Air System Sizing Summary For Default System
Air System Sizing Summary For Default System
1. Summary
Ventilation Sizing Method Sum of Space OA Airflows
2nd floor CLASS ROOM 11 1 522.2 30.0 942.7 10.00 0.12 0.0 0.0 362.7
2nd floor CLASS ROOM 12 1 426.8 30.0 1175.1 10.00 0.12 0.0 0.0 351.2
2nd floor CLASS ROOM 13 1 572.0 30.0 1184.9 10.00 0.12 0.0 0.0 368.6
2nd floor CLASS ROOM 14 1 572.0 30.0 1184.9 10.00 0.12 0.0 0.0 368.6
2nd floor CLASS ROOM 15 1 572.0 30.0 1184.9 10.00 0.12 0.0 0.0 368.6
2nd floor CLASS ROOM 16 1 614.4 30.0 1164.7 10.00 0.12 0.0 0.0 373.7
2nd floor CLASS ROOM 17 1 614.4 30.0 1164.7 10.00 0.12 0.0 0.0 373.7
2nd floor CLASS ROOM 2 1 528.0 30.0 1199.3 10.00 0.12 0.0 0.0 363.4
2nd floor CLASS ROOM 3 1 528.0 30.0 1165.4 10.00 0.12 0.0 0.0 363.4
2nd floor CLASS ROOM 4 1 528.0 30.0 1165.4 10.00 0.12 0.0 0.0 363.4
2nd floor CLASS ROOM 5 1 528.0 30.0 1165.4 10.00 0.12 0.0 0.0 363.4
2nd floor CLASS ROOM 6 1 528.0 30.0 1165.4 10.00 0.12 0.0 0.0 363.4
2nd floor CLASS ROOM 7 1 528.0 30.0 1165.4 10.00 0.12 0.0 0.0 363.4
2nd floor CLASS ROOM 8 1 533.5 30.0 1213.0 10.00 0.12 0.0 0.0 364.0
2nd floor CLASS ROOM 9 1 501.8 30.0 1412.0 10.00 0.12 0.0 0.0 360.2
2nd floor LAB 1 1 676.4 30.0 1459.1 10.00 0.18 0.0 0.0 421.8
2nd floor LAB 2 1 676.4 30.0 1544.0 10.00 0.18 0.0 0.0 421.8
2ND FLOOR STAFF ROOM 1 332.8 30.0 1145.3 5.00 0.06 0.0 0.0 170.0
Zone 4
3RD FLOOR CLAAS ROOM 1 1 484.5 30.0 1344.8 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 11 1 484.5 30.0 1182.8 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 12 1 484.5 30.0 1182.8 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 13 1 484.5 30.0 1182.8 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 14 1 484.5 30.0 1164.2 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 15 1 484.5 30.0 1164.2 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 2 1 484.5 30.0 1210.1 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 3 1 484.5 30.0 1163.3 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 4 1 484.5 30.0 1163.3 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 5 1 484.5 30.0 1163.3 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 6 1 484.5 30.0 1163.3 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 7 1 484.5 30.0 1163.3 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 8 1 484.5 30.0 942.7 10.00 0.12 0.0 0.0 358.1
3RD FLOOR CLAAS ROOM 9 1 484.5 30.0 942.7 10.00 0.12 0.0 0.0 358.1
Totals (incl. Space Multipliers) 87127.8 24929.8
TABLE 1.1.A. COMPONENT LOADS FOR SPACE '' AV ROOM 2 G.F '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 15 ft² 914 - 15 ft² - -
Wall Transmission 251 ft² 1143 - 251 ft² 623 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 15 ft² 136 - 15 ft² 97 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 558 ft² 0 - 558 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 3000 W 9088 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1780 308 5% 36 0
>> Total Zone Loads - 19579 6458 - 756 0
TABLE 1.1.B. ENVELOPE LOADS FOR SPACE '' AV ROOM 2 G.F '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 251 0.225 - 1143 - 623
WINDOW 1 15 0.588 0.811 136 914 97
TABLE 1.2.A. COMPONENT LOADS FOR SPACE '' AV ROOM G.F '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 236 ft² 1075 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 558 ft² 0 - 558 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 3000 W 9088 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1878 308 5% 39 0
>> Total Zone Loads - 20659 6458 - 818 0
TABLE 1.2.B. ENVELOPE LOADS FOR SPACE '' AV ROOM G.F '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 236 0.225 - 1075 - 585
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 1.3.A. COMPONENT LOADS FOR SPACE '' CLASS ROOM 1 '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 236 ft² 1817 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 481 ft² 0 - 481 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1739 308 5% 39 0
>> Total Zone Loads - 19127 6458 - 818 0
TABLE 1.3.B. ENVELOPE LOADS FOR SPACE '' CLASS ROOM 1 '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 236 0.225 - 1817 - 585
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 1.4.A. COMPONENT LOADS FOR SPACE '' CLASS ROOM 2 '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 236 ft² 1817 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 481 ft² 0 - 481 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1739 308 5% 39 0
>> Total Zone Loads - 19127 6458 - 818 0
TABLE 1.4.B. ENVELOPE LOADS FOR SPACE '' CLASS ROOM 2 '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 236 0.225 - 1817 - 585
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 1.5.A. COMPONENT LOADS FOR SPACE '' CLASS ROOM 3 '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.0 °F / 62.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 2442 - 30 ft² - -
Wall Transmission 325 ft² 2599 - 325 ft² 806 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 114 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 481 ft² 0 - 481 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1925 308 5% 50 0
>> Total Zone Loads - 21171 6458 - 1050 0
TABLE 1.5.B. ENVELOPE LOADS FOR SPACE '' CLASS ROOM 3 '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 325 0.225 - 2599 - 806
WINDOW 1 30 0.588 0.811 114 2442 194
TABLE 1.6.A. COMPONENT LOADS FOR SPACE '' CLASS ROOM 4 '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 236 ft² 1074 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 481 ft² 0 - 481 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1727 308 5% 39 0
>> Total Zone Loads - 18992 6458 - 818 0
TABLE 1.6.B. ENVELOPE LOADS FOR SPACE '' CLASS ROOM 4 '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 236 0.225 - 1074 - 585
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 1.7.A. COMPONENT LOADS FOR SPACE '' CLASS ROOM 5 '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 481 ft² 0 - 481 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1409 308 5% 0 0
>> Total Zone Loads - 15499 6458 - 0 0
TABLE 1.7.B. ENVELOPE LOADS FOR SPACE '' CLASS ROOM 5 '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 1.8.A. COMPONENT LOADS FOR SPACE '' CLASS ROOM 6 '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.0 °F / 62.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 2442 - 30 ft² - -
Wall Transmission 325 ft² 2599 - 325 ft² 806 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 114 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 481 ft² 0 - 481 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1925 308 5% 50 0
>> Total Zone Loads - 21171 6458 - 1050 0
TABLE 1.8.B. ENVELOPE LOADS FOR SPACE '' CLASS ROOM 6 '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 325 0.225 - 2599 - 806
WINDOW 1 30 0.588 0.811 114 2442 194
TABLE 1.9.A. COMPONENT LOADS FOR SPACE '' CLASS ROOM 7 '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 15 ft² 604 - 15 ft² - -
Wall Transmission 255 ft² 1965 - 255 ft² 633 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 15 ft² 136 - 15 ft² 97 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 367 ft² 0 - 367 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1680 308 5% 36 0
>> Total Zone Loads - 18475 6458 - 766 0
TABLE 1.9.B. ENVELOPE LOADS FOR SPACE '' CLASS ROOM 7 '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 255 0.225 - 1965 - 633
WINDOW 1 15 0.588 0.811 136 604 97
TABLE 1.10.A. COMPONENT LOADS FOR SPACE '' CLASS ROOM 8 '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 367 ft² 0 - 367 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1409 308 5% 0 0
>> Total Zone Loads - 15499 6458 - 0 0
TABLE 1.10.B. ENVELOPE LOADS FOR SPACE '' CLASS ROOM 8 '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 1.11.A. COMPONENT LOADS FOR SPACE '' COMPUTER LAB G.F '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 45 ft² 2742 - 45 ft² - -
Wall Transmission 496 ft² 2258 - 496 ft² 1230 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 45 ft² 409 - 45 ft² 291 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 1091 ft² 0 - 1091 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 3500 W 10603 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2253 308 5% 76 0
>> Total Zone Loads - 24782 6458 - 1597 0
TABLE 1.11.B. ENVELOPE LOADS FOR SPACE '' COMPUTER LAB G.F '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 496 0.225 - 2258 - 1230
WINDOW 1 45 0.588 0.811 409 2742 291
TABLE 1.12.A. COMPONENT LOADS FOR SPACE '' GROUND FLOOR DINING '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.4 °F / 66.8 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 165 ft² 6611 - 165 ft² - -
Wall Transmission 2800 ft² 17681 - 2800 ft² 6943 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 165 ft² 1480 - 165 ft² 1067 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 5575 ft² 0 - 5575 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 4W 11 - 0 0 -
Task Lighting 0W 0 - 0 0 -
Electric Equipment 3500 W 10720 - 0 0 -
People 150 29966 40500 0 0 0
Infiltration - 63731 -14699 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 13020 1290 5% 401 0
>> Total Zone Loads - 143219 27091 - 8411 0
TABLE 1.12.B. ENVELOPE LOADS FOR SPACE '' GROUND FLOOR DINING '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 751 0.225 - 5632 - 1861
WINDOW 1 60 0.588 0.811 538 2287 388
N EXPOSURE
WALL 1269 0.225 - 7691 - 3147
WINDOW 1 75 0.588 0.811 673 2373 485
W EXPOSURE
WALL 781 0.225 - 4357 - 1936
WINDOW 1 30 0.588 0.811 269 1951 194
TABLE 1.13.A. COMPONENT LOADS FOR SPACE '' HEAD MISTRESS OFFICE G.F '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 251 ft² 0 - 251 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 400 W 1175 - 0 0 -
Electric Equipment 3000 W 9088 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1531 308 5% 0 0
>> Total Zone Loads - 16842 6458 - 0 0
TABLE 1.13.B. ENVELOPE LOADS FOR SPACE '' HEAD MISTRESS OFFICE G.F '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 1.14.A. COMPONENT LOADS FOR SPACE '' LIBRARY G.F '' IN ZONE '' gf ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1600 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.4 °F / 66.8 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 538 ft² 4075 - 538 ft² 1333 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 969 ft² 0 - 969 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1515 - 0 0 -
Electric Equipment 3500 W 10863 - 0 0 -
People 100 17181 12000 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 3364 600 5% 67 0
>> Total Zone Loads - 37003 12600 - 1399 0
TABLE 1.14.B. ENVELOPE LOADS FOR SPACE '' LIBRARY G.F '' IN ZONE '' gf ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 538 0.225 - 4075 - 1333
TABLE 2.1.A. COMPONENT LOADS FOR SPACE '' EXAM ROOM F.F '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 15 ft² 914 - 15 ft² - -
Wall Transmission 166 ft² 754 - 166 ft² 411 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 15 ft² 136 - 15 ft² 97 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1589 308 5% 25 0
>> Total Zone Loads - 17484 6458 - 533 0
TABLE 2.1.B. ENVELOPE LOADS FOR SPACE '' EXAM ROOM F.F '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 166 0.225 - 754 - 411
WINDOW 1 15 0.588 0.811 136 914 97
TABLE 2.2.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROO15 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1109 - 30 ft² - -
Wall Transmission 324 ft² 1930 - 324 ft² 804 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 255 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1738 308 5% 50 0
>> Total Zone Loads - 19123 6458 - 1048 0
TABLE 2.2.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROO15 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 324 0.225 - 1930 - 804
WINDOW 1 30 0.588 0.811 255 1109 194
TABLE 2.3.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 1 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 45 ft² 1749 - 45 ft² - -
Wall Transmission 575 ft² 3879 - 575 ft² 1426 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 45 ft² 383 - 45 ft² 291 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2010 308 5% 86 0
>> Total Zone Loads - 22112 6458 - 1803 0
TABLE 2.3.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 1 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 251 0.225 - 1494 - 622
WINDOW 1 15 0.588 0.811 128 555 97
E EXPOSURE
WALL 324 0.225 - 2385 - 804
WINDOW 1 30 0.588 0.811 255 1194 194
TABLE 2.4.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 2 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 305 ft² 2346 - 305 ft² 755 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1792 308 5% 47 0
>> Total Zone Loads - 19708 6458 - 997 0
TABLE 2.4.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 2 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 305 0.225 - 2346 - 755
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 2.5.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 3 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 236 ft² 1817 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1739 308 5% 39 0
>> Total Zone Loads - 19127 6458 - 818 0
TABLE 2.5.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 3 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 236 0.225 - 1817 - 585
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 2.6.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 4 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 236 ft² 1817 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1739 308 5% 39 0
>> Total Zone Loads - 19127 6458 - 818 0
TABLE 2.6.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 4 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 236 0.225 - 1817 - 585
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 2.7.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 5 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 236 ft² 1817 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1739 308 5% 39 0
>> Total Zone Loads - 19127 6458 - 818 0
TABLE 2.7.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 5 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 236 0.225 - 1817 - 585
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 2.8.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 6 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 324 ft² 2497 - 324 ft² 804 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1807 308 5% 50 0
>> Total Zone Loads - 19874 6458 - 1048 0
TABLE 2.8.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 6 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 324 0.225 - 2497 - 804
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 2.9.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 7 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.0 °F / 62.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 2442 - 30 ft² - -
Wall Transmission 324 ft² 2594 - 324 ft² 804 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 114 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1924 308 5% 50 0
>> Total Zone Loads - 21165 6458 - 1048 0
TABLE 2.9.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 7 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 324 0.225 - 2594 - 804
WINDOW 1 30 0.588 0.811 114 2442 194
TABLE 2.10.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 8 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.0 °F / 62.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 2442 - 30 ft² - -
Wall Transmission 324 ft² 2594 - 324 ft² 804 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 114 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1924 308 5% 50 0
>> Total Zone Loads - 21165 6458 - 1048 0
TABLE 2.10.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 8 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 324 0.225 - 2594 - 804
WINDOW 1 30 0.588 0.811 114 2442 194
TABLE 2.11.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 9 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 236 ft² 1074 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1727 308 5% 39 0
>> Total Zone Loads - 18992 6458 - 818 0
TABLE 2.11.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM 9 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 236 0.225 - 1074 - 585
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 2.12.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM10 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1409 308 5% 0 0
>> Total Zone Loads - 15499 6458 - 0 0
TABLE 2.12.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM10 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 2.13.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM11 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 320 ft² 1457 - 320 ft² 793 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1765 308 5% 49 0
>> Total Zone Loads - 19413 6458 - 1037 0
TABLE 2.13.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM11 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 320 0.225 - 1457 - 793
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 2.14.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM12 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 320 ft² 1457 - 320 ft² 793 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1765 308 5% 49 0
>> Total Zone Loads - 19413 6458 - 1037 0
TABLE 2.14.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM12 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 320 0.225 - 1457 - 793
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 2.15.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM13 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 320 ft² 1457 - 320 ft² 793 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1765 308 5% 49 0
>> Total Zone Loads - 19413 6458 - 1037 0
TABLE 2.15.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM13 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 320 0.225 - 1457 - 793
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 2.16.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM14 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 320 ft² 1457 - 320 ft² 793 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1765 308 5% 49 0
>> Total Zone Loads - 19413 6458 - 1037 0
TABLE 2.16.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM14 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 320 0.225 - 1457 - 793
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 2.17.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM17 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1409 308 5% 0 0
>> Total Zone Loads - 15499 6458 - 0 0
TABLE 2.17.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM17 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 2.18.A. COMPONENT LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM18 '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1409 308 5% 0 0
>> Total Zone Loads - 15499 6458 - 0 0
TABLE 2.18.B. ENVELOPE LOADS FOR SPACE '' FIRST FLOOR CLASS ROOM18 '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 2.19.A. COMPONENT LOADS FOR SPACE '' STAFF ROOM F.F '' IN ZONE '' 1st f ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 3500 W 10603 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1712 308 5% 0 0
>> Total Zone Loads - 18832 6458 - 0 0
TABLE 2.19.B. ENVELOPE LOADS FOR SPACE '' STAFF ROOM F.F '' IN ZONE '' 1st f ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 3.1.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 1 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 45 ft² 1749 - 45 ft² - -
Wall Transmission 588 ft² 3966 - 588 ft² 1457 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 45 ft² 383 - 45 ft² 291 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2019 308 5% 87 0
>> Total Zone Loads - 22207 6458 - 1836 0
TABLE 3.1.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 1 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 255 0.225 - 1519 - 633
WINDOW 1 15 0.588 0.811 128 555 97
E EXPOSURE
WALL 333 0.225 - 2447 - 825
WINDOW 1 30 0.588 0.811 255 1194 194
TABLE 3.2.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 10 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1409 308 5% 0 0
>> Total Zone Loads - 15499 6458 - 0 0
TABLE 3.2.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 10 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 3.3.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 11 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1409 308 5% 0 0
>> Total Zone Loads - 15499 6458 - 0 0
TABLE 3.3.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 11 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 3.4.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 12 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 302 ft² 1374 - 302 ft² 748 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1757 308 5% 47 0
>> Total Zone Loads - 19322 6458 - 989 0
TABLE 3.4.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 12 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 302 0.225 - 1374 - 748
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 3.5.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 13 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 334 ft² 1521 - 334 ft² 828 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1771 308 5% 51 0
>> Total Zone Loads - 19483 6458 - 1073 0
TABLE 3.5.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 13 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 334 0.225 - 1521 - 828
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 3.6.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 14 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 334 ft² 1521 - 334 ft² 828 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1771 308 5% 51 0
>> Total Zone Loads - 19483 6458 - 1073 0
TABLE 3.6.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 14 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 334 0.225 - 1521 - 828
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 3.7.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 15 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 334 ft² 1521 - 334 ft² 828 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1771 308 5% 51 0
>> Total Zone Loads - 19483 6458 - 1073 0
TABLE 3.7.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 15 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 334 0.225 - 1521 - 828
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 3.8.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 16 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1109 - 30 ft² - -
Wall Transmission 328 ft² 1955 - 328 ft² 814 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 255 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1741 308 5% 50 0
>> Total Zone Loads - 19151 6458 - 1059 0
TABLE 3.8.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 16 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 328 0.225 - 1955 - 814
WINDOW 1 30 0.588 0.811 255 1109 194
TABLE 3.9.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 17 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1109 - 30 ft² - -
Wall Transmission 328 ft² 1955 - 328 ft² 814 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 255 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1741 308 5% 50 0
>> Total Zone Loads - 19151 6458 - 1059 0
TABLE 3.9.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 17 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 328 0.225 - 1955 - 814
WINDOW 1 30 0.588 0.811 255 1109 194
TABLE 3.10.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 2 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 306 ft² 2357 - 306 ft² 759 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1793 308 5% 48 0
>> Total Zone Loads - 19720 6458 - 1000 0
TABLE 3.10.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 2 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 306 0.225 - 2357 - 759
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 3.11.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 3 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 240 ft² 1850 - 240 ft² 596 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1742 308 5% 39 0
>> Total Zone Loads - 19162 6458 - 829 0
TABLE 3.11.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 3 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 240 0.225 - 1850 - 596
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 3.12.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 4 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 240 ft² 1850 - 240 ft² 596 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1742 308 5% 39 0
>> Total Zone Loads - 19162 6458 - 829 0
TABLE 3.12.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 4 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 240 0.225 - 1850 - 596
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 3.13.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 5 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 240 ft² 1850 - 240 ft² 596 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1742 308 5% 39 0
>> Total Zone Loads - 19162 6458 - 829 0
TABLE 3.13.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 5 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 240 0.225 - 1850 - 596
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 3.14.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 6 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 240 ft² 1850 - 240 ft² 596 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1742 308 5% 39 0
>> Total Zone Loads - 19162 6458 - 829 0
TABLE 3.14.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 6 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 240 0.225 - 1850 - 596
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 3.15.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 7 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 240 ft² 1850 - 240 ft² 596 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1742 308 5% 39 0
>> Total Zone Loads - 19162 6458 - 829 0
TABLE 3.15.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 7 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 240 0.225 - 1850 - 596
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 3.16.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 8 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 333 ft² 2561 - 333 ft² 825 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1813 308 5% 51 0
>> Total Zone Loads - 19945 6458 - 1070 0
TABLE 3.16.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 8 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 333 0.225 - 2561 - 825
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 3.17.A. COMPONENT LOADS FOR SPACE '' 2nd floor CLASS ROOM 9 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.0 °F / 62.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 45 ft² 2940 - 45 ft² - -
Wall Transmission 588 ft² 3904 - 588 ft² 1457 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 45 ft² 171 - 45 ft² 291 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2111 308 5% 87 0
>> Total Zone Loads - 23216 6458 - 1836 0
TABLE 3.17.B. ENVELOPE LOADS FOR SPACE '' 2nd floor CLASS ROOM 9 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 259 0.225 - 1276 - 643
WINDOW 1 15 0.588 0.811 57 498 97
S EXPOSURE
WALL 328 0.225 - 2627 - 814
WINDOW 1 30 0.588 0.811 114 2442 194
TABLE 3.18.A. COMPONENT LOADS FOR SPACE '' 2nd floor LAB 1 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 236 ft² 1074 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 4000 W 12118 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2181 308 5% 39 0
>> Total Zone Loads - 23991 6458 - 818 0
TABLE 3.18.B. ENVELOPE LOADS FOR SPACE '' 2nd floor LAB 1 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 236 0.225 - 1074 - 585
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 3.19.A. COMPONENT LOADS FOR SPACE '' 2nd floor LAB 2 '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Dec 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 85.0 °F / 62.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 2442 - 30 ft² - -
Wall Transmission 236 ft² 1888 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 114 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 4000 W 12118 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2308 308 5% 39 0
>> Total Zone Loads - 25387 6458 - 818 0
TABLE 3.19.B. ENVELOPE LOADS FOR SPACE '' 2nd floor LAB 2 '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
S EXPOSURE
WALL 236 0.225 - 1888 - 585
WINDOW 1 30 0.588 0.811 114 2442 194
TABLE 3.20.A. COMPONENT LOADS FOR SPACE '' 2ND FLOOR STAFF ROOM '' IN ZONE '' 2nd ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 3500 W 10603 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1712 308 5% 0 0
>> Total Zone Loads - 18832 6458 - 0 0
TABLE 3.20.B. ENVELOPE LOADS FOR SPACE '' 2ND FLOOR STAFF ROOM '' IN ZONE '' 2nd ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 4.1.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 1 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 45 ft² 1706 - 45 ft² - -
Wall Transmission 578 ft² 3921 - 578 ft² 1433 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 45 ft² 383 - 45 ft² 291 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 2010 308 5% 86 0
>> Total Zone Loads - 22111 6458 - 1810 0
TABLE 4.1.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 1 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 236 0.225 - 1405 - 585
WINDOW 1 30 0.588 0.811 255 1109 194
E EXPOSURE
WALL 342 0.225 - 2516 - 848
WINDOW 1 15 0.588 0.811 128 597 97
TABLE 4.2.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 11 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 327 ft² 1489 - 327 ft² 811 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1768 308 5% 50 0
>> Total Zone Loads - 19448 6458 - 1055 0
TABLE 4.2.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 11 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 327 0.225 - 1489 - 811
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 4.3.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 12 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 327 ft² 1489 - 327 ft² 811 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1768 308 5% 50 0
>> Total Zone Loads - 19448 6458 - 1055 0
TABLE 4.3.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 12 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 327 0.225 - 1489 - 811
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 4.4.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 13 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1828 - 30 ft² - -
Wall Transmission 327 ft² 1489 - 327 ft² 811 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1768 308 5% 50 0
>> Total Zone Loads - 19448 6458 - 1055 0
TABLE 4.4.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 13 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
W EXPOSURE
WALL 327 0.225 - 1489 - 811
WINDOW 1 30 0.588 0.811 273 1828 194
TABLE 4.5.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 14 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1109 - 30 ft² - -
Wall Transmission 327 ft² 1947 - 327 ft² 811 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 255 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1740 308 5% 50 0
>> Total Zone Loads - 19142 6458 - 1055 0
TABLE 4.5.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 14 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 327 0.225 - 1947 - 811
WINDOW 1 30 0.588 0.811 255 1109 194
TABLE 4.6.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 15 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jun 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 93.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1109 - 30 ft² - -
Wall Transmission 327 ft² 1947 - 327 ft² 811 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 255 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1740 308 5% 50 0
>> Total Zone Loads - 19142 6458 - 1055 0
TABLE 4.6.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 15 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
N EXPOSURE
WALL 327 0.225 - 1947 - 811
WINDOW 1 30 0.588 0.811 255 1109 194
TABLE 4.7.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 2 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 327 ft² 2518 - 327 ft² 811 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1809 308 5% 50 0
>> Total Zone Loads - 19897 6458 - 1055 0
TABLE 4.7.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 2 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 327 0.225 - 2518 - 811
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 4.8.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 3 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 236 ft² 1817 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1739 308 5% 39 0
>> Total Zone Loads - 19127 6458 - 818 0
TABLE 4.8.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 3 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 236 0.225 - 1817 - 585
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 4.9.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 4 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 236 ft² 1817 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1739 308 5% 39 0
>> Total Zone Loads - 19127 6458 - 818 0
TABLE 4.9.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 4 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 236 0.225 - 1817 - 585
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 4.10.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 5 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 236 ft² 1817 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1739 308 5% 39 0
>> Total Zone Loads - 19127 6458 - 818 0
TABLE 4.10.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 5 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 236 0.225 - 1817 - 585
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 4.11.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 6 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 236 ft² 1817 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1739 308 5% 39 0
>> Total Zone Loads - 19127 6458 - 818 0
TABLE 4.11.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 6 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 236 0.225 - 1817 - 585
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 4.12.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 7 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Aug 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 94.0 °F / 67.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 30 ft² 1207 - 30 ft² - -
Wall Transmission 236 ft² 1817 - 236 ft² 585 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 30 ft² 273 - 30 ft² 194 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1739 308 5% 39 0
>> Total Zone Loads - 19127 6458 - 818 0
TABLE 4.12.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 7 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
E EXPOSURE
WALL 236 0.225 - 1817 - 585
WINDOW 1 30 0.588 0.811 273 1207 194
TABLE 4.13.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 8 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1409 308 5% 0 0
>> Total Zone Loads - 15499 6458 - 0 0
TABLE 4.13.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 8 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
TABLE 4.14.A. COMPONENT LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 9 '' IN ZONE '' Zone 4 ''
DESIGN COOLING DESIGN HEATING
COOLING DATA AT Jan 1500 HEATING DATA AT DES HTG
COOLING OA DB / WB 84.0 °F / 61.0 °F HEATING OA DB / WB 59.0 °F / 48.9 °F
OCCUPIED T-STAT 75.0 °F OCCUPIED T-STAT 70.0 °F
Sensible Latent Sensible Latent
SPACE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr)
Window & Skylight Solar Loads 0 ft² 0 - 0 ft² - -
Wall Transmission 0 ft² 0 - 0 ft² 0 -
Roof Transmission 0 ft² 0 - 0 ft² 0 -
Window Transmission 0 ft² 0 - 0 ft² 0 -
Skylight Transmission 0 ft² 0 - 0 ft² 0 -
Door Loads 0 ft² 0 - 0 ft² 0 -
Floor Transmission 0 ft² 0 - 0 ft² 0 -
Partitions 0 ft² 0 - 0 ft² 0 -
Ceiling 0 ft² 0 - 0 ft² 0 -
Overhead Lighting 2W 5 - 0 0 -
Task Lighting 500 W 1469 - 0 0 -
Electric Equipment 2500 W 7574 - 0 0 -
People 30 5043 6150 0 0 0
Infiltration - 0 0 - 0 0
Miscellaneous - 0 0 - 0 0
Safety Factor 10% / 5% 1409 308 5% 0 0
>> Total Zone Loads - 15499 6458 - 0 0
TABLE 4.14.B. ENVELOPE LOADS FOR SPACE '' 3RD FLOOR CLAAS ROOM 9 '' IN ZONE '' Zone 4 ''
COOLING COOLING HEATING
Area U-Value Shade TRANS SOLAR TRANS
(ft²) (BTU/(hr-ft²-°F)) Coeff. (BTU/hr) (BTU/hr) (BTU/hr)
ZONE: gf
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 78.2 80.1 39 2161.7 108452.7 46251.8 45226.9 0.0 0.0
0100 77.2 80.1 39 1786.6 97888.5 38189.0 36931.6 0.0 0.0
0200 76.2 80.1 39 1419.5 87688.4 30313.6 28988.4 0.0 0.0
0300 75.5 80.1 39 1099.9 78753.2 23468.8 22240.2 0.0 0.0
0400 74.9 80.0 40 828.0 71066.4 17656.0 16617.4 0.0 0.0
0500 74.7 80.0 40 642.6 65500.2 13695.6 12861.1 0.0 0.0
0600 75.1 80.0 40 636.6 64174.1 13568.5 12801.6 0.0 0.0
0700 76.1 75.7 48 25005.5 95272.3 177311.8 179546.4 0.0 0.0
0800 77.8 75.9 65 25005.5 275532.4 340407.0 390205.1 0.0 0.0
0900 80.3 76.3 67 25005.5 273707.5 319739.2 361835.4 0.0 0.0
1000 83.2 76.2 66 25005.5 281343.7 327405.6 395025.5 0.0 0.0
1100 86.5 76.1 64 25005.5 298030.5 345446.8 450081.7 0.0 0.0
1200 89.6 76.1 64 25005.5 305992.7 346557.6 470157.2 0.0 0.0
1300 91.9 76.2 64 25005.5 305572.2 341962.2 474347.4 0.0 0.0
1400 93.4 76.4 64 25005.5 313681.8 339945.4 476007.8 0.0 0.0
1500 94.0 76.3 63 25005.5 330446.0 356496.1 510219.2 0.0 0.0
1600 93.4 80.4 43 7526.3 263400.2 163282.6 187631.2 0.0 0.0
1700 92.1 80.4 43 7555.0 254531.7 163918.6 185317.3 0.0 0.0
1800 89.9 80.3 40 5908.8 211643.5 127653.0 141473.3 0.0 0.0
1900 87.4 80.3 40 5493.2 198622.9 118548.0 128074.1 0.0 0.0
2000 84.9 80.2 39 4204.1 165239.3 90424.9 95224.1 0.0 0.0
2100 82.8 80.2 39 3644.4 149499.3 78275.3 80581.0 0.0 0.0
2200 80.9 80.2 39 3085.8 134002.1 66181.4 66708.2 0.0 0.0
2300 79.3 80.1 39 2590.5 120239.5 55487.9 54974.4 0.0 0.0
ZONE: 1st f
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 78.2 80.2 39 2571.9 84984.3 55139.1 53686.2 0.0 0.0
0100 77.2 80.2 39 2358.5 78794.2 50531.1 48562.8 0.0 0.0
0200 76.2 80.1 39 2153.2 72904.7 46105.6 43727.6 0.0 0.0
0300 75.5 80.1 39 1965.9 67529.7 42072.2 39477.5 0.0 0.0
0400 74.9 80.1 39 1796.5 62655.8 38426.8 35766.4 0.0 0.0
0500 74.7 80.1 39 1653.7 58475.1 35358.2 32823.0 0.0 0.0
0600 75.1 80.1 39 1612.5 56676.2 34472.1 32177.9 0.0 0.0
0700 76.1 75.6 47 21893.8 59061.7 122762.9 125518.7 0.0 0.0
0800 77.8 76.2 59 21893.8 298482.9 342609.4 377091.0 0.0 0.0
0900 80.3 76.7 59 21893.8 305948.8 338486.3 377209.5 0.0 0.0
1000 83.2 76.6 59 21893.8 313440.8 344181.4 405314.7 0.0 0.0
1100 86.5 76.6 58 21893.8 320392.3 348989.1 436735.5 0.0 0.0
1200 89.6 76.6 57 21893.8 327463.1 354085.7 465292.9 0.0 0.0
1300 91.9 76.6 56 21893.8 335737.2 360602.5 489042.5 0.0 0.0
1400 93.4 76.4 55 21893.8 343957.7 371290.2 519905.8 0.0 0.0
1500 94.0 76.1 55 21893.8 351571.9 381071.5 544907.8 0.0 0.0
1600 93.4 80.3 43 3924.9 135735.4 84482.3 99679.2 0.0 0.0
1700 92.1 80.3 43 4098.6 133150.1 88264.9 101982.9 0.0 0.0
1800 89.9 80.3 40 3867.6 125451.8 83234.9 93868.3 0.0 0.0
1900 87.4 80.2 40 3743.9 120432.6 80542.1 88180.4 0.0 0.0
2000 84.9 80.2 39 3549.8 113955.0 76322.7 81052.3 0.0 0.0
2100 82.8 80.2 39 3309.0 106572.8 71095.8 73527.5 0.0 0.0
2200 80.9 80.2 39 3049.4 98917.0 65466.8 66053.6 0.0 0.0
2300 79.3 80.2 39 2800.6 91659.1 60081.5 59407.2 0.0 0.0
ZONE: 2nd
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 78.2 80.2 39 2762.2 96087.3 59208.6 57620.3 0.0 0.0
0100 77.2 80.1 39 2517.4 88875.8 53925.6 51786.1 0.0 0.0
0200 76.2 80.1 39 2281.0 81995.9 48831.4 46265.4 0.0 0.0
0300 75.5 80.1 39 2066.4 75740.6 44210.6 41432.3 0.0 0.0
0400 74.9 80.1 39 1873.4 70096.2 40061.0 37234.7 0.0 0.0
0500 74.7 80.1 39 1714.3 65330.6 36643.7 33966.3 0.0 0.0
0600 75.1 80.1 39 1693.2 63803.1 36190.4 33735.6 0.0 0.0
0700 76.1 75.7 47 24095.2 67947.8 140319.8 142625.9 0.0 0.0
0800 77.8 75.9 59 24095.2 329656.1 387749.8 442016.8 0.0 0.0
0900 80.3 76.6 59 24095.2 338485.7 376727.1 427431.8 0.0 0.0
1000 83.2 76.6 58 24095.2 347320.5 384134.3 461019.6 0.0 0.0
1100 86.5 76.6 58 24095.2 355329.5 389431.4 496171.0 0.0 0.0
1200 89.6 76.6 57 24095.2 363413.3 395034.7 527970.8 0.0 0.0
1300 91.9 76.3 56 24095.2 372538.8 406884.5 565832.4 0.0 0.0
1400 93.4 76.5 56 24095.2 381127.5 408538.4 576279.9 0.0 0.0
1500 94.0 76.4 55 24095.2 388806.1 416671.5 597725.0 0.0 0.0
1600 93.4 80.3 43 4465.2 158018.1 96148.1 113799.4 0.0 0.0
1700 92.1 80.3 43 4630.2 154323.1 99746.6 115543.4 0.0 0.0
1800 89.9 80.3 40 4358.9 145196.9 93833.5 106048.8 0.0 0.0
1900 87.4 80.2 40 4184.9 138577.6 90045.7 98749.3 0.0 0.0
2000 84.9 80.2 39 3937.3 130453.0 84661.4 90010.0 0.0 0.0
2100 82.8 80.2 39 3647.0 121547.1 78359.0 81092.2 0.0 0.0
2200 80.9 80.2 39 3339.5 112437.3 71693.3 72349.7 0.0 0.0
2300 79.3 80.2 39 3048.5 103886.5 65395.2 64648.4 0.0 0.0
ZONE: Zone 4
DESIGN MONTH: JULY
ZONE TERMINAL TERMINAL ZONE
OA ZONE ZONE SENSIBLE ZONE COOLING HEATING HEATING
TEMP TEMP RH AIRFLOW LOAD COND COIL COIL UNIT
Hour (°F) (°F) (%) (CFM) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr) (BTU/hr)
0000 78.2 80.2 39 2014.4 66432.9 43206.4 41993.8 0.0 0.0
0100 77.2 80.2 39 1842.2 61512.6 39486.9 37851.9 0.0 0.0
0200 76.2 80.1 39 1676.6 56827.4 35912.4 33945.6 0.0 0.0
0300 75.5 80.1 39 1525.7 52559.2 32660.8 30523.0 0.0 0.0
0400 74.9 80.1 39 1389.5 48697.8 29728.6 27544.8 0.0 0.0
0500 74.7 80.1 39 1275.5 45408.3 27277.4 25202.6 0.0 0.0
0600 75.1 80.1 39 1263.6 44498.8 27021.7 25113.3 0.0 0.0
0700 76.1 75.8 47 16133.3 48020.8 92346.7 93428.7 0.0 0.0
0800 77.8 76.7 60 16133.3 223101.4 248897.4 261999.6 0.0 0.0
0900 80.3 76.6 59 16133.3 229392.8 254906.6 284867.9 0.0 0.0
1000 83.2 76.6 58 16133.3 235657.9 259354.8 307277.4 0.0 0.0
1100 86.5 76.6 57 16133.3 241257.6 263284.9 332121.1 0.0 0.0
1200 89.6 76.3 56 16133.3 246882.0 270945.7 363827.5 0.0 0.0
1300 91.9 76.0 55 16133.3 253117.8 279074.5 390755.3 0.0 0.0
1400 93.4 76.4 55 16133.3 258832.7 277769.3 392029.8 0.0 0.0
1500 94.0 76.5 55 16133.3 263878.3 279557.8 397430.7 0.0 0.0
1600 93.4 80.3 43 3212.7 108373.2 69239.6 82018.1 0.0 0.0
1700 92.1 80.3 43 3302.9 105819.2 71210.5 82904.5 0.0 0.0
1800 89.9 80.3 40 3113.3 99654.7 67070.7 76122.4 0.0 0.0
1900 87.4 80.3 40 2991.0 95206.3 64404.3 70854.6 0.0 0.0
2000 84.9 80.2 39 2819.2 89741.7 60664.9 64631.6 0.0 0.0
2100 82.8 80.2 39 2617.8 83719.8 56283.9 58310.7 0.0 0.0
2200 80.9 80.2 39 2404.7 77553.6 51658.7 52139.1 0.0 0.0
2300 79.3 80.2 39 2202.3 71747.9 47273.5 46703.3 0.0 0.0
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM)
Site Altitude = 3021.0 ft
Air Density x Heat Capacity x Conversion Factor: At sea level = 1.080; At site altitude = 0.967 BTU/(hr-CFM-F)
Air Density x Heat of Vaporization x Conversion Factor: At sea level = 4746.6; At site altitude = 4250.8 BTU/(hr-CFM)
Site Altitude = 3021.0 ft
1200
1000
800
600
400
200
0
00 02 04 06 08 10 12 14 16 18 20 22
01 03 05 07 09 11 13 15 17 19 21 23
Hour of Day
Zone: gf
Data for July
300K
250K
BTU/hr
200K
150K
100K
50K
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: 1st f
Data for July
350K
300K
250K
BTU/hr
200K
150K
100K
50K
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day
Zone: 2nd
Data for July
400K
350K
300K
250K
BTU/hr
200K
150K
100K
50K
0
00 01 02 03 04 05 06 07 08 09 10 11 12 13 14 15 16 17 18 19 20 21 22 23
Hour of Day