You are on page 1of 54

MICRO LAB RC BUILDING AT

AMBATTUR

Area Name : Rev. No. R00

PRELIMINARY BILL OF QUANTITIES


Notes:

1. The quantities mentioned below are indicative for tender purpose only.

2. The Final BOQ based on the design and MICROLAB requirement and Tender purpose drawings and submit offer accordingly. In no case escalation of rates due to om
in quantity would be entertained.

3. Civil work like Foundations for all Mechanical & Electrical Equipments Like DG & transformer Yard, Paver blocks are considered separately.

4. Road works, Drains, Gate & other Infra facilities are excluded in this BOQ.

5. Quantities are provided for RCC work & Brick walls only.

CIVIL WORKS

FOUNDATION DETAILS
1 Foundation Of 25 nos - 3m x 3m x 0.5m Nos. 18
2 Foundation Of Double Break Isolator Nos. 60
3 Foundation Of Current Transformer. Nos. 18
4 Foundation Of Potential Transformer Nos. 12
5 Foundation Of Lightning Arrestor Nos. 18
6 Foundation Of Post Insulator Nos. 35
7 Foundation Of Capacitive Voltage Transformer Nos. 2
8 Foundation Of Power Transformer with oil collection area, sump pit, rail & gravels Nos. 4
9 Foundation Of LM Nos. 4
10 Foundation Of TA Tower Nos. 16
11 Foundation Of NGR Nos. 4
Foundation Of N2 panel with oil collection pit (1500 mm (W) X 1500 mm (L) X 1000 mm (D)) and piping
12 arrangement as per main 132kV Switchyard layout Nos. 4

Main Oil Soak Pit (Oil Trap) alongwith pump and piping arrangement from transformer (Details shall be as per
13 Nos. 2
specification mentioned in 132kV RFQ)
14 Precast Fire wall for 4 hrs rated (Approx. 6.0 meter (H) x 8.0 meter (L)) Nos. 3

15 MRSS Building (Cellar + Ground Floor) as per arch. drawing and specification mentioned in 132kV RFQ. Nos. 1

ROAD
4 meter Wide RCC Road (Approximate Length - 115.0 meter) (Details shall be as per specification mentioned in
1 Mtrs. 115
132kV RFQ)
RCC CABLE TRENCH WITH PRECAST COVER
1 1000 mm (W) X 800 mm (D), Refer Section - A Mtrs. 205
2 1200 mm (W) X 1200 mm (D), Refer Section - B Mtrs. 122
3 1200 mm (W) X 1000 mm (D), Refer Section - C Mtrs. 62
4 1200 mm (W) X 1500 mm (D), Refer Section - D Mtrs. 20
5 Duct bank with 300mm DIA, 6 nos MDPE Pipe for 8.0 meter road crossing, Refer Details - E Nos 6
6 Pull Pit Chamber with Precast Cover - 2300 mm (W) X 2300 mm (L) X 2100 mm (D) Nos 6
7 Pull Pit Chamber with Precast Cover - 2500 mm (W) X 2500 mm (L) X 1800 mm (D) Nos 1

FENCE AND GATES


1 Chain link Fence (2500 mm Height) and Gates (3 Nos) Mtrs. 410
STRUCTURE
1 Structures For Equipment,Towers,LM etc. as per bidders design (Unit Rate Per Metric Tonne to be informed) MT. A/R

GRAVEL
1 40mm Gravel For Switchyard (Height - 150mm) In Cubic Meter (Rate to be quoted per cubic meter) CUM. A/R
Rev. Date 20.11.2018

es due to omissions / increase


APOLLO TYRES LIMITED (ATL) AP GREEN FIELD PROJECT

Document No. :

CIVIL STRUCTURAL, ARCHITECTURAL AND ROAD BILL OF QUANTITIES FOR 132

Sl No Category Description

EXCAVATION: The rates shall include all provision of slope cutting for safety measures,
dewatering the subsoil and rain water to keep the excavation dry and disposing the surplus eart
to a distance of 1000m, levelling and consolidation of 300mm layers to inside the premises
(Measurement of quantity as per requirement in drawing). Also shoring / stepped cutting shall b
done for soil excavated beyond 4m deep. Cost should include all material, labour, compaction
shorting, etc., including all.

Earthwork excavation in all types of soils including weathered/soft disintegrated rock, Murram,
boulders etc., which can be removed by mechanical means (Hydraulic
Excavator/Procliner)/manual and excluding rock which cannot be removed other than by blasting.
Earth works shall includes shoring wherever required, bailing out of water, levelling, dressing of
sides and ramming of bottom and strutting if necessary, including cutting and removal of stray
boulders. Also earth work includes all lead and lifts including segregating the excavated soil and
stacking temporarily at designated locations within site premises and reused as back fill (Upto 4m
depth: The foundation area with an additional clearance of 600mm all-round from RCC face or
actual measured at site whichever is smaller shall be paid for. For depth beyond 4m, min. of actua
1 EXCAVATION excavation or 1200mm clear space all-round RC concrete face shall be paid for.). The back filling
with selected excavated earth (which the maximum particle size shall not exceed 75mm) should
be consolidated in layers to achieve compacted thickness of 200 to 250mm using Mini Vibratory
rollers or 1.5MT plate compactor for foundations, pits, trenches etc., and for plinths and yards
rolling each deposited layer with 8-10 tonne mechanical Vibro roller (to achieve required gradient
and camber ) and Ramming by 1.5MT plate compactor/ hand rammer (where ever area is not
available for compaction by Mechanical Vibro roller),to achieve 95% Procter's density. Samples
shall be taken at every layer at 30m centres for checking field dry density. The Contractor shall
check the Optimum moisture content and Modified Proctor's density for the different type/source o
soil along with NABL accredited laboratory and approved by Engineer-in-Charge.

a EXCAVATION up to 2.0m depth

b EXCAVATION Depth Below 2.0m to 4m depth


Backfilling with selected excavated earth (which the maximum particle size shall not exceed
75mm) available within the site premises should be consolidated in layers to achieve compacted
thickness of 200 to 250mm using Mini Vibratory rollers or 1.5MT plate compactor for foundations,
pits, trenches etc., and for plinths and yards rolling each deposited layer with 8-10 tonne
mechanical Vibro roller (to achieve required gradient and camber ) and Ramming by 1.5MT plate
2 EXCAVATION compactor/ hand rammer (where ever area is not available for compaction by Mechanical Vibro
roller),to achieve 95% Procter's density. Samples shall be taken at every layer at 30m centres for
checking field dry density. The Contractor shall check the Optimum moisture content and Modified
Proctor's density for the different type/source of soil along with an external independent agency
and approved by Engineer-in-Charge. Rate should include all equipment, labour, lead, lift etc.,
complete in all respects.

Earthwork excavation in all types of soils including weathered/soft disintegrated rock, Murram,
boulders etc., and removal of black cotton soil, contaminated soil, medium dense clay, medium
stiff clay, soft clay, sand/sandy clay, boulders unused for filling etc., which can be removed by
mechanical means (Hydraulic Excavator/Proclainer)/manual. Earth works shall includes shoring,
3 EXCAVATION bailing out of water, levelling, dressing of sides and ramming of bottom and strutting if necessary,
including cutting and removal of stray boulder. Also cost shall includes all lead, lifts levelling and
stacking temporarily at designated locations within site premises. (The foundation area with an
additional clearance of 600mm at sides or actual measured at site whichever is smaller shall be
paid for)

a EXCAVATION up to 2.0m depth

b EXCAVATION Depth Below 2.0m to 4m depth

Provide and filling with crusher run 6mm down sized aggregate mixed in equal proportion o
quarry dust to be laid to suitable wherever required including, transportation, spreading
4 EXCAVATION levelling, watering, compacting by 1.5MT plate compactor / hand rammer etc. complete a
specified and as directed by the engineer in charge. (Only compacted volume shall be measure
for payment) Location : Sides of trenches.
CONCRETOR:
NOTES:
a) Cement shall be OPC of 43/53 grade only. No fly-ash/Pozzolana to be used in mix design.
b) River Sand shall be used. Crusher dust not allowed.
c) Rive sand to be sieved by 4.75 mm sieve before using in the concrete.
c) Cement brands ACC, BIRLA, CORAMANDAL, DALMIA, RAMCO, ULTRATECH, Zuari shall be
used.
d) Cost of concrete admixtures shall be included. (Only Admixtures of Fosroc/BASF/SIKA to be
used)
e) Cost of pumping, Boom placer wherever required shall be included.
f) The Quote to be made considering the quantity of cement to be used as per practical condition
to attain the specified grade of concrete, which should not be less than the minimum Quantity
specified. No extra payment will be considered for using additional cement in this regard.
g) Design mix should be carried out based on latest relevant IS code by approved third party
laboratory (Approved by client or Engineer-in-Charge) with contractor's own risk & cost and prior
approval to be obtained from engineer in charge and consultant before start-up the work, well in
advance to avoid any delay in starting of works.
h) Unless otherwise specifically mentioned rates quoted for all concrete items of work shall be
exclusive of the cost of formwork and reinforcement which shall be measured and paid for
separately.
i) Wherever controlled concrete is used this should be designed and laid as per the detailed
specifications attached.
j) It shall be very clearly understood that whenever the grade of concrete is specified it shall then
be contractors responsibility to ensure that minimum crushing strength stipulated for the
respective class of concrete is obtained.
k) All concrete shall be Ready Mix Concrete(RMC) unless otherwise mentioned.
l) All required cube tests shall be carried out for frequency of sampling as per IS code and shall be
submitted.

Minimum Cement content for various of grades of concrete shall be as below:

Concrete Grade M10 : 220 kg

Concrete Grade M15 : 280 kg

Concrete Grade M20 : 300 kg

Concrete Grade M25 : 300 kg

Concrete Grade M30 : 320 kg

Concrete Grade M35 : 340 kg


Providing, mixing and laying Plain Cement Concrete of Grade M10 with Ordinary Portlan
Cement using 20mm and downgraded coarse aggregate for any shape and thickness below
foundations, footings, plinth beams, Grade Slab, machine foundations, trenches, pits & sump
5 CONCRETOR etc., includes dewatering the excavation pit, shuttering, pumping & placing of concrete, tamping
ramming, vibrating, curing etc., with all material and labour complete in all respects at all levels
as per drawings, specifications and as directed by the Engineer-in-Charge. Source of concret
shall be from Ready Mix Concrete.

Providing, mixing and laying of Plain Cement Concrete of Grade M15 with Ordinary Portlan
Cement using 20mm and downgraded coarse aggregate for any thickness for plinth protection
etc., including preparation, levelling and compacting of the surface, formwork with all materia
6 CONCRETOR
machineries and labour complete in all respects, with smooth finish, grid marking of 450mm
450 mm using thread, curing etc as per drawings, specifications and as directed by th
Engineer-in-Charge.

Providing, mixing, placing, vibrating and curing, Reinforced Cement Concrete of grade a
mentioned, using 20 mm and down graded machine crushed stone aggregates, using ordinar
Portland cement of Grade 43, river sand complete as directed and as specified for all sizes an
shapes. Concrete shall be made with Water Cement ratio shall not be more than 0.45 an
necessary admixtures from Fosroc / BASF / Sika of approved make in recommended proportio
(as per IS 9103) to accelerate, retard setting of concrete, improve workability without impairin
7 CONCRETOR strength and durability, vibrating and necessary finishing etc., complete all as directed at all level
and heights etc all complete. Including all leads and lifts, scaffolding, compacting with mechanica
vibrators, hacking, tamping, curing and rendering the concrete surfaces, setting out using Tota
station for checking the alignment for the same, if required etc.,
Mix Design to be got approval from Client / Consultant before commencement of work etc., a
per relevant IS code and complete as directed By Engineer In Charge.
M30 Grade (as per design mix) - All RCC works at all levels - Raft, Foundations, Pedesta
Columns up to plinth top including encasement, retaining walls, RC Walls, Plinth beams,
a CONCRETOR Staircases, steps, machine foundations, piers, abutments, tanks / sump pits, posts and strut etc o
all sizes and shapes.

M25 Grade (as per design mix) - All RCC works - Trenches and Pits of all sizes and shapes at a
b CONCRETOR Levels

Supplying, cleaning, straightening,


NOTE: a) Reinforcement shall be of cutting, bending
Grade Fe500 D TMTfabricating
conformingandtoplacing
IS 1786inonly,position Thermo
8 FITTER mechanically
b) Reinforcement Treated
shall(TMT)
be of bars of Femake
approved 500 Dlike
of SAIL,
different
TATA,diameters, cutting,
TISCO, JINDAL andbending to require
RINL-VIZAG only.
sizes and
Testing to shapes
be doneincluding
as per ISfabricating, handling and transport complete for all RCC works with G
Code frequency.
binding wire of 18 gauge with double stranded for reinforcement work as per approved design
and drawings, including PVC / readymade concrete cover blocks of same concrete grade.
Note : Reinforcement shall be measured only in lengths of bars as actually placed in position o
Supplying,
standard weightdetailing,
basis, fabricating,
no allowancehoisting,
being made erecting
in the and
weightpainting as margin.
for rolling per specifications an
Quantity of stee
a FITTER approved fabrication drawings (which are to be prepared by Contractor and
shall be as per drawing and with Authorised laps and splices, chairs of any shape & profile got approved from
Engineering
Spacer bar of Consultant), transporting
any shape & profile only willtobesite & erecting
measured of Structural steel (Other tha
and paid.
Switchyard
Bar bending schedule should be prepared by contractor and gotthe
area) of approved make (TATA, TISCO, JSW, SAIL) of following
approved bygrade
PMC /ofEngineer-in
steel usin
standard MS hot rolled
charge / Consultant sections
before cutting,with necessary baseplates, stiffeners, gusset plates etc., at a
placing.
heights
One tonne & levels
for thewith connections.
purpose The quoted
of measurement shall rate
meanshall
ONEbe inclusive
METRIC TONNEof alli.e.materials,
1000 kg labours
9 FITTER tools
All required test certificates shall be submitted for frequency of samples as per and
and tackles, cranes, packing pieces, aligning and levelling including providing fixingTes
IS Code. 4.
Grade erection bolts, nuts, washers, straightening, bending,
certification from approved agencies (by consultant) shall be submitted. cutting, drilling, grinding, machining
welding & painting and transport to site. It should include one coat of zinc chromate prime
25micron complete with all labour, materials, tools & tackles, equipment etc. complete as pe
specifications, drawings and as directed by Engineer-in-charge.
Fabricated Members of any steel sections of 250 MPa grade of steel, like Steel beams, rafters
9.a FITTER Stair case, Cage ladder, pipeofracks, platforms shall
etc. at all heights.
One tonne for the purpose measurement mean ONE METRIC TONNE i.e. 1000 kg

Fabricated Members
Supplying, detailing, of any steel sections
fabricating, hoisting,of erecting
250 MPa and gradepainting
of steel, as
likeper
Tubular / Pipe section
specifications an
9.b FITTER as per IS4923 & IS1161, bracings, lintels,are
etc.toatbeallprepared
levels andbyheights
approved fabrication drawings (which Contractor and got approved from
Engineering Consultant), transporting to site & erecting of Galvanized structural steel (fo
Switchyard area) of approved make (TATA, TISCO, JSW, SAIL) of the following grade of steel usin
standard MS hot rolled sections with necessary baseplates, stiffeners, gusset plates etc., at a
heights & levels with connections. The quoted rate shall be inclusive of all materials, labours
10 FITTER
tools and tackles, cranes, packing pieces, aligning and levelling including providing and fixing 4.
Grade erection bolts, nuts, washers, straightening, bending, cutting, drilling, grinding, machining
welding & painting and transport to site. The above work shall also includes cleaning, Grindin
and removing the welding burr from the structural members etc. complete.
Fabricated Members of steel sections of 250 MPa grade of steel, like Steel beams, rafters, Sta
10.a FITTER One tonne
case, for the pipe
Cage ladder, purpose of platforms
racks, measurement etc. atshall mean ONE METRIC TONNE i.e. 1000 kg
all heights.
Providing, fixing and removing well supported, leak proof formwork to required size, leve
including forming chamfers, curves, wedges, cut-outs as per drawings and specification includin
staging, access and working platforms, for concreting etc. complete at all heights and levels. A
the staging shall be of Tubular steel structure with adequate bracing as approved. It shall be mad
sufficiently rigid by using adequate number of ties and braces, Screw jacks or hard board wedge
where required shall be provided to make up any settlement in the form work either before o
during the placing
Fabricated Membersof concrete.
of rolled Forms shall be so
steel sections of constructed
250 MPa grade as toof
besteel,
removable in sections
like Tubular / Pipi
10.b FITTER the desired
sections sequence,
as per IS4923 &without
IS1161,damaging
bracings, the surface
lintels, ofall
etc. at concrete. Staging
levels and heightsshould be as designe
with required extension pieces as approved by Engineer-in-Charge / EC to ensure proper slopes
as per design for slabs / beams etc. and as per levels as shown in drawings. Shuttering used sha
be of minimum 12mm thick water proof ply with sufficient stiffness to avoid excessive deflectio
and joints shall be tightly butted to avoid leakage of slurry. If required, heavy duty self adhesiv
11 FORMWORKER brown tape as approved by Engineer-in-Charge shall be provided in the joints. Provisions fo
inserts, projecting dowels, anchor bolts or any other fixture shall be included.
Cost to include application of approved quality shuttering oils (Waste Oil will not be permitted)
Note :
1)
All Plywood
works shuttering
below groundshall and
be considered
upto Finishedfor allground
Raft, Foundation,
floor level Curing
(i.e. SubTrench walls, Pit
Structure) walls
- Raft,
a FORMWORKER beam soffit, core
Foundations, walls, RCC
Pedestal, walls,up
Columns stairs, ramps,retaining
to plinth, tanks, RCC pedestals,
walls, slabs,
RC Walls, chajjas etc.
trenches, Plinth beams
2) All the Formwork
Staircases, should
steps, etc of give
all sizes andsmooth
shapesfinish to concrete Square,
like (Rectangular, surface.etc)
Finish
at allshould
levels be
andsuch tha
heights
plaster will be avoided

3)
AllMeasurement will be paid
works above Finished for the
ground area
floor of shuttering
level coming in contact
(i.e. Superstructure) with
all Levels concrete
- for onlyLintels
Columns,
b FORMWORKER 4) Shuttering holding bar should not go through the concrete member
sunshades, tie beams, Staircase Waist slab, steps, Sill concrete, Coping works, Floor beams, Slabs
5).
etc.,Design of shuttering
of all shapes, / cantering
sizes and / propping
shapes like for special
(Rectangular, Squarestructures shall
etc) and at be done
all levels andby contracto
heights.
and shall be approved from Engineer-in-charge.

Providing, fixing and removing well supported, leak proof formwork for Machine foundatio
pockets / Cut-outs to required size, level and as per drawings and mentioned below, keeping th
12 FORMWORKER same in position during concreting with proper line and level as per drawing and removal of th
same after a specified period etc. complete as directed by Engineer in charge.

12.a FORMWORKER up to 0.04 Sqm pocket area with maximum deep of 400mm

12.b FORMWORKER above 0.04 to 0.09 Sqm pocket Area with maximum deep of 400mm

Providing and laying design mix quality concrete of M30 grade mixed with minimum cemen
content 320kg/cum, including laying in panels of size as per drawings or as directed by Engineer
in-Charge with w/c ratio of 0.45 and slump not exceeding 90mm. Cost excludes finishing an
13 PAVIOUR screeding as workmanship shall be paid separately. Also as directed by Engineer-in-Charge/as pe
design drawings steel fibres / Reinforcement shall be added in concrete and the same shall b
paid separately.
Note: Temperature should not be more than 30-degree during concreting.
Providing. Laying, finishing with M20 grade concrete screed (Average thickness as per drawings)
14 PAVIOUR with 8mm down grade aggregate. Top surface shall be finished smooth and laid to slope as per
drawings over base concrete. Cost shall includes all material, labours etc.,

Fixing 12 mm wide isolation Hydrocel XL board (FOSROC make) around columns and opening
15 PAVIOUR only to full depth of concrete and sealing the top 12 mm depth of the joints with Polyurethan
sealant - Colpor 200 pf by FOSROC or approved equivalent

Providing and fixing sealant for 12 wide X 12 mm depth on top of Hydrocel XL board with
16 PAVIOUR
Polyurethane sealant.

Providing and spreading 200 micron thick LDPE sheet in one layer with staggered joints ove
17 PAVIOUR cleaned base surface (below the RCC slab) with overlap of 150mm, fixed using 100mm wide se
adhesive tape.
CERAMIC TILES FLOORING
Providing and fixing Anti skid ceramic tiles of approved size, design, Pattern and Shade, to prope
, line & level in floors on cement mortar 1:4 bedding of 30mm thickness with neat cement slurry
cement mixed with pigment of matching shade complete. The item shall include cleaning, makin
18 PAVIOUR mock-up
CERAMICfor TILEapproval
DADO of Architect/Engineer in charge , all accessories, tools , labour, etc. No extr
will be payable
Providing towards
and fixing wastage
glazed ceramic duetiles
to material
in dado pattern.
of approvedPleasesize,
notedesign,
payment will be
Pattern , to in proper
SQM o
finished
line areainonly.
& level dados etcover
complete
12 mmasthick directed
bed of Bycement
Engineer In Charge.
Mortar 1:3 (1 cement : 3 coarse sand) an
Anti skidwith
jointing flooring
greyincement
toilet - slurry
size 300 @ x3.3kg
300 mm per x8.5mm
sqm,andthick jointingKajaria/Somany (Basic price
with white cement 45/Sqft)
including PV
corner beading to match with tile colour, pointing in white cement mixed with pigment o
19 PAVIOUR matching shade complete curing, cleaning etc. complete., The item shall include cleaning
making mock-up for approval of Architect/Engineer in charge all accessories, tools , labour, etc
Providing
No extra willandbe constructing
payable towards 200mm thick precast
wastage due tosolid concrete
material block
pattern. masonry
Please note(including
payment will quoin,
be i
jamb,
EXTERNALcloser blocks,
ROLLING etc., )
SHUTTER of 400MMX200MMX200MM
SQM of finished area only. etc complete as directed By Engineer In Charge size having minimum average
compressive
Providing
Wall tiles /and strength
Dado fixing
- size of300
5.0 xNShutter
Rolling /mm2
300 mmthe for blocks
the
x8.5mm dockshall
thick be ofshall
doors approved
Kajaria/Somany make
be of(Basic conforming
motorized
price to stee
galvanized
45/Sq.ft)
20 MASON IS:2185
single wallin rolling
M10 grade in C.M.
shutter, (1:4)rolling
vertical mix with
type,12mm thickRolling
duty G.I. joints in super structure
Shutters with 1mmabove x 75mm Plinth
wid
level
G.I. using
Providing 43
Plain Streep, Grade
and constructing Ordinary
including 100mm Portland
M.S.Guide thick Cement
precast
75mm , at
by solidall
2.64mmlevels
concrete including
thick block
Minimum scaffolding,
masonry curing
(including
thickness etc.,
quoin,
of galvanize
complete
jamb,
steel closer
slats asblocks,
shallperbe drawing,
etc., ) of
1.2mm specifications
and400MMX100MMX200MM
shall confirm etc.,to all complete
IS6248.Each size as directed
having
slat by
minimum
section Engineer-in-Charge
shall average
be continuous singl
(Aeons/approved
compressive
piece without anyequivalent)
strength of 5.0Box
joint. N /mm2type side the blocks
guidesshall shallbebeof provided
approved for make conforming
higher to
wind resistance
IS:2185 in M10
Hexagonal shapegradeGI hoodin C.M.
cover(1:4)shallmixhe12mm
provided thick to joints
coverin thesuper
shaftstructure
and bracket above Plinth level
assembly. All th
21 MASON including RCCshall
components Bandsbeinpowder
M20 grade coatedof thickness
of approved 100 mm at every
colour. 1.2 m
Rolling heightshall
shutter of blockwork
be designed with t2
Nos of 8 mm
withstand windTorforces
Steel upto
(Noteand : the cost of shuttering
including 183 kmph.and steel reinforcement
Additional accessories likeshalldock
be inclusive).
bracing sha
using
be 43 Grade
provided to Ordinary
protect Portland
the rolling Cement
shutter , at
fromall levels
cyclones including
thereby scaffolding,
increasing curing
the etc.,resistance
wind
STEEL
completeDOOR as (GENERAL
pershall PURPOSE)
drawing, specifications etc., alldrivecomplete as directed
Rolling
Providing shutters
and fixing of be provided
hollow metal with door at direct
all levels fromelectrical motorsbycoupled
ISO 9001-2000
Engineer-in-Charge
certifiedwith reductio
manufacture
(Aeons/approved
gearbox for equivalent)
motorized operation. It shall also be provided with limit switches for operatio
CAPENTER / All hollow metal general doors with or without vision panel. Pressed galvanised steel Singl
22 control.
/Double The leafrolling shutters sizes
to required shall also be provided
of approved make withShakti
mechanizedHormann manualwhichhand crank operatio
consists of frame
JOINER system for emergency operation as standard etc. complete as directed by engineer in charge
shutter, infill and finish as detailed below and conforming to IS 277.
Shop
Door drawing
frame shall to bebe approved
Single by rebateEC. profile of size 125 x 60mm made out of 1.20mm thic
galvanised steel sheet (18 gauge). Frames should be mitered and field assembled with self tabs
Frames to have inbuilt grooved sealing system and shall be site fitted with PVC gasket as standard
Rolling
Framesshutter
shouldsize be 3.0m
providedx 4.0m with back plate bracket and anchor fasteners for installation on
finished plastered masonry wall opening. Once frame installed should be grouted with GP
(Fosroc) as directed by Engineer In charge.
Door leaf should be 46mm thick fully flush double skin door with or without vision Panel. Doo
leaf shall be manufactured from 0.8mm (22 gauge) minimum thick galvanised steel sheet. Th
CAPENTER / internal construction of the door should be rigid with steel stiffeners/ pads and reinforcemen
23
JOINER The infill material shall be resin bonded honeycomb core. All doors should be factory prepared fo
receiving appropriate hardware and provided with necessary reinforcement for hinges, locks, an
door closers. The edges should be interlocked with a bending radius of 1.4mm. For pair of door
integrated astragals has to be provided on the meeting stile for both active and inactive lea
Vision
Door sizePanel wherever
- 1.2m x 2.2m applicable
- Single Leaf should withbevision
size ofpanel
300x450mm
300mm x.The 450mm,glassand
should be 5mm
hardware set clea
toughened glass. All doors and frames shall be finished with polyurethane aliphatic grade powde
coating minimum 50 microns of approved colour. The door leaf and frame shall have passe
minimum 500 hours of salt spray test.
Rate should include supply and installation of door and hardware as a complete assembly a
Door
mentionedsize -in1.8m
the doorx 2.2mand-hardware
Double Leaf Vision Panel with vision panel 300mm x 450mm, an
schedule.
hardware set
Refer Hardware set document
Approved Vendor : Shakti
Approved hardware make : DORMA

Door size - 1.2m x 2.2m - Single Leaf (including Panic Bar and excluding Concealed flush bol
dead lock, pull handle) with vision panel 300mm x 450mm, and hardware set
ALUMINIUM VENTILATOR WITH LOUVRED GLASS SLATS
Providing and Fixing in position minimum 55 micron powder coated aluminium ventilator of
approved colour/ shade with 5mm thick float clear/frosted glass slats. The aluminium framing
CARPENTER / shall be of Jindal section by using 101.2 x 44.45 x 1.8mm thick box section / C section with all
24
JOINER accessories including necessary scaffolding, filling the gap in between aluminium frame and
adjacent RCC/Block/Metal work at top, bottom and sides with requisite P.V.C./neoprene
felt/polysulphide sealant/silicone sealant etc., all complete as per architectural drawings & as
directed By Engineer In Charge
size - 1.2m x 0.6m
ALUMINIUM VENTILATOR WITH ALUMINIUM LOUVER
Providing and Fixing in position minimum 55 micron thick powder coated aluminium ventilator with
aluminium louvers of approved make and colour. Pitch shall be less than 100mm with minimum
CARPENTER / 50% free air and the aluminium framing shall be of Jindal section by using 101.2 x 44.45 x 1.8mm
25
JOINER thick box section / C section with all accessories including necessary scaffolding, filling the gap in
between aluminium frame and adjacent RCC/Block/Metal work at top, bottom and sides with
requisite P.V.C./neoprene felt/polysulphide sealant/silicone sealant etc., all complete as per
architectural drawings & as directed By Engineer In Charge
size - 1.2m x 0.6m

ALUMINIUM GLAZED DOOR:


Providing and fixing 55 micron powder coated aluminium work for door with extruded built up
sections of approved make having minimum sheet thickness 2mm conforming to IS:733, IS1285
make of Indal / Jindal with a weight of not less than 1.9 kg/m for main frame and 1.0kg/m for
shutter frame, glazed with 8mm thick toughened glass shutter with frames fixed to the wall with
requisite rawl plugs and screws or with fixing clips, or with expansion hold fasteners including
CARPENTER / necessary filling up of gaps at junctions, at top, bottom and sides with requisite P.V.C./neoprene
26
JOINER felt/polysulphide sealant/silicone sealant etc., all complete with necessary hardware fittings like
double-action floor springs, handles and locks etc., all materials and labour complete as per
architectural drawings. Hardware to include Dorma make mortise door lock (vertical type) as per
IS:2209 and hydraulically regulated Door closer as per IS:3564 including cost of all fixtures,
(minimum 3 hinges per leaf), fasteners etc complete. Shop drawing to be submitted and approval
from Consultant shall be taken before procurement etc complete as per drawing, as directed by
the engineer in charge.

size - 1.2m x 2.2m

size - 0.75m x 2.2m

ALUMINIUM FRAMED FIXED WINDOW WITH SINGLE GLAZING


Providing and fixing with minimum 55 micron powder coated aluminium work for window with
extruded built up sections of approved make having minimum sheet thickness 1.8mm conforming
to IS:733, IS:1285 make of Indal / Jindal with a weight of not less than 1.3 kg/m for main frame
CARPENTER / and 0.7kg/m for shutter frame, hermetically sealed single glazed panels ( 6mm thick glass)
27
JOINER confirming to IS:2553, fixed to frame with aluminium snap beading and neoprene/P.V.C. gaskets/
C.P.brass/ stainless steel screws and fixed to the wall with requisite rawl plugs and screws or with
fixing clips, or with expansion hold fasteners including necessary filling up of gaps at junctions, at
top, bottom and sides with requisite P.V.C./neoprene polysulphide sealant/silicone sealant etc., all
complete as per architectural drawings and the directions of the engineers-in-charge.

Window size - 1.8m x 1.2m


ALUMINIUM PARTITION Providing &
fixing in position 55 micron powder coated Aluminium Partition partly glazed & partly panelled b
using extruded section from High grade alloy sections fabricated by standard manufacturer Jindal
make Aluminium sections consisting of main profile shall be 89.00 x 32.00 x 2.75mm @ 1.905
CARPENTER / Kg/Mtr. Glazing clip 19 x 17.30 x 0.90mm @ 0.124 Kg/Mtr Aluminium sections. Saint-Gobain
28
JOINER make 6mm thick clear toughen glass and novapan Sheet 12mm thick in bottom panel. Including
neoprene rubber lining gasket, filling of silicon sealant wacker brand of natural grade application
shall be done through application gun etc. including Covering of corner column with novapan all
complete as directed by engineer in charge.

EXTERIOR PLASTER
Providing and applying sand faced cement plaster 20 mm thick in double coat to all externa
surfaces at all heights, base coat with C.M 1 : 4, (1 part of cement : 4 parts of river sand) 12 mm
thk and finish coat 8 mm thk. with 1:3 (1 part of cement: 3 parts of river sand) cement morta
including finishing with steel trowel at all levels to correct line, The surface / wall to be plastere
29 PLASTERER shall be free from any dirt, loose material, and grease etc. Rate shall include curing, hacking
staging, scaffolding, making grooves / projection wherever required, damping the surface / wa
before plaster as per specification in two coats etc. complete as specified and as directed b
Engineer in charge (Plaster to be done in two coats). The plaster shall be carried out on jambs
bands, lintel and sill faces top and undersides etc. as directed by the Engineer-in-charge.

INTERIOR PLASTER
Providing Internal Plastering with 15mm thick in cement mortar 1:4 (1 part of cement: 4 parts o
river sand) for walls and all concrete surfaces finished smooth with trowel and float and even a
30 PLASTERER all levels and locations. The Quoted rate to be inclusive of scaffolding, staging, curing, including
providing grooves in plaster where 2 different materials are in line (e.g. R.C.C and brickwork
etc.,) all complete as directed by PMC / Engineer-in-charge

Supplying and fixing of Chicken Mesh (Make: Arpitha Plaster Mesh) made out of Galvanized iro
coils of nominal thickness 0.35mm with hot dip zinc coating of 120gms/sqm (minimum 300mm
31 PLASTERER width at junctions of concrete and brick work prior to plastering etc including tying in position b
using suitable nails / clamps / screws at all levels, etc., complete as directed By Engineer I
Charge.
Prepare surfaces of interior and exterior walls surfaces and apply three coats of cement paint o
32 PAINTING approved quality, make and shade in all floors. All the rates under this head include preparation o
surfaces scaffolding materials ,labours etc. complete

CEILING PAINTING (White wash)


Supply and applying two coats of White Cement on Ceilings for all height including scaffolding
33 PAINTING
preparing surface, cleaning etc complete as directed by Engineer In Charge. (for all heights o
walls & concrete surfaces) Approved vendor : Brila white

34 WATER PROOFING Terrace waterproofing:

Providing and laying waterproofing treatment with a primer coat of cement mixed with a
integral water proofing compound and two coats of polyurethane / acrylic based componen
a WATER PROOFING waterproofing system with neat finish sealing all joints of pipes, corners, edges with epoxy putt
all as required as per specifications, drawings and as directed for all floors and at all levels (mak
Fosroc / Sika or equivalent (Terrace floor)

Providing. Laying, finishing with required slope of M20 grade concrete screed (Average thickness
as per drawings) with 10mm down grade aggregate mixed with square welded wire mesh of
100x100x2.5mm approved as per drawings using Dr. Fixit Pidiproof LW+, including control joints
b WATER PROOFING
25mm deep with panel of size 3m X 4m and filling the panels with sealant, Dr. Fixit Pidiseal PS
41G etc., complete as per the manufacturer's methodology. Top surface shall be finished smooth
on top with cement plaster and laid to slope as per drawings over base concrete.

35 WATER PROOFING
Waterproofing on Toilet area : Toilet water
proofing with polymer modified cementitious coating. Providing and laying the following items fo
toilet water proofing in the sequence as listed below. All material and labour complete in all
respects.

a. Levelling Screed:
Average 30mm thick M15 grade levelling screed concrete with 6mm downgraded aggregat
finished smooth on top and laid to slope as per PHE drawings over base concrete.

b. Cementitious Waterproofing Coating

Minimum 1mm thick two component polymer modified elastomeric cementitious waterproofin
coating of approved make, applied in two coats on the levelling screed concrete as pe
manufacturer's specification and conforming to the following parameters:

(i) minimum adhesion strength of 1 N/mm 2

(ii) minimum tensile strength of 1.8 N/mm 2

NOTE: Rate shall include pipe & cable penetration treatment.

c. Protection Screed

20mm thick M15 grade screed concrete with 6mm downgraded aggregate admixed with integra
liquid waterproofing admix conforming to the following parameters and as per vendo
specification.

(i) minimum specific gravity of 1.05 and adhering to IS 2645 (latest rev) for water impermeability

(ii) minimum dosage of 150 ml per 100 kg of cement


Providing pre-constructional anti-termite treatment and creating a continuous chemical barrier b
using Imidacloprid 30% SC with 2.1ml in 1000ml of water under basement slab, footings and al
round footings, column pits, wall surface along the external perimeter of the building up t
natural ground level trenches, top surface of plinth filling, junction of wall and flooring alon
external perimeter of the building, surroundings of pipes and conduits etc., complete as per I
specification and as per instruction of chemical manufacturer, conduits etc., The treatment sha
be carried out strictly in accordance with IS:6313(Part-2). Plinth area of the building will b
36 MISCELLANEOUS measured and paid for. Rate quoted shall be on plinth area basis.

Note: The above specifications have to be reviewed by the contractor with vendor / applicato
Contractor should proceed only after getting technical approval from vendor / applicator. Being
specialised item, design team is not responsible for any discrepancy / damage. The contracto
shall render the building termite free for 10 years and give a guarantee to this effect on stam
paper as directed by Engineer - in - Charge/ Consultant.

Supply and fixing of MS anchor bolts of various diameters / lengths ANCHOR BOLTS o
property class 4.6 conforming to IS:1367 with machine turned threads (threaded lengt
as mentioned in design drawings), MS washers & nuts, bearing plates in positions a
any level including keeping them in line & level, correct position and alignment etc. a
37 MISCELLANEOUS as specified and adjustment of reinforcement and shuttering including necessar
welding to reinforcement etc. (Steel rounds complying to IS 2062, E 250 A grade ca
also be threaded and used as equivalent)
NOTE: No allowances will be permitted for welding or for rolling margins.

a Upto M20 dia

Providing and Grouting pockets, holes, pipes sleeves of any shape or size, column bases, machin
bases etc. with CONBEXTRA GP2 or equivalent, including shuttering, supply, mixing wit
38 MISCELLANEOUS mechanical means, surface cleaning, backing, wedging, finishing, side forms for exposed surface
with champhering (if any), incl. all materials, labour etc. complete as directed By Engineer I
Charge.

Providing and fixing in position of 20x10mm swellable water bars (Dr. Fixit / SIKA / FOSROC o
39 MISCELLANEOUS equivalent) at all levels grouted with sealants as per manufacturers specifications. Cost to includ
all material, labour, etc.,

Addition of waterproofing admixture compound (of Dr. Fixit / Fosroc or equivalent make) i
40 MISCELLANEOUS concrete dosage as per manufacturer's specification and as directed. Including all cost, materia
labour etc.,
Supplying, aligning, fixing in position at all levels Steel Reinforced Copolymer Polypropylen
Rungs, 20 mm size (round /square), 165 mm wide, 130mm projection from face of the wal
41 MISCELLANEOUS
minimum 130mm embedment length including materials, labour, tools and tackles, packin
pieces, in concrete walls of man holes, tanks, pits as per drawings, complete in all respects.

Providing and fixing in position of structural steel consists of chequered plates of thickness as pe
drawings and supporting frames as per the drawing and as directed including one coat of zin
chromate primer 25micron complete with all labour, materials, tools & tackles, equipment etc
42 MISCELLANEOUS complete as per specifications, drawings and as directed by Engineer-in-charge.

Providing and fixing in position of structural steel consists of MS grating of thickness & depth a
per drawings and supporting frames as per the drawing and as directed including one coat of zin
chromate primer 25micron complete with all labour, materials, tools & tackles, equipment etc
complete as per specifications, drawings and as directed by Engineer-in-charge.
43 MISCELLANEOUS

Applying two coats approved synthetic enamel paint of 25microns each coat over chequere
plates steel complete with all labour, material, tools etc., as per manufacturer specifications an
44 MISCELLANEOUS as directed by Engineer-in-Charge . Make: Berger or Asian

Supplying,, fabricating, erecting and fixing in position Gate of size 5m x 2.4m fabricated from G
pipes of minimum 50NB and chain link fabric of galvanized wire with PVC coating having 3.5mm
inner dia and 4.75mm outer dia, flats, angles, plates, round rods, etc. including fabricated hinges
45 MISCELLANEOUS
bearings, MS aldrops with locking arrangement, etc. including painting, including all labou
material, tools & tackles, equipment, handling, etc. complete as per specifications, drawings an
as directed

CAGE LADDER
Providing, fabricating and fixing in position, grill, railing, steel ladder of M.S ladder with M.S
rounds, squares, flats etc. as described, as per the drawing or as directed. The work shall includ
cutting to required sizes, welding, fixing in position, bending and curving the flat iron stringer at to
to form handles, embedding the bottom of ladders, providing and casting cement concrete at to
and bottom in 1:2:4 (nominal mix) (1 cement: 2 sand: 4 stone aggregate 20mm nominal size).Th
width of the ladder shall be 500 mm in between, the steel angle side member of 50x50x9mm i
46 welded to fixing plate of 75x150x9mm thk. Hot dipped galvanized flat bar bended bracket shoul
be welded to member and fixing plate with 2 nos M12x60 anchor bolts and 2 nos super fix. Th
20mm dia hot dipped galvanized ladders welded to 50x50x9mm side member 300mm apart c/c
The 40x9mm thk galvanized steel flat bar vertical cage runners welded to the cage guard ring i
which 50x9mm thk hot dipped galvanized steel flat bar cage guard ring welded to side member. A
the work shall receive one coat of red oxide zinc chromate primer and two coats of syntheti
enamel paint of approved make, quality, colour and shade as directed all materials and labou
complete in all respects
STAINLESS STEEL HANDRAIL
Providing and fixing in position SS pipe hand railing of Jindal or equivalent make, for staircase t
detail with 50mm dia with sheet thickness 1.65mm pipe with for top and vertical 1M height ,
with 40mm x 6mm lugs at approximately 0.90m spacings and 2 nos of 20 mm with sheet
47 MISCELLANEOUS
thickness 2.0mm dia with sheet thickness 1.65mm horizontal pipes placed between the
verticals, and 100 x5mm thk toe plate The verticals are embedded in RCC member complete in
all floors. Items shall be measured as total length of completed pipe railing. (not individual pipe
lengths).Supply of all consumables shall be under contractor's cope.

Supplying, providing and fixing of Galvanised - PVC coated - coloured in green chain link fencin
of mesh size 50mm x 50mm x 10G to MS posts using Galvanised binding wire with PVC coatin
48 MISCELLANEOUS having 3.5mm inner diameter & 4.75mm outer diameter, including providing 10G, GI tension wir
horizontally at top and bottom and middle with necessary U-clips, including cost of all materials
labour required for the work, etc. complete as directed by Engineer In charge.

Supplying, fabricating and erecting required tubular posts 3.00 mts height @ 2.4m C/C with cros
support at every 4th pole & at every corners, height of Chain link fencing post height 2.40m
49 MISCELLANEOUS above Toe wall including painting to angels with one coat of red oxide zinc chromate primer an
two coats of synthetic enamel paint of green colour etc complete as directed by Engineer I
Charge. etc.

Supplying and laying of 200thk solid block work toe Toe wall / Kerb wall which is of Min
compressive strength of 5 N/sq.m of minimum 450mm deep (min. 300mm below ground leve
50 MISCELLANEOUS and min. 150mm above ground level) to support chain link fence above, marked as per drawing
with necessary plastering, painting, complete in all respects and as directed by Engineer-In
Charge

Supplying and laying 150mm thick layer of granite / basalt / trap jelly of 40mm size over the are
51 MISCELLANEOUS marked as per drawing including soil sterilization, surface preparation and compaction to th
required slope / grade, complete in all respects

Providing and fixing SFRC precast man hole / pull pit cover (with or without perforations) wit
52 MISCELLANEOUS frame for the required size and thickness proper in position as per the drawing, includin
transport channelling.

ROAD BOQ

EARTHWORK EXCAVATION - Excavation for road way in soil by mechanical means includin
cutting and pushing the earth to site of embankment upto a distance including trimming bottom
53 EXCAVATION and side slopes in accordance with requirements of lines, grades and cross sections complete a
per specifications. MORTH Specification No. 301
(2012-13 SR Page No150, Item No.19.11) dumping in Contractor Scope as specified by EIC
RIGID PAVEMENT

Construction of dry lean cement concrete Sub- base over a prepared sub-grade with coarse an
fine aggregate conforming to IS: 383, the size of coarse aggregate not exceeding 25 mm
aggregate cement ratio not to exceed 15:1, aggregate gradation after blending to be as per tabl
600-1, cement content not to be less than 150 kg/ cum, optimum moisture content to b
54 CONCRETOR determined during trial length construction, concrete strength not to be less than 10 Mpa at
days, mixed in a batching plant, transported to site, laid with a paver with electronic senso
compacting with 8-10 tonnes vibratory roller, finishing and curing and all complete as pe
Technical specifications and as directed by the Engineer-in-charge.

Concrete Pavement: Construction of continuously Reinforced concrete pavement over


prepared sub base with OPC cement design mix M30, with 25mm and down size graded granit
metal coarse aggregate at 0.39cum and fine aggregate @0.46cum with super plasticizer at 3ltr
conforming to IS 9103-1999 reaffirmed 2008, coarse and fine aggregate conforming to IS 383
55 CONCRETOR
mixed in a batch rig and mixing plant as per approved mix design, transported to site, laid with
fixed form or slip form paver, spread, compacted and finished in a continuous operation includin
separation membrane, admixtures as approved, curing compound, finishing to lines and grades a
per drawing complete as per specifications.

Providing and Fixing in Position separation membrane of 200 microns thick above DLC as per th
56 PAVIOUR Directions of the Engineer in Charge

Transverse Reinforcement: 8mm dia bar with c/c spacing of 260mm provided for the total roa
area placed transverse to the road.
57 FITTER
Longitudinal Reinforcement: 10mm dia bar with c/c spacing of 100mm provided for the total roa
area placed longitudinally to the road (as per drawing).

Expansion joint: 25 mm dia 500mm long dowel bars are provided at 300 mm spacing for rigi
pavement(if the length of the road is more than 50m ,expansion joint with dowel bar should b
58 PAVIOUR
provided for every 50m interval along the width of the road),which should satisfy the IRC 58-201
& IRC 15 -2002 provisions.)

59 PAVIOUR Supply and erection of 20mm thick Sealing compound for expansion joint.
TOTAL in INR (Exclusive of Taxes)

VAT sales Tax in INR

Service Tax in INR

TOTAL in INR (Inclusive of Taxes)

NOTE: a. This BOQ is to be read in conjunction with Technical specifications (Electrical, Civil, Structural a

b. If any items are missed in this BOQ, the same shall be identified and added.

c. If any items mentioned in above BOQ are not required for this scope, The same need not be co

d. All cut-outs in the floor slabs shall be part of contractor's scope. All cut-out shall be finished edg
APOLLO TYRES LIMITED (ATL) AP GREEN FIELD PROJECT

Rev. No.: Rev. Date:

URAL, ARCHITECTURAL AND ROAD BILL OF QUANTITIES FOR 132 kV SWITCHYARD

Unit Rate in
Description Unit Qty INR

s shall include all provision of slope cutting for safety measures,


nd rain water to keep the excavation dry and disposing the surplus earth
levelling and consolidation of 300mm layers to inside the premises
y as per requirement in drawing). Also shoring / stepped cutting shall be
beyond 4m deep. Cost should include all material, labour, compaction,
l.

all types of soils including weathered/soft disintegrated rock, Murram,


be removed by mechanical means (Hydraulic
ual and excluding rock which cannot be removed other than by blasting.
s shoring wherever required, bailing out of water, levelling, dressing of
tom and strutting if necessary, including cutting and removal of stray
includes all lead and lifts including segregating the excavated soil and
esignated locations within site premises and reused as back fill (Upto 4m
ea with an additional clearance of 600mm all-round from RCC face or
whichever is smaller shall be paid for. For depth beyond 4m, min. of actual
ear space all-round RC concrete face shall be paid for.). The back filling
earth (which the maximum particle size shall not exceed 75mm) should
to achieve compacted thickness of 200 to 250mm using Mini Vibratory
mpactor for foundations, pits, trenches etc., and for plinths and yards
er with 8-10 tonne mechanical Vibro roller (to achieve required gradient
ng by 1.5MT plate compactor/ hand rammer (where ever area is not
by Mechanical Vibro roller),to achieve 95% Procter's density. Samples
yer at 30m centres for checking field dry density. The Contractor shall
ure content and Modified Proctor's density for the different type/source of
credited laboratory and approved by Engineer-in-Charge.

Cu.m 300.00

depth Cu.m
excavated earth (which the maximum particle size shall not exceed
he site premises should be consolidated in layers to achieve compacted
m using Mini Vibratory rollers or 1.5MT plate compactor for foundations,
r plinths and yards rolling each deposited layer with 8-10 tonne
o achieve required gradient and camber ) and Ramming by 1.5MT plate
(where ever area is not available for compaction by Mechanical Vibro Cu.m 200.00
octer's density. Samples shall be taken at every layer at 30m centres for
. The Contractor shall check the Optimum moisture content and Modified
ifferent type/source of soil along with an external independent agency
er-in-Charge. Rate should include all equipment, labour, lead, lift etc.,

all types of soils including weathered/soft disintegrated rock, Murram,


val of black cotton soil, contaminated soil, medium dense clay, medium
andy clay, boulders unused for filling etc., which can be removed by
aulic Excavator/Proclainer)/manual. Earth works shall includes shoring,
ing, dressing of sides and ramming of bottom and strutting if necessary,
oval of stray boulder. Also cost shall includes all lead, lifts levelling and
esignated locations within site premises. (The foundation area with an
00mm at sides or actual measured at site whichever is smaller shall be

Cu.m

depth Cu.m

crusher run 6mm down sized aggregate mixed in equal proportion of


to suitable wherever required including, transportation, spreading,
pacting by 1.5MT plate compactor / hand rammer etc. complete as Cu.m 35.00
by the engineer in charge. (Only compacted volume shall be measured
ides of trenches.
of 43/53 grade only. No fly-ash/Pozzolana to be used in mix design.
ed. Crusher dust not allowed.
by 4.75 mm sieve before using in the concrete.
BIRLA, CORAMANDAL, DALMIA, RAMCO, ULTRATECH, Zuari shall be

xtures shall be included. (Only Admixtures of Fosroc/BASF/SIKA to be

m placer wherever required shall be included.


considering the quantity of cement to be used as per practical condition
de of concrete, which should not be less than the minimum Quantity
ent will be considered for using additional cement in this regard.
carried out based on latest relevant IS code by approved third party
client or Engineer-in-Charge) with contractor's own risk & cost and prior
rom engineer in charge and consultant before start-up the work, well in
ay in starting of works.
ifically mentioned rates quoted for all concrete items of work shall be
rmwork and reinforcement which shall be measured and paid for

ncrete is used this should be designed and laid as per the detailed

nderstood that whenever the grade of concrete is specified it shall then


lity to ensure that minimum crushing strength stipulated for the
ete is obtained.
eady Mix Concrete(RMC) unless otherwise mentioned.
shall be carried out for frequency of sampling as per IS code and shall be

nt for various of grades of concrete shall be as below:

20 kg

80 kg

00 kg

00 kg

20 kg

40 kg
aying Plain Cement Concrete of Grade M10 with Ordinary Portland
d downgraded coarse aggregate for any shape and thickness below
inth beams, Grade Slab, machine foundations, trenches, pits & sumps
the excavation pit, shuttering, pumping & placing of concrete, tamping, Cu.m 80.00
g etc., with all material and labour complete in all respects at all levels,
fications and as directed by the Engineer-in-Charge. Source of concrete
Concrete.

aying of Plain Cement Concrete of Grade M15 with Ordinary Portland


downgraded coarse aggregate for any thickness for plinth protection,
n, levelling and compacting of the surface, formwork with all material,
Cu.m
complete in all respects, with smooth finish, grid marking of 450mm x
curing etc as per drawings, specifications and as directed by the

ng, vibrating and curing, Reinforced Cement Concrete of grade as


m and down graded machine crushed stone aggregates, using ordinary
e 43, river sand complete as directed and as specified for all sizes and
be made with Water Cement ratio shall not be more than 0.45 and
om Fosroc / BASF / Sika of approved make in recommended proportion
erate, retard setting of concrete, improve workability without impairing
ibrating and necessary finishing etc., complete all as directed at all levels
ete. Including all leads and lifts, scaffolding, compacting with mechanical
ng, curing and rendering the concrete surfaces, setting out using Total
lignment for the same, if required etc.,
proval from Client / Consultant before commencement of work etc., as
complete as directed By Engineer In Charge.
gn mix) - All RCC works at all levels - Raft, Foundations, Pedestal,
op including encasement, retaining walls, RC Walls, Plinth beams,
e foundations, piers, abutments, tanks / sump pits, posts and strut etc of Cu.m 775.00

n mix) - All RCC works - Trenches and Pits of all sizes and shapes at all
Cu.m

ghtening,
shall be of cutting, bending
Grade Fe500 D TMTfabricating
conformingandtoplacing
IS 1786inonly,position Thermo-
MT)
e of bars of Femake
approved 500 Dlike
of SAIL,
different
TATA,diameters, cutting,
TISCO, JINDAL andbending to required
RINL-VIZAG only.
gISfabricating, handling and transport complete for all RCC works with GI
Code frequency.
with double stranded for reinforcement work as per approved designs
VC / readymade concrete cover blocks of same concrete grade.
all be measured only in lengths of bars as actually placed in position on
bricating,
allowancehoisting,
being made erecting
in the and
weightpainting as margin.
for rolling per specifications and
Quantity of steel
wings (which are to be prepared by Contractor and got
and with Authorised laps and splices, chairs of any shape & profile, approved from MT 65.00
&, profile
transporting
only willtobesite & erecting
measured of Structural steel (Other than
and paid.
ould be prepared by contractor and gotthe
oved make (TATA, TISCO, JSW, SAIL) of following
approved bygrade
PMC /ofEngineer-in-
steel using
sections
re cutting,with necessary baseplates, stiffeners, gusset plates etc., at all
placing.
nnections.
se The quoted
of measurement shall rate
meanshall
ONEbe inclusive
METRIC TONNEof alli.e.materials,
1000 kg labours,
ates shall be submitted for frequency of samples as per and
packing pieces, aligning and levelling including providing fixingTest
IS Code. 4.6
s, washers, straightening, bending, cutting,
ed agencies (by consultant) shall be submitted. drilling, grinding, machining,
transport to site. It should include one coat of zinc chromate primer
all labour, materials, tools & tackles, equipment etc. complete as per
nd as directed by Engineer-in-charge.
any steel sections of 250 MPa grade of steel, like Steel beams, rafters,
peofracks, platforms shall
etc. at all heights. MT 32.00
se measurement mean ONE METRIC TONNE i.e. 1000 kg

any steel sections


bricating, hoisting,of erecting
250 MPa and gradepainting
of steel, as
likeper
Tubular / Pipe sections
specifications and
racings, lintels,are
etc.toatbeallprepared
levels andbyheights MT
wings (which Contractor and got approved from
transporting to site & erecting of Galvanized structural steel (for
oved make (TATA, TISCO, JSW, SAIL) of the following grade of steel using
sections with necessary baseplates, stiffeners, gusset plates etc., at all
nnections. The quoted rate shall be inclusive of all materials, labours,
packing pieces, aligning and levelling including providing and fixing 4.6
s, washers, straightening, bending, cutting, drilling, grinding, machining,
transport to site. The above work shall also includes cleaning, Grinding
g burr from the structural members etc. complete.
steel sections of 250 MPa grade of steel, like Steel beams, rafters, Stair
se of platforms
cks, measurement etc. atshall mean ONE METRIC TONNE i.e. 1000 kg
all heights. MT 5.00
moving well supported, leak proof formwork to required size, level,
ers, curves, wedges, cut-outs as per drawings and specification including
ing platforms, for concreting etc. complete at all heights and levels. All
bular steel structure with adequate bracing as approved. It shall be made
adequate number of ties and braces, Screw jacks or hard board wedges
provided to make up any settlement in the form work either before or
ncrete.
rolled Forms shall be so
steel sections of constructed
250 MPa grade as toof
besteel,
removable in sections
like Tubular in
/ Pipe
thout damaging
IS1161, bracings, the surface
lintels, ofall
etc. at concrete. Staging
levels and should be as designed
heights MT
pieces as approved by Engineer-in-Charge / EC to ensure proper slopes,
beams etc. and as per levels as shown in drawings. Shuttering used shall
hick water proof ply with sufficient stiffness to avoid excessive deflection
butted to avoid leakage of slurry. If required, heavy duty self adhesive
d by Engineer-in-Charge shall be provided in the joints. Provisions for
s, anchor bolts or any other fixture shall be included.
n of approved quality shuttering oils (Waste Oil will not be permitted)

all be considered
d and for allground
upto Finished Raft, Foundation,
floor level Curing Trench
(i.e. Sub walls, Pit
Structure) walls,
- Raft,
CC walls,up
olumns stairs, ramps,retaining
to plinth, tanks, RCC pedestals,
walls, slabs,
RC Walls, chajjas etc.
trenches, Plinth beams, Sq.m 500.00
uld give
l sizes andsmooth
shapesfinish to concrete Square,
like (Rectangular, surface.etc)
Finish
at allshould
levels be
andsuch that
heights

paid for the


ground area
floor of shuttering
level coming in contact
(i.e. Superstructure) with
all Levels concrete
- for onlyLintels,
Columns,
should not go through the concrete member
aircase Waist slab, steps, Sill concrete, Coping works, Floor beams, Slabs, Sq.m 1900.00
/ndcantering / propping
shapes like for special
(Rectangular, Squarestructures shall
etc) and at be done
all levels andby contractor
heights.
m Engineer-in-charge.

moving well supported, leak proof formwork for Machine foundation


uired size, level and as per drawings and mentioned below, keeping the
concreting with proper line and level as per drawing and removal of the
riod etc. complete as directed by Engineer in charge.

rea with maximum deep of 400mm Nos

ocket Area with maximum deep of 400mm Nos

sign mix quality concrete of M30 grade mixed with minimum cement
uding laying in panels of size as per drawings or as directed by Engineer-
of 0.45 and slump not exceeding 90mm. Cost excludes finishing and
p shall be paid separately. Also as directed by Engineer-in-Charge/as per Cu.m
res / Reinforcement shall be added in concrete and the same shall be

d not be more than 30-degree during concreting.


ng with M20 grade concrete screed (Average thickness as per drawings)
gregate. Top surface shall be finished smooth and laid to slope as per Cu.m
rete. Cost shall includes all material, labours etc.,

ion Hydrocel XL board (FOSROC make) around columns and openings


crete and sealing the top 12 mm depth of the joints with Polyurethane Rm
y FOSROC or approved equivalent

ant for 12 wide X 12 mm depth on top of Hydrocel XL board with


Rm

200 micron thick LDPE sheet in one layer with staggered joints over
elow the RCC slab) with overlap of 150mm, fixed using 100mm wide self Sqm
G
skid ceramic tiles of approved size, design, Pattern and Shade, to proper
cement mortar 1:4 bedding of 30mm thickness with neat cement slurry,
ent of matching shade complete. The item shall include cleaning, making
Architect/Engineer in charge , all accessories, tools , labour, etc. No extra Sqm 25
wastage
ed ceramic duetiles
to material
in dado pattern.
of approvedPleasesize,
notedesign,
payment will be
Pattern , to in proper
SQM of,
rmplete
12 mmasthick directed
bed of Bycement
Engineer In Charge.
Mortar 1:3 (1 cement : 3 coarse sand) and
t- slurry
size 300 @ x3.3kg
300 mm per x8.5mm
sqm,andthick Kajaria/Somany
jointing (Basic price
with white cement 45/Sqft)
including PVC
ch with tile colour, pointing in white cement mixed with pigment of
te curing, cleaning etc. complete., The item shall include cleaning, Sqm 60
roval of Architect/Engineer in charge all accessories, tools , labour, etc.
ng 200mm
towards thick precast
wastage due tosolid concrete
material block
pattern. masonry
Please note(including
payment will quoin,
be in
)y.of
TTER 400MMX200MMX200MM size
etc complete as directed By Engineer In Charge having minimum average
5.0ingxNShutter
00 /mm2
300 mmthefor blocks
the
x8.5mm dockshall
thick be ofshall
doors approved
Kajaria/Somany make
be of(Basic conforming
motorized
price to steel
galvanized
45/Sq.ft)
,C.M. (1:4)rolling
vertical mix with
type,12mm thickRolling
duty G.I. joints in super structure
Shutters with 1mmabove x 75mm Plinth
wide Cum 300
nary
ng 100mm Portland
M.S.Guide thickCement
precast
75mm , at
by solidall
2.64mmlevels
concrete including
thick block
Minimum scaffolding,
masonry curing
(including
thickness etc.,
quoin,
of galvanized
ng,
m ) of specifications
and400MMX100MMX200MM
shall confirm etc.,
to all complete
IS6248.Each size as directed
having
slat by
minimum
section Engineer-in-Charge
shall beaverage
continuous single
ent)
5.0 N /mm2
Box the blocks
type side guidesshallshallbebeof provided
approved for make conforming
higher to
wind resistance.
dC.M.
cover(1:4) shallmix
he12mm
providedthick to joints
coverin super
the shaftstructure
and bracket above Plinth level
assembly. All the
20 grade
wder coatedof thickness
of approved100 mm at every
colour. 1.2 m
Rolling heightshall
shutter of blockwork
be designed with to
2 Sqm 65
ote
to and: the cost of shuttering
including 183 kmph.and steel reinforcement
Additional accessories likeshalldock
be inclusive).
bracing shall
Portland
he rollingCement
shutter ,from
at all cyclones
levels including
therebyscaffolding,
increasingcuring
the windetc.,resistance.
URPOSE)
ng, specifications etc., alldrive
complete as directed bycoupled
Engineer-in-Charge
ollowprovided with direct electrical motors with reduction
ent) metalItdoor
operation. shall
at all levels from ISO 9001-2000 certified manufacturer.
also be provided with limit switches for operation
l doors with or without vision panel. Pressed galvanised steel Single
ers sizes
ed shall also be provided
of approved make withShakti
mechanized
Hormann manualwhichhand crank operation
consists of frame,
peration as standard etc. complete
detailed below and conforming to IS 277. as directed by engineer in charge.
oved
ngle by rebateEC. profile of size 125 x 60mm made out of 1.20mm thick
8 gauge). Frames should be mitered and field assembled with self tabs.
ooved sealing system and shall be site fitted with PVC gasket as standard.
x 4.0m
ded with back plate bracket and anchor fasteners for installation on a Sq.m 12
nry wall opening. Once frame installed should be grouted with GP2
ngineer In charge.
mm thick fully flush double skin door with or without vision Panel. Door
ed from 0.8mm (22 gauge) minimum thick galvanised steel sheet. The
the door should be rigid with steel stiffeners/ pads and reinforcement.
e resin bonded honeycomb core. All doors should be factory prepared for
dware and provided with necessary reinforcement for hinges, locks, and
should be interlocked with a bending radius of 1.4mm. For pair of doors
to be provided on the meeting stile for both active and inactive leaf.
pplicable
- Single Leaf should withbevision
size ofpanel
300x450mm
300mm x.The 450mm,glassand
should be 5mm
hardware set clear Sq.m 5.28
s and frames shall be finished with polyurethane aliphatic grade powder
crons of approved colour. The door leaf and frame shall have passed
alt spray test.
ply and installation of door and hardware as a complete assembly as
m
nd-hardware
Double Leaf Vision Panel with vision panel 300mm x 450mm, and
schedule. Sq.m
ument

e : DORMA

m - Single Leaf (including Panic Bar and excluding Concealed flush bolt,
Sq.m 10.56
ith vision panel 300mm x 450mm, and hardware set
OR WITH LOUVRED GLASS SLATS
osition minimum 55 micron powder coated aluminium ventilator of
with 5mm thick float clear/frosted glass slats. The aluminium framing
by using 101.2 x 44.45 x 1.8mm thick box section / C section with all
cessary scaffolding, filling the gap in between aluminium frame and
al work at top, bottom and sides with requisite P.V.C./neoprene
silicone sealant etc., all complete as per architectural drawings & as
Charge
Sq.m 0.72
OR WITH ALUMINIUM LOUVER
osition minimum 55 micron thick powder coated aluminium ventilator with
roved make and colour. Pitch shall be less than 100mm with minimum
minium framing shall be of Jindal section by using 101.2 x 44.45 x 1.8mm
ion with all accessories including necessary scaffolding, filling the gap in
e and adjacent RCC/Block/Metal work at top, bottom and sides with
felt/polysulphide sealant/silicone sealant etc., all complete as per
as directed By Engineer In Charge
Sq.m 14.04

OOR:
icron powder coated aluminium work for door with extruded built up
ke having minimum sheet thickness 2mm conforming to IS:733, IS1285
h a weight of not less than 1.9 kg/m for main frame and 1.0kg/m for
h 8mm thick toughened glass shutter with frames fixed to the wall with
crews or with fixing clips, or with expansion hold fasteners including
ps at junctions, at top, bottom and sides with requisite P.V.C./neoprene
silicone sealant etc., all complete with necessary hardware fittings like
s, handles and locks etc., all materials and labour complete as per
ardware to include Dorma make mortise door lock (vertical type) as per
regulated Door closer as per IS:3564 including cost of all fixtures,
af), fasteners etc complete. Shop drawing to be submitted and approval
taken before procurement etc complete as per drawing, as directed by

Sq.m 19.44

Sq.m

XED WINDOW WITH SINGLE GLAZING


minimum 55 micron powder coated aluminium work for window with
s of approved make having minimum sheet thickness 1.8mm conforming
of Indal / Jindal with a weight of not less than 1.3 kg/m for main frame
ame, hermetically sealed single glazed panels ( 6mm thick glass)
ed to frame with aluminium snap beading and neoprene/P.V.C. gaskets/
screws and fixed to the wall with requisite rawl plugs and screws or with
sion hold fasteners including necessary filling up of gaps at junctions, at
h requisite P.V.C./neoprene polysulphide sealant/silicone sealant etc., all
ural drawings and the directions of the engineers-in-charge.

m Sq.m
Providing &
on powder coated Aluminium Partition partly glazed & partly panelled by
om High grade alloy sections fabricated by standard manufacturer Jindal
s consisting of main profile shall be 89.00 x 32.00 x 2.75mm @ 1.905
17.30 x 0.90mm @ 0.124 Kg/Mtr Aluminium sections. Saint-Gobain Sq.m
ughen glass and novapan Sheet 12mm thick in bottom panel. Including
asket, filling of silicon sealant wacker brand of natural grade application
plication gun etc. including Covering of corner column with novapan all
engineer in charge.

sand faced cement plaster 20 mm thick in double coat to all external


se coat with C.M 1 : 4, (1 part of cement : 4 parts of river sand) 12 mm
thk. with 1:3 (1 part of cement: 3 parts of river sand) cement mortar
teel trowel at all levels to correct line, The surface / wall to be plastered
dirt, loose material, and grease etc. Rate shall include curing, hacking, Sq.m 1600
ng grooves / projection wherever required, damping the surface / wall
ecification in two coats etc. complete as specified and as directed by
ter to be done in two coats). The plaster shall be carried out on jambs,
top and undersides etc. as directed by the Engineer-in-charge.

ing with 15mm thick in cement mortar 1:4 (1 part of cement: 4 parts of
all concrete surfaces finished smooth with trowel and float and even at
he Quoted rate to be inclusive of scaffolding, staging, curing, including Sq.m 2100
ter where 2 different materials are in line (e.g. R.C.C and brickwork,
cted by PMC / Engineer-in-charge

Chicken Mesh (Make: Arpitha Plaster Mesh) made out of Galvanized iron
s 0.35mm with hot dip zinc coating of 120gms/sqm (minimum 300mm)
crete and brick work prior to plastering etc including tying in position by Sq.m
mps / screws at all levels, etc., complete as directed By Engineer In
ior and exterior walls surfaces and apply three coats of cement paint of
nd shade in all floors. All the rates under this head include preparation of Sq.m 3000
rials ,labours etc. complete

te wash)
o coats of White Cement on Ceilings for all height including scaffolding,
Sq.m 700
ning etc complete as directed by Engineer In Charge. (for all heights of
) Approved vendor : Brila white

terproofing treatment with a primer coat of cement mixed with an


compound and two coats of polyurethane / acrylic based component
th neat finish sealing all joints of pipes, corners, edges with epoxy putty Sq.m 650.00
cifications, drawings and as directed for all floors and at all levels (make
nt (Terrace floor)

ng with required slope of M20 grade concrete screed (Average thickness


mm down grade aggregate mixed with square welded wire mesh of
d as per drawings using Dr. Fixit Pidiproof LW+, including control joints Cu.m
size 3m X 4m and filling the panels with sealant, Dr. Fixit Pidiseal PS
r the manufacturer's methodology. Top surface shall be finished smooth
er and laid to slope as per drawings over base concrete.

Sq m
area : Toilet water
odified cementitious coating. Providing and laying the following items for
he sequence as listed below. All material and labour complete in all
15 grade levelling screed concrete with 6mm downgraded aggregate
nd laid to slope as per PHE drawings over base concrete.

roofing Coating

o component polymer modified elastomeric cementitious waterproofing


ake, applied in two coats on the levelling screed concrete as per
tion and conforming to the following parameters:

ength of 1 N/mm 2

ngth of 1.8 N/mm 2

pipe & cable penetration treatment.

creed concrete with 6mm downgraded aggregate admixed with integral


dmix conforming to the following parameters and as per vendor

vity of 1.05 and adhering to IS 2645 (latest rev) for water impermeability

50 ml per 100 kg of cement


nal anti-termite treatment and creating a continuous chemical barrier by
C with 2.1ml in 1000ml of water under basement slab, footings and all-
pits, wall surface along the external perimeter of the building up to
nches, top surface of plinth filling, junction of wall and flooring along
e building, surroundings of pipes and conduits etc., complete as per IS
nstruction of chemical manufacturer, conduits etc., The treatment shall
n accordance with IS:6313(Part-2). Plinth area of the building will be
ate quoted shall be on plinth area basis. Sq.m 650.00

ations have to be reviewed by the contractor with vendor / applicator.


ed only after getting technical approval from vendor / applicator. Being a
team is not responsible for any discrepancy / damage. The contractor
termite free for 10 years and give a guarantee to this effect on stamp
ineer - in - Charge/ Consultant.

anchor bolts of various diameters / lengths ANCHOR BOLTS of


orming to IS:1367 with machine turned threads (threaded length
gn drawings), MS washers & nuts, bearing plates in positions at
eping them in line & level, correct position and alignment etc. all
ustment of reinforcement and shuttering including necessary
ent etc. (Steel rounds complying to IS 2062, E 250 A grade can
used as equivalent)
will be permitted for welding or for rolling margins.

Nos

ockets, holes, pipes sleeves of any shape or size, column bases, machine
EXTRA GP2 or equivalent, including shuttering, supply, mixing with
ce cleaning, backing, wedging, finishing, side forms for exposed surfaces Cu.m
y), incl. all materials, labour etc. complete as directed By Engineer In

osition of 20x10mm swellable water bars (Dr. Fixit / SIKA / FOSROC or


routed with sealants as per manufacturers specifications. Cost to include Rm

ng admixture compound (of Dr. Fixit / Fosroc or equivalent make) in


manufacturer's specification and as directed. Including all cost, material, Cu.m
g in position at all levels Steel Reinforced Copolymer Polypropylene
und /square), 165 mm wide, 130mm projection from face of the wall, Nos
edment length including materials, labour, tools and tackles, packing
of man holes, tanks, pits as per drawings, complete in all respects.

osition of structural steel consists of chequered plates of thickness as per


frames as per the drawing and as directed including one coat of zinc
on complete with all labour, materials, tools & tackles, equipment etc.
tions, drawings and as directed by Engineer-in-charge. MT

osition of structural steel consists of MS grating of thickness & depth as


ting frames as per the drawing and as directed including one coat of zinc
on complete with all labour, materials, tools & tackles, equipment etc.
tions, drawings and as directed by Engineer-in-charge.
MT

roved synthetic enamel paint of 25microns each coat over chequered


h all labour, material, tools etc., as per manufacturer specifications and
n-Charge . Make: Berger or Asian Sq.m

recting and fixing in position Gate of size 5m x 2.4m fabricated from GI


and chain link fabric of galvanized wire with PVC coating having 3.5mm
ter dia, flats, angles, plates, round rods, etc. including fabricated hinges, No.
with locking arrangement, etc. including painting, including all labour,
equipment, handling, etc. complete as per specifications, drawings and

d fixing in position, grill, railing, steel ladder of M.S ladder with M.S.
. as described, as per the drawing or as directed. The work shall include
welding, fixing in position, bending and curving the flat iron stringer at top
ing the bottom of ladders, providing and casting cement concrete at top
inal mix) (1 cement: 2 sand: 4 stone aggregate 20mm nominal size).The
be 500 mm in between, the steel angle side member of 50x50x9mm is
75x150x9mm thk. Hot dipped galvanized flat bar bended bracket should
nd fixing plate with 2 nos M12x60 anchor bolts and 2 nos super fix. The
lvanized ladders welded to 50x50x9mm side member 300mm apart c/c.
ized steel flat bar vertical cage runners welded to the cage guard ring in
pped galvanized steel flat bar cage guard ring welded to side member. All
ne coat of red oxide zinc chromate primer and two coats of synthetic
d make, quality, colour and shade as directed all materials and labour
DRAIL
sition SS pipe hand railing of Jindal or equivalent make, for staircase to
sheet thickness 1.65mm pipe with for top and vertical 1M height ,
approximately 0.90m spacings and 2 nos of 20 mm with sheet Rm 100
h sheet thickness 1.65mm horizontal pipes placed between the
thk toe plate The verticals are embedded in RCC member complete in
measured as total length of completed pipe railing. (not individual pipe
sumables shall be under contractor's cope.

fixing of Galvanised - PVC coated - coloured in green chain link fencing


mm x 10G to MS posts using Galvanised binding wire with PVC coating
meter & 4.75mm outer diameter, including providing 10G, GI tension wire Sq.m
ottom and middle with necessary U-clips, including cost of all materials,
ork, etc. complete as directed by Engineer In charge.

d erecting required tubular posts 3.00 mts height @ 2.4m C/C with cross
le & at every corners, height of Chain link fencing post height 2.40m
painting to angels with one coat of red oxide zinc chromate primer and MT
namel paint of green colour etc complete as directed by Engineer In

200thk solid block work toe Toe wall / Kerb wall which is of Min.
5 N/sq.m of minimum 450mm deep (min. 300mm below ground level
ground level) to support chain link fence above, marked as per drawing, Rm
g, painting, complete in all respects and as directed by Engineer-In-

mm thick layer of granite / basalt / trap jelly of 40mm size over the area
including soil sterilization, surface preparation and compaction to the Cu.m
omplete in all respects

C precast man hole / pull pit cover (with or without perforations) with
size and thickness proper in position as per the drawing, including No's

ROAD BOQ

TION - Excavation for road way in soil by mechanical means including


earth to site of embankment upto a distance including trimming bottom
dance with requirements of lines, grades and cross sections complete as Cu.m
H Specification No. 301
Item No.19.11) dumping in Contractor Scope as specified by EIC
cement concrete Sub- base over a prepared sub-grade with coarse and
ng to IS: 383, the size of coarse aggregate not exceeding 25 mm,
ot to exceed 15:1, aggregate gradation after blending to be as per table
not to be less than 150 kg/ cum, optimum moisture content to be
ength construction, concrete strength not to be less than 10 Mpa at 7 Cu.m
ng plant, transported to site, laid with a paver with electronic sensor,
onnes vibratory roller, finishing and curing and all complete as per
nd as directed by the Engineer-in-charge.

Construction of continuously Reinforced concrete pavement over a


OPC cement design mix M30, with 25mm and down size graded granite
at 0.39cum and fine aggregate @0.46cum with super plasticizer at 3ltrs
999 reaffirmed 2008, coarse and fine aggregate conforming to IS 383,
Cu.m
mixing plant as per approved mix design, transported to site, laid with a
aver, spread, compacted and finished in a continuous operation including
dmixtures as approved, curing compound, finishing to lines and grades as
per specifications.

osition separation membrane of 200 microns thick above DLC as per the
r in Charge Sq.m

t: 8mm dia bar with c/c spacing of 260mm provided for the total road
the road.
MT
ent: 10mm dia bar with c/c spacing of 100mm provided for the total road
y to the road (as per drawing).

m dia 500mm long dowel bars are provided at 300 mm spacing for rigid
f the road is more than 50m ,expansion joint with dowel bar should be
MT
nterval along the width of the road),which should satisfy the IRC 58-2015
s.)

0mm thick Sealing compound for expansion joint. Rm


f Taxes)

Taxes)

in conjunction with Technical specifications (Electrical, Civil, Structural and Architectural) and all tender drawings

d in this BOQ, the same shall be identified and added.

in above BOQ are not required for this scope, The same need not be considered.

slabs shall be part of contractor's scope. All cut-out shall be finished edges with MS edge plates of 3mm thk (min.)
23-Aug-2018

Amount in
INR

You might also like