You are on page 1of 1

COMMENTS

M
CONTRACT NUMBER ERL/TC/T/02/17
T
CONTRACT TITLE: IEPIC OF NEW SANITARY WATER TREATMENT PLAN
T
O
MG TRANSMITTAL REFERENCE, DATED: 617-MG-MTO-T-131 Dated 7-Sep-2018
R
DOCUMENT NUMBER, REV & TITLE: ERev:A Piping GA for all SKID CODE 4
S
SR. NO. MEDGULF COMMENTS P METITO RESPONSE
O
N
1 Spectacle blind is missing as per P&ID S Spectacle blinds added as per
E

RLine nubers are included , however you will find all the l
2 Mark all the line number in the GA esee all the views
vthe line Numbers are not found in only plan or elvation o
.
B
3 Valve tag no should match with the P&ID Noted and matching

4 Drain & Isolation valves are missing as per P&ID Noted and added

5 Check the safe height requirement as mentioned in the P&ID Noted & corrected