[28] M. Karimi, H. Mohamad, H Mokhlis, A. H. A. Bakar, " Under- Engineering, University of Malaya. His main
Frequency Load Shedding Scheme for Islanded Distribution research interest is in distribution automation
Network Connected with Mini Hydro," International Journal of area and power system protection.
Electrical Power & Energy Systems, vol. 42, pp. 127-138, 2012.
[29] U. Rudez and R. Mihalic, "Monitoring the First Frequency A. H. A. Bakar received his B.Sc. in Electrical
Derivative to Improve Adaptive Underfrequency Load-Shedding Engineering in 1976 from Southampton
Schemes," IEEE Transactions on Power Systems, pp. 1-1, 2011. University UK and M.Eng. and PhD from
[30] M. Giroletti, et al., "A hybrid frequency/power based method for University Technology Malaysia in 1996 and
industrial load shedding," International Journal of Electrical 2003. He has 30 years of utility experience in
Power & Energy Systems, 2011. Malaysia before joining academia. Currently he
is Consultant in the Department of Electrical
Engineering, University of Malaya, Malaysia.
Authors’ information
1
Departement of Electrical Engineering, Faculty of Engineering,
University of Malaya, 50603 Kuala Lumpur, Malaysia
2
University of Malaya Power Energy Dedicated Advanced Centre
(UMPEDAC), Level 4, Wisma R&D UM, University of Malaya, 59990
Kuala Lumpur, Malaysia.
3
Faculty of Electrical Engineering, University of Technology MARA,
Malaysia.

M. Karimi received his B. Eng from Islamic


Azad University, Iran and M. Eng. from
University of Malaya, Malaysia in Electrical
Engineering field in 2002 and 2011,
respectively. He is currently PhD Student in
University of Malaya, Malaysia. His main
research interest is in Distributed Generation and
Electric Power System Stability.

H. Mohamad was born in Kota Bharu,Kelantan,


Malaysia in 1976. In 1999 and 2004, she
received the Bsc and MsEng degrees
respectively from the University of Malaya,
Malaysia where she is currently pursuing her
PhD degree. Her major research interests include
Islanding Operation of Distributed Generation
and Synchronous Generator Control.

Copyright © 2012 Praise Worthy Prize S.r.l. - All rights reserved International Review of Electrical Engineering, Vol. 7, N. 2

4162

You might also like