You are on page 1of 7

technical issues

Martin Achmus
Ahmed Rouili

Study on Erddruckbeanspruchung of angular


retaining walls

The design of the vertical leg of angle support walls according to current standards for German elevated and after the currently discussed redesign of the
soil pressure, that is the average of the active earth pressure and earth pressure at rest make. This DIN 4085 the mean value of active earth pressure
approach is, as overall in this paper shows is, in many cases significantly on the safe side. By means of a and earth pressure at rest (hereinafter referred to
numerical parameter study are shown the important influence factors. Based on the results, a method is as elevated soil pressure) to be recognized in
proposed that the compressive load, the more accurate determination of the earth allows taking into classical distribution. Here, the angle of wall friction δ
account the substantially influencing variables in a simple manner. equal to the angle of repose β to be set. For the
common case β = 0, ie horizontal terrain, thus
following earth pressure coefficients apply:

Investigation on the earth pressure loading of L-shaped retaining walls. Due to current German regulations the
structural design of the vertical wall stem of L-shaped retaining walls is based on the assumption of Increased
earth pressure loading, ie the average of active earth pressure and earth pressure at rest. In the presented paper
it is shown did with this approach the Resultant loading is in most cases overestimated. The influence of the
Active earth:
most important parameters is Investigated by a numerical model. Based on the results, a simple method for a
more accurate estimation of the Resultant loading is Proposed. • φ •
k Ah = k a = tan 2 45
• °-' • (1)
• 2 •

1 Introduction made out if the wall shifts in use are not sufficient rest earth pressure:

to reduce the load on the active earth, as these


Angular retaining walls are proven designs for the shifts would occur before reaching a breaking state k 0h = k 0 = 1 - sin φ ' (2)
support especially piled terrain jumps. However, in any case.
while the conventional system and loads for the Taking into account bottom dead weight load, and
detection of the external stability of an angular a surface of p, the wall bending moment M thus
support wall (sliding, allowable eccentricity, bearing results in a depth z below ground level as follows:
capacity, terrain fracture) to be reliable or accurate However, the actually acting in use earth
enough are composed, with respect to the pressure must be set for the design of the vertical
Erddruckansatzes for the design of the vertical wall wall spur. Because of the presence of the
122
leg need for clarification. horizontal spur is assumed that at least in the Mz() = γz kz Eg + pzkz Ep (3)
lower wall portion acts higher than the active earth
pressure. The "old" DIN 4085 (1987) was the With

indirect account by active earth pressure could be


1
set, but this spread to be trapezoidal with a twice k = ( kka + 0 ) (4)
2
For the detection of the external stability as large earth pressure on the base of the wall
usually a replacement heavyweight wall can be than was assumed at the wall head, resulting in an
1 1
considered, formed by the angular support wall over classical earth pressure increased rated z Eg = z. z Ep = z (5)
3 2
and superimposed on the horizontal spur backfill torque results for the reinforced concrete
soil. vertical rear wall "imaginary" is set as a load to cross-section. In compacted backfill would be to check whether a
the active earth pressure in the extension of the higher torque results in the recognition of a
spur end, said derWandreibungswinkel is to Verdichtungserddrucks instead of earth pressure
choose behind the wall equal to the angle of the due to surface load, which would then prevail, see
slope. The approach active earth pressure here is DIN 4085-100 (1996).
usually also warranted
In which size and distribution of the earth
pressure really works is not fully understood, see Goh proposed in [2] based on numerical
[1]. According to DIN 4085-100 (1996) investigations, the earth pressure from soil weight
to

942 © Ernst & Sohn · Publishers for Architecture and Technical Sciences GmbH & Co. KG, Berlin Structural Engineering 81 (2004), No. 12
M. Achmus / A. Rouili ​· investigation for Erddruckbeanspruchung of angular retaining walls

to be set as the active earth pressure to half the 2 structural behavior of an angular support wall to contact modeling is referenced here [4].
height of leg and in the lower half rising to earth 2.1 Reference System
pressure on raised for rough walls or on the full The Plaxis program also allows for gradually
rest earth pressure with smooth walls at the the system illustrated in Figure 1 is used as a increasing the vertical acceleration for simulating
Schenkelfuß. As compared with the approach in reference system for the study of the structural centrifuge experiments. The recalculation for the
accordance with DIN 4085-100 with increased behavior of an angular support wall with a wall trial of Djerbib et al. the next parameter of the
earth pressure over the entire wall height arise height of H = 9 m and a side length of B = 5.4 m is dense sand are summarized in Table 1 below. The
from naturally smaller wall bending moments. selected. This system was also Djerbib et al. [3] gravity and friction angles were as specified by Djerbib
studied in centrifuge experiments. The test results
are used zurVerifikation of the numerical model.
The angular support wall is first assumed to be
It is obvious that the displacements the wall approximately flexurally rigid.
and thus the actual size of the earth pressure on et al. selected in [3]. the bearing for medium-tight
the dimensions of the angular support wall (height and loose sand parameters used in the numerical
H, width B and ratio B / H) of the rigidity of the wall, calculations are also indicated. These were
the stiffness of the backfill material and especially selected in the range of ordinary skill values ​for
of the subsurface depends. In this article, the Feinbis medium sand (see. Eg. B. EAU 1996 [5]).
effects of these parameters are quantified by 2.2 Numerical model For better comparison of the results of the specific
numerical investigations, the considerations are gravity was set the same for all storage densities.
limited to non-cohesive backfill material with a In order to simulate the structural behavior of an
horizontal ground surface. On this basis, angular support wall realistically, both the shear
recommendations are made to approach the strength and the stiffness of the soil must be
pressure acting on the vertical wall leg earth detected realistic. To use the program system
pressure from bottom dead weight and load Plaxis comes here with the implemented therein
surface. "Hardening Soil" -Stoffgesetz. This material law 2.3 Verification of the numerical model
allows, inter alia, considering the voltage
dependence of the stiffness of the bottom module
E S according to the following equation: In the centrifuge experiments of
Djerbib et al. was a reduced scale factor to the wall
60 model (H = 15 cm, B = 9 cm) was prepared,
and the wall shifts and the earth pressures were
measured under the effect of an acceleration of 60
m times the acceleration of gravity. For the wall, a
• σ •
EES = oed ref
. • • (6) steel profile is used, which is to be considered
• p ref •
under the experimental conditions as bending rigid.
It is e oed ref oedometrische the stiffness of the soil As substrate and backfill material, a dry fine
at a reference voltage of the p ref ( here 100 kN / m 2) enggestufter was incorporated in a sealed storage
to medium sand ( "Leighton Buzzard" sand). The
corresponding ground voltage σ. parameters of this sand are of Djerbib et al.
The shear strength of the soil is determined specified as follows: gravity γ = 17 kN / m 3,
by the parameters φ '( internal angle of friction), ψ ( Dilatancy)
and c '( Cohesion) described. The contact behavior
between the reinforced concrete wall and the floor
is taken into account via interface elements. The
maximum shear stress is mobilizable by a
parameter R inter Installation void ratio e = 0.56, related storage
density I D = 0.77, effective angle of internal friction φ

Figure 1. angular retaining wall reference system '= 46.5 °. The numerical simulation was carried
specified, the tan the ratio for non-cohesive soil δ / tan out by recognizing the parameters specified in
Fig. 1. L-shaped retaining wall, reference φ ' indicates. For details on the material law and Table 1 for dense
system

1. Parameters used table for sand, constitutive law "Hardening Soil" Table 1. Parameters used
for the sand soil, material law "Hardening Soil"

storage density γ φ' ψ e oed ref m e 50 e ur R inter


in kN / m 3 in in in MN / m 2 in one in MN / m 2 in MN / m 2 in one

close 17 46.5 10 30 0.6 30 120 0.8

medium density 17 35 2.5 25 0.65 25 100 0.8

relaxed 17 32 0 20 0.7 20 100 0.8

Building Technology 81 (2004), Heft 12 943


M. Achmus / A. Rouili ​· investigation for Erddruckbeanspruchung of angular retaining walls

Sand. The model dimensions were similar to those


of the centrifuge test. In the first calculation steps,
the production of the model system was simulated
by progressively installing individual layers of the
soil and the wall. After that, the vertical
acceleration was increased to 60 times the
acceleration of gravity.

The earth pressures experimentally


determined and wall shifts for an unsupported wall
under the action of ground weight and also the
earth pressures under zusätzlicherWirkung a
Obeflächenlast of 50 kN / m 2 are shown in Figure 2
and compared with the results of numerical
calculations.

The comparison of the earth pressures


shows a fairly good agreement between
experiment and calculation, especially for the
interest here earth pressure due to soil weight.
Both of measurement and calculation is made in
the upper wall region an approximately
corresponding to the active earth pressure load,
while in the lower half of the wall is an increase in
resting pressure on the theoretical or even higher
determine addition. Similar results were also Goh [ get
2].

derWandverschiebungen regarding
compliance is sufficient to note the order of the wall
chief position. In this regard, however, to be noted Image 2 centrifuge test: Comparison of the measurement results of Djerbib et al. [3] with the results of
that the measured values ​of the centrifuge test numerical calculation
result in a movement of the wall towards the foot of Fig. 2. Centrifuge test: comparison of the results from Djerbib et al. [3] with results of the numerical
the backfill, which is not very plausible. calculations

The overall conclusion is that the numerical


model, both qualitatively and quantitatively
reproduces the earth pressure from soil own
weight on the vertical wall leg very well and thus is
suitable for parametric studies.

2.4 structural behavior of the reference system

With the verified numerical model the structural


behavior of the reference system shown in Figure
1 was calculated. Backfill and substrate were each
uniformly once as a dense, medium dense and
accepted once as once stored as a favorite. The
finite element mesh used is wiedergege- in Figure Figure 3. Reference system: finite element mesh and Hauptdehnungsinkremente for medium density
3
Figure 3. Reference system: finite element mesh and principal strain increments for medium dense sand.

944 Building Technology 81 (2004), Heft 12


M. Achmus / A. Rouili ​· investigation for Erddruckbeanspruchung of angular retaining walls

ben. It was chosen a very fine discretization to loose bedding he falls below it. greater than the average full Auflastspannung γ H
obtain an accurate resolution of the wall voltage is.
curve. example in the case of medium density of The horizontal wall spur from above directly Under the wall Sporn a higher soil pressure
the soil material - - yield the greatest strain only by approx. 90% of (above pending on the air-side end occurs in accordance with the
increments, the areas in which are marked in Bodenauflast γ HB) loaded. Significantly reduced tilting stress the angle support wall. For the case of
Figure 3. Can be clearly seen here, the expected the Auflastspannung is in the area immediately densely packed sand results in approximately a
formation of two, from the end of the wall spur behind the vertical wall, while at the femoral end to trapezoidal voltage distribution,
outgoing and upwardly extending slip planes. In something
calculating a deformation-free initial stress state
was first generated for the underground. Then the
wall construction and backfill were simulated. For
the latter case, the application in the individual
layers of 1 m thickness was simulated.

Figure 4 shows the forces acting on the


vertical wall leg Erddruckspannungen horizontal
and acting on the horizontal wall spur from above
and below respectively loads for dense, medium
dense and loose storage of the substrate and the
backfill material are shown. Also indicated are the
wall shifts determined.

The Erddruckverteilungen are similar to the


distribution obtained for the centrifuge test in all
three cases, ie in the upper wall portion
approximately active earth pressure in the lower
region is increasingly in the direction of the notional
rest earth pressure. The point of application of the
resulting Erddruckbeanspruchung in all cases at z e
= approx. 0.30 H above the base of the wall, ie
slightly below the third point derWandhöhe.

The size of the earth pressure can be


described dimensionless over the middle earth
pressure coefficient k:

EHH
k =05 (7)
2
. γ

The following k-values ​are obtained from the


calculated Erddruckverteilungen:
- dense sand: k = 0.227 corresponds to 0.59 k 0 + 0.41
ka
- medium density Sand: k = 0.308 corresponds to
0.24 k 0 + 0.76 k a
- loose sand: k = 0.335 corresponds to 0.17 k 0 + 0.83
ka
In the case of the dense substrate and
backfill material, the value is thus exceeded in
accordance with DIN 4085-100, at medium and Figure 4. Reference system: results of the numerical calculations Figure 4. Reference
denser system:. Results of numerical calculations

Building Technology 81 (2004), Heft 12 945


M. Achmus / A. Rouili ​· investigation for Erddruckbeanspruchung of angular retaining walls

Table 2. Comparison of the calculated, the Wandfußmoment parameters determining the values ​according to DIN 4085-100 Table 2. Comparison of
Calculated wall stem bending moments with values ​gemäß to DIN 4085-100

numerical calculation Approach to DIN 4085-100


-
k ze/ H M Foot/( 0.5 γ H 3) k=k ze/ H M Foot/( 0.5 γ H 3)

relaxed 0.335 0,302 .1012 0.389 0.333 .1295

medium density 0.308 0.304 0.0936 0.349 0.333 .1162

close 0.227 0.296 0.0672 0.217 0.333 .0723

as it is also commonly recognized in the Backfill material assumed. the wall height H and as the ratio of the horizontal side length to the wall
assessment. Considering that a support wall the length of the horizontal leg wall B and the ratio height of between about 0.5 and 0.8.
usually integrates in practice in the building - which B / H for an approximately rigid wall and also Corresponding side lengths B were included in the
is not included in the numerical model - and thus medium-dense sand ground are initially varied. calculations.
may occur on the air-side end to the case of loose Then, the influence of the wall thickness or
and medium density larger soil pressures, as also stiffness of the wall and, finally, the influence of the
appears in these cases the approach of a base rigidity can be investigated. In Figure 5 the respectively determined for a
trapezoidal voltage distribution justified. rigid wall k-values ​are compared with the
Erddruckgrenzwerten according to DIN 4085-100.
For all considered wall heights to a unified picture
emerges. For small segment lengths, the k value is
The considerations are limited to the only slightly above the active earth pressure
following Eq. (7) defined k value, which determines coefficient (mind determined δ = 0), with large side
Main target of the considerations in this the absolute magnitude of the horizontal earth lengths it is still below the DIN 4085-100 to be
paper is the size of the earth pressure distribution pressure. The lever arm with respect to the wall toe applied in average from Ruhedruck- and active
of the vertical wall leg and in particular the z e varies only relatively slightly, ie the qualitative earth pressure. It must also be borne in mind that
resultant nominal torque M foot at the base of the distribution of Erddruckspannungen is similar in all the calculation values ​representing the wall upper
wall. This can be as a product of the resulting limits because of the assumed rigidity.
cases. For the medium-density surface were all z E- Values
horizontal earth pressure e H with the lever arm with ​between 0.28 H and 0.31 H, that is slightly below
respect to the foot wall z e to calculate. the third point of the wall height, the values ​at high
wall height slightly greater than with a low wall
height. Only with very rigid background values
​were up to z e = 0.325 H determined.

e 1 3
M foot = concentrationγ camp (8th)
HH 2
3.3 Influence of wall stiffness
The determined for the three tested storage
densities at the reference system values ​for the To study the influence of the wall stiffness different
rated torque or the determining parameters k and z e wall thicknesses were considered, the thicknesses
/ H are summarized in Table 2 below. Also given 3.2 Influence of the wall height and of the vertical and horizontal leg were respectively
the values ​according to the approach with length of the legs the same size and constant applied. The
increased earth pressure to DIN 4085-100 are. calculation results are in
Were examined wall heights H of 2 m, 5 m and 9
m. customarily

It is apparent that the latter approach is on


the safe side, and provides for the loosely
deposited soil around 28% and for the mid-tight
bottom by 24% higher design moments. For the
dense soil the difference still amounts to approx.
8th %.

3 parametric study on the influence of the


geometry and stiffness of the
underground
3.1 General Figure 5. earth pressure depending on wall height and leg length for rigid angle retaining walls

For the parametric study uniform medium density Figure 5. Earth pressure Coefficients for rigid L-shaped walls dependent on wall height and base
storage of will width.

946 Building Technology 81 (2004), Heft 12


M. Achmus / A. Rouili ​· investigation for Erddruckbeanspruchung of angular retaining walls

Figure 6 reproduced. The flexural stiffness was mixed-grained soil and thus one may still 4 Conclusions and Recommendations
under each approach of the uncracked state of sufficiently strong, but quite compressible surface.
reinforced concrete with a modulus of elasticity E B The voltage-independent set-stiffness modulus for The results of the numerical study show that the
= 3 x 10 4 MN / m 2 determined. the latter substrate represents an extremely rigid approach of DIN 4085-100 is used to determine
non-cohesive soil such. B. dense gravel. the earth pressure on the vertical leg of an angular
A reduced wall thickness leads as expected retaining wall as a rule clearly on the safe side.
according to the additional displacement of the wall Only at extremely rigid base and walls of relatively
by bending and hence of the larger ground shifts to low height values ​can occur in the size of the DIN
a reduction of the horizontal earth pressure, approach. The approach is thus so far confirmed
respectively, the k-value. The greatest effect is Figure 7 shows the results for the three are not detected as parameters such as geometry
obtained here at the very high wall with H = 9 m, considered wall heights are shown, for reasons of and wall and ground stiffness herein and that
while in the wall of small height of H = 2 m only clarity, only the values ​for each have a wall therefore must lead in all cases to lie on the safe
gives a small reduction. thickness are shown. side results. However, it is advisable to use the
existing in "normal" conditions profitability reserves.

While only an insignificant additional


decrease of the k value with respect to the value
for medium density building occurs in a soft
3.4 Influence of the substrate stiffness ground, the very stiff ground leads, in particular at
low wall height to a significant increase of the k
In the parametric study was once a relatively soft value and thus the horizontal earth pressure. H = 2
ground (E oed ref = 10 MN / m 2, m = 0.5) and once a m even higher values ​than for the approach of the
very rigid base (E S = 200 MN / m 2) accepted. The DIN give 4085- The size of the to be applied
former represents about a rigid to semi-solid or a Erddruckbeiwertes is essentially determined by the
Silt surface rigidity because of this, the settlement and
thus the size of a possible rigid body rotation the
100th wall depend. In addition, the displacement of the
vertical wall of the leg due to bending stress affects
the magnitude of the earth pressure. Both effects
(rigid body rotation and bending deformation) effect
on the resulting misalignment of the vertical wall
limb, which can thus be used as an integral,
substantially influences the sensing evaluation
size. This resulting average misalignment is
defined herein with the difference of the horizontal
displacements of the head wall and base of the
wall and with derWandhöhe as follows:

Figure 6. earth pressure coefficients for different wall thicknesses d Fig. 6. Earth
pressure Coefficients for different wall thicknesses d
δ h .head - δ h .walk
tan θ v
= (9)
H

In Figure 8, the determined parameters in the


study earth pressure k depending on the inclination
are tan θ v shown. Not reproduced calculated for the
only theoretical limit of a rigid wall values ​are here
only. It is clear that the k value can be determined
in good approximation according to the defined
inclination. tan for misalignment θ v> 0.01 k may be
equal to the active earth pressure coefficient for δ
= be 0. For small misalignment can between this
value and the increased ground

Figure 7. earth pressure depending on the stiffness of the floor Fig. 7. Earth pressure Coefficient
dependent on the underground stiffness

Building Technology 81 (2004), Heft 12 947


M. Achmus / A. Rouili ​· investigation for Erddruckbeanspruchung of angular retaining walls

pressure coefficient according to DIN 4085-100, Wall leg due to bending deformation by earth Author but pointed to the approach presented here,
the tan θ v = 0, are linearly interpolated. A possible pressure. Simplifies active earth pressure can a convenient and praktikablerWeg for the future
slight underestimation of the k value would be likewise be applied. desirable accurate determination of the earth
about the approach of a classical earth pressure pressure on the vertical wall leg.
distribution and thus the consistent approach of - Selecting a Erddruckbeiwertes, depending on
e.g. e = the determined resultant misalignment. With this
coefficient of the vertical leg may then be
H / 3 for the determination of the rated torque to calculated by recognizing the classical earth literature

compensate. pressure.
An expedient for practical design approach [1] Arnold, M .: Model tests for earthworks
pressure on angular retaining walls. In: Communications of
results from the fact as follows: Finally, please note that the results
the Institute of Geotechnical Engineering at the University
presented here and recommendations initially
of Dresden, No. 9 (2001)
- Determining the ratios and thus the "rigid body" apply only to medium-dense Hinterfüllboden and
S. 23-34.
-Schiefstellung derWinkelstützwand by horizontal ground surface. Also requires the tan
[2] Goh, TC: Behavior of cantilever
conventional calculation of an active earth here with about θ v = 0.01 limit of the inclination for retaining walls. Journal of Geotechnical Engineering,
pressure polluted by replacement heavyweight the active earth pressure approach, of course, Vol. 119 (1993), No. 11, pp. 1751-1770. [3] Djerbib, Y.,
wall. determined nor the verification. According to the Hird, CC, Touahmia, M .:

- Calculating said additional middle inclination of Centrifugal model tests of uniform surcharge loading

the vertical on L-shaped retaining walls. 15 th Int. Conf. on Soil


Mechanics and Foundation Engineering, Istanbul
(2001), Vol. 2, pp. 1137-1140. [4] Brinkgreve, RBJ,
Vermeer, PA:

Plaxis Version 8 (Handbook). AA Balkema, Rotterdam


/ Brookfield 2002. [5] EAU recommendations of lost
working
Committee waterfront structures, ports and
waterways. 9th edition, Berlin: Ernst & Sohn 1996th

Authors of this article:


Univ. Dr.-Ing. Martin Achmus, Institute of Foundation
Engineering, Soil Mechanics and Energy Engineering,
University of Hannover, Appelstraße 9A, 30167 Hannover,
achmus@igbe.uni-hannover.de Ahmed Rouili, M. Phil., Ing.,
Institut de Genie Civil, Universite de Tebessa Algerie, route de
Figure 8. earth pressure coefficients k tan depending on the average inclination θ v Constantine, 12002 Tebessa, Algeria, arouili@hotmail.com
the vertical wall leg
Figure 8. Earth pressure Coefficient k dependent on the average tilt tan. θ v of the wall stem

948 Building Technology 81 (2004), Heft 12

You might also like