Chapter 9
NATIONAL PLUMBING CODE OF THE
PHILIPPINES
1999
Sections 902 & 908: Vents Not 902.2 & 908.2 Traps serving sinks
Required which are part of the
902.1 & 908.1 Where permitted equipment of bars, soda
by the Administrative fountains and counters need
Authority, vent piping may be not be vented when the
omitted on an interceptor location and construction of
when such interceptor acts as such bars, soda fountains and
a primary settling tank and counters is to make it
discharges through a impossible to do so. When
horizontal indirect waste pipe such conditions exist, said sink
into a secondary interceptor. shall discharge by means of
The second interceptor shall
be properly tapped and approved indirect waste pipe
vented. into a floor sink or other
approved type receptor.
903.1 VENT PIPES 903.1.2 HORIZONTAL & VERTICAL 903.2 VENT FITTINGS
VENT LINES & VENT PIPES
CAST IRON, DUCTILE CAST IRON, COPPER CAST IRON
GALVANIZED WROUGHT IRON
GALVANIZED STEEL CAST IRON GALVANIZED MALLEABLE IRON or
GALVANIZED STEEL
LEAD GALVANIZED WROUGHT IRON LEAD
BRASS BRASS
No galvanized malleable iron or galvanized steel pipes and fittings shall be buried
underground but shall be kept at least 152 mm above finish ground level.
152 mm
(minimum)
Vent Stack
Purpose:
to maintain atmospheric pressure throughout the length
of the soil and waste stacks, provide a convenient
connection point for individual, branch and stack vents.
Definition:
"Vent Stack means a vent pipe that is connected at its
upper end to a header or is terminated in an open air and
that is used to limit pressure differential in a soil or waste
stack."
Installation:
Vent Stack must be installed in conjunction with the soil or waste stack
•in any building of 2 or more storeys except residential ,
•in residential buildings of 4 storeys and more, where back vents, relief vents or
circuit vents (vent piping in general) are installed.
3000 mm
900 mm
300 mm
300 mm 150 mm
900 mm
150 mm
2100 mm
(minimum)
Every waste pipe shall be installed and back Back vent may be connected to the
vented at the same time. vertical leg of a water closet or other
S-trap fixture.
An individual vent as a vent installed to protect
one fixture trap.
back vent
continuous waste and vent
No restrictions
"the maximum length of a fixture outlet pipe of any fixture is 900 mm".
There is no minimum length requirements for a fixture outlet pipe. This means that
two different fixtures may be dual vented and connect at the same level with a
double Y and two 450 elbows.
Wet vent must be located within At least one of the wet venting fixtures must
1500 mm of the elbow serving a be drained through a continuous waste and
water closet or any floor vent
mounted siphonic fixture
If two wet
venting fixtures
connect to the wet
vent at the same
level, the wet
venting fixtures must
be dual vented.
DANILO V. RAVINA NAMPAP - CEBU
CHAPTER
Vents and Venting: WET VENT
Circuit Vent
Circuit vent means a vent pipe
that functions for two or more
traps connecting to a
horizontal branch where the
lowest end of the vent pipe
connects to the waste pipe on
the downstream side of the
highest fixture of the group
and the upper end connects to
branch vent, vent stack, stack
vent or extends to open air
independently and "circuit
vented" has a corresponding
meaning.
the circuit
the circuit
vented branch
vented branch
shall be relief
shall be relief
vented.
vented.
A relief vent required by Where circuit vented fixture traps are connected
sentence (2) may be a wet to 2 or more horizontal branches that connect to
vent if it is of 2" size and the same horizontal branch, the horizontal
greater and not more than branches may have a combined relief vent
one fixture having a
maximum of 1 1/2 fixture
units is drained into it
Where two water closets are installed, they must be connected at the same level to
the stack.
All other fixtures must be connected directly and independently to the stack above
the center line of water closets and the uppermost fixture must be connected to
the vertical portion of the stack.
Where there is only one water closet in a stack vented group, it may connect to the
vertical stack or horizontal continuation of the stack and remaining fixtures
upstream of the water closet must be connected directly and independently to the
stack and the uppermost fixture must be connected to the vertical portion of the
stack.
The total number of fixture units connected above the water closet is 8.
Maximum size of a fixture drain connected above the water closet is 2".
Additional Requirements The upper end of every soil or waste stack shall
The developed length of a terminate in a stack vent and the stack vent
fixture drain measured from shall terminate in open air outside the building
the trap weir to the stack is 2 or connect directly or through a header to
pipe diameters minimum or another stack vent, a vent stack that does
1500 mm maximum. terminate in open air outside the building.
Connection :
"Yoke vent shall be connected to the soil or waste stack by means of a drainage
fitting at or immediately below the lowest soil or waste pipe from the lowest storey
.
300 mm (minimum)
Air admittance valves offer a substitute for You can use air admittance valves for:
running vent pipes to the outside of •trap vents
buildings. These valves open automatically •group vents
to let fresh air into the sanitary system if •stack vents
there is a decrease in air pressure within •branch drains.
the system. The valves close automatically, These are not suitable for upstream
to avoid the discharge of foul air, whenever venting of a main drain (unless there are
the pressure in the system is equal to or two upstream vents, in which case one
greater than the external pressure. may be an air admittance valve). They
should be installed in the same location
and using the same method as the vent
they are replacing.