You are on page 1of 1

Foam Compound requirement for fighting Class A storage Tank fire OISD -116

NB: Enter only the diameter of tank

CONE ROOF FLOATING ROOF FLOATING ROOF


TANK TANK TANK PROTECTION
Tank type PROTECTION PROTECTION (Roof sink ) Unit
Tank dia 33 39 38
Foam solution rate 4274.325 1175.616 9181.674 lpm
Foam Compound rate 128.22975 35.26848 275.45022 lpm
Foam compound for 65min 8334.93375 2292.4512 17904.2643 lit
Foam Compound required for 1 foam
monitor (cap 4680 4680 4680 lit
Foam Compound required 2 hose
streams 4446 4446 4446 lit
Total foam compound require for
17460.93375 11418.4512 27030.2643 lit
fighting fire