You are on page 1of 148

AMCA

Publication 203-90
(R2007)

Field Performance
Measurement of Fan Systems

AIR MOVEMENT AND CONTROL


ASSOCIATION INTERNATIONAL, INC.

The International Authority on Air System Components


AMCA PUBLICATION 203-90 (R2007)

Field Performance Measurement


of Fan Systems

Air Movement and Control Association International, Inc.


30 West University Drive
Arlington Heights, IL 60004-1893
© 2007 by Air Movement and Control Association International, Inc.

All rights reserved. Reproduction or translation of any part of this work beyond that permitted by Sections 107 and
108 of the United States Copyright Act without the permission of the copyright owner is unlawful. Requests for
permission or further information should be addressed to the Executive Director, Air Movement and Control
Association International, Inc. at 30 West University Drive, Arlington Heights, IL 60004-1893 U.S.A.
Forward

The original edition of Publication 203 was released in 1976. This, the second edition, updates much of the
information that was presented.

Annex K (estimating the power output of three phase motors) and Annex L (estimating belt drive losses) were
rewritten and adjusted based on new information received from motor and drive manufacturers. Over four hundred
belt drive loss tests were analyzed.

New axial fan System Effect Factors were established based on a test project conducted and underwritten by
AMCA. These factors were incorporated in their respective, applicable field test examples shown in Annex A.

The intent of this publication is to provide information from which test procedures can be developed to meet the
conditions and requirements encountered in specific field test situations. They include the proper procedure for
determining various System Effect Factors. Numerous examples of actual field tests are presented in detail in
Annex A. These examples provide sufficient guidance for the proper field testing of most fan system installations.

Authority

AMCA Publication 203 was approved by the Air Movement Control Association Membership in 1990. It was
reaffirmed July, 2007.

AMCA 203 Review Committee

Robert H. Zaleski, Chairman Acme Engineering & Manufacturing Corp.

Narsaiah Dasa TLT-Babcock, Inc.

James L. Smith Aerovent, Inc.

Jack E. Saunders Barry Blower/SnyderGeneral Corp.

Erling Schmidt Novenco, Inc.

Gerald P. Jolette AMCA Staff

Disclaimer

AMCA uses its best efforts to produce standards for the benefit of the industry and the public in light of available
information and accepted industry practices. However, AMCA does not guarantee, certify or assure the safety or
performance of any products, components or systems tested, designed, installed or operated in accordance with
AMCA standards or that any tests conducted under its standards will be non-hazardous or free from risk.

Objections to AMCA Standards and Certifications Programs

Air Movement and Control Association International, Inc. will consider and decide all written complaints regarding
its standards, certification programs, or interpretations thereof. For information on procedures for submitting and
handling complaints, write to:

Air Movement and Control Association International


30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.

or

AMCA International, Incorporated


c/o Federation of Environmental Trade Associations
2 Waltham Court, Milley Lane, Hare Hatch
Reading, Berkshire
RG10 9TH United Kingdom
Related AMCA Standards and Publications

Publication 200 AIR SYSTEMS

System Pressure Losses


Fan Performance Characteristics
System Effect
System Design Tolerances

Air Systems is intended to provide basic information needed to design effective and energy efficient air systems.
Discussion is limited to systems where there is a clear separation of the fan inlet and outlet and does not cover
applications in which fans are used only to circulate air in an open space.

Publication 201 FANS AND SYSTEMS

Fan Testing and Rating


The Fan "Laws"
Air Systems
Fan and System Interaction
System Effect Factors

Fans and Systems is aimed primarily at the designer of the air moving system and discusses the effect on inlet and
outlet connections of the fan's performance. System Effect Factors, which must be included in the basic design
calculations, are listed for various configurations. AMCA 201-02 and AMCA 203-90 are companion documents.

Publication 202 TROUBLESHOOTING

System Checklist
Fan Manufacturer's Analysis
Master Troubleshooting Appendices

Troubleshooting is intended to help identify and correct problems with the performance and operation of the air
moving system after installation.

Publication 203 FIELD PERFORMANCE MEASUREMENTS OF FAN SYSTEMS

Acceptance Tests
Test Methods and Instruments
Precautions
Limitations and Expected Accuracies
Calculations

Field Performance Measurements of Fan Systems reviews the various problems of making field measurements
and calculating the actual performance of the fan and system. AMCA 203-90 and AMCA 201-02 are companion
documents.
TABLE OF CONTENTS

1. Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

2. Scope . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

3, Types of Field Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .1

4. Alternatives to Conducting Field Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

5. System Effect Factors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

6. Fan Performance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

7. Referenced Planes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .2

8. Symbols and Subscripts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

9. Fan Flow Rate . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

9.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

9.2 Velocity measuring instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

9.3 Location of traverse plane . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .4

9.4 The traverse . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

9.5 Flow rate calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .7

9.6 Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

10. Static Pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

10.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .8

10.2 Pressure measuring instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

10.3 Static pressure measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .9

10.4 Static pressure calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10

10.5 Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11

11. Fan Power Input . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

11.1 General . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

11.2 Power measurement methods . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .12

11.3 Power measuring instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13

11.4 Power transmission losses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .13


11.5 Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

12. Fan Speed . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

12.1 Speed measuring instruments . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

12.2 Speed measurements . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

13. Densities . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

13.1 Locations of density determinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

13.2 Data required at each location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

13.3 Additional data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

13.4 Density values . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .14

13.5 Temperatures . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

13.6 Barometric pressure . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

13.7 Accuracy . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15

14. Conversion Calculations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

15. Test Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .16

16. Precautions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .17

17. Typical Fan-System Installations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

17.1 Free inlet, free outlet fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .18

17.2 Free inlet, ducted outlet fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

17.3 Ducted inlet, ducted outlet fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

17.4 Ducted inlet, free outlet fans . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

17.5 Air handling units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .19

Annex A Field Test Examples . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21

Annex B Pitot-Static Tubes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .97

Annex C Double Reverse Tube . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .98

Annex D Pitot-Static Tube Holder . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .99

Annex E Static Pressure Tap . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .100

Annex F Pitot-Static Tube Connections . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .101

Annex G Manometer Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .102

Annex H Distribution of Traverse Points . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .104


Annex J Instrumentation Characteristics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .106

Annex K Phase Current Method for Estimating the Power Output of


Three Phase Fan Motors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .108

Annex L Estimated Belt Drive Loss . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .110

Annex M Density Determinations . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .112

Annex N Density Charts and Tables . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .117

Annex P Diffusion at Fan Outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .125

Annex R Diffusion at Fan Outlets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .126

Annex S Typical Format for Field Test Data . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .130

Annex T Uncertainties Analysis . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .131


AMCA INTERNATIONAL, INC. AMCA 203-90 (R2007)

Field Performance Fans for Rating

Measurement of Fan Systems 2. Scope

1. Introduction The recommendations and examples in this


publication may be applied to all types of centrifugal,
Performance ratings of fans are developed from axial, and mixed flow fans in ducted or nonducted
laboratory tests made according to specified installations used for heating, ventilating, air
procedures on standardized test setups. In North conditioning, mechanical draft, industrial process,
America, the standard is ANSI/AMCA Standard 210 / exhaust, conveying, drying, air cleaning, dust
ANSI/ASHRAE 51 Laboratory Methods of Testing collection, etc. Although the word air is used when
Fans for Rating. reference is made in the general sense to the
medium being handled by the fan, gases other than
In actual systems in the field, very few fans are air are included in the scope of this publication.
installed in conditions reproducing those specified in
the laboratory standard. This means that, in Measurement of sound, vibration, and stress levels
assessing the performance of the installed fan- are not within the scope of this publication.
system, consideration must be given to the effect on
the fan’s performance of the system connections, 3. Types of Field Tests
including elbows, obstructions in the path of the
airflow, sudden changes of area, etc. The effects of There are three general categories of field tests:
system conditions on fan performance is discussed in
Section 5, and more completely in AMCA Publication A) General Fan System Evaluation - A
201, Fans and Systems. measurement of the fan-system’s performance to
use as the basis of modification or adjustment of
A major problem of testing in the field is the difficulty the system.
of finding suitable locations for making accurate
measurements of flow rate and pressure. Sections B) Acceptance Test - A test specified in the sales
9.3 and 10.3 outline the requirements of suitable agreement to verify that the fan is achieving the
measurement sections. specified performance.

Because these problems and others will require C) Proof of Performance Test - A test in response
special consideration on each installation, it is not to a complaint to demonstrate that the fan is
practical to write one standard procedure for the meeting the specified performance requirement.
measurement of the performance of all fan-systems
in the field. This publication offers guidelines to As acceptance and proof of performance tests are
making performance measurements in the field related to contract provisions, they are usually
which are practical and flexible enough to be applied subject to more stringent requirements and are
to a wide range of fan and system combinations. usually more costly than a general evaluation test. In
the case of large fans used in industrial applications
Because of the wide variety of fan types and systems and of mechanical draft fans used in the electrical
encountered in the field, Annex A includes examples power generation industry the performance of a field
of a number of different field tests. In most cases, test may be part of the purchase agreement between
these examples are based on actual tests which have the fan manufacturer and the customer. In addition to
been conducted in the field. Publication 203, AMCA Standard 803 Site
Performance Test Standard-Power Plant and
Before performing any field test, it is strongly Industrial Fans defines the conditions which must be
recommended that the following AMCA publications met to achieve higher accuracy of measurement. In
be carefully reviewed: new installations of this type, it is desirable to include
a suitable measuring section in the design.
AMCA Publication 200 - Air Systems Agreement must be reached on the test method to be
AMCA Publication 201 - Fans and Systems used prior to performance of the test.
AMCA Publication 202 - Troubleshooting
AMCA Standard 210 - Laboratory Methods of Testing

1
AMCA 203-90 (R2007)

4. Alternatives to Field Tests Examples of the application of SEFs in determining


the results of field tests are included in Annex A.
In some cases, considerations such as cost and
problems of making accurate measurements may In field tests of fan-system installations in which
make the following alternative methods of testing system effects have not been accounted for, it is
worth investigation: important that their sources be recognized and their
magnitudes be established prior to testing.
A) Testing the fan before installation in a laboratory
equipped to perform tests in accordance with The alternative to dealing with a large magnitude
AMCA Standard 210. Limitations in laboratory SEF is to eliminate its source. This requires revisions
test facilities may preclude tests on full size fans. to the system. This alternative course of action is
In this case, the full size fan can be tested at the recommended when swirl exists at the fan inlet (see
installation site in accordance with AMCA Publication 201, Figure 9.8). The effect on fan
Standard 210. This will usually require the performance as a result of swirl at the inlet is
installation of special ductwork. impossible to estimate accurately as the system
effect is dependent upon the degree of swirl. The
B) Testing a reduced scale model of the fan in effect can range from a minor amount to an amount
accordance with AMCA Standard 210 and that results in the fan-system performance being
determining the performance of the full size fan completely unacceptable.
as described in AMCA Publication 802, Power
Plant Fans – Establishing Performance Using 6. Fan Performance
Laboratory Methods.
Fan performance is a statement of fan flow rate, fan
C) Testing a reduced scale model of the complete total or static pressures, and fan power input at stated
fan and system using the test methods outlined fan speed and fan air density. Fan total or static
in this publication. efficiencies may be included. The fan air density is
the density at the fan inlet. The fan flow rate is the
Tests conducted in accordance with AMCA Standard volume flow rate at the fan inlet density.
210 will verify the performance characteristics of the
fan but will not take into account the effect of the 7. Referenced Planes
system connections on the fan’s performance (see
Section 5). Certain locations within a fan-system installation are
significant to field tests. These locations are
5. System Effect Factors designated as follows:

AMCA Publication 201, Fans and Systems, deals in Plane 1: Plane of fan inlet
detail with the effect of system connections on fan Plane 2: Plane of fan outlet
performance. It gives system effect factors for a wide Plane 3: Plane of Pitot-static tube traverse for
variety of obstructions and configurations which may purposes of determining flow rate
affect a fan’s performance. Plane 4: Plane of static pressure measurement
upstream of fan
System Effect Factor (SEF) is a pressure loss which Plane 5: Plane of static pressure measurement
recognizes the effect of fan inlet restrictions, fan downstream of fan
outlet restrictions, or other conditions influencing fan
performance when installed in the system. The use of the numerical designations as subscripts
indicate that the values pertain to those locations.
SYSTEM EFFECT FACTORS (SEFs) ARE
INTENDED TO BE USED IN CONJUNCTION WITH
THE SYSTEM RESISTANCE CHARACTERISTICS
IN THE FAN SELECTION PROCESS. Where SEFs
are not applied in the fan selection process, SEFs
must be applied in the calculations of the results of
field tests. This is done for the purpose of allowing
direct comparison of the test results to the design
static pressure calculation. Thus, for a field test, the
fan static pressure is defined as:

Ps = Ps2 - Ps1 – Pv1 + SEF 1 + SEF 2 + …+ SEF n

2
AMCA 203-90 (R2007)

8. Symbols and Subscripts 9. Fan Flow Rate

SYMBOL DESCRIPTION UNIT 9.1 General

A Area of cross-section ft2 Determine fan flow rate using the area, velocity
D Diameter ft pressure, and density at the traverse plane and the
De Equivalent diameter ft density at the fan inlet. The velocity pressure at the
FLA Full load amps amps traverse plane is the root mean square of the velocity
H Fan power input hp pressure measurements made in a traverse of the
HL Power transmission loss hp plane. The flow rate at the traverse plane is
Hmo Motor power output hp calculated by converting the velocity pressure to its
kW Electrical power kilowatts equivalent velocity and multiplying by the area of the
L Length ft traverse plane.
N Speed of rotation rpm
NLA No load amps amps 9.2 Velocity measuring instruments
NPH Nameplated horsepower hp
NPV Nameplated volts volts Use a Pitot-static tube of the proportions shown in
Ps Fan static pressure in. wg Annex B or a double reverse tube, shown in Annex C,
Psx Static pressure at Plane x in. wg and an inclined manometer to measure velocity
Pt Fan total pressure in. wg pressure. The velocity pressure at a point in a gas
stream is numerically equal to the total pressure
Ptx Total pressure at Plane x in. wg
diminished by the static pressure. The Pitot-static
Pv Fan velocity pressure in. wg
tube is connected to the inclined manometer as
Pvx Velocity pressure at Plane x in. wg shown in Annex F. The double reverse tube is
pb Barometric pressure in. Hg connected to the inclined manometer as shown in
pe Saturated vapor pressure at tw in. Hg Annex C.
pp Partial vapor pressure in. Hg
px Absolute pressure at Plane x in. Hg 9.2.1 Pitot-static tube. The Pitot-static tube is
Q Fan flow rate cfm considered to be a primary instrument and need not
Qi Interpolated flow rate cfm be calibrated if maintained in the specified condition.
Qx Flow rate at Plane x cfm It is suited for use in relatively clean gases. It may be
SEF System effect factor in. wg used in gases that contain moderate levels of
T Torque lb-in. particulate matter such as dust, water, or dirt,
td Dry-bulb temperature °F provided certain precautions are employed (see
tw Wet-bulb temperature °F Section 15).
V Velocity fpm
9.2.2 Double reverse tube. The double reverse tube
ΔPx,x’ Pressure loss between
is used when the amount of particulate matter in the
Planes x and x’ in. wg gas stream impairs the function of the Pitot-static
ΔPs Pressure loss across damper in. wg tube. The double reverse tube requires calibration. It
ρ Fan gas density lbm/ft3 is important that the double reverse tube be used in
ρx Gas density at Plane x lbm/ft3 the same orientation as used during calibration. Mark
Σ Summation sign --- the double reverse tube to indicate the direction of
Airflow direction --- the gas flow used in its calibration.

SUBSCRIPT DESCRIPTION 9.2.3 Inclined manometers. Inclined manometers


are available in both fixed and adjustable range
c Value converted to specified conditions types. Both types require calibration. The adjustable
r Reading range type is convenient in that it may be adjusted at
x Plane 1, 2, 3, ..., as appropriate the test site to the range appropriate to the velocity
1 Plane 1 (fan inlet) pressures which are to be measured. It is adjusted by
2 Plane 2 (fan outlet) changing the slope to any of the various fixed
3 Plane 3 (plane of Pitot-static traverse for settings and by changing the range scale
purpose of determining flow rate accordingly. Each setting provides a different ratio of
4 Plane 4 (plane of static pressure the length of the indicating column to its indicated
measurement upstream of fan) height. Adjustable range type manometers in which
5 Plane 5 (plane of static pressure the slope may be fixed at 1:1, 20:1, and intermediate
measurement downstream of fan) ratios are available (see Figure 10 in Annex G).

3
AMCA 203-90 (R2007)

The accuracy of the manometer used in the than 75% of the velocity pressure measurements
measurement of velocity pressures is of prime are greater than 1/10 of the maximum
importance. Select a manometer that will provide an measurement (see Figure 9.1)
acceptable degree of accuracy; consider the range,
slope, quality, scale graduations, indicating fluid of 2) The flow streams should be at right angles to the
the instrument and the range of the velocity traverse plane. Variations from this flow condition
pressures to be measured. The graph in Annex G as a result of swirl or other mass turbulence are
indicates the effect of expected resolution of considered acceptable when the angle between
manometer readings on the accuracy of velocity the flow stream and the traverse plane is within
determinations. The basis for this graph is described 10 degrees of a right angle. The angle of the flow
in Section 9.6. Determine velocities in the very low stream in any specific location is indicated by the
range more accurately by using a manometer with a orientation of the nose of the Pitot-static tube that
slope of 20:1. Due to practical limitations in length, its produces the maximum velocity pressure reading
use is restricted to measurements where the at the location.
velocities are very low. Also, errors in velocity
determinations made by using a Pitot-static tube and 3) The cross-sectional shape of the airway in which
manometer exceed normally acceptable values at the traverse plane is located should not be
velocity pressure readings less than 0.023 in. wg. irregular. Proper distribution of traverse points
This corresponds to a velocity of approximately 600 and accurate determination of the area of the
fpm for air of 0.075 lbm/ft3 density. traverse plane are difficult to achieve when the
airway does not conform closely to a regular
9.2.4 Low velocity instruments. Normally, velocities shape.
encountered in the field test situations are well in
excess of 600 fpm. Therefore, recommendations 4) The cross-sectional shape and area of the airway
regarding alternate test procedures and should be uniform throughout the length of the
instrumentation for use for velocities less than 600 airway in the vicinity of the traverse plane. When
fpm are not presented in this publication. the divergence or convergence of the airway is
Descriptions of various types of instruments used to irregular or more than moderate in degree,
determine range velocities are presented in Annex J. significantly nonuniform flow conditions may
Most of the instruments require frequent calibration, exist.
and some are not suited for use in high temperature,
dirty, wet, corrosive, or explosive atmospheres. If it is 5) The traverse plane should be located to minimize
necessary to use one of these instruments, the the effects of gas leaks between the traverse
procedure for its use, its calibration, and the expected plane and the fan.
accuracy of results should be agreed upon by all
interested parties. 6) When it is necessary to locate the traverse plane
in a converging or diverging airway (not
9.3 Location of traverse plane recommended), note that the traverse plane and
area is located at the tip of the Pitot-static tube.
For field tests, suitable test measurement station
locations must be provided in the system. When A location well downstream in a long, straight run of
suitable locations are not available, consider making uniform cross-section duct will usually provide
temporary or permanent alterations to the ducting for acceptable conditions for the Pitot traverse plane.
improved test accuracy. When locating the traverse plane close to the fan, as
is often done in order to minimize the effect of
For free inlet, free outlet fans, convert a free inlet, leakage, flow conditions upstream of the fan are
free outlet fan to a ducted inlet, free outlet fan by the usually more suitable. In some installations, more
addition of a temporary duct. Estimate free inlet, free than one traverse plane may be required in order to
outlet fan flow rate by measuring other parameters account for the total flow (Annex A contains
and interpreting certified ratings performance (see examples).
Section 17.1).
When a field test is anticipated, particularly when the
A Pitot traverse plane suitable for the measurements requirement for a field test is an item in the
used to determine flow rate are as follows: specifications, the system designer should provide a
suitable traverse plane location in the system.
1) The velocity distribution should be uniform
throughout the traverse plane. The uniformity of When the fan is ducted outlet and the traverse plane
distribution is considered acceptable when more is to be located downstream from the fan, the

4
AMCA 203-90 (R2007)

Pv MAX Pv MAX Pv MAX Pv MAX


10 10

A: IDEAL Pv DISTRIBUTION B: GOOD Pv DISTRIBUTION


(ALSO SATISFACTORY FOR FLOW INTO FAN INLETS.
MAY BE UNSATISFACTORY FOR FLOW INTO INLET
BOXES - MAY PRODUCE SWIRL IN BOXES)

Pv MAX Pv MAX Pv MAX Pv MAX


10 10

60%
80%

C: SATISFACTORY Pv DISTRIBUTION - MORE D: DO NOT USE


THAN 75% OF Pv READINGS GREATER THAN: UNSATISFACTORY Pv DISTRIBUTION -
LESS THAN 75% OF Pv READINGS GREATER
Pv MAX THAN: Pv MAX
10
10
(UNSATISFACTORY FOR FLOW INTO FAN INLETS OR (UNSATISFACTORY FOR FLOW INTO FAN INLETS OR
INLET BOXES) INLET BOXES)

Pv MAX Pv MAX Pv MAX Pv MAX


10 10

40% 35%

20% 35%

E: DO NOT USE F: DO NOT USE


UNSATISFACTORY Pv DISTRIBUTION UNSATISFACTORY Pv DISTRIBUTION
LESS THAN 75% OF Pv READINGS GREATER LESS THAN 75% OF Pv READINGS GREATER
THAN: P MAX THAN: P MAX
v v
10 10
(UNSATISFACTORY FOR FLOW INTO FAN INLETS OR (UNSATISFACTORY FOR FLOW INTO FAN INLETS OR
INLET BOXES) INLET BOXES)

Figure 9.1 - Typical Velocity Pressure Distributions Encountered in Velocity


Pressure Measurement Planes in Fan-System Installations
5
AMCA 203-90 (R2007)

MEASUREMENT PLANE

De
MIN.
2

12 in. MIN.

4YZ
WHERE: De =
π INLET BOX DAMPERS
Z

Note: The measurement plane should be located a minimum of ½ De from the inlet cone, but not less than 12 in.
from the leaving edge of the damper blades.

Figure 9.2

STACK

VELOCITY
PROFILE

Note: Spiral vortex may form when fan discharges directly into a stack or similar arrangement.

Figure 9.3
6
AMCA 203-90 (R2007)

traverse plane should be situated a sufficient equivalent diameters from the inlet of the duct.
distance downstream from the fan to allow the flow to Where the duct is small, its length may
diffuse to a more uniform velocity distribution and to necessarily be greater than 2 equivalent
allow the conversion of velocity pressure to static diameters in order to ensure that the tip of the
pressure. Annex P provides guidance for the location Pitot-static tube is a minimum of 1½ equivalent
of the traverse plane in these cases. The location of diameters from the duct inlet. This short length of
the traverse plane on the inlet side of the fan should duct should produce no significant addition to the
not be less than ½ equivalent diameter from the fan system resistance, but in some cases it may alter
inlet. Regions immediately downstream from elbows, the pattern of flow into the fan impeller, and
obstructions and abrupt changes in airway area are thereby affect the performance of the fan slightly.
not suitable traverse plane locations. Regions where
unacceptable levels of swirl are usually present, such 9.4 The traverse
as the region downstream from an axial flow fan that
is not equipped with straightening vanes, should be Annex H contains recommendations for the number
avoided. Swirl may form when a fan discharges and distribution of measurement points in the
directly into a stack or similar arrangement (see traverse plane. If the flow conditions at the traverse
Figure 9.2). plane are less than satisfactory, increase the number
of measurement points in the traverse to improve
9.3.1 Inlet box location. When the traverse plane accuracy.
must be located within an inlet box, the plane should
be located a minimum of 12 inches downstream from Since the flow at a traverse plane is never strictly
the leaving edges of the damper blades and not less steady, the velocity pressure measurements
than ½ equivalent diameter upstream from the edge indicated by the manometer will fluctuate. Each
of the inlet cone (see Figure 9.3). Do not locate velocity pressure measurement should be mentally
traverse points in the wake of individual damper averaged on a time-weighted basis. Any velocity
blades. In the case of double inlet fans, traverses pressure measurement that appears as a negative
must be conducted in both inlet boxes in order to reading is to be considered a velocity pressure
determine the total flow rate. measurement of zero and included as such in the
calculation of the average velocity pressure.
9.3.2 Alternative locations. On occasion, an
undesirable traverse plane location is unavoidable, or When it is necessary to locate the traverse plane in a
each of a limited number of prospective locations converging or diverging airway, orient the nose of the
lacks one or more desirable qualities. In such cases, Pitot-static tube such that it coincides with the
the alternatives are: anticipated line of the flow stream. This is particularly
important at measurement points near the walls of
1) Accept the most suitable location and evaluate the airway (see Annex A-1A).
the effects of the undesirable aspects of the
location on the accuracy of the test results. In No appreciable effect on Pitot-static tube readings
some instances, the estimated accuracy may occur until the angle of misalignment between the
indicate that the results of the test would be airflow and the tube exceeds 10 degrees.
meaningless, particularly in acceptance tests and
proof of performance tests. 9.5 Flow rate calculations

2) Provide a suitable location by modifying the 9.5.1 Flow rate at traverse plane. The flow rate at
system. This course of action is recommended the traverse plane is calculated as follows:
for acceptance tests and proof of performance
tests. The modifications may be temporary, Q3 = V3A3
permanent, minor or extensive, depending on the
specific conditions encountered. When the inlet Where:
side of the fan is not ducted but is designed to
accept a duct, consider installing a short length of A3 = the area of the traverse plane
inlet duct to provide a suitable traverse plane V3 = the average velocity at the traverse plane
location. This duct should be of a size and shape
= 1096 (Pv3/ρ3)0.5
to fit the fan inlet, a minimum of 2 equivalent
diameters long and equipped with a bell shaped ρ3 = the density at the traverse plane
or flared fitting at its inlet. The traverse plane Pv3 = the root mean square velocity pressure at the
should be located a minimum of ½ equivalent traverse plane
diameters from the fan inlet and not less than 1½ = [∑(Pv3r)0.5 / number of readings]2

7
AMCA 203-90 (R2007)

Pv3r is the velocity pressure reading, corrected for determinations. This graph indicates the effect of
manometer calibration and where applicable, expected resolution of velocity determinations. This
corrected for the calibration of the double reverse effect is shown for several manometer slope ratios.
tube. It is important that the calibration of the double For all ratios, the expected resolution used as a basis
reverse tube be applied correctly. The use of the for the graph is the length of indicating column
calibration of the double reverse tube is described in equivalent to 0.05 in. wg in a manometer with slope
Annex C. ratio of 1:1. As indicated in the graph, reading
resolution uncertainty can be significant. However,
9.5.2 Continuity of mass. The calculations of fan this uncertainty can be controlled by selecting a
flow rate are based on considerations of continuity of manometer with a slope suited to the velocity
mass, and as such, it is assumed that no mass is pressures to be measured and by avoiding regions of
added or removed from the gas stream between the very low velocity in the selection of the traverse plane
traverse plane and the fan inlet. In the general location. Reading resolution uncertainties exceed
application, having determined the flow rate and normally acceptable values at velocity pressures less
density at the traverse plane, the flow rate at any than 0.023 in. wg. This corresponds to a velocity of
location, (x), in the fan-system installation may be approximately 600 fpm for air of 0.075 lbm/ft3 density.
calculated, providing the density at this location is Generally, ducts are sized for velocities considerably
known and the assumption noted above is valid, i.e.: in excess of 600 fpm. Velocities less than 600 fpm
may exist in certain sections of the system in some
Qx = Q3 (ρ3/ρx) installations, but these sections can usually be
avoided. Do no use a Pitot-static tube and
9.5.3 Fan flow rate, single traverse plane. Where a manometer to determine velocities in the low ranges
single traverse plane is used, the calculation of the associated with filters and cooling coils in air
fan flow rate is: conditioning, heating, and ventilating units. In some
instances, the uncertainties incurred in the
Q = Q1 determinations of low velocity flows may be
= Q3 (ρ3/ρ1) acceptable. For example, an uncertainty of 15% in
the determination of the flow rate in a branch duct
Where: that accounts for 20% of the total flow rate for the
system affects the accuracy of the total flow rate
Q3 and ρ3 = as described in Section 9.5.1 determination by only 3%.

ρ1 = the density at the fan inlet In addition to low range velocities, other conditions
may exist at the traverse plane which can
significantly affect the accuracy of the flow rate
9.5.4 Fan flow rate, multiple traverse planes.
determination. These include nonuniform velocity
When it is necessary to use more than one traverse
distribution, swirl, and other mass turbulence.
plane in order to account for the total flow:
Improve the accuracy of the flow rate determination
by avoiding these conditions in the selection of the
Q = Q1
traverse plane location, or improve the conditions by
= Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1) + ... + Q3n (ρ3n/ρ1)
modifying the system.

9.6 Accuracy 10. Fan Static Pressure


The performance item of major concern in most fan-
10.1 General
system installations is the flow rate. Every effort
should be made to improve the accuracy of the flow
Determine fan static pressure by using the static
rate determination. The uncertainty analysis
pressures at the fan inlet and outlet, the velocity
presented in Annex T indicates that the uncertainties
pressure at the fan inlet, and applicable System
in flow rate determinations will range from 2% to
Effect Factors. The use of System Effect Factors in
10%. This range is based on considerations of the
the determination of fan static pressure is described
conditions that are encountered in most field test
in Section 5. The velocity pressure at the fan inlet is
situations. This includes instances in which the
the calculated average velocity pressure at this
conditions at the Pitot traverse plane do not conform
location, and as such, its determination is based on
to all of the qualifications indicated in Section 9.3.
the fan flow rate, the density at the fan inlet, and the
fan inlet area. The static pressures at the fan inlet and
The graph in Annex G provides guidance for
outlet may be obtained directly by making pressure
improving the accuracy of the flow rate
measurements at these locations; or they may be

8
AMCA 203-90 (R2007)

determined by making pressure measurements at between the measurement plane and the plane of
other locations, upstream and downstream of the fan. interest is straight and without change in cross-
In the latter case, the determinations must account sectional area. Then the duct friction loss between
for the effects of velocity pressure conversions and the measurement plane and the plane of interest is
pressure losses, as may occur between the usually insignificant, and considerations of velocity
measurement planes and the planes of interest. pressure conversions and calculations of pressure
losses for duct fitting and other system components
10.2 Pressure measuring instruments can be avoided.

This section describes only the instruments for use in When a system component is situated between the
measuring static pressure. Instruments for use in the measurement plane and the plane of interest, the
other measurements involved in the determination of pressure loss of the component must be calculated
fan static pressure are described in Section 13. and credited to the fan. The calculation of the
pressure loss is usually based on the component’s
Use a Pitot-static tube of the proportions shown in performance ratings, which may be obtained from the
Annex B, a double reverse tube as shown in Annex manufacturer of the item.
C, or a side wall pressure tap as shown in Annex E,
and a manometer to measure static pressure. If there is a change in area between the
measurement plane and the plane of interest, then
10.2.1 Pitot-static tube. The comments that appear the calculation of the static pressure at the plane of
in Section 9.2 regarding the use and calibration of the interest must account for velocity pressure
Pitot-static tube are applicable to its use in the conversion and include any associated pressure
measurement of static pressures. loss. When the change in area is moderate and
gradual, the conversion of velocity pressure is
10.2.2 Double reverse tube. The double reverse considered to occur without loss and the static
tube cannot be used to measure static pressure pressure is calculated on the basis of no change in
directly. It must be connected to two manometers and total pressure between the measurement plane and
the static pressure for each point of measurement the plane of interest. This assumes that the duct
must be calculated. Both the manometer connections friction loss between the two planes is negligible.
and the method of calculation are shown in Annex C. When the change in area is an abrupt and sizable
enlargement, as in a duct leading into a large
10.2.3 Pressure tap. The pressure tap does not plenum, the loss is considered to be equivalent to the
require calibration. Use no fewer than four taps velocity pressure in the smaller area, and the static
located 90 degrees apart. In rectangular ducts, a pressure at the plane of interest is considered to be
pressure tap should be installed near the center of the same as the static pressure at the measurement
each wall. It is important that the inner surfaces of the plane. This assumes that the velocity pressure in the
duct in the vicinities of the pressure taps be smooth larger area and the duct friction loss are negligible.
and free from irregularities, and that the velocity of
the gas stream does not influence the pressure 10.3.1 Location of the measuring plane. When the
measurements. fan is ducted outlet, the static pressure measurement
plane downstream of the fan should be situated a
10.2.4 Manometers. A manometer with either sufficient distance from the fan outlet to allow the flow
vertical or inclined indicating column may be used to to diffuse to a more uniform velocity distribution and
measure static pressure. Inclined manometers used to allow the conversion of velocity pressure to static
to measure static pressures require calibration and pressure. See Annex P for guidance in locating the
should be selected for the quality, range, slope, scale measurement plane in these cases. In general,
graduations, and indicating fluid necessary to pressure taps should be used if it is necessary to
minimize reading resolution errors. measure static pressure in the immediate vicinity of
the fan outlet. The static pressure at this location is
10.3 Static pressure measurements difficult to measure accurately with a Pitot-static tube
due to the existence of turbulence and localized high
It is important that all static pressure measurements velocities. If the surface conditions or the velocities at
be referred to the same atmospheric pressure, and the duct walls are unsuited for the use of pressure
this atmospheric pressure be that for which the taps, then a Pitot-static tube must be used with
barometric pressure is determined. extreme care, particularly in aligning the nose of the
tube with the lines of the flow streams.
Make static pressure measurements near the fan
inlet and the fan outlet, and where the airway The location of the static pressure measurement

9
AMCA 203-90 (R2007)

plane upstream of the fan should not be less than ½ negative. By definition, positive values are those
equivalent diameter from the fan inlet. In the event measured as being greater than atmospheric
that static pressure measurements must be made in pressures; negative values are those measured as
an inlet box, the measurement plane should be being less than atmospheric pressure. In all of the
located as indicated in Figure 9.2. In the case of equations in this publication, the values of static
double inlet fans, static pressure measurements must pressures must be entered with their proper signs
be made in both inlet boxes in order to determine the and combined algebraically.
average static pressure on the inlet side of the fan.
10.4.1 Static pressure at measuring planes. The
In general, the qualifications for a plane well suited static pressure at a plane of measurement (x) is
for the measurement of static pressure are the same calculated as follows:
as those for the measurement of velocity pressure,
as indicated in Section 9.3:
Psx =
∑P sxr

1) The velocity distribution should be uniform number of readings


throughout the traverse plane.
Where:
2) The flow streams should be at right angles to the
plane. Psxr = the static pressure reading, corrected for
manometer calibration
3) The cross-sectional shape of the airway in which
the plane is located should not be irregular. 10.4.2 Static pressure at fan inlet or outlet. The
static pressure at the fan inlet, Ps1, and the static
4) The cross-sectional shape and area of the airway pressure at the fan outlet, Ps2, may be measured
should be uniform throughout the length of the directly in some cases. In most cases, the static
airway in the vicinity of the plane. pressure measurements for use in determining fan
static pressure will not be made directly at the fan
5) The plane should be located such as to minimize inlet and outlet, but at locations a relatively short
the effects of leaks in the portion of the system distance upstream from the fan inlet and downstream
that is located between the plane and the fan. from the fan outlet. These static pressure
measurements are designated Ps4 and Ps5,
A long, straight run of duct upstream of the
respectively. Static pressure at the fan inlet, Ps1, is
measurement plane will usually provide acceptable
derived as follows:
conditions at the plane. Regions immediately
downstream from elbows, obstructions, and abrupt
Pt4 = Pt1 + ΔP4,1
changes in airway area are generally unsuitable
locations. Regions where unacceptable levels of
turbulence are present should be avoided. Where:

If in any fan-system installation the prospective Pt4 = the total pressure plane of measurement
locations for static pressure measurement planes Pt1 = the total pressure at the fan inlet
lack one or more desirable qualities, the alternatives ΔP4,1 = the sum of the pressure losses between the
are to accept the best qualified locations and two planes
evaluate the effects of the undesirable aspects of the
conditions on the accuracy of the test results or These losses (ΔP) include those attributable to duct
provide suitable locations by modifying the system. friction, duct fittings, other system components, and
changes in airway area. Although ΔP represents a
10.3.2 When using a Pitot-static tube or a double loss in all cases, it is considered a positive value as
reverse tube to measure static pressure, a number of used in the equations in this publication. By
measurements must be made throughout the plane. substitution and rearrangement:
Use Annex H to determine the number and
distribution of the measurement points. When using Ps1 = Ps4 + Pv4 - Pv1 - ΔP4,1
pressure taps, a single measurement at each of the
taps located at the plane is sufficient. Similarly, for static pressure at the fan outlet, Ps2:

10.4 Static pressure calculations Pt2 = Pt5 + ΔP2,5

Static pressure measurements may be positive or Ps2 = Ps5 + Pv5 - Pv2 + ΔP2,5

10
AMCA 203-90 (R2007)

Where: 10.5 Accuracy

The velocity pressures at the various planes can be The uncertainty analyses in Annex T indicate that the
determined from the following general equations for uncertainties in fan static pressure determinations
the velocity pressure at a plane of measurement (x): are expected range from 2% to 8%. This range is
based on considerations of the conditions expected
Pvx = Pv3 (A3/Ax)2 (ρ3/ρx) to be encountered in most field test situations.

Or: Improve the accuracy of the fan static pressure


determination by avoiding static pressure
Pvx = (Qx/1096Ax)2 ρx measurement plane locations where turbulence or
other unsteady flow conditions will produce
Locate the static pressure measurement planes such significant uncertainties in the mental averaging of
that the pressure losses between the measurement pressure readings. Other reading resolution
planes and the planes of interest are insignificant. uncertainties are not as significant in the fan static
This will eliminate the uncertainties involved in the pressure determination as in the determination of
determination of the pressure losses, and the flow rate. Generally, static pressure measurements
equations for Ps1 and Ps2 reduce to the following: are much greater in magnitude than velocity pressure
measurements, and the selection of a manometer
Ps1 = Ps4 + Pv4 - Pv1 that will provide reasonably good accuracy is not
usually a problem.
Ps2 = Ps5 + Pv5 - Pv2
The uncertainty analyses in Annex T and the
These equations may be used when changes in area resulting anticipated uncertainty range do not
between the measurement planes and the planes of account for uncertainties that may occur in the
interest are moderate and gradual, and the pressure following:
losses associated with conversions of velocity
pressure to static pressure are negligible. • Determinations of velocity pressure conversions
occurring between the measurement planes and
If, in addition to the losses being negligible there are the planes of the fan inlet or fan outlet. The area
no changes in the areas between the measurement and density values that are involved in these
planes and the respective planes of interest, then the determinations are usually obtained without
equations are further reduced to: significant uncertainties. However, pressure
losses associated with velocity pressure
Ps1 = Ps4 conversions are often difficult to determine
accurately.
Ps2 = Ps5
• Determinations of other pressure losses
occurring between the measurement planes and
These equations may also be used when the only
the fan inlet or fan outlet. This includes pressure
losses between the measurement planes and the
losses in ducts, duct fittings, and other system
planes of interest are those associated with changes
components. The calculations of these losses
in area that are abrupt and sizable enlargements in
are based on the assumption of uniform flow
the direction of flow. This assumes that the velocity
conditions. This assumption may not be valid,
pressure in the larger area is negligible.
and the calculated pressure loss values may be
significantly inaccurate.
10.4.3 Fan static pressure. The equation for fan
static pressure is:
• Determinations of the values of System Effect
Factors. These determinations are based on
Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2 + ... + SEF n
limited information, and as such, are subject to
uncertainty.
Where:
Avoid situations requiring these determinations,
SEF 1, SEF 2, ... SEF n = System Effect Factors that thereby eliminating them as sources for uncertainties.
account for the various System Effects that are The uncertainties involved in determining the values
uncorrected and exist at the time of the field test. of System Effect Factors can be avoided only by
correcting the causes of the System Effects. This
requires alterations to the system.

11
AMCA 203-90 (R2007)

11. Fan Power Input 11.2.2 Typical motor performance data. Typical
motor performance data may be used to determine
11.1 General fan power input. These data, which are referred to as
typical in that the data and the actual performance of
Fan power input data included as part of the fan the motor are expected to correspond closely, can
performance ratings are normally defined and limited usually be obtained from the motor manufacturer.
to either: The data provided can be in a variety of forms, but
are sufficient to determine motor power output based
• power input to the fan shaft on electrical input measurements. It is important that
the power supplied to the motor during the field test
• the total of the power input to the fan shaft and be consistent with that used as the basis for the
the power transmission loss motor performance data. The phase voltage should
be stable and balanced, and the average should be
The losses in fan shaft bearings are included in either withing 2% of the voltage indicated in the
case. Since the results of field tests are usually performance data.
compared to the rated performance characteristics of
the fan, field test values of fan power input should be Depending on the form of the typical motor
determined on the same basis as that used in the fan performance data, motor power output is determined
ratings. For belt driven fans, the rated fan power input by one of the following methods:
may or may not include belt drive losses. The
information regarding the basis of the rated fan 1) Given the typical motor performance chart of
power input accompanies the rating data or is watts input versus motor power output at a stated
otherwise available from the fan manufacturer. In voltage.
most instances, when a power transmission loss Hmo, is the value in the typical motor performance
occurs, the loss will have to be determined and data that corresponds to the field test
subtracted from the motor output in order to obtain measurement of watts input to the motor.
the fan power input.
2) Given the typical motor performance chart of
11.2 Power measurement methods watts input versus torque output and speed at a
stated voltage.
In view of the fact that accuracy requirements for field Use the field test measurement of watts input
test determinations of fan power input vary and the corresponding typical motor performance
considerably, a number of test methods are data values of torque output and speed; the
recommended. These methods are intended to motor power output is calculated as:
provide economical and practical alternatives for
dealing with various levels of accuracy requirements. T ×N
Hmo =
63025
11.2.1 Phase current method. This method for
estimating the power output of three phase motors is
3) Given the typical motor performance chart of
based on the relationship of motor current and motor
watts input versus motor efficiency at a stated
power output. The method, described in Annex K,
voltage.
requires measurements of the phase currents and
Use the field test measurement of watts input
voltages supplied to the motor while driving the fan.
and the corresponding typical motor performance
Depending on the operating load point of the motor, it
data value of motor efficiency, the motor power
may also involve the measurements of the no load
output is calculated as:
phase currents.

The phase current method is convenient and watts input × motor efficiency
Hmo =
sufficiently accurate for most field tests. In this 746
method, the closer the actual phase current is to the
motor nameplate value of full load amps, the greater 4) Given the typical motor performance chart of
the accuracy. Since fan motors are normally selected amps versus power factor and motor efficiency at
for operation at or near the full load point, this method a stated voltage.
provides a reasonably accurate estimate of the Use the field test measurements of amps input
power output of the fan motor. Determine fan power and volts, and the typical motor performance
input by using the motor power output and, where data values of power factor (pf) and motor
applicable, the power transmission loss. efficiency, corresponding to the measured amps
input; the motor power output is calculated as:
12
AMCA 203-90 (R2007)

amps × volts × pf × motor efficiency accommodate its installation. The torquemeter is


Hmo = extremely limited in field test application. This is due
746
mainly to is high cost and the cost of its installation.
In addition, the length of the shut down time and the
Or, for three phase motors: revisions to site conditions required for its installation
are usually undesirable. For practical considerations,
(3)0.5 × amps × volts × pf × motor efficiency it is not normally used in cases where the fan is belt
Hmo = driven and where the fan impeller is installed directly
746
on the motor shaft.
In both equations, amps and volts are the field test
11.3 Power measuring instruments
measurement values and, in the case of three phase
motors, are the averages of the measured phase
Measurement of current, voltage, watts, and power
values.
factor can be obtained by using an industrial type
power analyzer of good quality. This type of
The fan power input is the motor power output minus
instrument is available with accuracies of 1% full
the power transmission loss, where applicable.
scale for volts, amps and power factor, and 2% full
scale for watts. Normally, the higher levels of
11.2.3 Calibrated motors. A calibrated motor may be accuracy requirements can be met by using this type
used to determine fan power input. When intending of instrument, providing the measurements are well
to use this method, it is usually necessary to specify up on the scales.
in the motor purchase arrangements that the motor
be calibrated since an additional cost is normally In many cases, accuracy level requirements will
involved. Calibration data are similar to typical motor permit the use of a clip-on type ammeter-voltmeter.
performance data with the exception that, instead of Clip-on instruments with accuracies of 3% full scale
being merely typical, the calibration data represent are available.
the performance of a specific motor, based on a test
of the motor. The motor is calibrated over a range of 11.4 Power transmission losses
operation. Electrical input data and other data
sufficient for the determination of power output are Several types of power transmission equipment are
obtained in the calibration. The calibration normally used in driving fans. Those in which power
provides data for operation at nameplate voltage, but transmission losses should be considered in the
may include data for operation at voltages 10% determination of fan power input include belt drives,
greater and 10% less than nameplate voltage. It is gear boxes, fluid drives, and electromechanical
important that the power supplied to the motor during couplings.
the field test be consistent with that used in its
calibration. The phase voltage should stable and Information as to whether the fan power input ratings
balanced, and the average should be within 2% of include power transmission losses is included in the
the voltage at which the motor was calibrated. The published performance ratings or is otherwise
field test measurements and the calculations available from the fan manufacturer. It is important
involved in the determination of motor power output that this be established and that the fan power input
are the same as those described in Section 11.2.2 for be determined accordingly in order to provide a valid
use with typical motor performance data. The fan comparison of field test results to the fan
power input is the motor power output minus the performance ratings. In most cases, fan power input
power transmission loss, where applicable. ratings do not include power transmission losses.

A calibrated motor provides accurate data to 11.4.1 Estimating belt drive losses. In view of the
determine motor power output. However, the cost of lack of published information available for use in
the calibration is a limiting factor in the use of this calculating belt drive losses, a graph is included in
method in field tests. For low horsepower Annex L for this purpose. As indicated in the graph,
applications, the fan manufacturer may be able to belt drive loss, expressed as a percentage of motor
calibrate a motor. power output, decreases with increasing motor
power output and increases with increasing speed.
11.2.4. Torquemeters. Another method to determine This graph is based on the results of over 400 drive
fan power input involves the use of a torquemeter loss tests provided to AMCA by drive manufacturers.
installed between the fan and the driver. The use of a The graph serves as a reasonable guide in
torquemeter requires some prearrangement with the evaluating belt drive losses. The calculation of belt
purchaser, who would normally have specified such drive loss, using this graph, is included in many of the
equipment, so that site conditions can be altered to examples in Annex A.
13
AMCA 203-90 (R2007)

11.4.2 Estimating other transmission losses. For determination is required. The pressures at Planes 1
other types of power transmission equipment, consult and 2 are based on the static pressure
the fan manufacturer to establish whether measurements made for the purpose of determining
transmission losses are included in the fan ratings, the fan static pressure. The pressure at Plane 3 is
and if so, request the magnitudes of the losses obtained by averaging static pressure measurements
allowed in the ratings. Otherwise, it will be necessary made concurrent with the velocity pressure
to consult the manufacturer of the power measurements made in a traverse of Plane 3. The
transmission equipment for the information regarding absolute pressure at a plane is calculated by using
transmission losses. the static pressure at the plane and the barometric
pressure. For this reason, it is important that the
11.5 Accuracy barometric pressure be determined for the
atmosphere to which static pressure measurements
The uncertainty analyses presented in Annex T are referred. The temperatures used in density
indicate that the uncertainties in fan power input determinations are measured at the planes of
determinations are expected to range from 4% to 8%. interest.
This range is based on considerations of the
conditions encountered in most field test situations, 13.3 Additional data
estimated accuracies of the various test methods
presented in this publication and allowances for Additional data required in the determination of
uncertainties in the determinations of power density depends on the gas stream as indicated
transmission losses. below:

12. Fan Speed 1) For air, the wet-bulb temperature is required


unless it is otherwise known that the air is
12.1 Speed measuring instruments saturated with water vapor or that the water
vapor content of the air is insignificant. It should
Measure speed with a revolution counter and be noted that incorrect assumptions as to
chronometer, a stroboscopic tachometer, an whether the air is dry or saturated can result in
electronic counter-timer, or any other precision type substantial errors in density determinations.
tachometer which has a demonstrated accuracy of
0.5% of the measured value. Friction driven and 2) For gases other than air, the normal procedure is
magnetic type pickups should not be used in low fan to rely on process personnel for the data
power ranges where they can influence speed and necessary to determine the density of the gas.
fan power input measurements. The information provided will include density or
data sufficient to calculate the density, which
12.2 Speed measurements should be for stated conditions of temperature
and pressure.
Establish the speed by averaging a minimum of three
measurements made during the test determination 13.4 Density values
period. The variation in the measurements should not
exceed 1% for any single point of operation. Gas stream density can be established when the
pressure, temperature, and additional data, as
indicated in Section 13.3, have been obtained.
13. Densities
Procedures for establishing density are described in
the examples in Annex M and are further illustrated in
13.1 Locations of density determinations the field test examples in Annex A.
Determine the densities of the gas stream for Plane Although the pressure and temperature of the gas
1, the fan inlet; and for Plane 3, the velocity pressure stream must be obtained for each plane at which a
measurement plane. In addition, the density at Plane density value is required, it is usually necessary to
2, the fan outlet, must be determined whenever the obtain additional data, such as the wet-bulb
fan total pressure, the fan velocity pressure, or an temperature, for only one plane in order to establish
SEF at the outlet side of the fan is required. the densities at all planes. The densities at the planes
for which the additional data is not obtained can be
13.2 Data required at each location calculated, providing the gas stream does not change
composition or undergo a change in phase between
The pressure and temperature of the gas stream planes. The calculation is based on density being
must be obtained for each plane at which a density directly proportional to absolute pressure and

14
AMCA 203-90 (R2007)

inversely proportional to absolute temperature. thermometer should be accurate within 5°F of the
measured value and readable to 5°F or finer.
13.4.1 Example calculation - ρ3 from ρ1. Use Figure
N.1 of Annex N to establish the density of air at Plane The temperature determination should be
1 based on the test determinations of barometric representative of the average temperature of the gas
pressure, pb, and the following Plane 1 values: stream throughout the plane of interest. When the
temperature varies with time or temperature
Ps1, static pressure, in. wg stratification exists at the measurement plane,
td1, dry-bulb temperature, °F several temperature measurements may be
tw1, wet-bulb temperature, °F necessary in order to obtain a representative
average. At elevated temperatures, the thermometer
may have to be shielded to prevent radiation effects
The following data are obtained for Plane 3:
from exposed heat sources.
Ps3, static pressure, in. wg
Locate the wet-bulb thermometer downstream from
td3, dry-bulb temperature, °F
the dry-bulb thermometer in order to prevent the dry-
bulb temperature measurement from being adversely
Calculate the density at Plane 3 as follows: affected. The wet-bulb thermometer wick should be
clean, closely fitted, and wetted with fresh water. The
⎛ P + 13.6 pb ⎞ ⎛ t d1 + 460 ⎞ velocity of the air over the wick should be between
ρ3 = ρ1 ⎜ s3 ⎟⎜ ⎟ 700 and 2000 fpm. Use a sling psychrometer to
⎝ 13.6 p1 ⎠ ⎝ t d3 + 460 ⎠ obtain dry and wet-bulb air temperature
measurements at the fan inlet for free inlet fans.
Where:
13.6 Barometric pressure
p1 = the absolute pressure, in. Hg at Plane 1,
calculated as follows: Use a portable aneroid barometer for field test
determinations of barometric pressure when an
p1 = pb + (Ps1/13.6) acceptable site barometer is not available. The
barometer should be accurate within 0.05 in. Hg of
In this manner, ρ3 can be calculated without having to the measured value. Determine the test value of
measure the wet-bulb temperature at Plane 3. These barometric pressure by averaging measurements
equations can be used for gases other than air and made at the beginning and end of the test period.
can be adapted for use in calculations involving any
two planes, subject to the limitations noted earlier. When the test value of barometric pressure is to be
based on data obtained from a nearby airport, it is
In the example calculation of ρ3, pb is determined for important that the data include the barometric
the atmosphere to which the measurements of Ps1 pressure for the airport site and the elevation for
and Ps3 are referred. Refer static pressure which the pressure was determined (often the
measurements to a common atmosphere. When barometric pressure is corrected to sea level). This
the pressures cannot be referred to a common pressure value must then be corrected to the test site
atmosphere, the absolute pressure for each plane is elevation. Barometric pressure decreases
calculated by using the static pressure measurement approximately 0.1 in. Hg for every 100 ft increase in
at the plane and the barometric pressure for the elevation
atmosphere to which the static pressure
measurement is referred. However, for the purposes 13.7 Accuracy
of accuracy, static pressure measurements that are
used in the determination of fan static pressure must As indicated in Annex T, uncertainties in density
be referred to a common atmosphere. determinations are expected to be less than 3%.
However, care must be exercised in obtaining
13.5 Temperatures representative test measurements in order to prevent
the uncertainties from exceeding this value.
Measure temperatures with mercury-in-glass, dial, or
thermocouple type thermometers. For temperatures 14. Conversion Calculations
through 220°F, the thermometer should be accurate
within 2°F of the measured value and readable to 1°F Generally, the test fan will be operating at a speed
or finer. For temperatures above 220°F, the and inlet density that are somewhat different from the

15
AMCA 203-90 (R2007)

fan performance rating values of fan speed and inlet Work required to accommodate test
density. In order to provide a common basis for measurements (drilling of traverse holes,
comparing the field test results to the fan installation of static pressure taps and
performance ratings, each of these two items must thermometer wells, etc.) should be completed
be the same in both sets of data. This can be prior to the test date.
accomplished by converting the results of the field
test to the speed and density conditions of the fan 4) System Effect Factors, if any, must be
performance ratings. The equations for the established prior to the conduct of the test.
conversion are as follows.
5) The expected test uncertainties must be agreed
Qc = Q (Nc / N) upon prior to the test (see Annex T).

Psc = Ps (Nc / N)2 (ρc / ρ) 6) Responsibility for the cost of the test or any fan-
system modifications required as a result of the
Ptc = Pt (Nc / N)2 (ρc / ρ) test should be established.

7) Prior to testing, an inspection must be made to


Pvc = Pv (Nc / N)2 (ρc / ρ)
ensure that the fan is installed in accordance with
the fan manufacturer’s recommendations. The
Hc = H (Nc / N)3 (ρc / ρ) duct system should also be inspected for
compliance with design specifications, conditions
Where the subscript c designates values converted of filters, abnormal duct restrictions, etc.
to specified conditions, and items without the
subscript c are field test values. 8) The majority of fan field performance tests cover
a single point of operation, namely, the design
These conversion equations do not account for the duty. If it is deemed necessary to cover several
effect of the compressibility of the gas stream. points of operation, provision must be made in
However, since the test fan usually operates at advance for changing the system resistance. The
conditions of speed and inlet density that are means used to vary the system resistance must
reasonably close to the quoted fan performance, the not cause adverse flow conditions in the vicinities
conversion calculations usually result in small of the fan and measurement planes. If the fan
changes from field test values and the effect of the cannot be tested at the quoted system design
compressibility of the gas stream is considered to be point, then it is sufficient for the evaluation of fan
negligible. Where test conditions are considerably field performance to establish the proximity of the
different than design conditions, the effect of field test point to any portion of the fan
compressibility may need to be considered. performance rating curve within the limitations of
the uncertainty analysis (see Annex T).
15. Test Preparation
9) It must be established that the system remains
15.1 The following items should be agreed upon by constant for the duration of the test. Modulating
all interested parties prior to the start of a field dampers should be set in a fixed position, no
performance test: process changes shall be undertaken, etc.
Variable inlet vane controls or inlet box dampers
1) AMCA Publication 200, Air Systems, AMCA must be set in the full open position for the
Publication 201, Fans and Systems, and AMCA duration of the test, except when testing for
Publication 202, Troubleshooting, should be control characteristics.
reviewed and implemented before starting the
field test. 10) All precautions to ensure the safety of test
personnel must be observed.
2) Personnel conducting field tests on fans must be
technically competent and fully conversant with 11) The fan-system should be operated for a length
all four parts of the AMCA Fan Application of time sufficient to ensure steady state
Manual. The person responsible for conducting conditions prior to the start of the test.
the test should be designated and agreed upon
by all parties. 12) It is advisable that representatives of all parties
interested in the test results be present at the
3) The test instrumentation and locations of test time of the test to cover their areas of
measurement planes should be established. responsibility.

16
AMCA 203-90 (R2007)

15.2 It is recommended that as a minimum, the 2) Static and total pressure manometer tubing must
following equipment be taken to or be otherwise be “pinched off” prior to inserting or removing the
available at the job site: Pitot-static tube from the test duct. Release both
legs of the tubing simultaneously after the Pitot-
1) Pitot-static tubes of suitable lengths for the static tube is inside the test duct and properly
maximum duct size to be traversed. oriented. Failure to release simultaneously may
Considerations should be given to the use of a result in manometer fluid being blown from the
double reverse tube in dirty atmospheres. manometer.

2) Manometers suitable for measuring static 3) Loop the manometer tubing well above the
pressures. Manometer fluids other than water are manometer so that any fluid which is
acceptable, provided the specific gravity is inadvertently blown from the gauge will drain
known. A spare bottle of manometer fluid is back into the manometer.
advisable.
4) The Pitot-static tube is intended for measuring
3) Inclined manometer suitable for measuring pressures in relatively clean gases. When using
velocity pressures. Pitot-static tubes in dirty, wet, or corrosive
atmospheres, both legs of the Pitot-static tube
4) Flexible tubing of suitable length to enable must be cleaned out frequently during the test.
manometers to be installed at a convenient Since fan pressure readings are never strictly
location. steady, absence of fluctuations is an
indication of a plugged Pitot-static tube.
5) Tubing couplings and “T” type tubing connectors. Consider using a double reverse tube in these
situations.
6) Thermometers to cover the range of anticipated
temperatures. 5) When making measurements in wet gas
streams, continually check for the presence of
7) Sling psychrometer for obtaining dry-bulb and moisture in the tubing. Clear plastic tubing is
wet-bulb temperatures. ideal from this standpoint. If moisture collects in
the tubing, immediately remove the Pitot-static
8) Clip-on ammeter-voltmeter, power analyzer, or tube and clean the inside of the tubing and Pitot-
other suitable electrical measurement static tube before proceeding with the test.
instruments for the determination of fan power
input. 6) Before performing any work inside a fan,
ductwork, or other system components, make
9) Fan speed measurement instrument. certain that the fan motor starter is “locked out.”

10) Aneroid barometer. 7) The area at the plane of flow measurement


should be measured internally to account for
11) Flashlight, tape, measuring rule, hand tools, internal insulation or other obstructions.
coveralls, etc.
8) Do not rely on damper control indicators to
12) Test data sheets, calculator, and necessary ensure that dampers are fully open. Check
drawings. visually.

13) Complete AMCA Fan Application Manual 9) Measure temperatures on both sides of double
containing Publications 200, 201, 202, and 203. inlet fans as temperature differences may exist
between each side.
16. Precautions
10) When measuring in high temperature, corrosive
The following precautions should be observed when or explosive atmospheres, instruments should be
conducting a field test: selected for suitability for such atmospheres.

1) Connect the Pitot-static tube to the manometers 17. Typical Fan-System Installations
according to anticipated pressures, i.e., whether
the pressures are positive or negative, and the A fan assembly may include any number of
magnitudes of pressures. appurtenances: variable inlet vanes, inlet boxes, inlet

17
AMCA 203-90 (R2007)

box dampers, outlet dampers, inlet screens, belt a) The operations of ovens, furnaces, paint booths,
guards, inlet bells, diffusers (evasés). Alternately, air conditioning equipment, other fans, and
these items may be included in the fan-system similar items that may supply or exhaust air from
installation, but not be a part of the fan assembly. In the building in intermittent or modulating
order to determine the proper field test procedure fashions.
and to provide a valid basis for comparing field test
results to the fan performance ratings, it is important b) The use of doors providing access to the
to establish which of these items are considered a building. The effect is most significant when large
part of the fan and which are considered a part of the doors that are normally closed are kept open for
system. The fan performance ratings may be extended periods such as in loading operations.
assumed to include the appurtenances that are
established as being a part of the fan assembly. c) The velocity and direction of the wind outside the
building, particularly in conjunction with the item
The locations of the fan inlet and fan outlet depend immediately above and as it may affect the flow
on whether specific appurtenances are considered of air from the outlet of the ventilator.
to be a part of the fan assembly. If the assembly
includes an inlet box, the fan inlet is the inlet to the d) The use of interior doors that my restrict the flow
inlet box. For a fan assembly that includes a diffuser, of air from areas normally expected to be
the fan outlet is the outlet of the diffuser. ventilated.

In the case of heating, ventilating, and air- Assuming that these difficulties can be resolved and
conditioning equipment, the field test procedure will the desired system is fixed for the duration of the test,
depend on whether the equipment is a factory determine the fan performance by using one of the
assembled central station unit, a built-up unit, or a following methods:
packaged unit (see Section 17.4).
1) Make field test measurements sufficient for
The performance ratings for a fan that includes inlet determining fan static pressure, fan power input,
box dampers, variable inlet vanes or outlet dampers fan speed, and the density of the air at the fan
cover operation of the fan with these items in the full inlet. In this method for testing a free inlet, free
open positions. In order to be able to compare the outlet fan, the fan static pressure is calculated as
field test results to the fan performance ratings, it is the static pressure on the outlet side of the fan
essential that these items be fixed in their full open less the static pressure on the inlet side of the
positions for the duration of the test. In addition, when fan: Ps = Ps2 - Ps1. The static pressure
the loss through a damper must be calculated, it is measurements involved must be referred to the
essential that the damper blades be fixed in their full same atmospheric pressure and made at
open positions during the test since this is the locations sufficiently distant from the fan inlet and
condition on which the damper pressure loss ratings outlet so as to be unaffected by the velocity of the
are based. This consideration arises when a damper, air entering and leaving the fan. Using the fan
which is not considered a part of the fan is located manufacturer’s certified performance ratings,
between a static pressure measurement plane and draw a performance curve for the fan for
the fan. In order to determine the fan static pressure, operation at the test values of fan speed and
the loss through the damper must be calculated. In entering air density. Determine the fan air flow
these cases, the calculation of the loss is based on rate by entering this curve at the test values of
the performance ratings for the damper. fan static pressure and fan power input (see
Example 5C in Annex A).
17.1 Free inlet, free outlet fans
2) Use the method as described above with the
It is difficult to achieve an accurate field test of a free exception that the performance curve is
inlet, free outlet fan. The most obvious problem is the established by a laboratory test of the fan,
lack of a suitable location for the velocity pressure conducted in accordance with AMCA Standard
measurement plane. In addition, in the case of 210. For the laboratory test, the fan must be set
ventilators that supply or exhaust air from a building- up in a manner that duplicates the field
the most commonly encountered applications of free installation conditions. That is, all appurtenances
inlet, free outlet fans-it is extremely difficult to define, must be in place and any restrictions or
set, and maintain for the duration of the test the obstructions to the free flow of air into the fan
“normal” system condition. Items affecting the system inlet and away from the fan outlet must be
include: accurately duplicated in the laboratory test setup.

18
AMCA 203-90 (R2007)

3) Install a duct on the inlet side of the fan for the Ps = Ps2 + SEF 1 +SEF 2 + ... + SEF n
purpose of providing a location for the velocity
pressure measurement plane. All of the test 17.3 Ducted inlet, ducted outlet fans
measurements and calculations in this method
for testing a free inlet, free outlet fan are the In this type of fan-system configuration, there is no
same as those required for a fan with a ducted special consideration in the calculation of fan static
inlet and a free outlet. The cross-sectional shape pressure. The equation for this calculation is:
and area of the duct, which is temporarily
installed for purposes of the test, should be Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2 + ... + SEF n
selected on the basis of minimizing its
interference with the flow of air into the fan inlet In this configuration, the flow conditions on the inlet
while providing velocity pressure of magnitudes side of the fan are usually more favorable for the
that can be accurately measured. The length of location of the velocity pressure measurement plane.
the duct should be a minimum of twice its
diameter or equivalent diameter, and the 17.4 Ducted inlet, free outlet fans
entrance to the duct should be flared in order to
reduce the entrance loss. The velocity pressure In this type of fan-system configuration, the static
measurement plane should be located a pressure at the fan outlet, Ps2, is zero gauge
minimum of 1.5 diameters or equivalent
pressure, referred to the atmospheric pressure in the
diameters downstream from the duct inlet. The
region of the fan outlet. However, the gas stream may
effect of this duct on the system is negligible, but
be discharging from the fan into a region in which the
in changing the pattern of the flow of air into the
atmospheric pressure is somewhat different from that
fan inlet, it may affect the performance of the fan
to which all other pressure measurements are
slightly. Applications of this method of test are
referred. When this possibility exists, it is essential
presented in Examples 5A and 5B in Annex A.
that the static pressure measurements in the region
The equation for calculating fan static pressure
of the fan outlet be referred to the same atmospheric
for this configuration is:
pressure as used in all other pressure
measurements.
Ps = Ps2 - (Ps1 + Pv1)
Ps = -Ps1 - Pv1 + SEF 1 + SEF 2 + ... + SEF n
17.2 Free inlet, ducted outlet fans
17.5 Air handling units
In the calculation of fan static pressure for this type of
fan-system configuration, the sum of the static
This category consists of draw-through and blow-
pressure at the fan inlet, Ps1, and the velocity
through types of equipment assemblies used in
pressure at the fan inlet, Pv1, is considered to be heating, ventilating, and air-conditioning applications.
equal to the sum of the static pressure, Psx, and the In addition to fans, these equipment assemblies may
velocity pressure, Pvx, at a point sufficiently distant include any number of combinations of coils, filters,
from the fan inlet as to be in still air. At this point, the access sections, humidifiers, mixing boxes, dampers,
static pressure is zero, and the velocity pressure in etc. Air handling units include packaged units, factory
still air is zero. assembled central station units, and built-up units.
The basis used in establishing the air performance
Ps1 + Pv1 = Psx + Pvx = 0 ratings for each of these unit types is described
below. It is important that the field test method
This consideration, which is the same as that used in correspond to the rating method in each case.
the methods for testing fans for performance rating
purposes, charges to the fan the losses incurred in 17.5.1 Packaged units. This type of unit is supplied
accelerating the air into the fan inlet and eliminates and rated by the manufacturer as an assembly. The
inaccuracies which may occur in any attempt to static pressures at the inlet and outlet to the
measure velocity pressure and static pressure at the assembly and the velocity pressure at the inlet to the
fan inlet. Since Ps1 + Pv1 = 0, the equation for assembly are used in calculating the static pressure
calculating fan static pressure for this configuration generated by this type of air handling unit. See
is: Examples 4C and 4D in Annex A.

17.5.2 Factory assembled central station units.


The air performance ratings for this type of unit are
based on the operation of the fan section assembly
only, but include the effects of the air flow conditions
19
AMCA 203-90 (R2007)

entering and leaving the fan section which are


created by accessory equipment such as plenums,
coils, filters, mixing boxes, etc. The fan section
assembly includes the fan and the cabinet in which
the fan has been installed. The accessory items are
considered to be included in the system in which the
fan section operates. The static pressure and the
velocity pressure at the inlet of the fan section and
the static pressure at the fan section outlet, which
coincides with the fan outlet, are used in calculating
the static pressure generated by the fan section
assembly. See examples 4B and 4E in Annex A.

17.5.3 Built-up units. Built-up units are similar to


factory assembled central station units, except that in
built-up units, the components are normally obtained
from a number of equipment suppliers and the unit is
assembled at the installation site. The fans which are
used in built-up units are rated as free-standing,
unencumbered by the cabinets in which they are
installed. In the field test determination of the
performance of the fan, the static pressure and
velocity pressure at the fan inlet and the static
pressure at the fan outlet are used in calculating the
fan static pressure. An SEF that accounts for the
effect of the cabinet is normally included in this
calculation, and it may be necessary to include an
SEF to account for the conditions at the fan outlet.
See Example 4A in Annex A.

20
AMCA 203-90 (R2007)

Annex A. Field Test Examples

This annex contains examples of field tests. The examples are presented in detail and cover several types of fan-
system combinations. Field test procedures are illustrated in a variety of situations. Portions of the procedures are
typical for all fan-system installations. Other portions of the procedures demonstrate methods for dealing with the
more difficult features encountered in some installations. Not all of the possible fan-system combinations are
included in the examples, but it is expected that the examples will provide sufficient guidance for dealing with those
cases not covered.

EXAMPLES OF FANS, INSTALLATION TYPE B: FREE INLET, DUCTED OUTLET

1A: Centrifugal Forced Draft Fan


1B: Centrifugal Forced Draft Fan with Inlet Silencers
1C: Axial Forced Draft Fan with Inlet Silencers
1D: Centrifugal Fans in Parallel

EXAMPLE OF FANS, INSTALLATION TYPE D: DUCTED INLET, DUCTED OUTLET

2A: Utility Fan in a Ventilating System


2B: Centrifugal Fan in a Sawdust Conveying System
2C: Axial Fan in a Dryer System
2D: Centrifugal Fan in a Scrubber System
2E: Centrifugal Fan in a Process System
2F: Axial Fan in a Ventilation System
2G: High Pressure Centrifugal Fans in Series

EXAMPLES OF FANS, INSTALLATION TYPE C: DUCTED INLET, FREE OUTLET

3A: Centrifugal Fan in an Exhaust System


3B: Axial Fan in an Exhaust System
3C: Centrifugal Fan in a Scrubber System
3D: Centrifugal Roof Ventilator with Ducted Inlet

EXAMPLES OF AIR HANDLING UNITS

4A: Centrifugal Fan in a Built-up Air conditioning Unit


4B: Central Station Air Conditioning Unit, Factory Assembled Draw-Through Type
4C: Packaged Air Conditioning Unit
4D: Packaged Air Conditioning Unit
4E: Central Station Air Conditioning Unit, Factory Assembled Blow-Through Type

EXAMPLES OF FANS, INSTALLATION TYPE A: FREE INLET, FREE OUTLET

5A: Free Inlet, Free Outlet Roof Ventilator with temporary duct
5B: Free Inlet, Free Outlet Propeller Fan with temporary duct
5C: Free Inlet, Free Outlet Roof Ventilator as installed

21
AMCA 203-90 (R2007)

EXAMPLE 1A: CENTRIFUGAL FORCED DRAFT FAN

SEF 1
DIFFUSER

3 2

L
A2
VARIABLE
INLET VANES
A3

SIDE VIEW OUTLET SIDE VIEW

LOCATIONS OF
PLANES 2 AND 3

ORIENTATION
OF PITOT TUBE

COMMENTS

1. The variable inlet vanes are considered part of the 3. Measure td1 and tw1 in the path of the air flowing
fan. Performance ratings for fans with inlet vanes into the fan inlets. Determine pb for the general
cover operation with the inlet vanes in their full open vicinity of the fan. Measure td3 in Plane 3. All of these
position. In order to be able to compare the test measurements are used in the determination of
results to the fan performance ratings, it is essential densities at the various planes of interest.
that the inlet vanes be fixed in their full open positions
for the duration of the test. 4. Measure the fan speed and the motor amps, volts,
and, if possible, watts. Record all pertinent motor
2. Determine Pv3 by using the root mean square of nameplate data, including volts (NPV) and full load
the velocity pressure measurements made in a amps (FLA). If the motor power output is to be
traverse of Plane 3, located near the end of the fan estimated by using the phase current method
diffuser (evasé). Determine Ps3 by averaging the described in Annex K, it is not necessary to measure
static pressure measurements made in the same motor watts; however, it may be necessary to
traverse. Procedures for the traverse are described in disconnect the drive and measure the no load amps
Section 9.4. These velocity pressure and static (NLA) if the motor is not operating at or near its full
pressure measurements are susceptible to error due load point (refer to Annex K).
to the turbulence existing in the region of the fan
outlet. In addition, it is undesirable to have Plane 3 5. SEF 1 is due to the effect of insufficient length of
located in a diverging airway. However, no other duct at the fan outlet. In order to calculate the value
more suitable location for Plane 3 exists in this of SEF 1, it is necessary to measure the length of the
example. It is recommended that the Pitot-static tube outlet duct, L; the outlet area of the fan, A2; and the
be oriented so that its nose is aligned with the blast area of the fan.
anticipated flow streams, particularly near the walls of
the diffuser, as shown in the diagram. Determine the 6. The sum of the static pressure, Ps1, and velocity
area of the traverse plane, A3, which is located at the pressure, Pv1, at the inlets of a fan with unrestricted
tip of the Pitot-static tube, as shown in the diagram, inlets is considered to be equal to the sum of the
not at the location of the Pitot-static tube access static pressure, Psx, and the velocity pressure, Pvx, at
holes in the diffuser. a point sufficiently distant from the fan inlets as to be
in still air. At this point, the static pressure is zero, and

22
AMCA 203-90 (R2007)

the velocity pressure in still air is zero. GENERAL

Ps1 + Pv1 = Psx + Pvx = 0 VIVs in full open positions.


Fan direct connected to motor.
This consideration, which is the same as that used in
the methods for testing fans for performance rating CALCULATIONS
purposes, charges to the fan losses incurred in
accelerating the air into the fan inlets and eliminates DENSITIES
the inaccuracies which arise in any attempt to
measure the velocity pressure and static pressure at For fan inlet conditions of:
the fan inlets. To calculate the fan static pressure:
td1 = 85°F
Ps = Ps2 - Ps1 - Pv1 + SEF 1 tw1 = 63°F
= Ps2 - (Ps1 + Pv1) + SEF1 p1 = pb
= 28.91 in. Hg
Since:
Use Figure N.1 in Annex N to obtain ρ1 = 0.0701
Ps1 + Pv1 = 0 lbm/ft3
Ps = Ps2 + SEF 1
The density at Plane 3:
7. In order to compare the test results to the quoted
fan curve drawn for operation at 1780 rpm and
⎛ P + 13.6 pb ⎞ ⎛ t d1 + 460 ⎞
0.0701 lbm/ft3 density, it is necessary to convert the ρ3 = ρ1 ⎜ s3 ⎟⎜ ⎟
results to the specified conditions. In this case, the ⎝ 13.6 p1 ⎠ ⎝ t d3 + 460 ⎠
test conditions are identical to the specified ⎛ 14.4 + 13.6 × 28.91 ⎞ ⎛ 545 ⎞
= 0.0701⎜
conditions and no calculations are required. ⎝ 13.6 × 28.91 ⎟⎠ ⎜⎝ 556 ⎟⎠
= 0.0712 lbm/ft 3
OBSERVATIONS

SITE MEASUREMENTS In this case, ρ2 is considered to be equal to ρ3.

pb = 28.91 in. Hg FLOW RATES


td1 = 85°F
tw1 = 63°F V3 = 1096 (Pv3/ρ3)0.5
td3 = 96°F = 1096 (1.52/0.0712)0.5
Ps3 = 14.4 in. wg = 5064 fpm
Pv3 = 1.52 in. wg
N = 1780 rpm Q3 = V3A3
A2 = 11.94 ft2 = 5064 × 11.3
A3 = 11.3 ft2 = 57223 cfm
Blast Area = 7.76 ft2 Q = Q1
L = 3 ft.
= Q3 (ρ3/ρ1)
= 57223 (0.0712/0.0701)
MEASURED MOTOR DATA
= 58121 cfm
Volts = 570, 560, 572
FAN POWER INPUT
= 567 av.
Amps = 160, 166, 163
Measured amps/FLA = (163/181)
= 163 av.
= 0.90
= 90%
MOTOR NAMEPLATE DATA
Annex K indicates that Equation A will provide a
200 hp, 3 phase, 60 hertz
reasonably accurate estimate of motor power output
575 volts, 1800 rpm, 181 FLA
for a 200 hp motor operating at 90% FLA.

23
AMCA 203-90 (R2007)

Hmo = 200 (163/181) (567/575) FAN STATIC PRESSURE


= 178 hp
Since A2 is greater than A3, there may be some
Since the fan is direct connected to the motor: conversion of velocity pressure to static pressure
between Planes 3 and 2. However, the amount of
H = Hmo conversion will be very small relative to the static
= 178 hp pressure measured at Plane 3 and ignoring any
change in static pressure from Plane 3 to Plane 2 will
SYSTEM EFFECT FACTOR have no appreciable effect on the test results.
Therefore, Ps2 is considered equal to Ps3.
AMCA Publication 201-90, Figures 7.1 and 8.3
indicate the following calculations: Ps = Ps2 + SEF 1
= 14.4 + 0.57
Q2 = Q3 (ρ3/ρ2) = 14.97 in. wg
= 57223 (0.0712/0.0712)
= 57223 cfm CONVERSION TO SPECIFIED CONDITIONS

V2 = (Q2/A2) Qc = Q
= (57223/11.94) = 58121 cfm
= 4793 fpm Psc = Ps
= 14.97 in. wg
Duct diameter equivalent to the diffuser outlet area: Hc = H
= 178 hp
De2 = 4 A2 / π
= ( 4 × 11.94 ) / π
= 3.9 ft.

Figure 8.3 shows that for velocities over 2500 fpm,


100% effective duct length is one duct diameter per
1000 fpm,

= De2 (V2/1000)
= 3.9 (4793/1000)
= 18.7 ft

L in % effective duct length


= (L/18.7) 100
= (3/18.7) 100
= 16%

Blast area ratio = Blast Area/A2


= 7.76/11.94
= 0.65

For blast area ratio of 0.65, and 16% effective duct


length, Figure 8.3 shows System Effect Curve U
applies. For 4793 fpm velocity and curve U, Figure
7.1 shows SEF 1 = 0.6 in. wg at 0.075 lbm/ft3. At
0.0712 lbm/ft3.

SEF 1 = 0.6 (0.0712/0.075)


= 0.57 in. wg

24
AMCA 203-90 (R2007)

EXAMPLE 1B: CENTRIFUGAL FORCED DRAFT FAN WITH INLET SILENCERS

TEMPORARY
DUCT

DIFFUSER
STATIC 3a 3b
PRESSURE TAPS 0.5 De
SILENCERS

A2

SEF 1

VARIABLE INLET VANES


SIDE VIEW 2 OUTLET SIDE VIEW

COMMENTS

1. This fan, as supplied and rated by the entrances to the inlet boxes (Plane 1). Determine Ps2
manufacturer, includes the variable inlet vanes and by averaging the pressure measurements at each of
inlet boxes, but does not include the silencers. four static pressure taps located near the end of the
Performance ratings for fans with inlet vanes cover fan diffuser (evasé). See Annex E for details of static
operation with the inlet vanes in the full open pressure taps.
positions. In order to be able to compare the test
results to the fan performance ratings, it is essential 4. Measure td3 and tw3 near the inlet ducts. Determine
that the inlet vanes be fixed in their full open positions pb for the general vicinity of the fan. Measure td2 in
for the duration of the test. Plane 2. All of these measurements are used in the
determination of densities at the various planes of
2. Determine Pv3a and Pv3b by using the root mean interest.
square of the velocity pressure measurements made
in traverses of Planes 3a and 3b. A3a and A3b are the 5. Measure the fan speed and the motor amps, volts,
areas traversed. Determine Ps3a and Ps3b by and if possible, watts. Record all pertinent motor
averaging each of the two sets of static pressure nameplate data, including volts (NPV) and amps
measurements made in the same traverses. (FLA). If the motor power output is to be estimated by
Procedures for traverses are described in Section using the phase current method described in Annex
9.4. Ps3a and Ps3b are used in determining the density K, it is not necessary to measure motor watts;
at the traverse plane. A location for Plane 3 however, it may be necessary to disconnect the drive
measurements may be obtained by installing ducts and measure the no load amps (NLA) if the motor is
on each silencer inlet, as shown in the diagram. The not operating at or near its full load point. Refer to
ducts should be a minimum of one equivalent Annex K.
diameter in length, and have flared inlets to reduce
entrance losses and provide more uniform velocity 6. SEF 1 is due to the effect of there being no duct
profiles at the pressure measurement planes. at the fan outlet. In order to calculate the value of
SEF 1, it is necessary to measure the fan outlet area,
3. Measure Ps1a and Ps1b at locations close to the A2, and the blast area of the fan.
entrances to the inlet boxes and in planes which are
substantially equal in area to the planes of the 7. To calculate the fan static pressure:

25
AMCA 203-90 (R2007)

Ps = Ps2 - Ps1 - Pv1 + SEF 1 CALCULATIONS

Where: DENSITIES

Pv1 = (Q/1096A1)2 ρ1 For Plane 3 conditions of:

8. In order to compare the test results to the quoted td3 = 85°F


fan curve drawn for operation at 1180 rpm and 0.075 tw3 = 58°F
lbm/ft3 density, it is necessary to convert the results
to the specified conditions. The basis for the Ps3 = (Ps3a + Ps3b)/2
calculations is described in Section 14. = (-0.65 - 0.70)/2
= -0.675 in. wg
OBSERVATIONS p3 = pb + (Ps3/13.6)
= 29.31 + (-0.675/13.6)
SITE MEASUREMENTS = 29.26 in. Hg

pb = 29.31 in. Hg Use Figure N.1 in Annex N to obtain ρ3 = 0.0712


td2 = 93°F lbm/ft3
td3 = 85°F
tw3 = 58°F It is assumed that the temperature at Plane 1 are the
Ps1a= -1.20 in. wg same as those at Plane 3. The density at Plane 1:
Ps1b= -1.30 in. wg
Ps2 = 10.1 in. wg ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ1 = ρ3 ⎜ s1 ⎟⎜ ⎟
Ps3a= -0.65 in. wg
⎝ 13.6 p3 ⎠ ⎝ t d1 + 460 ⎠
Ps3b= -0.70 in. wg
⎛ −1.25 + 13.6 × 29.31 ⎞ ⎛ 545 ⎞
Pv3a= 0.61 in. wg = 0.0712 ⎜ ⎟ ⎜ 545 ⎟
⎝ 13.6 × 29.26 ⎠⎝ ⎠
Pv3b= 0.62 in. wg
N = 1180 rpm = 0.0711 lbm/ft 3
A1a = A1b
= 12.5 ft2 The density at Plane 2:
A2 = 18 ft2
A3a = A3b ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
= 12.5 ft2 ρ2 = ρ3 ⎜ s2 ⎟⎜ ⎟
⎝ 13.6 p3 ⎠ ⎝ t d2 + 460 ⎠
Blast Area = 13.5 ft2
⎛ 10.1 + 13.6 × 29.31 ⎞ ⎛ 545 ⎞
= 0.0712 ⎜ ⎟⎜ ⎟
MEASURED MOTOR DATA ⎝ 13.6 × 29.26 ⎠ ⎝ 553 ⎠
= 0.0721 lbm/ft 3
Volts = 460, 455, 465
= 460 av
FLOW RATES
Amps = 257, 256, 258
= 257 av
V3a = 1096 (Pv3a/ρ3)0.5
MOTOR NAMEPLATE DATA = 1096 (0.61/0.0712)0.5
= 3208 fpm
200 HP, 3 phase 60 hertz
460 volts, 1180 rpm, 285 FLA Q3a = V3aA3a
= 3208 × 12.5
GENERAL = 40100 cfm

VIVs in full open positions. Fan direct connected to V3b = 1096 (Pv3b/ρ3)0.5
motor. The motor manufacturer advises that this = 1096 (0.62/0.0712)0.5
motor type has a peak efficiency of 91% at a power = 3234 cfm
factor of approximately 0.89.
Q3b = V3bA3b
= 3234 × 12.5
= 40425 cfm
26
AMCA 203-90 (R2007)

Q3 = Q3a + Q3b SYSTEM EFFECT FACTOR


= 40100 + 40425
= 80525 cfm AMCA Publication 201-90, Figures 7.1 and 8.3
indicate the following calculations:
Q = Q1
= Q3 (ρ3/ρ1) Q3 (ρ3/ρ2) = 80525 (0.0712/0.0721)
= 80525 (0.0712/0.0711) = 79520 cfm
= 80638 cfm
(Q2/A2) = (79520/18)
FAN POWER INPUT = 4418 fpm

Measured amps/FLA = (257/285) Blast area ratio = Blast Area/A2


= 0.90 = 13.5/18
= 90% = 0.75

Annex K indicates that Equation A will provide a For a blast area ratio of 0.75, and no duct, Figure 8.3
reasonably accurate estimate of motor power output shows System Effect Curve T applies. For 4418 fpm
for a 250 hp motor operating at 90% FLA. velocity and curve T, Figure 7.1 shows SEF 1 = 0.65
in. wg at 0.075 lbm/ft3. At 0.0720 lbm/ft3:
Hmo = 250 (257/285) (460/460)
= 225 hp SEF 1 = 0.65 (0.0721/0.075)
= 0.62 in. wg
As a check of this value, using the motor efficiency
data and the appropriate equation in Section 11.2.2: FAN STATIC PRESSURE

Pv1 = (Q1/1096 A1)2


3 × 257 × 460 × 0.89 × 0.91
Hmo = = (80638/1096 × 25)2 0.0711
746
= 0.62 in. wg
= 222 hp
Ps = Ps2 - Ps1 - Pv1 + SEF 1
Since the motor is not fully loaded, the power factor = 10.1 - (-1.25) - 0.62 + 0.62
and efficiency may be less, which would reduce Hmo = 11.33 in. wg
as calculated using the second method. However,
this is a reasonable check. The value of Hmo is CONVERSION TO SPECIFIED CONDITIONS
selected to be the average of the two results:
Qc = Q
Hmo = 224 hp = 80638 cfm

Since the fan is direct-connected to the motor, there Psc = 11.33 (0.075/0.0711)
is no drive loss, and: = 11.95 in. wg

H = Hmo Hc = 224 (0.075/0.0711)


= 224 hp = 236 hp

27
AMCA 203-90 (R2007)

EXAMPLE 1C: AXIAL FORCED DRAFT FAN WITH INLET SILENCER

TEMPORARY
PLANE 3
SHORT DUCT
LOCATION
3 STATIC PRESSURE TAPS
SILENCER
TRANSITION

0.5 De 5
DIFFUSER
INLET SECTION 2
BOX INNER
1 CYLINDER

SIDE VIEW L
GUIDE VANES

COMMENTS

1. This is a variable pitch axial flow fan. The fan See Annex E for details of static pressure taps. In this
assembly, as supplied and rated by the manufacturer, example, Ps2 is considered to be equal to Ps5.
includes the inlet box and diffuser section, but does
not include the silencer. It is essential that the blade 4. Measure td3 and tw3 near the entrance to the short
pitch angle be fixed for the duration of the test. This inlet duct. Determine pb for the general vicinity of the
blade angle should be agreed upon by all interested fan. Measure td5 in Plane 5. All of these
parties. measurements are used in the determination of
densities at the various planes of interest.
2. A temporary short duct is installed upstream of the
silencer to establish Plane 3 in which more uniform 5. Measure the fan speed and the motor amps, volts,
pressures can be obtained. The duct should be a and if possible, watts. Record all pertinent motor
minimum of one equivalent diameter in length, and nameplate data, including volts (NPV) and full load
have a flared inlet to reduce entrance losses and amps (FLA). If the motor power output is to be
provide a more uniform velocity profile at the estimated by using the phase current method
pressure measurement plane. Determine Pv3 by described in Annex K, it is not necessary to measure
using the root mean square of the velocity pressure motor watts; however, it may be necessary to
measurements made in a traverse of Plane 3. Ps3 is disconnect the drive and measure the no load amps
determined by averaging the static pressure (NLA) if the motor is not operating at or near its full
measurements made in the same traverse. load point. Motor performance data, supplied by the
Procedures for traverses are described in Section motor manufacturer, are used in the determination of
9.4. Ps3 is used in determining the density at the motor power output for this example.
traverse plane.
6. SEF 1 is due to the effect of insufficient length of
3. Measure Ps1 at a location close to the entrance to duct between the diffuser outlet and the elbow
the inlet box and in a plane which is substantially downstream of the diffuser. In order to calculate the
equal in area to the plane of the entrance to the inlet value of SEF 1, it is necessary to measure the length
box (Plane 1). Determine Ps5 by averaging the of the transition, L, and the outlet area of the diffuser,
pressure measurements at each of four static A2.
pressure taps located near the end of the fan diffuser.

28
AMCA 203-90 (R2007)

7. To calculate the Fan Static Pressure: CALCULATIONS

Ps = Ps2 - Ps1 - Pv1 + SEF 1 DENSITIES

Where: For Plane 3 conditions of:

Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1) td3 = 68°F


tw3 = 62°F
8. Axial fans are often rated in Fan Total Pressure.
Computation of Fan Total Pressure is illustrated in the p3 = pb + (Ps3/13.6)
CALCULATIONS section of this example. = 29.8 + (-1.40/13.6)
= 29.70 in. Hg
9. In order to compare the test results to the quoted
fan curve drawn for operation at 880 rpm and 0.0740 Use Figure 20 in Annex N to obtain ρ3 = 0.0744
lbm/ft3 density, it is necessary to convert the results lbm/ft3
to the specified conditions. In this case, the test
conditions are identical to the specified conditions It is assumed that td1 = td3. The density at Plane 1:
and no calculations are required.

OBSERVATIONS ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞


ρ1 = ρ3 ⎜ s1 ⎟⎜ ⎟
⎝ 13.6 p3 ⎠ ⎝ t d1 + 460 ⎠
SITE MEASUREMENTS ⎛ −1.8 + 13.6 × 29.8 ⎞ ⎛ 528 ⎞
= 0.0744 ⎜ ⎟⎜ ⎟
pb = 29.8 in. Hg ⎝ 13.6 × 29.70 ⎠ ⎝ 528 ⎠
td3 = 68°F = 0.0743 lbm/ft 3
tw3 = 62°F
td5 = 88°F The density at Plane 2:
Ps1 = -1.80 in. wg
Ps3 = -1.40 in. wg ρ 2 = ρ5
Ps5 = 20.8 in. wg
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
Pv3 = 1.30 in. wg = ρ3 ⎜ s5 ⎟⎜ ⎟
N = 880 rpm ⎝ 13.6 p3 ⎠ ⎝ t d5 + 460 ⎠
A1 = 170.3 ft2 ⎛ 20.8 + 13.6 × 29.8 ⎞ ⎛ 528 ⎞
= 0.0744 ⎜ ⎟⎜ ⎟
A2 = 176 ft2 ⎝ 13.6 × 29.70 ⎠ ⎝ 548 ⎠
A3 = 170.3 ft2 = 0.0756 lbm/ft 3
A5 = A2
L = 15 ft FLOW RATE

MEASURED MOTOR DATA V3 = 1096 (Pv3/ρ3)0.5


= 1096 (1.3/0.0744)0.5
Volts = 4000, 4000, 4100
= 4581 fpm
= 4033 av
Amps = 450, 445, 448
Q3 = V3A3
= 448 av
= 4581 × 170.3
MOTOR NAMEPLATE DATA = 780144 cfm

4000 hp, 3 phase 60 hertz Q = Q1


4000 volts, 900 rpm, 520 FLA = Q3 (ρ3/ρ1)
= 780144 (0.0744/0.0743)
GENERAL = 781194 cfm

Fan direct connected to motor. Motor performance


data at operating load, as supplied by motor
manufacturer: 0.88 power factor, 95% efficiency.

29
AMCA 203-90 (R2007)

FAN POWER INPUT SEF 1 = 0.32 (0.0756/0.075)


= 0.32 in. wg
3 × volts × amps × power factor × efficiency
Hmo = FAN STATIC PRESSURE
746
3 × 4033 × 448 × 0.88 × 0.95 Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
=
746 = 1.3 (170.3/170.3)2 (0.0744/0.0743)
= 3507 hp = 1.30 in. wg

Since the fan is direct connected to the motor, there Ps2 = Ps5
is no drive loss, and: = 20.8 in. wg

H = Hmo Ps = Ps2 - Ps1 - Pv1 + SEF 1


= 3507 hp = 20.8 - (-1.80) - 1.30 + 0.32
= 21.62 in. wg
SYSTEM EFFECT FACTOR
FAN TOTAL PRESSURE
AMCA Publication 201-90, Figures 7.1, 8.1, and 8.4
indicate the following calculations: Pt1 = Ps1 +Pv1
= -1.8 + 1.30
Q2 = Q3 (ρ3/ρ2) = -0.50 in. wg
= 780144 (0.0744/0.0756)
= 767761 cfm Pv2 = Pv3 (A3/A2)2 (ρ3/ρ2)
= 1.3 (170.3/176)2 (0.0744/0.0756)
V2 = (Q2/A2) = 1.20 in. wg
= (767761/176)
= 4362 Pt2 = Ps2 + Pv2
= 20.8 + 1.20
Duct diameter equivalent to the diffuser outlet area: = 22.00 in. wg

Pt = Pt2 - Pt1 + SEF 1


De2 = 4 A2 / π
= 22.00 - (-0.50) + 0.32
= ( 4 × 176 ) / π = 22.82 in. wg
= 15 ft.
Also:
Pt = Ps + Pv
Figure 8.1 shows that for velocities over 2500 fpm, Pv = Pv2
100% effective duct length is one duct diameter for
= 1.20 in. wg
every 1000 fpm:
Pt = 21.62 + 1.20
= 22.82 in. wg
= De2 (V2/1000)
= 15 (4362/1000)
CONVERSION TO SPECIFIED CONDITIONS
= 65.43 ft.
Qc = Q
L in % effective duct length
= 781194 cfm
Psc = Ps
= (L/65.43) 100
= (15/65.43) 100 = 21.62 in. wg
= 23% Ptc = Pt
= 22.82 in. wg
For 23% effective duct length and a vaneaxial fan Hc = H
with a 2 piece elbow, Figure 8.4 shows System Effect = 3507 hp
Curve V applies. For 4362 fpm velocity and curve V,
Figure 7.1 shows SEF 1 = 0.32 in. wg at 0.075
lbm/ft3. At 0.0756 lbm/ft3.

30
AMCA 203-90 (R2007)

EXAMPLE 1D: CENTRIFUGAL FANS IN PARALLEL

STATIC PRESSURE TAPS

OUTLET DAMPER

SEF 1
PLENUM

1 PLAN VIEW 1 SIDE VIEW

COMMENTS

1. Each of the fans, as supplied and rated by the between the outlet damper and the plenum. See
manufacturer, includes an outlet damper. Annex E for details of static pressure taps. Measure
Performance ratings for fans with outlet dampers td2 in Plane 2 for each fan.
cover operation with the outlet damper in the full
open position. In order to be able to compare the test 4. For each fan, measure td1 and tw1 in the path of the
results to the fan performance ratings it is essential air flowing into the fan inlet. Determine pb for the
that the outlet dampers be fixed in the full open general vicinity of the fans. Measure td3 in Plane 3. All
positions for the duration of the test. of these measurements are used in the determination
of densities at the various planes of interest.
2. In this example, there are no suitable locations for
traverse planes for use in determining directly the 5. Measure the fan speed and the motor amps, volts,
flow rate for each fan. The alternative is to determine and if possible, watts for each fan. Record all
the total flow rate and since the fans and their pertinent motor nameplate data, including volts
operating speeds are alike, assume that each fan (NPV) and full load amps (FLA). If the motor power
delivers a flow rate proportional to its actual speed. outputs are to be estimated by using the phase
Determine Pv3 by using the root mean square of the current method described in Annex K, it is not
velocity pressure measurements made in a traverse necessary to measure motor watts; however, it may
of Plane 3, located near the end of a straight run of be necessary to disconnect the drives and measure
duct, such as shown in the diagram. Determine Ps3 by the no load amps (NLA) if the motors are not
averaging the static pressure measurements made in operating at or near their full load points. Refer to
the same traverse. Procedures for traverses are Annex K.
described in Section 9.4. Ps3 is used in determining
the density at the traverse plane. Measure the area of 6. SEF 1 is due to the effect of insufficient length of
traverse plane, A3, which is located at the tip of the duct between the outlet of each fan and the plenum.
Pitot-static tube. In this case, the duct length is so short as to be
judged equivalent to there being no duct at all. In
3. Determine Ps2 for each fan by averaging the order to calculate the value of SEF 1, it is necessary
pressure measurements at each of four static to measure the outlet areas of the fans, A2, and their
pressure taps located in the short length of duct blast areas.

31
AMCA 203-90 (R2007)

Ps2 = 6.4 in. wg


7. The sum of the static pressure, Ps1, and the N = 1890 rpm, RH fan speed
velocity pressure, Pv1, at the inlet of a fan with an A2 = 3.2 ft2
unrestricted inlet is considered to be equal to the sum Blast Area = 2.25 ft2
of the static pressure, Psx, and the velocity pressure,
Pvx, at a point sufficiently distant from the inlet as to MEASURED MOTOR DATA
be in still air. At this point, the static pressure is zero,
and the velocity pressure in still air is zero. LH Fan
Volts = 575, 572, 578
Ps1 + Pv1 = Psx + Pvx = 575 av
=0 Amps = 16, 17, 17
= 16.7 av
This consideration, which is the same as that used in NLA = 7.0
the methods for testing fans for performance rating
purposes, charges to the fan losses incurred in RH Fan
accelerating the air into the fan inlet and eliminates Volts = 575, 574, 573
the inaccuracies which arise in any attempt to = 574 av
measure the velocity pressure and static pressure at Amps = 15, 16, 16
the fan inlet. To calculate the Fan Static Pressure: = 15.7 av
NLA = 7.0
Ps = Ps2 - Ps1 - Pv1 + SEF 1
= Ps2 - (Ps1 + Pv1) + SEF 1 MOTOR NAMEPLATE DATA

Since Ps1 + Pv1 = 0: LH Fan


25 hp, 3 phase, 60 hertz
Ps = Ps2 + SEF 1 575 volts, 1780 rpm, 23 FLA

RH Fan
8. In order to compare the test results to the quoted
25 hp, 3 phase, 60 hertz
fan curve drawn for operation at 1900 rpm and 0.075
575 volts, 1780 rpm, 23 FLA
lbm/ft3 density, it is necessary to convert the results
to the specified conditions. The basis for the
GENERAL
calculations is described in Section 14.
Outlet dampers in full open positions. Fans
OBSERVATIONS
connected to motors through belt drives.
SITE MEASUREMENTS
CALCULATIONS
pb = 29.05 in. Hg
DENSITIES
td3 = 78°F
Ps3 = 5.6 in. wg For inlet conditions for both fans of:
Pv3 = 0.47 in. wg
A3 = 7.4 ft2 td1 = 75°F
tw1 = 57°F
LH Fan p1 = pb
td1 = 75°F = 29.05 in. Hg
tw1 = 57°F
td2 = 79°F Use Figure N.1 in Annex N to obtain ρ1 = 0.0718
Ps2 = 6.4 in. wg lbm/ft3
N = 1910 rpm, LH fan speed
A2 = 3.2 ft2 The density at Plane 2:
Blast Area = 2.25 ft2

RH Fan
td1 = 75°F
tw1 = 57°F
td2 = 79°F

32
AMCA 203-90 (R2007)

Annex K indicates that the average of the results of


⎛ P + 13.6 pb ⎞ ⎛ t d1 + 460 ⎞
ρ2 = ρ1 ⎜ s2 ⎟⎜ ⎟ Equation A and Equation B will provide a reasonably
⎝ 13.6 p1 ⎠ ⎝ t d2 + 460 ⎠ accurate estimate of motor power output for a 25 hp
⎛ 6.4 + 13.6 × 29.05 ⎞ ⎛ 535 ⎞ motor operating at approximately 70% FLA.
= 0.0718 ⎜ ⎟⎜ ⎟
⎝ 13.6 × 29.05 ⎠ ⎝ 539 ⎠
LH Fan
= 0.0724 lbm/ft 3 Eqn A = 25 (16.7/23) (575/575)
= 18.15 hp
The density at Plane 3:
Eqn B = 25 [(16.7 - 7)/(23 - 7)] (575/575)
= 15.16 hp
⎛ P + 13.6 pb ⎞ ⎛ t d1 + 460 ⎞
ρ3 = ρ1 ⎜ s3 ⎟⎜ ⎟
⎝ 13.6 p1 ⎠ ⎝ t d3 + 460 ⎠ Hmo = (18.15 + 15.16)/2
⎛ 5.6 + 13.6 × 29.05 ⎞ ⎛ 535 ⎞ = 16.66 hp
= 0.0718 ⎜ ⎟⎜ ⎟
⎝ 13.6 × 29.05 ⎠ ⎝ 538 ⎠
RH Fan
= 0.0724 lbm/ft 3 Eqn A = 25 (15.7/23) (574/575)
= 17.04 hp
FLOW RATES
Eqn B = 25 [(15.7 - 7)/(23 - 7)] (574/575)
V3 = 1096 (Pv3/ρ3)0.5 = 13.57 hp
= 1096 (0.47/0.0724)0.5
= 2792 fpm Hmo = (17.04 + 13.57)/2
= 15.31 hp
Q3 = V3A3
= 2792 × 7.4 Figure L.1 in Annex L indicates estimated belt drive
= 20661 cfm loss of 5% for each fan.

Q = Q1 LH Motor
= Q3 (ρ3/ρ1) HL = 0.05 Hmo
= 20661 (0.0724/0.0718) = 0.05 × 16.66
= 20834 cfm = 0.83 hp
Assume that the air flow rate for each fan is H = Hmo - HL
proportional to its speed. = 16.66 - 0.83
= 15.83 hp
LH Fan
Q = Q1 RH Motor
= 20834 [1910/(1910 + 1890)] HL = 0.05 Hmo
= 10472 cfm = 0.05 × 15.31
= 0.77 hp
RH Fan H = Hmo - HL
Q = Q1 = 15.31 - 0.77
= 20834 [1890/(1910 + 1890)] = 14.54 hp
= 10362 cfm
SYSTEM EFFECT FACTOR
FAN POWER INPUT
AMCA Publication 201-90, Figures 7.1 and 8.3
LH Fan indicate the following calculations:
Measured amps/FLA = (16.7/23)
= 0.73 LH Fan
= 73% Q2 = Q1 (ρ1/ρ2)
= 10472 (0.0718/0.0724)
RH Fan = 10385 cfm
Measured amps/FLA = (15.7/23)
= 0.68 V2 = (Q2/A2)
= 68% = (10385/3.2)
= 3245 fpm

33
AMCA 203-90 (R2007)

Blast area ratio = Blast Area/A2 CONVERSION TO SPECIFIED CONDITIONS


= 2.25/3.2
= 0.70 LH Fan
Qc = 10472 (1900/1910)
RH Fan = 10417 cfm
Q2 = Q1 (ρ1/ρ2)
= 10362 (0.0718/0.0724) Psc = 6.88 (1900/1910)2 (0.075/0.0718)
= 10276 cfm = 7.11 in. wg

V2 = (Q2/A2) Hc = 15.83 (1900/1910)3 (0.075/0.0718)


= (10276/3.2) = 16.28 hp
= 3211 fpm
RH Fan
Blast area ratio = Blast Area/A2 Qc = 10362 (1900/1890)
= 2.25/3.2 = 10417 cfm
= 0.70
Psc = 6.88 (1900/1890)2 (0.075/0.0718)
For a blast area ratio of 0.7 and no duct, Figure 8.3 = 7.26 in. wg
shows System Effect Curve S applies. For each fan
with velocities of 3245 fpm and 3211 fpm and curve
Hc = 14.54 (1900/1890)3 (0.075/0.0718)
S, Figure 7.1 shows SEF 1 = 0.5 in. wg at 0.075
= 15.43 hp
lbm/ft3. At 0.0724 lbm/ft3:

SEF 1 = 0.5 (0.0724/0.075)


= 0.48 in. wg

FAN STATIC PRESSURE

Ps = Ps2 + SEF 1

LH Fan
Ps = 6.4 + 0.48
= 6.88 in. wg

RH Fan
Ps = 6.4 + 0.48
= 6.88 in. wg

34
AMCA 203-90 (R2007)

EXAMPLE 2A: UTILITY FAN IN A VENTILATION SYSTEM

STATIC PRESSURE TAPS

PLAN VIEW 2

3-PIECE
ELBOW
R/D = 1
SEF 1
SEF 2
L
SIDE VIEW OUTLET SIDE VIEW

COMMENTS

1. Determine Pv3 by using the root mean square of described in Annex K, it is not necessary to measure
the velocity pressure measurements made in a motor watts; however, it may be necessary to
traverse of Plane 3, located near the end of a straight disconnect the drive and measure the no load amps
run of duct, such as shown in the diagram. Determine (NLA) if the motor is not operating at or near its full
Ps3 by averaging the static pressure measurements load point. Refer to Annex K.
made in the same traverse. Procedures for traverses
are described in Section 9.4. Ps3 is used in 5. SEF 1 is due to the effect of the elbow located at
determining the density at the traverse plane. the fan inlet. SEF 2 is due to the effect of insufficient
Measure the area of the traverse plane, A3, which is length of duct between the fan outlet and the elbow
located at the tip of the Pitot-static tube. downstream of the fan. In order to calculate the
values of the SEFs, it is necessary to measure the
2. Determine Ps1 by averaging the pressure inlet area and the outlet area of the fan, A1 and A2;
measurements at each of four static pressure taps in the length of the outlet duct, L; and the blast area of
the collar connection at the fan inlet. Determine Ps2 the fan.
by averaging the pressure measurements at each of
6. To calculate the Fan Static Pressure:
four static pressure taps located near the fan outlet.
Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
3. Measure td3 and tw3 in the traverse plane. Assume
td1 is equal to td3. Determine pb for the general vicinity
Where:
of the fan. Measure td2 in Plane 2. All of these
measurements are used in determining densities at
Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
the various planes of interest.
7. In order to compare the test results to the quoted
4. Measure the fan speed and the motor amps, volts,
fan curve drawn for operation at 1880 rpm and 0.075
and if possible, watts. Record all pertinent motor
nameplate data, including volts (NPV) and full load lbm/ft3 density, it is necessary to convert the results
amps (FLA). If the motor power output is to be to the specified conditions. The basis for the
estimated by using the phase current method calculations is described in Section 14.

35
AMCA 203-90 (R2007)

OBSERVATIONS The density at Plane 1:

SITE MEASUREMENTS
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ1 = ρ3 ⎜ s1 ⎟⎜ ⎟
pb = 29.20 in. Hg ⎝ 13.6 p3 ⎠ ⎝ t d1 + 460 ⎠
td2 = 72°F ⎛ −2.18 + 13.6 × 29.20 ⎞ ⎛ 532 ⎞
= 0.0719 ⎜ ⎟ ⎜ 532 ⎟
td3 = 72°F ⎝ 13.6 × 29.06 ⎠⎝ ⎠
tw3 = 66°F = 0.0718 lbm/ft 3
Ps1 = -2.18 in. wg
Ps2 = 0.35 in. wg
The density at Plane 2:
Ps3 = -1.95 in. wg
Pv3 = 0.45 in. wg
N = 1730 rpm ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ2 = ρ3 ⎜ s2 ⎟⎜ ⎟
A1 = 1.07 ft2 ⎝ 13.6 p3 ⎠ ⎝ t d2 + 460 ⎠
A2 = 1.17 ft2 ⎛ 0.35 + 13.6 × 29.20 ⎞ ⎛ 532 ⎞
= 0.0719 ⎜ ⎟ ⎜ 532 ⎟
A3 = 1.07 ft2 ⎝ 13.6 × 29.06 ⎠⎝ ⎠
Blast Area = 0.7 ft2 = 0.0723 lbm/ft 3

L = 0.83 ft

MEASURED MOTOR DATA FLOW RATES

Volts = 227, 229, 228 V3 = 1096 (Pv3/ρ3)0.5


= 228 av = 1096 (0.45/0.0719)0.5
Amps = 10.2, 10.3, 10.4 = 2742 fpm
= 10.3 av
NLA = 7.1 Q3 = V3A3
= 2742 × 1.07
MOTOR NAMEPLATE DATA = 2934 cfm

5 hp, 3 phase, 60 hertz Q = Q1


230 volts, 1750 rpm, 14 FLA = Q3 (ρ3/ρ1)
= 2934 (0.0719/0.0718)
GENERAL = 2938 cfm

Fan connected to motor through belt drive. FAN POWER INPUT

CALCULATIONS Measured amps/FLA = 10.3/14


= 0.74
DENSITIES = 74%

For Plane 3 conditions of: Annex K indicates that the average of the results of
Equation A and Equation B will provide a reasonably
td3 = 72°F accurate estimate of motor power output for a 5 hp
tw3 = 66°F motor operating at 74% FLA.

p3 = pb + (Ps3/13.6) Eqn A = 5 (10.3/14) (228/230)


= 29.20 + (-1.95/13.6) = 3.65 hp
= 29.06 in. Hg
Eqn B = 5 [(10.3 - 7.1)/(14 - 7.1)] (228/230)
Use Figure N.1 in Annex N to obtain ρ3 = 0.0719 = 2.30 hp
lbm/ft3
Hmo = (3.65 + 2.30)/2
It is assumed that td1 = td3 = 2.98 hp

36
AMCA 203-90 (R2007)

Figure L.1 in Annex L indicates estimated belt drive L in % effective duct length
loss of 6.5%.
= (L/3.05) 100
HL = 0.065 Hmo = (0.83/3.05) 100
= 0.065 × 2.98 = 27%
= 0.19 hp
Blast area ratio = Blast Area/A2
H = Hmo - HL = 0.7/1.17
= 2.98 - 0.19 = 0.6
= 2.79 hp
For blast area ratio of 0.6, 27% effective duct length
SYSTEM EFFECT FACTORS and elbow position C, Figure 8.5 shows System
Effect Curve P - Q applies. For 2494 fpm velocity and
To determine the value of SEF 1, calculate the curve P - Q, Figure 7.1 shows SEF 2 = 0.7 in. wg at
velocity at the fan inlet: 0.075 lbm/ft3. At 0.0723 lbm/ft3:

V1 = Q1/A1 SEF 2 = 0.7 (0.0723/0.075)


= 2938/1.07 = 0.67 in. wg
= 2746 fpm
FAN STATIC PRESSURE
AMCA Publication 201-90, Figure 9.5 indicates that
for a three piece elbow with radius to diameter ratio Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
of 1, and with no duct between the elbow and the fan = 0.45 (1.07/1.07)2 (0.0719/0.0718)
inlet, System Effect Curve R applies. For 2746 fpm = 0.45 in. wg
velocity and curve R, Figure 7.1 shows SEF 1 = 0.55
in. wg at 0.075 lbm/ft3. At 0.0718 lbm/ft3: Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
= 0.35 - (-2.18) - 0.45 + 0.53 + 0.67
SEF 1 = 0.55 (0.0718/0.075) = 3.28 in. wg
= 0.53 in. wg
CONVERSION TO SPECIFIED CONDITIONS
For SEF 2, AMCA Publication 201-90, Figures 7.1,
8.1, and 8.5 indicate the following calculations: Qc = 2938 (1880/1730)
= 3193 cfm
Q2 = Q3 (ρ3/ρ2)
= 2934 (0.0719/0.0723) Psc = 3.28 (1880/1730)2 (0.075/0.0718)
= 2918 cfm = 4.05 in. wg
V2 = (Q2/A2)
Hc = 2.79 (1880/1730)3 (0.075/0.0718)
= 2918/1.17
= 3.74 hp
= 2494 fpm

Duct diameter equivalent to the fan outlet area:

De2 = (4A2/π)0.5
= (4 × 1.17/π)0.5
= 1.22 ft

Figure 8.1 shows that for velocities of 2500 fpm or


less, the 100% effective outlet duct length is 2.5 duct
diameters,

= 2.5 × 1.22
= 3.05 ft

37
AMCA 203-90 (R2007)

EXAMPLE 2B: CENTRIFUGAL FAN IN A SAWDUST CONVEYING SYSTEM

SEF 2 2
1

SEF 1
4-PIECE ELBOW
R/D = 1

L2

L1

OUTLET SIDE VIEW SIDE VIEW

COMMENTS

1. Determine Pv3 by using the root mean square of atmospheric pressure as used in all other pressure
the velocity pressure measurements made in a measurements. In this case, the pressure was
traverse of Plane 3, located near the end of a straight measured as 0.1 in. wg.
run of duct, such as shown in the diagram. Determine
Ps3 by averaging the static pressure measurements 3. Measure td3 and tw3 in the traverse plane.
made in the same traverse. Procedures for traverses Determine pb for the general vicinity of the fan.
are described in Section 9.4. Ps3 is used in Measure td1 and td2. All of these measurements are
determining the density at the traverse plane. used in determining densities at the various planes of
Measure the area of the traverse plane, A3, which is interest.
located at the tip of the Pitot-static tube.
4. Measure the fan speed and the motor amps, volts,
2. Determine Ps1 by using a Pitot-static tube or static and if possible, watts. Record all pertinent motor
pressure taps in the duct connection at the fan inlet. nameplate data, including volts (NPV) and full load
If a Pitot-static tube is used, it should not project into amps (FLA). If the motor power output is to be
the upstream elbow but be located well within the estimated by using the phase current method
length of the duct connection as shown in the described in Annex K, it is not necessary to measure
diagram. The friction loss in the short length of outlet motor watts; however, it may be necessary to
duct is assumed to be negligible, and Ps2 is disconnect the drive and measure the no load amps
considered to be equal to the static pressure at the (NLA) if the motor is not operating at or near its full
duct outlet. The static pressure at the outlet of the load point. Refer to Annex K.
duct is zero gauge pressure, referred to the
atmospheric pressure in the region of the duct outlet. 5. SEF 1 is due to the effect of insufficient length of
In situations such as this example, the air may be duct between the fan inlet and the elbow upstream of
discharging from the duct into a region in which the the fan. SEF 2 is due to the effect of insufficient
atmospheric pressure is somewhat different from that length of duct at the fan outlet. In order to calculate
to which all other pressure measurements are the values of the SEFs, it is necessary to measure
referred. When this possibility exists, it is essential the inlet area and the outlet area of the fan, A1 and
that the static pressure in the region of the A2; the lengths of the inlet connection and the outlet
discharging air be measured, referred to the same duct, L1 and L2; and the blast area of the fan.

38
AMCA 203-90 (R2007)

6. To calculate the Fan Static Pressure: CALCULATION

Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2 DENSITIES

Where: For Plane 2 conditions of:

Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1) td2 = 91.3°F


tw2 = 70.4°F
7. In order to compare the test results to the quoted
fan curve drawn for operation at 2075 rpm and 0.075 p2 = pb + (Ps2/13.6)
lbm/ft3, it is necessary to convert the results to the = 29.82 + (0.1/13.6)
specified conditions. The basis for the calculations is = 29.83 in. Hg
described in Section 14.
Use Figure N.1 in Annex N to obtain ρ2 = 0.0714
OBSERVATIONS lbm/ft3

SITE MEASUREMENTS The density at Plane 1:

pb = 29.82 in. Hg
⎛ P + 13.6 pb ⎞ ⎛ t d2 + 460 ⎞
td1 = 86.6°F ρ1 = ρ2 ⎜ s1 ⎟⎜ ⎟
td2 = 91.3°F ⎝ 13.6 p2 ⎠ ⎝ t d1 + 460 ⎠
tw2 = 70.4°F ⎛ −11.4
4 + 13.6 × 29.82 ⎞ ⎛ 551.3 ⎞
= 0.0714 ⎜ ⎟ ⎜ 546.6 ⎟
td3 = 86°F ⎝ 13.6 × 29.83 ⎠⎝ ⎠
Ps1 = -11.4 in. wg = 0.0700 lbm/ft 3
Ps2 = 0.1 in. wg
Ps3 = -8.9 in. wg
The density at Plane 3:
Pv3 = 1.24 in. wg
N = 2120 rpm, fan speed
A1 = 1.40 ft2 ⎛ P + 13.6 pb ⎞ ⎛ t d2 + 460 ⎞
ρ3 = ρ2 ⎜ s3 ⎟⎜ ⎟
A2 = 1.40 ft2 ⎝ 13.6 p3 ⎠ ⎝ t d3 + 460 ⎠
A3 = 1.57 ft2 ⎛ −8.9 + 13.6 × 29.82 ⎞ ⎛ 551.3 ⎞
= 0.0714 ⎜ ⎟ ⎜ 546 ⎟
⎝ 13.6 × 29.83 ⎠⎝ ⎠
Blast Area = 1.26 ft2 = 0.0705 lbm/ft 3
L1 = 1.33 ft
L2 = 3.0 ft
FLOW RATES
MEASURED MOTOR DATA
V3 = 1096 (Pv3/ρ3)0.5
Volts = 460, 460, 459 = 1096 (1.24/0.0705)0.5
= 460 av = 4596 fpm
Amps = 26.5, 25.5, 26
= 26 av Q3 = V3A3
NLA = 11.3 = 4596 × 1.57
= 7216 cfm
MOTOR NAMEPLATE DATA
Q = Q1
30 hp, 3 phase, 60 hertz = Q3 (ρ3/ρ1)
460 volts, 1750 rpm, 36 FLA = 7216 (0.0705/0.0700)
= 7268 cfm
GENERAL
FAN POWER INPUT
Fan connected to motor through belt drive.
Measured amps/FLA = (26/36)
= 0.72
= 72%

39
AMCA 203-90 (R2007)

Annex K indicates that the average of the results of For SEF 2, AMCA Publication 201-90, Figure 8.3
Equation A and Equation B will provide a reasonably indicates the following calculations:
accurate estimate of motor power output for a 30 hp
motor operating at 72% FLA. Q2 = Q3 (ρ3/ρ2)
= 7216 (0.0705/0.0714)
Eqn A = 30 (26/36) (460/460) = 7125 cfm
= 21.67 hp
V2 = (Q2/A2)
Eqn B = 30 [(26 - 11.3)/(36 - 11.3)] (460/460) = (7125/1.40)
= 17.85 hp = 5089 fpm

Hmo = (21.67 + 17.85)/2 Duct diameter equivalent to the fan outlet area:
= 19.76 hp
De2 = (4A2/π)0.5
Figure L.1 in Annex L indicates estimated belt drive = (4 × 1.40/π)0.5
loss of 4.8%. = 1.34 ft
HL = 0.048 Hmo Figure 8.3 shows that for velocities over 2500 fpm,
= 0.048 × 19.76 100% effective duct length is one duct diameter per
= 0.95 hp 1000 fpm:

H = Hmo - HL = D2 (V2/1000)
= 19.76 - 0.95 = 1.34 (5089/1000)
= 18.81 hp = 6.82 ft

SYSTEM EFFECT FACTORS The length of the outlet duct in % effective duct
length:
To determine the value of SEF 1, calculate the
velocity at the fan inlet: = (L2/6.82) 100
= (3.0/6.82) 100
V1 = (Q1/A1) = 44%
= (7268/1.40)
= 5191 fpm Blast ratio area = Blast Area/A2
= 1.26/1.40
The diameter of the fan inlet: = 0.9

D1 = (4A1/π)0.5 For blast area ratio of 0.9 and 44% effective duct
= (4 × 1.40/π)0.5 length, Figure 8.3 shows no System Effect Curve
= 1.34 ft. applies and SEF 2 = 0.

The length of the duct between the elbow and the fan FAN STATIC PRESSURE
inlet in terms of D1:
Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
= (L1/D1) = 1.24 (1.57/1.40)2 (0.0705/0.0700)
= (1.33/1.34) = 1.57 in. wg
= 1.0
Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
AMCA Publication 201-90, Figure 9.5 indicates that = 0.1 - (-11.4) - 1.57 + 1.2 + 0
for a four piece elbow with a radius to diameter ratio = 11.13 in. wg
of 1, and with a length of duct between the elbow and
the fan inlet equal to 1 equivalent diameter, System CONVERSIONS TO SPECIFIED CONDITIONS
Effect Curve S applies. For 5191 fpm velocity and
curve S, Figure 7.1 shows SEF 1 = 1.3 in. wg at Qc = 7268 (2075/2120)
0.075 lbm/ft3. At 0.0700 lbm/ft3: = 7114 cfm

SEF 1 = 1.3 (0.0700/0.075) Psc = 11.13 (2075/2120)2 (0.075/0.0700)


= 1.2 in. wg = 11.42 in. wg

40
AMCA 203-90 (R2007)

Hc = 18.81 (2075/2120)2 (0.075/0.0700)


= 18.90 hp

41
AMCA 203-90 (R2007)

EXAMPLE 2C: AXIAL FAN IN A DRYER SYSTEM

4 5 STRAIGHTENING VANES
2 3
1
SEF 2 STATIC PRESSURE TAPS

A3

PLAN VIEW
SEF 1
INNER CYLINDER
LOCATION OF PLANE 3

SIDE VIEW

COMMENTS

1. This type of installation is normally classified as located at the tip of the Pitot-static tube, as shown in
one in which a satisfactory test cannot be conducted. the diagram, not at the location of the Pitot-static tube
Due to the configurations of the airways, there are no access holes.
locations at which reasonably accurate pressure
measurements can be made. In addition, the 3. Determine Ps4 by averaging the pressure
judgments required in determining the values of the measurements at each of four static pressure taps
SEFs are susceptible to error. The purpose of located near the fan inlet. In the same manner,
presenting this example is to illustrate the not determine Ps5 at a location near the fan outlet. It is
uncommon instance in which a test must be conducted undesirable to have pressure measurement planes
in order to provide performance information, even located in converging and diverging airways, but
though the results will be innaccurate to a degree there are no other more suitable locations for these
which is not normally acceptable. planes in this installation. Measure A4 and A5, the
cross-sectional areas of the airways at Planes 4 and 5.
2. Determine Pv3 by using the root mean square of
the velocity pressure measurements made in a 4. Measure td3, tw3, and td4. Determine pb for the
traverse of Plane 3, located as shown in the diagram. general vicinity of the fan. These measurements are
Determine Ps3 by averaging the static pressure used in the determination of densities at the various
measurements made in the same traverse. planes of interest.
Procedures for traverses are described in Section
9.4. These velocity pressure and static pressure 5. Measure the fan speed and the motor amps, volts,
measurements are susceptible to error due to the and if possible, watts. Record all pertinent motor
turbulence existing in the region of the fan outlet. In nameplate data, including volts (NPV) and full load
addition, it is undesirable to have Plane 3 located in amps (FLA). If the motor power output is to be
a diverging airway. However, no other more suitable estimated by using the phase current method
location for Plane 3 exists in this example. It is described in Annex K, it is not necessary to measure
recommended that the Pitot-static tube be oriented motor watts; however, it may be necessary to
so that its nose is aligned with the anticipated flow disconnect the drive and measure the no load amps
streams, particularly near the walls of the diffuser. (NLA) if the motor is not operating at or near its full
Determine the area of the traverse plane, A3, which is load point. Refer to Annex K.

42
AMCA 203-90 (R2007)

6. Although an elbow is located a short distance MOTOR NAMEPLATE DATA


upstream of the fan, it is considered to produce no
system effect since it is equipped with turning vanes 25 hp, 3 phase, 60 hertz
and the average velocity through the elbow will be 460 volts, 1750 rpm, 31 FLA
relatively low due to its large cross-sectional area.
Therefore, SEF 1 = 0. In judging SEF 2, the rapidly GENERAL
diverging transition fitting downstream of the fan is
considered equivalent to no duct at the fan outlet. In Fan connected to motor through belt drive
order to calculate the value of SEF2, it is necessary
to measure the outlet area of the fan, A2. CALCULATIONS

7. To calculate the Fan Static Pressure, DENSITIES

Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2 For Plane 3 conditions of:

Where: td3 = 86.5°F


tw3 = 75.5°F
Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
p3 = pb + (Ps3/13.6)
Ps1 and Ps2 are calculated on the basis of total = 28.90 + (1.5/13.6)
pressure considerations, using Ps4, Ps5, and the = 29.01 in. Hg
calculated velocity pressures at Planes 1, 2, 4, and 5.
Use Figure N.1 from Annex N to obtain ρ3 = 0.0694
8. In order to compare the test results to the quoted lbm/ft3
fan curve drawn for operation at 1580 rpm and
0.0690 lbm/ft3 density, it is necessary to convert the The density at Plane 4:
results to the specified conditions. The basis for the
calculations is described in Section 14. ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ 4 = ρ3 ⎜ s4 ⎟⎜ ⎟
OBSERVATIONS ⎝ 13.6 p3 ⎠ ⎝ t d4 + 460 ⎠
⎛ −1.57 + 13.6 × 28.90 ⎞ ⎛ 546.5 ⎞
= 0.0694 ⎜ ⎟ ⎜ 545 ⎟
SITE MEASUREMENTS ⎝ 13.6 × 29.01 ⎠⎝ ⎠
= 0.0691 lbm/ft 3
pb = 28.90 in. Hg
td3 = 86.5°F
tw3 = 75.5°F It is assumed that td1 = td4 and at the low pressure
td4 = 85°F levels which exist at Planes 1 and 4, the difference
between these pressures will be small, and assuming
Ps3 = 1.5 in. wg
ρ1 = ρ4, will result in an error which is considered
Pv3 = 0.044 in. wg
negligible. By similar reasoning, it is assumed that
Ps4 = -1.57 in. wg
ρ5 = ρ2 = ρ3.
Ps5 = 1.22 in. wg
N = 1590 rpm FLOW RATES
A1 = A2 = 8.0 ft2
A3 = 29.8 ft2 V3 = 1096 (Pv3/ρ3)0.5
A4 = 12.4 ft2 = 1096 (0.044/0.0694)0.5
A5 = 9.6 ft2 = 873 fpm

MEASURED MOTOR DATA Q3 = V3A3


= 873 × 29.8
Volts = 450, 449, 448 = 26015 cfm
= 449 av
Amps = 25.0, 24.5, 25.0 Q = Q1
= 24.8 av = Q3 (ρ3/ρ1)
NLA = 9.4 = 26015 (0.0694/0.0691)
= 26128 cfm

43
AMCA 203-90 (R2007)

FAN POWER INPUT FAN STATIC PRESSURE

Measured amps/FLA = (24.8/31) Pv4 = Pv3 (A3/A4)2 (ρ3/ρ4)


= 0.80 = 0.044 (29.8/12.4)2 (0.0694/0.0691)
= 80% = 0.26 in. wg

Annex K indicates that the average of the results of Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
Equation A and Equation B will provide a reasonably
accurate estimate of motor power output for a 25 hp = 0.044 (29.8/8.0)2 (0.0694/0.0691)
motor operating at 80% FLA. = 0.61 in. wg

Eqn A = 25 (24.8/31) (449/460) Ps1 + Pv1 = Ps4 + Pv4


= 19.52 hp Ps1 = Ps4 + Pv4 - Pv1
= -1.57 + 0.26 - 0.61
Eqn B = 25 [(24.8 - 9.4)/(31 - 9.4)] (449/460) = -1.92 in. wg
= 17.40 hp
Pv5 = Pv3 (A3/A5)2 (ρ3/ρ5)
Hmo = (19.52 + 17.40)/2 = 0.044 (29.8/9.6)2 (0.0694/0.0694)
= 18.46 hp = 0.42 in. wg

Figure L.1 in Annex L indicates estimated belt drive Pv2 = Pv3 (A3/A2)2 (ρ3/ρ2)
loss of 4.9%. = 0.044 (29.8/8.0)2 (0.0694/0.0694)
= 0.61 in. wg
HL = 0.049 Hmo
= 0.049 × 18.46 Ps2 + Pv2 = Ps5 + Pv5
= 0.90 hp Ps2 = Ps5 + Pv5 - Pv2
= 1.22 + 0.42 - 0.61
H = Hmo - HL = 1.03 in. wg
= 18.46 - 0.90 Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
= 17.56 hp = 1.03 - (-1.92) - 0.61 + 0 + 0.24
= 2.58 in. wg
SYSTEM EFFECT FACTORS
Losses between Planes 1 and 4 and between Planes
SEF 1 = 0 See item 6 under COMMENTS. 2 and 5 have been ignored.
To determine the value of SEF 2, AMCA Publication CONVERSION TO SPECIFIED CONDITIONS
201-90, Figure 8.2 indicates that a vaneaxial fan with
no outlet duct will use System Effect Curve U. Qc = 26128 (1580/1590)
= 25964 cfm
Q2 = Q3 (ρ3/ρ2)
= 26015 (0.0694/0.0694)
Psc = 2.58 (1580/1590)2 (0.0690/0.0691)
= 26015 cfm
= 2.54 in. wg
V2 = (Q2/A2)
Hc = 17.56 (1580/1590)3 (0.0690/0.0691)
= (26015/8.0)
= 3252 fpm = 17.21 hp

From Figure 7.1, using 3252 fpm and curve U, SEF 2


= 0.26 in. wg at 0.075 lbm/ft3. At 0.0694 lbm/ft3:

SEF 2 = 0.26 (0.0694/0.075)


= 0.24 in. wg

44
AMCA 203-90 (R2007)

EXAMPLE 2D: CENTRIFUGAL FAN IN A SCRUBBER SYSTEM

INLET BOX DAMPER

STATIC PRESSURE TAPS

SEF 1

3
1

L
INLET BOX

DIFFUSER

SIDE VIEW OUTLET SIDE VIEW

COMMENTS

1. This fan, as supplied and rated by the 5. Measure the fan speed and the motor amps, volts,
manufacturer, includes the inlet box damper and the and if possible, watts. Record all pertinent motor
inlet box. Performance ratings for fans with inlet box nameplate data, including volts (NPV), and full load
dampers cover operation with the dampers in the full amps (FLA). If the motor power output is to be
open positions. In order to be able to compare the estimated by using the phase current method
test results to the fan performance ratings, it is described in Annex K, it is not necessary to measure
essential that the damper be fixed in the full open motor watts; however, it may be necessary to
position for the duration of the test. disconnect the drive and measure the no load amps
(NLA) if the motor is not operating at or near its full
2. Determine Pv3 by using the root mean square of load point. Refer to Annex K.
the velocity pressure measurements made in a
traverse of Plane 3, located shortly upstream of the 6. SEF 1 is due to the effect of insufficient length of
inlet damper. Determine Ps3 by averaging the static duct at the fan outlet. In order to calculate the value
pressure measurements made in the same traverse. of SEF 1, it is necessary to measure the length of the
Procedures for traverses are described in Section outlet duct, L; the fan outlet area, A2; and the blast
9.4. Measure A3, the area of the traverse plane, area of the fan.
located at the tip of the Pitot-static tube and A1, the
area of the inlet to the damper. 7. To calculate the Fan Static Pressure:

3. Determine Ps2 by averaging the pressure Ps = Ps2 - Ps1 - Pv1 + SEF 1


measurements at each of four static pressure taps
located near the end of the fan outlet. See Annex E Since Plane 1 is located shortly downstream of Plane
for details of static pressure taps. 3 in an airway of uniform cross-section (A1 = A3), the
conditions which exist at Plane 3 are assumed to
4. Measure td3 and tw3 in the traverse plane. exist at Plane 1. Therefore, Ps1 = Ps3 and Pv1 = Pv3.
Determine pb for the general vicinity of the fan.
Measure td2 in Plane 2. These measurements are 8. In order to compare the test results to the quoted
used in the determination of densities at the various fan curve drawn for operation at 1780 rpm and 0.059
planes of interest. lbm/ft3 density, it is necessary to convert the results

45
AMCA 203-90 (R2007)

to the specified conditions. The basis for the pe = 0.5603 in. Hg


calculations is described in Section 14.
pp = pe - [p3 (td3 - tw3)/2700]
OBSERVATIONS = 0.5603 - [24.28 (63 - 62)/2700]
= 0.5513 in. Hg
SITE MEASUREMENTS
1.3257( p3 − 0.378 pp )
pb = 29.44 in. Hg ρ3 =
td2 = 97°F t d3 + 460
td3 = 63°F 1.3257 ( 24.28 − 0.378 × 0.5513 )
=
tw3 = 62°F 63 + 460
Ps2 = 1.1 in. wg = 0.0610 lbm/ft 3
Ps3 = -70.2 in. wg
Pv3 = 0.64 in. wg
Consider ρ1 to be equal to ρ3.
N = 1790 rpm
A1 = 6.5 ft2 The density at Plane 2:
A2 = 5.32 ft2
A3 = 6.5 ft2 ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
Blast Area = 1.89 ft2 ρ2 = ρ3 ⎜ s2 ⎟⎜ ⎟
L = 2.50 ft ⎝ 13.6 p3 ⎠ ⎝ t d2 + 460 ⎠
⎛ 1.1 + 13.6 × 29.44 ⎞ ⎛ 523 ⎞
= 0.0610 ⎜ ⎟⎜ ⎟
MEASURED MOTOR DATA ⎝ 13.6 × 24.28 ⎠ ⎝ 557 ⎠
= 0.0696 lbm/ft 3
Volts = 4160, 4150, 4150
= 4153 av
Amps = 50, 51, 52 FLOW RATES
= 51 av
NLA = 14 V3 = 1096 (Pv3/ρ3)0.5
= 1096 (0.64/0.0610)0.5
MOTOR NAMEPLATE DATA = 3550 fpm

500 hp, 3 phase, 60 hertz Q3 = V3A3


4160 volts, 1785 rpm, 61 FLA = 3550 × 6.5
= 23075 cfm
GENERAL Q = Q1 = Q3
= 23075 cfm
Inlet box damper in full open position. Fan direct
connected to motor. FAN POWER INPUT

CALCULATIONS Measured amps/FLA = 51/61


= 0.84
DENSITIES = 84%

For Plane 3 conditions of: Annex K indicates that the average of the results of
Equation A and Equation B will provide a reasonably
td3 = 63°F accurate estimate of motor power output for a 500 hp
tw3 = 62°F motor operating at 84% FLA.

p3 = pb + (Ps3/13.6) Eqn A = 500 (51/61) (4153/4160)


= 29.44 + (-70.2/13.6) = 417 hp
= 24.28 in. Hg
Eqn B = 500 [(51 - 14)/(61 - 14)] (4153/4160)
Use the modified Apjohn equation, described in = 393 hp
Section M.2.3 in Annex M, and the table in Figure N.2
in Annex N to calculate the density at Plane 3. Hmo = (417 + 393)/2
= 405 hp

46
AMCA 203-90 (R2007)

Since the fan is direct-connected to the motor, there Blast area ratio = Blast Area/A2
is no drive loss, and: = 1.89/5.32
= 0.36
H = Hmo
= 405 hp For a blast area ratio of 0.36, and 25% effective duct
length, Figure 8.3 shows System Effect Curve U
SYSTEM EFFECT FACTOR applies. For 3802 fpm velocity and curve U, Figure
7.1 shows SEF 1 = 0.36 in. wg at 0.075 lbm/ft3. At
AMCA Publication 201-90, Figures 7.1 and 8.3 0.0696 lbm/ft3:
indicate the following calculations.
SEF 1 = 0.36 (0.0696/0.075)
Q2 = Q3 (ρ3/ρ2) = 0.33 in. wg
= 23075 (0.0610/0.0696)
= 20224 cfm FAN STATIC PRESSURE

V2 = Q2/A2 Ps1 = Ps3


= 20224/5.32 = - 70.2 in. wg
= 3802 fpm Pv1 = Pv3
= 0.64 in. wg
Duct diameter equivalent to the diffuser outlet area: Ps = Ps2 - Ps1 - Pv1 + SEF 1
= 1.1 - (-70.2) - 0.64 + 0.33
De2 = (4A2/π)0.5 = 71.0 in. wg
= (4 × 5.32/π)0.5
= 2.60 ft CONVERSION TO SPECIFIED CONDITIONS

Figure 8.3 shows that for velocities over 2500 fpm Qc = 23075 (1780/1790)
100% effective duct length is one duct diameter for = 22946 cfm
every 1000 fpm:
Psc = 71.0 (1780/1790)2 (0.059/0.0610)
= De2 (V2/1000) = 67.9 in. wg
= 2.60 (3802/1000)
= 9.89 ft. Hc = 405 (1780/1790)3 (0.059/0.0610)
= 385 hp
L in % effective duct length:

= (L/9.89) 100
= (2.50/9.89) 100
= 25%

47
AMCA 203-90 (R2007)

EXAMPLE 2E: CENTRIFUGAL FAN IN A PROCESS SYSTEM

STATIC OUTLET DAMPER


PRESSURE TAPS 5
2

INLET BOXES

INLET BOX 1a 1b
DAMPERS 3a 3b

SIDE VIEW OPPOSITE OUTLET SIDE VIEW

COMMENTS

1. This fan, as supplied and rated by the 4. Measure td3a, td3b, and td5. Since flue gas is being
manufacturer, includes the inlet box dampers and the handled by the fan, the Orsat apparatus is used by
inlet boxes, but does not include the outlet damper. process personnel to determine the density of the
Performance ratings for fans with inlet box dampers gas. Determine pb for the general vicinity of the fan.
cover operation with the dampers in the full open These data are used in the determination of densities
positions. Also, performance ratings for items such as at the various planes of interest.
the outlet damper are for operation in the full open
position. In order to be able to compare the test 5. Measure the fan speed and the motor amps, volts,
results to the fan performance ratings, it is essential and if possible, watts. Record all pertinent motor
that the outlet damper and the inlet dampers be fixed nameplate data, including volts (NPV) and full load
in their full open positions. amps (FLA). If the motor power output is to be
estimated by using the phase current method
2. Determine Pv3a and Pv3b by using the root mean described in Annex K, it is not necessary to measure
square of the velocity pressure measurements made motor watts; however, it may be necessary to
in Planes 3a and 3b. Determine Ps3a and Ps3b by disconnect the drive and measure the no load amps
averaging each of the two sets of static pressure (NLA) if the motor is not operating at or near its full
measurements made in the same traverses. load point. Motor performance data, supplied by the
Procedures for traverses are described in Section motor manufacturer, are used in the determination of
9.4. Measure A3a and A3b, the areas of the traverse motor power output for this example.
planes and A1a and A1b, the areas of the inlets to the
inlet dampers. 6. In this example, the duct downstream of the outlet
damper is of sufficient length, and no SEF applies.
3. Determine Ps5 by averaging the pressure
measurements of each of four static pressure taps 7. To calculate the Fan Static Pressure:
located downstream of the outlet damper.
Ps = Ps2 - Ps1 - Pv1

48
AMCA 203-90 (R2007)

Ps2 is calculated on the basis of total pressure MOTOR NAMEPLATE DATA


considerations using Ps5, the outlet damper pressure
loss, and the calculated velocity pressures at Planes 3000 hp, 3 phase, 60 hertz
2 and 5. Since the inlets to the inlet dampers (Planes 4000 volts, 880 rpm, 385 FLA
1a and 1b) are located shortly downstream of the
traverse planes (Planes 3a and 3b) in an airway of GENERAL
uniform cross-section, the conditions which exist at
the traverse planes are assumed to exist at the inlets Inlet box dampers and outlet damper in full open
to the inlet dampers. positions. Fan direct connected to motor. Motor
efficiency data supplied by motor manufacturer.
Ps1 = Ps3 Pressure loss data supplied by manufacturer of outlet
= (Ps3a + Ps3b)/2 damper.

Pv1 is calculated using the total flow rate and the total CALCULATIONS
area at the inlets to the inlet dampers.
DENSITIES
Pv1 = (Q1/1096A1)2 ρ1
The densities at Planes 3a and 3b are:
8. In order to compare the test results to the quoted
fan curve drawn for operation at 880 rpm and 0.049 ⎛ P + 13.6 pb ⎞ ⎛ 70 + 460 ⎞
ρ3a = 0.0725 ⎜ s3a ⎟⎜ ⎟
lbm/ft3 density, it is necessary to convert the results ⎝ 13.6 × 29.92 ⎠ ⎝ t d3a + 460 ⎠
to the specified conditions. The basis for calculations ⎛ −18.8 + 13.6 × 30.12 ⎞ ⎛ 530 ⎞
is described in Section 14. = 0.0725 ⎜ ⎟ ⎜ 805 ⎟
⎝ 13.6 × 29.92 ⎠⎝ ⎠
OBSERVATIONS = 0.0458 lbm/ft 3

SITE MEASUREMENTS
⎛ P + 13.6 pb ⎞ ⎛ 70 + 460 ⎞
ρ3b = 0.0725 ⎜ s3b ⎟⎜ ⎟
pb = 30.12 in. Hg ⎝ 13.6 × 29.92 ⎠ ⎝ t d3b + 460 ⎠
td3a= 345°F ⎛ −18.3 + 13.6 × 30.12 ⎞ ⎛ 530 ⎞
td3b= 359°F = 0.0725 ⎜ ⎟ ⎜ 819 ⎟
⎝ 13.6 × 29.92 ⎠⎝ ⎠
td5 = 363°F
= 0.0451 lbm/ft 3
Ps3a= -18.8 in. wg
Ps3b= -18.3 in. wg
Pv3a= 2.053 in. wg It is assumed that ρ1a = ρ3a and ρ1b = ρ3b.
Pv3b= 2.028 in. wg
The density at Plane 5:
Ps5 = -1.6 in. wg
N = 892 rpm
A1a = A1b ⎛ P + 13.6 pb ⎞ ⎛ 70 + 460 ⎞
ρ5 = 0.0725 ⎜ s5 ⎟⎜ ⎟
= 60.7 ft2 ⎝ 13.6 × 29.92 ⎠ ⎝ t d5 + 460 ⎠
A2 = 115 ft2 ⎛ −1.6 + 13.6 × 30.12 ⎞ ⎛ 530 ⎞
A3a = A3b = 0.0725 ⎜ ⎟ ⎜ 823 ⎟
⎝ 13.6 × 29.92 ⎠⎝ ⎠
= 60.7 ft2
= 0.0468 lbm/fft 3

A5 = 140 ft2
Blast Area = 80 ft2
It is assumed that ρ2 = ρ5.
The density of the gas, as determined by Orsat
analysis, is 0.0725 lbm/ft3 at 29.92 in. Hg and 70°F. FLOW RATES

MEASURED MOTOR DATA V3a = 1096 (Pv3a/ρ3a)0.5


= 1096 (2.053/0.0458)0.5
Volts = 4300, 4250, 4200 = 7338 fpm
= 4250 av
Amps = 378, 376, 380 Q3a = V3aA3a
= 378 av = 7338 × 60.7
kW = 2519 = 445417 cfm
49
AMCA 203-90 (R2007)

V3b = 1096 (Pv3b/ρ3b)0.5 FAN STATIC PRESSURE


= 1096 (2.028/0.0451)0.5
= 7349 fpm Pv1 = (Q1/1096A1)2 ρ1
= (891501/1096 × 121.4)2 0.0455
Q3b = V3bA3b = 2.04 in. wg
= 7349 × 60.7
= 446084 cfm Pv2 = Pv1 (A1/A2)2 (ρ1/ρ2)
= 2.04 (121.4/115)2 (0.0455/0.0468)
Q3 = Q3a + Q3b = 2.21 in. wg
= 445417 + 446084
= 891501 cfm Pv5 = Pv1 (A1/A5)2 (ρ1/ρ5)
= 2.04 (121.4/140)2 (0.0455/0.0468)
Since the air is divided evenly between the two inlet = 1.49 in. wg
boxes:
Ps2 + Pv2 = Ps5 + Pv5 + Damper Loss
ρ1 = ρ3
= (ρ3a + ρ3b)/2 Ps2 = Ps5 + Pv5 + Damper Loss - Pv2
= (0.0458 + 0.0451)/2 = -1.6 + 1.49 + 0.75 - 2.21
= 0.0455 lbm/ft3 = -1.57 in. wg

Q = Q1 Ps1 = Ps3
= Q3 (ρ3/ρ1) = (Ps3a + Ps3b)/2
= 891501 (0.0455/0.0455) = (-18.8 - 18.3)/2
= 891501 cfm = -18.55 in. wg

FAN POWER INPUT Ps = Ps2 - Ps1 - Pv1


= -1.57 - (-18.55) - 2.04
Measured amps/FLA = (378/385) = 14.94 in. wg
= 0.98
= 98% CONVERSION TO SPECIFIED CONDITIONS
Annex K indicates that Equation A will provide a Qc = 891501 (880/892)
reasonably accurate estimate of motor power output
= 879508 cfm
for a 3000 hp motor operating at 98% FLA.

Hmo = 3000 (378/385) (4250/4000) Psc = 14.94 (880/892)2 (0.049/0.0455)


= 3130 hp = 15.66 in. wg

The data supplied by the motor manufacturer indicate Hc = 3174 (880/892)3 (0.049/0.0455)
motor efficiency of 94% at the measured power input = 3282 hp
of 2519 kW. Using this information:

Hmo = (2519 × 0.94)/0.746


= 3174 hp

The more accurate method of estimating the motor


power output is assumed to be the latter. Since the
fan is direct connected to the motor, there is no drive
loss, and:

H = Hmo
= 3174 hp

50
AMCA 203-90 (R2007)

EXAMPLE 2F: AXIAL FAN IN A VENTILATION SYSTEM

GUIDE VANES STATIC PRESSURE TAPS

4 5

SEF 1

2-PIECE ELBOW
(TYPICAL)

INNER SEF 2
L1 L2
CYLINDER

1 2

COMMENTS

1. The unusual duct arrangement in this example 4. Measure td3 and tw3 in the traverse plane.
makes it very difficult to obtain accurate pressure Determine pb for the general vicinity of the fan.
measurements, and this fact should be understood Measure td4. These measurements are used in
before testing begins. Also, the use of a diverging determining densities at the various planes of
inlet fitting and a converging outlet fitting with this fan interest.
can pose additional problems. Unless the degrees of
divergence and convergence are moderate, as they 5. Measure the fan speed, motor amps, volts, and if
are in this example, the fan performance will be possible, watts. Record all pertinent motor nameplate
adversely affected. data, including volts (NPV) and full load amps (FLA).
If the motor power output is to be estimated by using
2. Determine Pv3 by using the root mean square of the phase current method described in Annex K, it is
the velocity pressure measurements made in a not necessary to measure motor watts; however, it
traverse of Plane 3, located well downstream in a may be necessary to disconnect the drive and
straight run of duct, such as shown in the diagram. measure the no load amps (NLA) if the motor is not
Determine Ps3 by averaging the static pressure operating at or near its full load point. Motor
measurements made in the same traverse. performance data, supplied by the motor
Procedures for traverses are described in Section manufacturer, are used in the determination of motor
9.4. Ps3 is used in determining the density at the power output for this example.
traverse plane. Measure the area of the traverse
plane, A3. 6. SEF 1 is due to the effect of insufficient length of
duct between the fan inlet and the elbow upstream of
3. Determine Ps5 by averaging the pressure the fan. SEF 2 is due to the effect of insufficient
measurements at each of four static pressure taps length of duct between the fan outlet and the elbow
located near the end of the duct connection at the fan downstream of the fan. In order to calculate the
outlet. Determine Ps4 by using static pressure taps in values of the SEFs, it is necessary to measure the
the duct connection at the fan inlet. Measure A4 and inlet area and the outlet area of the fan, A1 and A2;
A5, the cross-sectional areas of the duct connections and the lengths of the inlet and outlet duct
at the static pressure taps. connections, L1 and L2.

51
AMCA 203-90 (R2007)

7. To calculate the Fan Static Pressure: 460 volts, 1760 rpm, 24.6 FLA

Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2 GENERAL

Where: Fan direct connected to motor. Motor efficiency data


supplied by motor manufacturer. Fan speed
Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1) measurement was not obtained due to the closed
duct arrangements on both sides of the fan. The
Ps2 and Ps1 are calculated using measured static measured amps indicate that the motor is operating
pressure values and constant total pressure very close to the full load condition, so the rpm was
considerations. assumed to be the motor nameplate value of 1760.

Ps1 + Pv1 = Ps4 + Pv4 CALCULATIONS


Ps2 + Pv2 = Ps5 + Pv5
DENSITIES
Where each velocity pressure is calculated in a
For Plane 3 conditions of:
manner similar to the calculation of Pv1, shown
above. td3 = 82.8°F
tw3 = 57.2°F
8. In order to compare the test results to the quoted
fan curve drawn for operation at 1750 rpm and 0.075
p3 = pb + (Ps3/13.6)
lbm/ft3 density, it is necessary to convert the results
= 29.76 + (0.5/13.6)
to the specified conditions. The basis for the
= 29.80 in. Hg
calculations is described in Section 14.
Use Figure N.1 in Annex N to obtain ρ3 = 0.0728
OBSERVATIONS
lbm/ft3.
SITE MEASUREMENTS
It is assumed ρ2 = ρ5 = ρ3.
pb = 29.76 in. Hg
td3 = 82.8°F The density at Planes 1 and 4:
tw3 = 57.2°F
td4 = 80°F ρ1 = ρ 4
Ps3 = 0.5 in. wg ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
Pv3 = 0.783 in. wg = ρ3 ⎜ s4 ⎟⎜ ⎟
⎝ 13.6 p3 ⎠ ⎝ t d4 + 460 ⎠
Ps4 = -1.1 in. wg
⎛ −1.1 + 13.6 × 29.76 ⎞ ⎛ 542.8 ⎞
Ps5 = 0.82 in. wg = 0.0728 ⎜ ⎟ ⎜ 540 ⎟
A1 = A2 ⎝ 13.6 × 29.80 ⎠⎝ ⎠
= 7.1 ft2 = 0.0729 lbm/ft 3
A3 = A5
= 4.91 ft2 FLOW RATES
A4 = 6.2 ft2
L1 = 3.0 ft V3 = 1096 (Pv3/ρ3)0.5
L2 = 3.5 ft = 1096 (0.783/0.0728)0.5
= 3594 fpm
MEASURED MOTOR DATA
Q3 = V3A3
Volts = 460, 461, 459 = 3594 × 4.91
= 460 av = 17647 cfm
Amps = 25.0, 25.0, 24.8
= 24.9 av Q = Q1
kW = 18.0 = Q3 (ρ3/ρ1)
= 17647 (0.0728/0.0729)
MOTOR NAMEPLATE DATA
= 17623 cfm
20 hp, 3 phase, 60 hertz

52
AMCA 203-90 (R2007)

FAN POWER INPUT Diameter of the fan outlet:

The data supplied by the motor manufacturer indicate D2 = (4A2/π)0.5


motor efficiency of 87.5% at the measured power = (4 × 7.1/π)0.5
input of 18.0 kW. Using this information: = 3.01 ft

Hmo = (18.0 × 0.875)/0.746 Figure 8.1 shows that for velocities of 2500 fpm or
= 21.1 hp less, the 100% effective duct length is 2.5 diameters:

Since the fan is direct connected to the motor, there = 2.5 × 3.01
is no drive loss, and: = 7.53 ft

H = Hmo The length of the outlet duct in % effective duct


= 21.1 hp length:

SYSTEM EFFECT FACTORS = (L2/7.53) 100


= (3.5/7.53) 100
To determine the value of SEF 1, calculate the = 46%
velocity at the fan inlet:
From Figure 8.4, for a vaneaxial fan with a 46%
V1 = (Q1/A1) effective duct length between its discharge and a two
= (17623/7.1) piece elbow, System Effect Curve W applies. From
= 2482 fpm Figure 7.1 for 2485 fpm velocity and curve W, SEF 2
is less than 0.1 in. and is considered negligible.
Diameter of the fan inlet:
SEF 2 = 0.00
D1 = (4A1/π)0.5
= (4 × 7.1/π)0.5 FAN STATIC PRESSURE
= 3.01 ft
Pv5 = Pv3 (A3/A5)2 (ρ3/ρ5)
The length of the duct between the elbow and the fan = 0.783 (4.91/4.91)2 (0.0728/0.0728)
inlet in terms of the fan inlet diameter: = 0.783 in. wg

= (L1/D1) Pv2 = Pv3 (A3/A2)2 (ρ3/ρ2)


= (3.0/3.01) = 0.783 (4.91/7.1)2 (0.0728/0.0728)
= 1.00 = 0.37 in. wg

AMCA Publication 201-90, Figure 9.2 indicates that Ps2 + Pv2 = Ps5 + Pv5
for a two piece elbow with a length of duct between Ps2 = Ps5 + Pv5 - Pv2
the elbow and the fan inlet equal to 1.00 diameter = 0.82 + 0.783 - 0.37
System Effect Curve S-T applies. For a velocity of = 1.23 in. wg
2482 fpm and curve S-T, Figure 7.1 shows SEF 1 =
0.25 in. wg at 0.075 lbm/ft3. At 0.0729 lbm/ft3: Pv4 = Pv3 (A3/A4)2 (ρ3/ρ4)
SEF 1 = 0.25 (0.0729/0.075) = 0.783 (4.91/6.2)2 (0.0728/0.0729)
= 0.24 in. wg = 0.49 in. wg

For SEF 2, AMCA Publication 201-90, Figures 7.1, Pv1 = Pv3 (A3/A1)2 (ρ3/ρ1)
8.1, and 8.4 indicate the following calculations: = 0.783 (4.91/7.1)2 (0.0728/0.0729)
= 0.37 in. wg
Q2 = Q3 (ρ3/ρ2)
= 17647 (0.0728/0.0728) Ps1 + Pv1 = Ps4 + Pv4
= 17647 cfm Ps1 = Ps4 + Pv4 - Pv1
= -1.1 + 0.49 - 0.37
V2 = Q2/A2 = -0.98 in. wg
= 17647/7.1
= 2485 fpm

53
AMCA 203-90 (R2007)

Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2


= 1.23 - (-0.98) - 0.37 + 0.24 + 0
= 2.08 in. wg

CONVERSION TO SPECIFIED CONDITIONS

Qc = 17623 (1750/1760)
= 17523 cfm

Psc = 2.08 (1750/1760)2 (0.075/0.0729)


= 2.12 in. wg

Hc = 21.1 (1750/1760)3 (0.075/0.0729)


= 21.3 hp

54
AMCA 203-90 (R2007)

EXAMPLE 2G: HIGH PRESSURE CENTRIFUGAL FAN IN A SERIES

2b
STATIC PRESSURE TAPS

1b
2a FAN B
1a

DAMPER

INLET BOX INLET BOX


FAN A

SIDE VIEW

COMMENTS

1. The two single inlet fans in this example have measurements are assumed to exist at the
been rated by the manufacturer as a two stage respective plane of interest because of the close
assembly. Although rated as an assembly, sufficient proximity and the fact that the two planes are equal in
measurements are made to provide performance area. The static pressure at each plane may be
data for each fan. The damper downstream of the determined by averaging the static pressure
second fan is not included as part of the rated measurements at each of four static pressure taps, or
assembly. In virtually all cases in which an air flow by averaging the static pressure measurements
control damper, such as the one shown in the made in a Pitot-static tube traverse of the plane.
diagram, is included in the system, the point of However, due to the turbulence existing in the
operation of major interest and for which the fan has regions of the outlets of the fans, it is recommended
been selected is at the maximum air flow rate. This that static pressure taps be used at Planes 1b-2a and
example is no exception. Therefore, it is essential 2b.
that the damper be fixed in its full open position for
the duration of the test. 4. Measure td3, tw3, td1b, and td2b; td1a is assumed to be
equal to td3. Determine pb for the general vicinity of
2. Determine Pv3 by using the root mean square of the fan. These measurements are used in
the velocity pressure measurements made in a determining densities at the planes of interest.
traverse of Plane 3. Determine Ps3 by averaging the
static pressure measurements made in the same 5. Measure the fan speed and the motor amps, volts,
traverse. Procedures for traverses are described in and if possible, watts for each fan. Record all
Section 9.4. Ps3 is used in determining the density at pertinent motor nameplate data, including volts
the traverse plane, A3, which is located at the tip of (NPV), and full load amps (FLA). If the motor power
the Pitot-static tube. outputs are to be estimated by using the phase
current method described in Annex K, it is not
3. Determine the static pressures at Planes 1a, 1b- necessary to measure motor watts; however, it may
2a, and 2b. As shown in the diagram, these planes be necessary to disconnect the drives and measure
are located shortly downstream of the inlets and the no load amps (NLA) if the motors are not
outlets of the fans, which are the planes of interest. In operating at or near their full load points. In this
each case, the conditions which exist at the plane of example, a watts input measurement is made for

55
AMCA 203-90 (R2007)

each motor and motor performance data, supplied by Second Stage


the motor manufacturer, are used in determining Volts = 4080, 4040, 4020
motor power outputs. = 4047 av
Amps = 44, 44.5, 45
6. The SEF which would normally be attributed to = 44.5 av
insufficient length of duct at the outlet of the first kW = 272
stage fan does not apply in this case because the
fans have been rated as an assembly. MOTOR NAMEPLATE DATA

7. To calculate the static pressure for the two stage Data identical for each stage:
assembly: 350 hp, 3 phase, 60 hertz
4000 volts, 1790 rpm, 44.5 FLA
Ps = Ps2b - Ps1a - Pv1a
GENERAL
Where:
Fans direct connected to motors. Motor efficiency
Pv1a = Pv3 (A3/A1a)2 (ρ3/ρ1a) data supplied by motor manufacturer.

8. In order to compare the test results to the CALCULATIONS


performance quoted for the two stage assembly for
operation at 1780 rpm and 0.045 lbm/ft3 density, it is DENSITIES
necessary to convert the results to the specified
conditions. The basis for the calculations is described For Plane 3 conditions of:
in Section 14.
td3 = 35°F
OBSERVATIONS tw3 = 33°F

SITE MEASUREMENTS p3 = pb + (Ps3/13.6)


= 28.64 + (-150/13.6)
pb = 28.64 in. Hg = 17.61 in. Hg
td3 = 35°F
tw3 = 33°F Use the modified Apjohn equation for partial vapor
td1b = td2a pressure and the density equation based on perfect
gas relationships, both of which are described in
= 95°F
Annex M, and the data in Figure N.2 in Annex N to
td2b = 147°F
calculate the density at Plane 3.
Pv3 = 0.745 in. wg
Ps3 = -150 in. wg pe = 0.1879 in. Hg
Ps1b = Ps2a
= -79.5 in. wg
p3 (t d3 − t w3 )
Ps2b = 0.5 in. wg pp = pe −
Na = 1790 rpm, first stage fan speed 2700
Nb = 1790 rpm, second stage fan speed 17.61(35 − 33)
= 0.1879 −
A1a = A2a = A1b = A2b 2700
= 5.6 ft2 = 0.1749 in. Hg
A3 = 4.92 ft2
1.3257( p3 − 0.378 pp )
MEASURED MOTOR DATA ρ3 =
t d3 + 460
First Stage 1.3257 (17.61 − 0.378 × 0.1749 )
=
Volts = 4000, 4040, 4080 35 + 460
= 4040 av = 0.0470 lbm/ft 3
Amps = 44.5, 45, 45.5
= 45 av
kW = 278 Any conversion of velocity pressure to static pressure
which may occur between Planes 3 and 1a can be
ignored with no significant effect on the accuracy of
the test results. Therefore:

56
AMCA 203-90 (R2007)

Ps1a = Ps3 FAN POWER INPUT


= -150 in. wg
At the measured power input values of 278 kW and
Assuming no change in temperature between Planes 272 kW, the data supplied by the motor manufacturer
3a and 1a: indicate efficiency of 95% for each motor.

ρ1a = ρ3 Hmoa = (278 × 0.95)/0.746


= 0.0470 lbm/ft3 = 354 hp

To provide information regarding the flow rates Hmob = (272 × 0.95)/0.746


between stages and leaving the second stage, = 346 hp
additional density values are calculated as follows:
Since each fan is direct connected to its motor, there
ρ1b = ρ2a are no drive losses and:

⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞ Ha = Hmoa


= ρ3 ⎜ s1b ⎟⎜ ⎟
⎝ 13.6 p3 ⎠ ⎝ t d4 + 460 ⎠ = 354 hp
⎛ −79.5 + 13.6 × 28.64 ⎞ ⎛ 495 ⎞
= 0.0470 ⎜ ⎟ ⎜ 555 ⎟ Hb = Hmob
⎝ 13.6 × 17.61 ⎠⎝ ⎠
= 346 hp
= 0.0543 lbm/fft 3
FAN STATIC PRESSURE
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ2b = ρ3 ⎜ s2b ⎟⎜ ⎟ Pv1a = Pv3 (A3/A1a)2 (ρ3/ρ1a)
⎝ 13.6 p3 ⎠ ⎝ t d2b + 460 ⎠ = 0.745 (4.92/5.6)2 (0.0470/0.0470)
⎛ 0.5 + 13.6 × 28.64 ⎞ ⎛ 495 ⎞ = 0.575 in. wg
= 0.0470 ⎜ ⎟⎜ ⎟
⎝ 13.6 × 17.61 ⎠ ⎝ 607 ⎠
= 0.0624 lbm/ftt 3 The static pressure for the two stage assembly:

Ps = Ps2b - Ps1a - Pv1a


FLOW RATES
= 0.5 - (-150) - 0.575
= 149.9 in. wg
V3 = 1096 (Pv3/ρ3)0.5
= 1096 (0.745/0.0470)0.5 CONVERSION TO SPECIFIED CONDITIONS
= 4364 fpm
Qc = 21471 (1780/1790)
Q3 = V3A3 = 21351 cfm
= 4364 × 4.92
= 21471 cfm Psc = 149.9 (1780/1790)2 (0.045/0.0470)
= 141.9 in. wg
Q = Q1a
= Q3 (ρ3/ρ1a) Hac = 354 (1780/1790)3 (0.045/0.0470)
= 21471 (0.0470/0.0470) = 333 hp
= 21471 cfm
Hbc = 346 (1780/1790)3 (0.045/0.0470)
Q1b = Q2a
= 326 hp
= Q3 (ρ3/ρ2a)
= 21471 (0.0470/0.0543)
= 18584 cfm

Q2b = Q3 (ρ3/ρ2b)
= 21471 (0.0470/0.0624)
= 16172 cfm

57
AMCA 203-90 (R2007)

EXAMPLE 3A: CENTRIFUGAL FAN IN AN EXHAUST SYSTEM

AIR INTAKE VENTS


BACKDRAFT DAMPER

SEF 1

3a
2

3c

3b

STATIC PRESSURE TAPS


PLAN VIEW

COMMENTS

1. This fan, as supplied and rated by the Pitot-static tube is used, it should be positioned well
manufacturer, does not include the backdraft damper. within the inlet collar in which Plane 1 is located.
Measure the area of Plane 1 for use in calculating
2. Normally, velocity pressure measurements would Pv1. The static pressure at the outlet of the backdraft
be made in a single plane, located in a duct common damper is zero gauge pressure, referred to the
to all branches. In this example, a measurement atmospheric pressure in the region of the outlet of the
plane which provides a satisfactory velocity profile backdraft damper. In situations such as this example,
cannot be located within the short length of duct the air may be discharging from the damper into a
between the point of connection of the branch ducts region in which the atmospheric pressure is
and the fan inlet. The alternative, as indicated in the somewhat different from that to which all other
diagram, is to make a velocity pressure pressure measurements are referred. When this
measurement traverse in the longest available duct possibility exists, it is essential that the static
run of each branch. The velocity pressure for each pressure in the region of the discharging air be
branch is determined by using the root mean square measured, referred to the same atmospheric
of the velocity pressure measurements made in the pressure as used in all other pressure
traverse. The static pressure at each traverse plane measurements.
is determined by averaging the static pressure
measurements made in the same traverse. These 4. Measure the dry-bulb and wet-bulb temperatures
static pressure values are used in determining the at each velocity traverse plane and the dry-bulb
densities at the traverse planes. Procedures for temperature at Plane 1. In this example, td2 is
traverses are described in Section 9.4. In order to assumed to be equal to td1. Determine pb for the
determine the air flow rates it is necessary to general vicinity of the fan. These measurements are
measure the area of each traverse point. used in determining densities at the planes of
interest.
3. Ps1, the static pressure at the fan inlet may be
determined by averaging the static pressure 5. Measure the fan speed and the motor amps, volts,
measurements at each of four static pressure taps or and if possible, watts. Record all pertinent motor
by averaging the static pressure measurements nameplate data, including volts (NPV) and full load
made in a Pitot-static tube traverse of Plane 1. If a amps (FLA). If the motor power output is to be

58
AMCA 203-90 (R2007)

estimated by using the phase current method Pv3a = 0.765 in. wg


described in Annex K, it is not necessary to measure Pv3b = 0.88 in. wg
motor watts; however, it may be necessary to Pv3c = 0.86 in. wg
disconnect the drive and measure the no load amps N = 800 rpm
(NLA) if the motor is not operating at or near its full A1 = 16.8 ft2
load point. Refer to Annex K.
A2 = 13.8 ft2
6. SEF 1 is due to the effect of there being no duct A3a = 5.4 ft2
at the fan outlet. In order to calculate the value of A3b = A3c
SEF 1, it is necessary to measure the outlet area of = 3.0 ft2
the fan, A2, and the blast area of the fan. Blast Area = 11.0 ft2

7. Determine the backdraft damper pressure loss by MEASURED MOTOR


using the performance ratings supplied by the
manufacturer and the pressure loss multiplier data in Volts = 460, 458, 462
Figure 8.7 of AMCA Publication 201-90. The use of = 460 av
the multiplier is indicated because the damper is Amps = 28, 27, 26
mounted directly to the fan outlet. = 27 av
NLA = 14.7
8. To calculate the Fan Static Pressure:
MOTOR NAMEPLATE DATA
Ps = Ps2 - Ps1 - Pv1 + SEF 1
25 hp, 3 phase, 60 hertz
Where: 460 volts, 1760 rpm, 32 FLA

Pv1 = (Q1/1096 A1)2 ρ1 GENERAL

Q1 = Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1) + Q3c (ρ3c/ρ1) Fan connected to motor through belt drive. Pressure
loss data supplied by manufacturer of backdraft
Ps2 is the sum of the static pressure in the region of damper.
the damper outlet, which was measured as zero, and
the backdraft damper pressure loss. CALCULATIONS

9. In order to compare the test results to the quoted DENSITIES


fan curve drawn for operation at 810 rpm and 0.075
Since the static pressure values at Planes 1, 3a, 3b,
lbm/ft3 density, it is necessary to convert the results
and 3c are very small, no appreciable error will occur
to the specified conditions. The basis for the
by using the barometric pressure instead of the
calculations is described in Section 14.
absolute pressure at each plane in the determination
of the densities. The densities at these planes are
OBSERVATIONS
obtained by using Figure N.1 in Annex N.
SITE MEASUREMENTS
ρ1 = 0.0739 lbm/ft3
pb = 29.8 in. Hg ρ3a = 0.0731 lbm/ft3
td1 = 72°F ρ3b = 0.0750 lbm/ft3
tw1 = 62°F ρ3c = 0.0741 lbm/ft3
td3a = 77°F
tw3a = 67°F FLOW RATES
td3b = 65°F
tw3b = 56°F V3a = 1096 (Pv3a/ρ3a)0.5
td3c = 70°F = 1096 (0.765/0.0731)0.5
tw3c = 62°F = 3546 fpm
Ps1 = -1.00 in. wg
Ps3a = -0.80 in. wg V3b = 1096 (Pv3b/ρ3b)0.5
Ps3b = -0.45 in. wg = 1096 (0.88/0.0750)0.5
Ps3c = -0.040 in. wg = 3754 fpm

59
AMCA 203-90 (R2007)

V3c = 1096 (Pv3c/ρ3c)0.5 SYSTEM EFFECT FACTOR


= 1096 (0.86/0.0741)0.5
= 3734 fpm AMCA Publication 201-90, Figures 7.1 and 8.3
indicate the following calculations:
Q3a = V3aA3a
= 3546 × 5.4 Q2 = Q1
= 19148 cfm = 41603 cfm

Q3b = V3bA3b It is assumed that ρ2 = ρ1.


= 3754 × 3.0
= 11262 cfm V2 = (Q2/A2)
= (41603/13.8)
Q3c = V3cA3c = 3015 fpm
= 3734 × 3.0
= 11202 cfm Blast area ratio = Blast area/A2
= 11.0/13.8
= 0.80
Q = Q1
= Q3a ( ρ3a / ρ1 ) + Q3 b ( ρ3 b / ρ1 ) + Q3c ( ρ3c / ρ1 )
For a blast area ratio of 0.8 and no duct, Figure 8.3
⎛ 0.0731 ⎞ ⎛ 0.0750 ⎞ ⎛ 0.0741 ⎞ shows System Effect Curve T-U applies. For 3015
= 19148 ⎜ ⎟ + 11262 ⎜ 0.0739 ⎟ + 11202 ⎜ 0.0739 ⎟
⎝ 0.0739 ⎠ ⎝ ⎠ ⎝ ⎠ fpm velocity and curve T-U, Figure 7.1 shows SEF 1
= 41603 cfm = 0.27 in. wg at 0.075 lbm/ft3 density. At 0.0739
lbm/ft3:

FAN POWER INPUT SEF 1 = 0.27 (0.0739/0.075)


= 0.27 in. wg
Measured amps/FLA = (27/32)
= 0.84 BACKDRAFT DAMPER LOSS MULTIPLIER
= 84%
The data supplied by the manufacturer of the damper
Annex K indicates that the average of the results of indicate that the pressure loss for the damper, ΔPs, is
Equation A and Equation B will provide a reasonably 0.4 in. wg at the flow rate of 41603 cfm at 0.075
accurate estimate of motor power output for a 25 hp lbm/ft3 density. AMCA Publication 201-90, Figure 8.7
motor operating at 84% FLA. indicates a ΔPs multiplier of 1.9 for a damper which is
mounted directly to the outlet of a fan which has a
Eqn A = 25 (27/32) (460/460) blast area ratio of 0.8.
= 21.1 hp
Backdraft damper loss = ΔPs × 1.9 × (ρ2/0.075)
Eqn B = 25 [(27 - 14.7)/(32 - 14.7)] (460/460) = 0.4 × 1.9 (0.0739/0.075)
= 17.8 hp = 0.75 in. wg

Hmo = (21.1 + 17.8)/2 FAN STATIC PRESSURE


= 19.45 hp
Pv1 = (Q1/1096 A1)2 ρ1
Figure L.1 in Annex L indicates estimated belt drive = [41603/(1096 × 16.8)]2 0.0739
loss of 4.8%. = 0.38 in. wg
HL = 0.048 Hmo Ps2 is equal to the static pressure at the outlet of the
= 0.048 × 19.45 damper, which is zero, plus the damper loss.
= 0.93 hp
Ps2 = 0 + damper loss
H = Hmo - HL
= 0 + 0.75
= 19.45 - 0.93 = 0.75 in. wg
= 18.52 hp Ps = Ps2 - Ps1 - Pv1 + SEF 1
= 0.75 - (-1.0) - 0.38 + 0.27
= 1.64 in. wg

60
AMCA 203-90 (R2007)

CONVERSION TO SPECIFIED CONDITIONS

Qc = 41603 (810/800)
= 42123 cfm

Psc = 1.64 (810/800)2 (0.075/0.0739)


= 1.71 in. wg

Hc = 18.52 (810/800)3 (0.075/0.0739)


= 19.51 hp

61
AMCA 203-90 (R2007)

EXAMPLE 3B: AXIAL FAN IN AN EXHAUST SYSTEM

2-PIECE ELBOW

SEF 1

L1
1
STATIC GUIDE VANES
PRESSURE TAPS
INNER CYLINDER
2
SEF 2
L2
5

PLAN VIEW

COMMENTS

1. Determine Pv3 by using the root mean square of load amps (FLA). If the motor power output is to be
the velocity pressure measurements made in a estimated by using the phase current method
traverse of Plane 3, located near the end of a straight described in Annex K, it is not necessary to measure
run of duct, as shown in the diagram. Determine Ps3 motor watts; however, it may be necessary to
by averaging the static pressure measurements disconnect the drive and measure the no load amps
made in the same traverse. Procedures for traverses (NLA) if the motor is not operating at or near its full
are described in Section 9.4. Ps3 is used in load point. Refer to Annex K.
determining the density at the traverse plane.
Measure the area of the traverse plane, A3, which is 5. SEF 1 is due to the effect of insufficient length of
located at the tip of the Pitot-static tube. duct between the fan inlet and the elbow upstream of
the fan. SEF 2 is due to the effect of insufficient
2. Determine Ps5 by averaging the pressure length of duct between the fan outlet and the elbow
downstream of the fan. In order to calculate the
measurements at each of four static pressure taps
values of the SEFs, it is necessary to measure the
located near the end of the duct connection at the fan
inlet area and the outlet area of the fan, A1 and A2;
outlet. Determine Ps1 by using a Pitot-static tube or
and the lengths of the inlet and outlet duct
static pressure taps in the duct connection at the fan
connections, L1 and L2.
inlet. If a Pitot-static tube is used, it should not project
into the upstream elbow but be located well within the
6. To calculate the Fan Static Pressure:
length of the duct connection.
Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
3. Measure td3 and tw3 in the traverse plane; td1 is
assumed to be equal to td3. Determine pb for the
Where: Pv1 = Pv3
general vicinity of the fan. Measure td5. These
measurements are used in determining densities at
Since:
the planes of interest.
A1 = A3
4. Measure the fan speed and the motors amps,
volts, and if possible, watts. Record all pertinent
And:
motor nameplate data, including volts (NPV), and full
62
AMCA 203-90 (R2007)

ρ1 = ρ3 CALCULATIONS

Due to the close proximity of Planes 2 and 5 and the DENSITIES


fact that there is no change in area between the two
planes, all conditions which exist at Plane 5 are For Plane 3 conditions of:
assumed to exist at Plane 2.
td3 = 72°F
Therefore: tw3 = 66°F

Ps2 = Ps5 p3 = pb + (Ps3/13.6)


= 29.20 + (-1.92/13.6)
7. In order to compare the test results to the quoted = 29.06 in. Hg
fan curve drawn for operation at 1730 rpm and 0.075
lbm/ft3 density, it is necessary to convert the results Use Figure N.1 in Annex N to obtain ρ3 = 0.0719
to the specified conditions. The basis for the lbm/ft3.
calculations is described in Section 14.
Assume that td1 = td3.
OBSERVATIONS

SITE MEASUREMENTS ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞


ρ1 = ρ3 ⎜ s1 ⎟⎜ ⎟
⎝ 13.6 p3 ⎠ ⎝ t d1 + 460 ⎠
pb = 29.20 in. Hg
⎛ −2.02 + 13.6 × 29.20 ⎞ ⎛ 532 ⎞
td3= 72°F = 0.0719 ⎜ ⎟ ⎜ 532 ⎟
⎝ 13.6 × 29.06 ⎠⎝ ⎠
tw3= 66°F
td5= 73°F = 0.0719 lbm/ft 3
Ps1= -2.02 in. wg
Ps3= -1.92 in. wg Assume that td2 = td5 and Ps2 = Ps5.
Pv3= 0.35 in. wg
Ps5= 0.10 in. wg ρ 2 = ρ5
N = 1710 rpm
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
A1 = A2 = A3 = A5 = ρ3 ⎜ s5 ⎟⎜ ⎟
= 2.64 ft2 ⎝ 13.6 p3 ⎠ ⎝ t d5 + 460 ⎠
L1 = 1.5 ft, length of inlet duct ⎛ 0.10 + 13.6 × 29.20 ⎞ ⎛ 532 ⎞
= 0.0719 ⎜ ⎟ ⎜ 533 ⎟
L2 = 2.25 ft, length of the outlet duct ⎝ 13.6 × 29.06 ⎠⎝ ⎠
= 0.0721 lbm/ft 3
MEASURED MOTOR DATA

Volts = 227, 229, 228 FLOW RATES


= 228 av
Amps = 12.2, 12.3, 12.4 V3 = 1096 (Pv3/ρ3)0.5
= 12.3 av = 1096 (0.35/0.0719)0.5
NLA = 7 = 2418 fpm

MOTOR NAMEPLATE DATA Q3 = V3A3


= 2418 × 2.64
5 hp, 3 phase, 60 hertz = 6384 cfm
230 volts, 1760 rpm, 14.0 FLA
Q = Q1
GENERAL = Q3 (ρ3/ρ1)
= 6384 (0.0719/0.0719)
Fan connected to motor through belt drive.
= 6384 cfm

Q2 = Q5
= Q3 (ρ3/ρ5)
= 6384 (0.0719/0.0721)
= 6366 cfm

63
AMCA 203-90 (R2007)

FAN POWER INPUT R-S, Figure 7.1 shows SEF 1 = 0.24 in. wg at 0.075
lbm/ft3 density. At 0.0719 lbm/ft3:
Measured amps/FLA = (12.3/14.0)
= 0.88 SEF 1 = 0.24 (0.0719/0.075)
= 88% = 0.23 in. wg
Annex K indicates that the average of the results of
Equation A and Equation B will provide a reasonably For SEF 2, AMCA Publication 201-90, Figures 7.1,
accurate estimate of motor power output for a 5 hp 8.1, and 8.4 indicate the following calculations:
motor operating at 88% FLA.
V2 = (Q2/A2)
Eqn A = 5 (12.3/14) (228/230) = (6366/2.64)
= 4.35 hp = 2411 fpm

Eqn B = 5 [(12.3 - 7)/(14 - 7)] (228/230) The diameter of the fan outlet:
= 3.75 hp
D2 = (4A2/π)0.5
Hmo = (4.35 + 3.75)/2
= (4 × 2.64/π)0.5
= 4.05 hp = 1.83 ft
Figure L.1 in Annex L indicates estimated belt drive Figure 8.1 shows that for velocities of 2500 fpm or
loss of 6.3%. less, the 100% effective duct length is 2.5 diameters:
HL = 0.063 Hmo = 2.5 × 1.83
= 0.063 × 4.05 = 4.58 ft
= 0.26 hp
The length of the outlet duct in % effective duct
H = Hmo - HL length:
= 4.05 - 0.26
= 3.79 hp = (L2/4.58) 100
= (2.25/4.58) 100
SYSTEM EFFECT FACTORS = 49%

To determine the value of SEF 1, calculate the From Figure 8.4, for a vaneaxial fan with a 49%
velocity at the fan inlet: effective duct length between its discharge and a two
piece elbow, System Effect Curve W applies. From
V1 = (Q1/A1) Figure 7.1, for 2411 fpm velocity and curve W, SEF 2
= (6384/2.64) is less than 0.1 in. wg, and is considered negligible.
= 2418 fpm
SEF 2 = 0.00
Calculate the diameter of the fan inlet:
FAN STATIC PRESSURE
D1 = (4A1/π)0.5
= (4 × 2.64/π)0.5 Since:
= 1.83 ft.
A 1 = A3
Calculate the length of duct between the elbow and ρ1 = ρ3
the fan inlet in terms of the fan inlet diameter: Pv1 = Pv3

= (L1/D1) Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2


= (1.5/1.83) = 0.10 - (-2.02) - 0.35 + 0.23 + 0.00
= 0.82 = 2.00 in. wg

AMCA Publication 201-90, Figure 9.2, indicates that


for a vaneaxial fan with a two piece elbow with a
length of duct between the elbow and the fan inlet
equal to 0.8 diameters, System Effect Curve R-S
(estimated) applies. For 2418 fpm velocity and curve

64
AMCA 203-90 (R2007)

CONVERSION TO SPECIFIED CONDITIONS

Qc = 6384 (1730/1710)
= 6459 cfm

Psc = 2.00 (1730/1710)2 (0.075/0.0719)


= 2.14 in. wg

Hc = 3.79 (1730/1710)3 (0.075/0.0719)


= 4.09 hp

65
AMCA 203-90 (R2007)

EXAMPLE 3C: CENTRIFUGAL FAN IN A SCRUBBER SYSTEM

3
WET CELL SCRUBBER
1

2
PLAN VIEW
SEF 1

SIDE VIEW

COMMENTS

1. Determine Pv3 by using the root mean square of amps (FLA). If the motor power output is to be
the velocity pressure measurements made in a estimated by using the phase current method
traverse of Plane 3, located in the duct connection at described in Annex K, it is not necessary to measure
the fan inlet, as shown in the diagram. Determine Ps3 motor watts; however, it may be necessary to
by averaging the static pressure measurements disconnect the drive and measure the no load amps
made in the same traverse. Procedures for traverses (NLA) if the motor is not operating at or near its full
are described in Section 9.4. Ps3 is used in load point. Refer to Annex K.
determining the density at the traverse plane.
Measure the area of the traverse plane, A3, which is 5. SEF 1 is due to the effect of there being no duct
located at the tip of the Pitot-static tube. In locating at the fan outlet. In order to calculate the value of
Plane 3 downstream of the scrubber, changes in the SEF 1, it is necessary to measure the outlet area of
composition of the air as a result of the action of the the fan, A2, and the blast area of the fan.
scrubber are properly taken into account in the
determination of fan air flow rate. Due to the close 6. To calculate the Fan Static Pressure:
proximity of Planes 1 and 3, and the fact that there is
no change in area between the two planes, the Ps = Ps2 - Ps1 - Pv1 + SEF 1
conditions which exist at Plane 3 are assumed to
exist at Plane 1. Where:

2. Ps2, the static pressure at the fan outlet, is zero. Pv1 = Pv3
Ps1 = Ps3
3. Measure td3 and tw3 in the traverse plane. Ps2 = 0
Determine pb for the general vicinity of the fan.
Measure td2. These measurements are used in 7. In order to compare the test results to the quoted
determining densities at the planes of interest. fan curve drawn for operation at 1700 rpm and 0.071
lbm/ft3 density, it is necessary to convert the results
4. Measure the fan speed and the motor amps, volts, to the specified conditions. The basis for the
and if possible, watts. Record all pertinent motor calculations is described in Section 14.
nameplate data, including volts (NPV), and full load
66
AMCA 203-90 (R2007)

OBSERVATIONS
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ2 = ρ3 ⎜ s2 ⎟⎜ ⎟
SITE MEASUREMENTS ⎝ 13.6 p3 ⎠ ⎝ t d2 + 460 ⎠
⎛ 0 + 13.6 × 29.80 ⎞ ⎛ 525 ⎞
pb = 29.80 in. Hg = 0.0732 ⎜ ⎟⎜ ⎟
⎝ 13.6 × 29.21 ⎠ ⎝ 530 ⎠
td3= 65°F
= 0.0740 lbm/ft 3
tw3= 64°F
td2= 70°F
Ps3= -8.0 in. wg FLOW RATES
Pv3= 0.337 in. wg
N = 1672 rpm V3 = 1096 (Pv3/ρ3)0.5
A1 = A3 = 1096 (0.337/0.0732)0.5
= 7.06 ft2 = 2352 fpm
A2 = 5.15 ft2
Q3 = V3A3
Blast Area = 3.67 ft2 = 2353 × 7.06
= 16605 cfm
MEASURED MOTOR DATA
Q = Q1
Volts = 450, 458, 462
= Q3 (ρ3/ρ1)
= 457 av
= 16605 (0.0732/0.0732)
Amps = 44, 45, 44.5
= 16605 cfm
= 44.5 av
Q2 = Q3 (ρ3/ρ2)
MOTOR NAMEPLATE DATA
= 16605 (0.0732/0.0740)
40 hp, 3 phase, 60 hertz = 16425 cfm
460 volts, 1780 rpm, 49 FLA
FAN POWER INPUT
GENERAL
Measured amps/FLA = (44.5/49)
Fan connected to motor through belt drive. = 0.91
= 91%
CALCULATIONS
Annex K indicates that Equation A will provide a
DENSITIES reasonably accurate estimate of motor power output
for a 40 hp motor operating at 91% FLA.
For Plane 3 conditions of:
td3 = 65°F Hmo = 40 (44.5/49) (457/460)
tw3 = 64°F = 36.1 hp

Figure L.1 in Annex L indicates estimate belt drive


p3 = pb + (Ps3/13.6)
loss of 4.5%.
= 29.80 + (-8.0/13.6)
= 29.21 in. Hg
HL = 0.045 Hmo
= 0.045 × 36.1
Use Figure N.1 in Annex N to obtain ρ3 = 0.0732
= 1.6 hp
lbm/ft3.
H = Hmo - HL
It is assumed that:
= 36.1 - 1.6
td1 = td3
= 34.5 hp
Ps1 = Ps3
ρ1 = ρ3 SYSTEM EFFECT FACTOR

AMCA Publication 201-90, Figures 7.1 and 8.3,


indicate the following calculations:

67
AMCA 203-90 (R2007)

V2 = (Q2/A2)
= (16425/5.15)
= 3189 fpm

Blast area ratio = Blast area/A2


= 3.67/5.15
= 0.71

For a blast area ratio of 0.7 and no duct, Figure 8.3


shows System Effect Curve S applies. For 3189 fpm
velocity and curve S, Figure 7.1 shows SEF 1 = 0.5
in. wg at 0.075 lbm/ft3 density. At 0.0740 lbm/ft3:

SEF 1 = 0.5 (0.074/0.075)


= 0.49 in. wg

FAN STATIC PRESSURE

Pv1 = Pv3
= 0.337 in. wg

Ps = Ps2 - Ps1 - Pv1 + SEF 1


= 0 - (-8.0) - 0.337 + 0.49
= 8.15 in. wg

CONVERSION TO SPECIFIED CONDITIONS

Qc = 16605 (1700/1672)
= 16883 cfm

Psc = 8.15 (1700/1672)2 (0.071/0.0732)


= 8.17 in. wg

Hc = 34.5 (1700/1672)3 (0.071/0.0732)


= 35.2 hp

68
AMCA 203-90 (R2007)

EXAMPLE 3D: CENTRIFUGAL ROOF VENTILATOR WITH DUCTED INLET

2
1

BACKDRAFT DAMPER
4
STATIC PRESSURE TAPS

3a SIDE VIEW 3b

COMMENTS

1. This centrifugal roof ventilator, as supplied and 3. Ps4 may be determined by averaging the static
rated by the manufacturer, does not include the pressure measurements at each of four static
backdraft damper. It is essential that the backdraft pressure taps or by averaging the static pressure
damper blades be fixed in their full open positions, measurements made in a Pitot-static tube traverse of
otherwise uneven velocity distribution will occur at Plane 4. If a Pitot-static tube is used, it should be
the inlet to the ventilator, adversely affecting its positioned well within the duct in which Plane 4 is
performance. located, and not project into the upstream elbows.
Measure the area of Plane 1 for use in calculating
2. Normally, velocity pressure measurements would Pv1. In this example, A4 = A1. Ps2, the static pressure
be made in a single plane, located in a duct common at the outlet of the ventilator, is zero gauge pressure,
to all branches. In this example, a measurement referred to the atmospheric pressure in the region of
plane which provides a satisfactory velocity profile the ventilator outlet. In situations such as this
cannot be located within the short length of duct example, the air may be discharging from the
between the point of connection of the branch ducts ventilator into a region in which the atmospheric
and the ventilator inlet. The alternative, as indicated pressure is somewhat different from that to which all
in the diagram, is to make a velocity pressure other pressure measurements are referred. When
measurement traverse in each branch. The velocity this possibility exists, it is essential that the static
pressure for each branch is determined by using the pressure in the region of the discharging air be
root mean square of the velocity pressure measured, referred to the same atmospheric
measurements made in the traverse. The static pressure as used in all other pressure
pressure at each traverse plane is determined by measurements. In this case, Ps2 was measured as
averaging the static pressure measurements made in zero.
the same traverse. These static pressure values are
used in determining the densities at the traverse 4. Measure the dry-bulb and wet-bulb temperatures
planes. Procedures for traverses are described in at each velocity traverse plane. In this example, td1
Section 9.4. In order to determine the air flow rates, it and td4 are assumed to be equal to td3a. Determine pb
is necessary to measure the area of each traverse
for the general vicinity of the fan. These
plane.
measurements are used in determining densities at
the planes of interest.

69
AMCA 203-90 (R2007)

5. Measure the fan speed and the motor amps, volts, MEASURED MOTOR DATA
and if possible, watts. Record all pertinent motor
nameplate data, including volts (NPV) and full load Volts = 450, 455, 460
amps (FLA). If the motor power output is to be = 455 av
estimated by using the phase current method Amps = 5.7, 5.85, 5.9
described in Annex K, it is not necessary to measure = 5.82 av
motor watts; however, it may be necessary to
disconnect the drive and measure the no load amps MOTOR NAMEPLATE DATA
(NLA) if the motor is not operating at or near its full
load point. Refer to Annex K. 5 hp, 3 phase, 60 hertz
460 volts, 1780 rpm, 5.95 FLA
6. Determine the backdraft damper pressure loss by
using the performance ratings supplied by the GENERAL
manufacturer.
Fan connected to motor through belt drive. Pressure
7. To calculate the Fan Static Pressure: loss data supplied by manufacturer of backdraft
damper.
Ps = Ps2 - Ps1 - Pv1
CALCULATIONS
Where:
DENSITIES
Pv1 = (Q1/1096 A1)2 ρ1
For Planes 3a and 3b conditions of:
Q1 = Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1)
td3a = td3b
Ps1 = Ps4 - backdraft damper pressure loss = 72°F
Ps2 = 0 tw3a = tw3b
= 66°F
8. In order to compare the test results to the quoted
fan curve drawn for operation at 620 rpm and 0.075 p3a = p3b
lbm/ft3 density, it is necessary to convert the results = pb + (Ps3a/13.6)
to the specified conditions. The basis for the = 29.20 + (-0.85/13.6)
calculations is described in Section 14. = 29.14 in. Hg

OBSERVATIONS Use Figure N.1 in Annex N to obtain:

SITE MEASUREMENTS ρ3a = ρ3b


= 0.0721 lbm/ft3
pb = 29.20 in. Hg
td3a = td3b It is assumed that:
= 72°F
tw3a = tw3b td1 = td4 = td3a = td3b
= 66°F
Ps2 = 0 in. wg Since the differences in the static pressures at
Ps4 = -0.88 in. wg Planes 1, 3a, and 4 are very small, no appreciable
error will occur by assuming:
Ps3a = Ps3b
= -0.85 in. wg
ρ1 = ρ4 = ρ3a = ρ3b
Pv3a = 0.27 in. wg
Pv3b = 0.275 in. wg
FLOW RATES
N = 625 rpm
A1 = A4
V3a = 1096 (Pv3a/ρ3a)0.5
= 7.9 ft2
= 1096 (0.27/0.0721)0.5
A3a = 3.4 ft2 = 2121 fpm
A3b = 3.3 ft2

70
AMCA 203-90 (R2007)

V3b = 1096 (Pv3b/ρ3b)0.5 BACKDRAFT DAMPER LOSS


= 1096 (0.275/0.0721)0.5
= 2140 fpm The data supplied by the manufacturer of the damper
indicate that the pressure loss for the damper, ΔPs, is
Q3a = V3aA3a 0.22 in. wg at the flow rate of 14273 cfm at 0.075
= 2121 × 3.4 lbm/ft3 density.
= 7211 cfm
Backdraft damper loss = ΔPs (ρ4/0.075)
Q3b = V3bA3b = 0.22 (0.0721/0.075)
= 2140 × 3.3 = 0.21 in. wg
= 7062 cfm
FAN STATIC PRESSURE
Q = Q1
= Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1) Pv1 = (Q1/1096 A1)2 ρ1
= 7211 (0.0721/0.0721) + 7062 (0.0721/0.0721) = [14273/(1096 × 7.9)]2 0.0721
= 14273 cfm = 0.20 in. wg

FAN POWER INPUT Ps1 = Ps4 - damper loss


= -0.88 - 0.21
Measured amps/FLA = (5.82/5.95) = -1.09 in. wg
= 0.98
= 98% Ps = Ps2 - Ps1 - Pv1
= 0 - (-1.09) - 0.20
Annex K indicates that Equation A will provide a = 0.89 in. wg
reasonably accurate estimate of motor power output
for a 5 hp motor operating at 98% FLA. CONVERSION TO SPECIFIED CONDITIONS

Hmo = 5 (5.82/5.95) (455/460) Qc = 14273 (620/625)


= 4.84 hp = 14159 cfm

Figure L.1 in Annex L indicates estimated belt drive Psc = 0.89 (620/625)2 (0.075/0.0721)
loss of 5.8%. = 0.91 in. wg

HL = 0.058 Hmo Hc = 4.56 (620/625)3 (0.075/0.0721)


= 0.058 × 4.84 = 4.63 hp
= 0.28 hp

H = Hmo - HL
= 4.84 - 0.28
= 4.56 hp

71
AMCA 203-90 (R2007)

EXAMPLE 4A: CENTRIFUGAL FAN IN A BUILT-UP AIR CONDITIONING UNIT

4 SEF 1 5
L

RETURN SEF 2
PLAN VIEW
AIR 3a
SPRAY
SECTION FAN SECTION
+ +
OUTSIDE
+
AIR +
+
+ +

+
+ +

PREHEAT COILS DIFFUSER REHEAT COIL


FILTER SECTION PLATE 3b
SIDE VIEW

COMMENTS

1. This is an air conditioning unit which has been is determined by using the root mean square of the
assembled at the installation site. The subject of the velocity pressure measurements made in the
test is the fan, which is rated by the manufacturer as traverse. the static pressure at each traverse plane is
free-standing, unencumbered by the cabinet in which determined by averaging the static pressure
it has been installed. The fan performance ratings are measurements made in the same traverse. These
based on operation with the fan outlet ducted. Before static pressure values are used in determining the
proceeding with the test, it is essential that all densities at the traverse planes. Procedures for
dampers--outside air, return air, mixing box, traverses are described in Section 9.4. In order to
multizone, face and bypass or volume control--be determine the air flow rates, it is necessary to
fixed in the positions agreed upon by all interested measure the area of each traverse plane.
parties as being applicable for the installation. Also,
the temperatures of the heating coils must be kept 3. Determine Ps4 by averaging the static pressure
constant throughout the test period. It may be measurements made in a traverse of Plane 4.
necessary to lock out, disconnect, or otherwise Determine Ps5 in a similar manner. Pitot-static tube
modify automatic control devices in order to prevent traverses are used in determining these static
the positions of the dampers and temperatures of the pressures because the installation of suitable
coils from changing during the test. Refer to Section pressure taps is usually prevented by the insulating
17.4.3 for additional considerations affecting the test material encountered in this type of equipment. Due
procedure for fans in this type of installation. to the abrupt expansion in area from Plane 2 to Plane
5, it is assumed that there is no conversion of velocity
2. Normally, velocity pressure measurements would pressure at Plane 2 to static pressure at Plane 5.
be made in a single plane, located in a duct common Therefore, it is assumed that Ps2 = Ps5. Measure the
to all branches. In this example, a measurement area of Plane 4 for use in calculating Pv4.
plane which provides a satisfactory velocity profile
cannot be located upstream of the fan or between the 4. Measure the dry-bulb and wet-bulb temperatures
point of connection of the branch ducts and the fan at Plane 4 and the dry-bulb temperatures at Planes
outlet. The alternative, as indicated in the diagram, is 3a, 3b, and 5. Determine pb for the general vicinity of
to make a velocity pressure measurement traverse in
the air conditioning unit. These measurements are
each branch. The velocity pressure for each branch
used in determining densities at the planes of interest.

72
AMCA 203-90 (R2007)

5. Measure the fan speed and motor amps, volts, OBSERVATIONS


and if possible, watts. Record all pertinent motor
nameplate data, including volts (NPV), and full load SITE MEASUREMENTS
amps (FLA). If the motor power output is to be
estimated by using the phase current method pb = 28.72 in. Hg
described in Annex K, it is not necessary to measure td3a = 59°F
motor watts; however, it may be necessary to td3b = 90°F
disconnect the drive and measure the no load amps td4 = 56°F
(NLA) if the motor is not operating at or near its full td5 = 58°F
load point. Refer to Annex K.
Ps4 = -1.75 in. wg
Ps3a = 3.65 in. wg
6. SEF 1 is due to the effect of insufficient distance
between the fan inlets and the side walls of the fan Ps3b = 3.45 in. wg
cabinet. SEF 2 is attributed to the high degree of Pv3a = 0.60 in. wg
divergence of the transition fitting at the fan outlet. Pv3b = 0.47 in. wg
The effect created by this fitting is considered to be Ps5 = 3.77 in. wg
equivalent to the effect created by having no duct at N = 1160 rpm
the fan outlet. In order to determine the values of the A2 = 18.9 ft2
SEFs, it is necessary to measure the diameter of an A3a = 7.2 ft2
inlet of the fan, the distance between a fan inlet and
A3b = 9.7 ft2
a side wall of the fan cabinet, and the outlet area and
blast area of the fan. A4 = 93.2 ft2
Blast Area = 13.3 ft2
7. To calculate the Fan Static Pressure: D1 = 3.92 ft, fan inlet diameter
L = 2.83 ft
Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2
= Ps2 - (Ps1 + Pv1) + SEF 1 + SEF 2 MEASURED MOTOR DATA

Where: Volts = 462, 465, 465


= 464 av
Ps2 = Ps5 Amps = 82, 81, 83
Ps1 + Pv1 = Ps4 + Pv4 = 82 av

MOTOR NAMEPLATE DATA


Pv4 = (Q4/1096 A4)2 ρ4
75 hp, 3 phase, 60 hertz
Q4 = Q1
460 volts, 1780 rpm, 90.3 FLA
= Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1)
GENERAL
The calculation of Pv4 is often ignored in instances
similar to this example on the basis that the Fan connected to motor through belt drive.
calculated value of Pv4 is relatively small and its
omission does not affect the test results significantly. CALCULATIONS

8. In order to compare the test results to the quoted DENSITIES


fan curve drawn for operation at 1170 rpm and 0.075
lbm/ft3 density, it is necessary to convert the results For Plane 4 conditions of:
to the specified conditions. The basis for the
calculations is described in Section 14. td4 = 56°F
tw4 = 54°F

p4 = pb + (Ps4/13.6)
= 28.72 + (-1.75/13.6)
= 28.59 in. Hg

73
AMCA 203-90 (R2007)

Use Figure N.1 in Annex N to obtain ρ4 = 0.0731 FAN POWER INPUT


lbm/ft3.
Measured amps/FLA = (82/90.3)
It is assumed that ρ1 = ρ4. = 0.91
= 91%

⎛ P + 13.6 pb ⎞ ⎛ t d4 + 460 ⎞ Annex K indicates that Equation A will provide a


ρ5 = ρ 4 ⎜ s5 ⎟⎜ ⎟
⎝ 13.6 p4 ⎠ ⎝ t d5 + 460 ⎠ reasonably accurate estimate of motor power output
for a 75 hp motor operating at 91% FLA.
⎛ 3.77 + 13.6 × 28.72 ⎞ ⎛ 516 ⎞
= 0.0731⎜ ⎟ ⎜ 518 ⎟
⎝ 13.6 × 28.59 ⎠⎝ ⎠ Hmo = 75 (82/90.3) (464/460)
= 0.0739 lbm/ft 3 = 68.7 hp

Figure L.1 in Annex L indicates estimated belt drive


⎛ P + 13.6 pb ⎞ ⎛ t d4 + 460 ⎞ loss of 4.3%.
ρ3a = ρ 4 ⎜ s3a ⎟⎜ ⎟
⎝ 13.6 p4 ⎠ ⎝ t d3a + 460 ⎠
HL = 0.043 Hmo
⎛ 3.65 + 13.6 × 28.72 ⎞ ⎛ 516 ⎞
= 0.0731⎜ ⎟ ⎜ 519 ⎟ = 0.043 × 68.7
⎝ 13.6 × 28.59 ⎠⎝ ⎠
= 2.95 hp
= 0.0737 lbm/ft 3
H = Hmo - HL
= 68.7 - 2.95
⎛ P + 13.6 pb ⎞ ⎛ t d4 + 460 ⎞
ρ3b = ρ 4 ⎜ s3b ⎟⎜ ⎟ = 68.75 hp
⎝ 13.6 p4 ⎠ ⎝ t d3b + 460 ⎠
⎛ 3.45 + 13.6 × 28.72 ⎞ ⎛ 516 ⎞ SYSTEM EFFECT FACTORS
= 0.0731⎜ ⎟ ⎜ 550 ⎟
⎝ 13.6 × 28.59 ⎠⎝ ⎠
SEF 1 is due to the effect of insufficient distance
= 0.0695 lbm/ft 3 between the fan inlets and the side walls of the fan
plenum. The distance is 2.83 ft, or:
FLOW RATES
(2.83/3.92) = 0.72
V3a = 1096 (Pv3a/ρ3a )0.5 = 72%
= 1096 (0.60/0.0737)0.5
Of the fan inlet diameter. The area of the fan inlets:
= 3127 fpm
A1 = 2 (π D12/4)
V3b = 1096 (Pv3b/ρ3b)0.5
= 2 (π × 3.922/4)
= 1096 (0.47/0.0695)0.5
= 2850 fpm = 24.1 ft2

Q3a = V3aA3a The fan inlet velocity:


= 3127 × 7.2
V1 = (Q1/A1)
= 22514 cfm
= (48982/24.1)
Q3b = V3bA3b = 2032 fpm
= 2850 × 9.7
AMCA Publication 201-90, Figure 9.11A, indicates
= 27645 cfm
that for a plenum wall spacing of 72% of the fan inlet
diameter System Effect Curve V applies. For 2032
Q = Q1
fpm inlet velocity and curve V, Figure 7.1 shows SEF
= Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1)
1 = 0.06 in. wg at 0.075 lbm/ft3 density. At 0.0731
= 22514 (0.0737/0.0731) + 27645 (0.0695/0.0731)
lbm/ft3:
= 48982 cfm
SEF 1 = 0.06 (0.0731/0.075)
Q2 = Q1 (ρ1/ρ2)
= 0.06 in. wg
= 48982 (0.0731/0.0739)
= 48452 cfm
For SEF 2, AMCA Publication 201-90, Figures 7.1
and 8.3, indicate the following calculations:

74
AMCA 203-90 (R2007)

V2 = (Q2/A2) CONVERSION TO SPECIFIED CONDITIONS


= (48452/18.9)
= 2564 fpm Qc = 48982 (1170/1160)
= 49404 cfm
Blast area ratio = Blast Area/A2
= 13.3/18.9 Psc = 5.89 (1170/1160)2 (0.075/0.0731)
= 0.70 = 6.15 in. wg

For a blast area ratio of 0.7 and no duct, Figure 8.3 Hc = 65.75 (1170/1160)3 (0.075/0.0731)
shows System Effect Curve S applies. For 2564 fpm = 69.22 hp
velocity and curve S, Figure 7.1 shows SEF 2 = 0.33
in. wg at 0.075 lbm/ft3 density. At 0.0739 lbm/ft3:

SEF 2 = 0.33 (0.0739/0.075)


= 0.33 in. wg

FAN STATIC PRESSURE

Pv4 = (Q4/1096 A4)2 ρ4

Since:

ρ4 = ρ1
Q4 = Q1

Pv4 = (48982/1096 × 93.2)2 0.0731


= 0.02 in. wg

Ps1 + Pv1 = Ps4 + Pv4


= -1.75 + 0.02
= -1.73 in. wg

Ps = Ps2 - Ps1 - Pv1 + SEF 1 + SEF 2


= Ps2 - (Ps1 + Pv1) + SEF 1 + SEF 2
= 3.77 - (-1.73) + 0.06 + 0.33
= 5.89 in. wg

75
AMCA 203-90 (R2007)

EXAMPLE 4B: CENTRAL STATION AIR CONDITIONING UNIT, FACTORY ASSEMBLED DRAW-
THROUGH TYPE
1

RETURN AIR PLAN VIEW 3


STATIC PRESSURE TAPS

L
SEF 1 5
2
OUTSIDE + +

AIR

+ +
FAN SECTION
SIDE VIEW
FILTER SECTION COIL SECTION

COMMENTS

1. This is a factory assembled, draw-through central Section 9.4. In order to determine the air flow rate, it
station unit. The subject of the test is the fan section, is necessary to measure the area of the traverse
which is rated by the manufacturer as an assembly of plane.
the fan and the cabinet in which the fan has been
installed. As a draw-through unit, the performance 3. Determine Ps1 by averaging the static pressure
ratings for the fan section are based on operation measurements made in a traverse of Plane 1. Ps5
with the fan outlet ducted. Before proceeding with the may be determined in a similar manner or by
test, it is essential that all dampers--outside air, return averaging the pressure measurements at each of
air, mixing box, multizone, face and bypass, or four static pressure taps. If it is possible to install
volume control--be fixed in the positions agreed upon suitable pressure taps, their use is preferred in the
by all interested parties as being applicable for the region of the fan outlet. due to the close proximity of
installation. Also, the temperatures of heating and Planes 2 and 5, and the fact that there is no change
cooling coils must be kept constant throughout the in area between the two planes, the conditions which
test period. It may be necessary to lock out, exist at Plane 5 are assumed to exist at Plane 2.
disconnect, or otherwise modify automatic control Measure the area of Plane 1 for use in calculating
devices in order to prevent the positions of the Pv1.
dampers and temperatures of the coils from changing
during the test. Refer to Section 17.4.2 for additional 4. Measure the dry-bulb and wet-bulb temperatures
considerations affecting the test procedure in this at Plane 3 and the dry-bulb temperatures at Planes 1
type of installation. and 5. Determine pb for the general vicinity of the air
conditioning unit. These measurements are used to
2. Determine Pv3 by using the root mean square of determine densities at the planes of interest.
the velocity pressure measurements made in a
traverse of Plane 3, located near the end of a straight 5. Measure the fan speed and the motor amps, volts,
run of duct, as shown in the diagram. Determine Ps3 and if possible, watts. Record all pertinent motor
by averaging the static pressure measurements nameplate data, including volts (NPV), and full load
made in the same traverse. This static pressure value amps (FLA). If the motor power output is to be
is used to determine the density at the traverse estimated by using the phase current method
plane. Procedures for traverses are described in described in Annex K, it is not necessary to measure

76
AMCA 203-90 (R2007)

motor watts; however, it may be necessary to MEASURED MOTOR DATA


disconnect the drive and measure the no load amps
(NLA) if the motor is not operating at or near its full Volts = 440, 444, 442
load point. Refer to Annex K. = 442 av
Amps = 47.4, 47.7, 48.0
6. SEF 1 is due to the effect of insufficient length of = 47.7 av
duct between the fan outlet and the elbow
downstream of the fan. In order to determine the MOTOR NAMEPLATE DATA
value of SEF 1, it is necessary to measure the outlet
area of the fan, A2; the length of the outlet duct, L; 40 hp, 3 phase, 60 hertz
and the blast area of the fan. 440 volts, 1770 rpm, 49.7 FLA

7. To calculate the Fan Section Static Pressure: GENERAL

Ps = Ps2 - Ps1 - Pv1 + SEF 1 Fan connected to motor through belt drive.

Where: CALCULATIONS

Ps2 = Ps5 DENSITIES

Pv1 = (Q1/1096A1)2 ρ1 For Plane 3 conditions of:

td3 = 49.3°F
The calculation of Pv1 is often ignored in instances
tw3 = 47.3°F
similar to this example on the basis that the
calculated value of Pv1 is relatively small, and it
p3 = pb + (Ps3/13.6)
omission does not affect the test results significantly.
= 29.27 + (1.31/13.6)
8. In order to compare the test results to the quoted = 29.37 in. Hg
fan section curve drawn for operation at 1430 rpm
Use Figure N.1 in Annex N to obtain ρ3 = 0.0762
and 0.075 lbm/ft3 density, it is necessary to convert
the results to the specified conditions. The basis for lbm/ft3.
the calculations is described in Section 14.
⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
OBSERVATIONS ρ1 = ρ3 ⎜ s1 ⎟⎜ ⎟
⎝ 13.6 p3 ⎠ ⎝ t d1 + 460 ⎠
SITE MEASUREMENTS ⎛ −0.847 + 13.6 × 29.27 ⎞ ⎛ 509.3 ⎞
= 0.0762 ⎜ ⎟ ⎜ 507.5 ⎟
⎝ 13.6 × 29.37 ⎠⎝ ⎠
pb = 29.27 in. Hg = 0.0760 lbm/ftt 3
td1 = 47.5°F
td3 = 49.3°F
tw3 = 47.3°F ⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ5 = ρ3 ⎜ s5 ⎟⎜ ⎟
td5 = 49°F ⎝ 13.6 p3 ⎠ ⎝ t d5 + 460 ⎠
Ps1 = -0.847 in. wg
⎛ 1.39 + 13.6 × 29.27 ⎞ ⎛ 509.3 ⎞
Ps3 = 1.31 in. wg = 0.0762 ⎜ ⎟ ⎜ 509 ⎟
⎝ 13.6 × 29.37 ⎠⎝ ⎠
Pv3 = 0.294 in. wg
Ps5 = 1.39 in. wg = 0.0763 lbm/ft 3
N = 1402 rpm
A1 = 147.2 ft2 It is assumed ρ2 = ρ5.
A2 = A3 = A5
= 15.42 ft2 FLOW RATES
Blast Area = 9.4 ft2
L = 2.0 ft, length of outlet duct V3 = 1096 (Pv3/ρ3)0.5
= 1096 (0.294/0.0762)0.5
= 2153 fpm

77
AMCA 203-90 (R2007)

Q3 = V3A3 For velocities of 2500 fpm or less, the 100% effective


= 2153 × 15.42 outlet duct length is 2.5 duct diameters:
= 33199 cfm
= 2.5 × 4.43
Q = Q1 = 11.1 ft
= Q3 (ρ3/ρ1)
= 33199 (0.0762/0.0760) The length of the outlet duct in % effective duct
= 33286 cfm length:

Q2 = Q5 = (L/11.1) 100
= Q3 (ρ3/ρ5) = (2.0/11.1) 100
= 18%
= 33199 (0.0762/0.0763)
= 33155 cfm
Blast area ratio = Blast Area/A2
FAN POWER INPUT = 9.4/15.42
= 0.61
Measured amps/FLA = (47.7/49.7)
= 0.96 For a blast area ratio of 0.6, 18% effective duct length
= 96% and elbow position A, Figure 8.5 shows System
Effect Curve R applies. For 2150 fpm velocity and
Annex K indicates that Equation A will provide a curve R, Figure 7.1 shows SEF 1 = 0.34 in. wg at
reasonably accurate estimate of motor power output 0.075 lbm/ft3 density. At 0.0762 lbm/ft3:
for a 40 hp motor operating at 96% FLA.
SEF 1 = 0.34 (0.0762/0.075)
Hmo = 40 (47.7/49.7) (442/440) = 0.35 in. wg
= 38.6 hp
FAN SECTION STATIC PRESSURE
Figure L.1 in Annex L indicates estimated belt drive
loss of 4.5%. Pv1 = (Q1/1096 A1)2 ρ1
= (33286/1096 × 147.2)2 0.0760
HL = 0.045 Hmo = 0.003 in. wg
= 0.045 × 38.6
= 1.74 hp It is assumed that Ps2 = Ps5

H = Hmo - HL Ps = Ps2 - Ps1 - Pv1 + SEF 1


= 38.6 - 1.74 = 1.39 - (-0.847) - 0.003 + 0.35
= 36.86 hp = 2.58 in. wg

SYSTEM EFFECT FACTOR CONVERSION TO SPECIFIED CONDITIONS

To determine SEF 1, AMCA Publication 201-90, Qc = 33286 (1430/1402)


Figures 7.1 and 8.5, indicate the following = 33951 cfm
calculations:
Psc = 2.58 (1430/1402)2 (0.075/0.0760)
V2 = (Q2/A2) = 2.65 in. wg
= (33155/15.42)
= 2150 fpm Hc = 36.86 (1430/1402)3 (0.075/0.0760)
= 38.60 hp
Duct diameter equivalent to the fan outlet area:

De2 = (4 A2/π)0.5
= (4 × 15.42/π)0.5
= 4.43 ft

78
AMCA 203-90 (R2007)

EXAMPLE 4C: PACKAGED AIR-CONDITIONING UNIT

3
2

SEF 1
4 1 PLAN VIEW
INLET PLENUM FILTERS FANS 5

COOLING COIL SIDE VIEW

COMMENTS

1. The subject of the test in this example is the air 3. Ps4 may be determined by averaging the pressure
conditioning unit assembly. This assembly does not measurements at each of four static pressure taps or
include the inlet plenum. The performance ratings for by averaging the static pressure measurements
the unit assembly are based on operation with the made in a Pitot-static tube traverse of Plane 4. Ps5 is
outlets of the fans ducted. Before proceeding with the determined in a similar manner. However, if it is
test, it is essential that all system dampers be fixed in possible to install suitable static pressure taps, their
the positions agreed upon by all interested parties as use is preferred in the regions of the outlets of the
being applicable for the installation. Also, the fans. Due to the close proximity of Planes 1 and 4
temperature of the cooling coil must be kept constant and the fact that there is no change in area between
throughout the test period. It may be necessary to the two planes, the conditions which exist at Plane 4
lock out, disconnect or otherwise modify automatic are assumed to exist at Plane 1. Although Plane 5 is
control devices in order to prevent the positions of the greater in area that Plane 2, the degree of divergence
dampers and the temperature of the coil from is relatively small. Therefore, Ps2 will be calculated
changing during the test. Refer to Section 17.4.1 for based on Ps5 and the assumption that there is no
additional considerations affecting the test procedure change in total pressure from Plane 2 to Plane 5.
in this type of installation.
4. Measure the dry-bulb and wet-bulb temperatures
2. Determine Pv3 by using the root mean square of at Plane 4 and the dry-bulb temperatures at Planes 3
the velocity pressure measurements made in a and 5. In this example, the cooling medium, normally
traverse of Plane 3, located near the end of a straight circulated in the coil was shut off in order to maintain
run of duct, as shown in the diagram. Determine Ps3 constant air temperatures during the test. In order to
by averaging the static pressure measurements account for water vapor which may have been added
made in the same traverse. This static pressure value to the air as a result of evaporation of moisture
is used to determine the density at the traverse previously condensed on the coil, the wet-bulb
plane. Procedures for traverses are described in temperature at Plane 3 was measured. Determine pb
Section 9.4. in order to determine the air flow rate, it for the general vicinity of the air conditioning unit.
is necessary to measure the area of the traverse These measurements are used in determining
plane. densities at the planes of interest.

79
AMCA 203-90 (R2007)

5. Measure the fan speed and the motor amps, volts, A 1 = A4


and if possible, watts. Record all pertinent motor = 31.7 ft2
nameplate data including volts (NPV), and full load A2 = 11.5 ft2
amps (FLA). If the motor power output is to be
A3 = 16.4 ft2
estimated by using the phase current method
described in Annex K, it is not necessary to measure A5 = 14.3 ft2
motor watts; however, it may be necessary to Blast Area = 4.0 ft2 per fan
disconnect the drive and measure the no load amps L = 2.0 ft, length of outlet duct
(NLA) if the motor is not operating at or near its full
load point. Refer to Annex K. MEASURED MOTOR DATA

6. Although an elbow is located shortly downstream Volts = 460, 455, 465


of the fans, SEF 1 is judged to be more closely = 460 av
characterized as the effect due to insufficient lengths Amps = 38.2, 38, 37.9
of duct on the outlets of the fans. In order to = 38.0 av
determine the value of SEF 1, it is necessary to
measure the outlet area and the blast area of one of MOTOR NAMEPLATE DATA
the fans and the length, L, of its outlet duct.
25 hp, 3 phase, 60 hertz
7. To calculate the static pressure for the unit 460 volts, 1760 rpm, 39.5 FLA
assembly:
GENERAL
Ps = Ps2 - Ps1 - Pv1 + SEF 1
Fans connected to motor through belt drive.
Where:
CALCULATIONS
Ps1 = Ps4
DENSITIES
Pv1 = (Q1/1096A1)2 ρ1
For Plane 3 conditions of:
Ps2 = Ps5 + Pv5 - Pv2
td3 = 75.0°F
tw3 = 59.5°F
Pv2 and Pv5 are calculated in manners similar to the
calculation of Pv1.
p3 = pb + (Ps3/13.6)
= 29.65 + (2.03/13.6)
8. In order to compare the test results to the quoted
= 29.80 in. Hg
unit assembly curve drawn for operation at 1050 rpm
and 0.075 lbm/ft3 density, it is necessary to convert Use Figure N.1 in Annex N to obtain ρ3 = 0.0736
the results to the specified conditions. The basis for
the calculations is described in Section 14. lbm/ft3.

OBSERVATIONS For Plane 4 conditions of:

SITE MEASUREMENTS td4 = 72.5°F


tw4 = 58.5°F
pb = 29.65 in. Hg
td3 = 75.0°F p4 = pb + (Ps4/13.5)
tw3 = 59.5°F = 29.65 + (-0.32/13.6)
td4 = 72.5°F = 29.63 in. Hg
tw4 = 58.5°F
Use Figure N.1 in Annex N to obtain ρ4 = 0.0735
td5 = 74.5°F
lbm/ft3.
Ps3 = 2.02 in. wg
Pv3 = 0.35 in. wg It is assumed that ρ1 = ρ4.
Ps4 = -0.32 in. wg
Ps5 = 2.11 in. wg
N = 1025 rpm

80
AMCA 203-90 (R2007)

SYSTEM EFFECT FACTOR


⎛ P + 13.6 pb ⎞ ⎛ t d3 + 460 ⎞
ρ5 = ρ3 ⎜ s5 ⎟⎜ ⎟
⎝ 13.6 p3 ⎠ ⎝ t d5 + 460 ⎠ To determine SEF 1, AMCA Publication 201-90,
⎛ 2.11 + 13.6 × 29.65 ⎞ ⎛ 535 ⎞ Figures 7.1 and 8.3, indicate the following
= 0.0736 ⎜ ⎟ ⎜ 534.5 ⎟ calculations:
⎝ 13.6 × 29.80 ⎠⎝ ⎠
= 0.0737 lbm/ft 3 V2 = (Q2/A2)
= (39143/11.5)
It is assumed ρ2 = ρ5. = 3404 fpm

FLOW RATES Duct diameter equivalent to the outlet area of one fan:

V3 = 1096 (Pv3/ρ3)0.5 De2 = (4A2/2π)0.5


= 1096 (0.35/0.0736)0.5 = (4 × 11.5/2π)0.5
= 2390 fpm = 2.71 ft

Q3 = V3A3 Figure 8.3 shows that for velocities over 2500 fpm,
= 2390 × 16.4 100% effective duct length is one diameter for every
= 39196 cfm 1000 fpm:

Q2 = Q5 = De2 (V2/1000)
= Q3 (ρ3/ρ5) = 2.71 (3404/1000)
= 39196 (0.0736/0.0737) = 9.22 ft
= 39143 cfm
L in % effective duct length:
Q = Q1 = Q4
= Q3 (ρ3/ρ4) = (L/9.22) 100
= (2.0/9.22) 100
= 39196 (0.0736/0.0735)
= 22%
= 39249 cfm
Blast area ratio = Blast area/A2
FAN POWER INPUT
= (2 × 4.0)/11.5
Measured amps/FLA = (38.0/39.5) = 0.70
= 0.96
= 96% For a blast area ratio of 0.7, and 22% effective duct
length Figure 8.3 shows System Effect Curve W
Annex K indicates that Equation A will provide a applies. For 3404 fpm velocity and curve W, Figure
reasonably accurate estimate of motor power output 7.1 shows SEF 1 = 0.13 in. wg at 0.075 lbm/ft3
for a 25 hp motor operating at 96% FLA. density. At 0.0737 lbm/ft3:

Hmo = 25 (38.0/39.5) (460/460) SEF 1 = 0.13 (0.0737/0.075)


= 24.1 hp = 0.13 in. wg

Figure L.1 in Annex L indicates estimated belt drive STATIC PRESSURE OF UNIT
loss of 4.8%.
Pv5 = (Q5/1096 A5)2 ρ5
HL = 0.048 Hmo = (39143/1096 × 14.3)2 0.0737
= 0.048 × 24.1 = 0.46 in. wg
= 1.2 hp
Pv2 = (Q2/1096 A2)2 ρ2
H = Hmo - HL = (39143/1096 × 11.5)2 0.0737
= 24.1 - 1.2 = 0.71 in. wg
= 22.9 hp

81
AMCA 203-90 (R2007)

Ps2 + Pv2 = Ps5 + Pv5 CONVERSION TO SPECIFIED CONDITIONS


Ps2 = Ps5 + Pv5 - Pv2
= 2.11 + 0.46 - 0.71 Qc = 39249 (1050/1025)
= 1.86 in. wg = 40206 cfm

Pv1 = (Q1/1096 A1)2 ρ1 Psc = 2.22 (1050/1025)2 (0.075/0.0735)


= (39249/1096 × 31.7)2 0.0735 = 2.38 in. wg
= 0.09 in. wg
Hc = 22.9 (1050/1025)3 (0.075/0.0735)
Ps = Ps2 - Ps1 - Pv1 + SEF 1 = 25.1 hp
= 1.86 - (-0.32) - 0.09 + 0.13
= 2.22 in. wg

82
AMCA 203-90 (R2007)

EXAMPLE 4D: PACKAGED AIR-CONDITIONING UNIT

3a

3b

PLAN VIEW

STATIC PRESSURE TAPS

5
L
2
FILTER SECTION
SEF 1 1

+ +

HEATING COIL INLET LOUVER

SIDE VIEW

COMMENTS

1. The subject of the test in this example is the air pressure at each traverse plane is determined by
conditioning unit assembly. This assembly includes using the root mean square of the velocity
the filter section and the inlet louver. The measurement traverse in each of two branches. The
performance ratings for the unit assembly are based velocity pressure for each branch is determined by
on operation with the outlets of the fans ducted. using the root mean square of the velocity pressure
Before proceeding with the test, it is essential that all measurements made in the traverse. The static
system dampers be fixed in the positions agreed pressure at each traverse plane is determined by
upon by all interested parties as being applicable for averaging the static pressure measurements made in
the installation. Also, the temperature of the heating the same traverse. These static pressure values are
coil must be kept constant throughout the test period. used in determining the densities at the traverse
It may be necessary to lock out, disconnect or planes. Procedures for traverses are described in
otherwise modify automatic control devices in order Section 9.4. In order to determine the air flow rates, it
to prevent the positions of the dampers and the is necessary to measure the area of each traverse
temperature of the coil from changing during the test. plane.
Refer to Section 17.5.1 for additional considerations
affecting the test procedure in this type of installation. 3. Determine Ps5 by averaging the pressure
measurements at each of four static pressure taps
2. Normally, velocity pressure measurements would located in the duct fitting at the outlets of the fans.
be made in a single plane, located in a duct common The conditions which exist at Plane 5, including the
to all branches. In this example, a measurement static pressure, are assumed to exist at Plane 2,
plane which provides a satisfactory velocity profile based on their close proximity and the fact that there
cannot be located upstream of the fans or between is no change in area between the two planes. In
the point of connection of the branch ducts and the situations such as this example, it is important to be
outlets of the fans. The alternative, as indicated in the certain that all pressure measurements are referred
diagram, is to make a velocity pressure to the same atmospheric pressure.
measurement traverse in each of two branches. the
velocity pressure for reach branch is determined by 4. Measure the dry-bulb and wet-bulb temperatures
using the root mean square of the velocity pressure at Plane 1 and the dry-bulb temperatures at Planes
measurements made in the traverse. The static 3a, 3b, and 5. Determine pb for the general vicinity of

83
AMCA 203-90 (R2007)

the air conditioning unit. These measurements are 8. In order to compare the test results to the quoted
used to determine densities at the planes of interest. performance curve for the packaged unit drawn for
operation at 1720 rpm and 0.075 lbm/ft3 density, it is
5. Measure the fan speed and the motor amps, volts, necessary to convert the results to the specified
and if possible, watts. Record all pertinent motor conditions. The basis for the calculations is described
nameplate data, including volts (NPV), and full load in Section 14.
amps (FLA). If the motor power output is to be
estimated by using the phase current method OBSERVATIONS
described in Annex K, it is not necessary to measure
motor watts; however, it may be necessary to SITE MEASUREMENTS
disconnect the drive and measure the no load amps
(NLA) if the motor is not operating at or near its full pb = 29.65 in. Hg
load point. Motor performance data, supplied by the td1 = 72°F
motor manufacturer, are used in the determination of tw1 = 61°F
motor power output in this example. td5 = 85°F
td3a= 82.5°F
6. SEF 1 is due to the effect of insufficient length of
td3b= 83°F
duct between the outlets of the fans and the elbow
downstream of the fans. In order to determine the Ps5 = 1.25 in. wg
value of SEF 1, it is necessary to measure the outlet Ps3a= 1.15 in. wg
area and the blast area of one of the fans and the Ps3b= 1.22 in. wg
length of the duct, L, between the fan and the elbow. Pv3a= 0.56 in. wg
Pv3b= 0.60 in. wg
7. The sum of the static pressure, Ps1, and velocity N = 1710 rpm
pressure, Pv1, at the inlet to the unit assembly is A2 = A5
considered to be equal to the sum of the static = 5.64 ft2
pressure, Psx, and velocity pressure, Pvx, at a point A3a = 3.1 ft2
sufficiently distant from the inlet as to be in still air. At A3b = 2.2 ft2
this point, the static pressure is zero, and the velocity
Blast Area = 2.5 ft2 per fan
pressure in still air is zero.
L = 0.96 ft, length of outlet duct
Ps1 + Pv1 = Psx + Pvx = 0
MEASURED MOTOR DATA
This consideration, which is the same as that used in
Volts = 460, 458, 462
the methods for testing this type of unit for
= 460 av
performance rating purposes, charges to the unit
Amps = 10.0, 10.0, 9.8
losses incurred in accelerating the air into its inlet and
= 9.9 av
eliminates the inaccuracies which arise in any
attempt to measure the velocity pressure and static
MOTOR NAMEPLATE DATA
pressure at the inlet. To calculate the static pressure
for the unit assembly:
10 hp, 3 phase, 60 hertz
460 volts, 1750 rpm, 13.5 FLA
Ps = Ps2 - Ps1 - Pv1 + SEF 1
= Ps2 - (Ps1 + Pv1) + SEF 1 GENERAL

Since: Fans connected to motor through belt drive. The


following motor performance data was supplied by
Ps1 + Pv1 = 0 the motor manufacturer:
Ps = Ps2 + SEF 1
Motor Efficiency:
Where: 82.5% at 1/2 load
84.5% at 3/4 load
Ps2 = Ps5 84.5% at full load

Power Factor = 0.85

84
AMCA 203-90 (R2007)

DENSITIES Q = Q1
= Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1)
For Plane 1 conditions of: = 9455 (0.0723/0.0735) + 6950 (0.0722/0.0735)
= 16128 cfm
td1 = 72°F
tw1 = 61°F Q2 = Q5
p1 = pb = Q1 (ρ1/ρ5)
= 29.65 in. Hg = 16128 (0.0735/0.0720)
= 16464 cfm
Use Figure N.1 in Annex N to obtain ρ1 = 0.0735
lbm/ft3. FAN POWER INPUT

Measured amps/FLA = (9.9/13.5)


⎛ P + 13.6 pb ⎞ ⎛ t d1 + 460 ⎞
ρ5 = ρ1 ⎜ s5 ⎟⎜ ⎟ = 0.73
⎝ 13.6 p1 ⎠ ⎝ t d5 + 460 ⎠ = 73%
⎛ 1.25 + 13.6 × 29.65 ⎞ ⎛ 532 ⎞
= 0.0735 ⎜ ⎟ ⎜ 545 ⎟ The data supplied by the motor manufacturer indicate
⎝ 13.6 × 29.65 ⎠⎝ ⎠
power factor of 0.85 and motor efficiency of 84.5% for
= 0.0720 lbm/ft 3 the motor operating at 73% FLA. Using the
appropriate equation in Section 10.2.2:
It is assumed that ρ2 = ρ5
Hmo = (3)0.5 × 9.9 × 460 × 0.85 × 0.845/746
= 7.59 hp
⎛ P + 13.6 pb ⎞ ⎛ t d1 + 460 ⎞
ρ3a = ρ1 ⎜ s3a ⎟⎜ ⎟
⎝ 13.6 p1 ⎠ ⎝ t d3a + 460 ⎠ Figure L.1 in Annex L indicates estimated belt drive
⎛ 1.15 + 13.6 × 29.65 ⎞ ⎛ 532 ⎞ loss of 5.6%.
= 0.0735 ⎜ ⎟ ⎜ 542.5 ⎟
⎝ 13.6 × 29.65 ⎠⎝ ⎠
HL = 0.056 Hmo
= 0.0723 lbm/ft 3 = 0.056 × 7.59
= 0.43 hp
⎛ P + 13.6 pb ⎞ ⎛ t d1 + 460 ⎞
ρ3b = ρ1 ⎜ s3b ⎟⎜ ⎟ H = Hmo - HL
⎝ 13.6 p1 ⎠ ⎝ t d3b + 460 ⎠ = 7.59 - 0.43
⎛ 1.22 + 13.6 × 29.65 ⎞ ⎛ 532 ⎞ = 7.16 hp
= 0.0735 ⎜ ⎟ ⎜ 543 ⎟
⎝ 13.6 × 29.65 ⎠⎝ ⎠
SYSTEM EFFECT FACTOR
= 0.0722 lbm/ft 3
SEF 1 is due to the effect of insufficient lengths of
FLOW RATES duct between the outlets of the fans and the elbow
downstream of the fans. AMCA Publication 201-90,
V3a = 1096 (Pv3a/ρ3a)0.5 Figures 7.1, 8.1, and 8.5 indicate the following
= 1096 (0.56/0.0723)0.5 calculations:
= 3050 fpm
V2 = (Q2/A2)
V3b = 1096 (Pv3b/ρ3b)0.5 = (16464/5.64)
= 2919 fpm
= 1096 (0.60/0.0722)0.5
= 3159 fpm
Duct diameter equivalent to the outlet area of one
fan:
Q3a = V3aA3a
= 3050 × 3.1
De2 = (4A2/2π)0.5
= 9455 cfm
= (4 × 5.64/2π)0.5
Q3b = V3bA3b = 1.89 ft
= 3159 × 2.2
= 6950 cfm Figure 8.1 shows that for velocities over 2500 fpm
100% effective duct length is one diameter for every
1000 fpm:

85
AMCA 203-90 (R2007)

STATIC PRESSURE OF UNIT


= De2 (V2/1000)
= 1.89 (2919/1000) Ps2 = Ps5
= 17% = 1.25 in. wg

L, in % effective duct length: Ps = Ps2 + SEF 1


= 1.25 + 0.41
= (L/5.52) 100 = 1.66 in. wg
= (0.96/5.52) 100
= 17% CONVERSION TO SPECIFIED CONDITIONS

Blast area ratio = Blast Area/A2 Qc = 16128 (1720/1710)


= (2 × 2.5)/5.64 = 16222 cfm
= 0.89
Psc = 1.66 (1720/1710)2 (0.075/0.0735)
For a blast area ratio of 0.89, 17% effective duct = 1.71 in. wg
length and elbow position C, Figure 8.5 shows
System Effect Curve S applies. For 2919 fpm velocity Hc = 7.16 (1720/1710)3 (0.075/0.0735)
and curve S, Figure 7.1 shows SEF 1 = 0.43 in. wg at
= 7.44 hp
0.075 lbm/ft3 density. At 0.0720 lbm/ft3:

SEF 1 = 0.43 (0.0720/0.075)


= 0.41 in. wg

86
AMCA 203-90 (R2007)

EXAMPLE 4E: CENTRAL STATION AIR CONDITIONING UNIT, FACTORY ASSEMBLED BLOW-
THROUGH TYPE

2
1
5 STATIC PRESSURE TAPS

PLAN VIEW 3b 3a
RETURN
AIR SPRAY HEATING COIL
SECTION
+

+ +
+
OUTSIDE +

AIR +

+ +

FILTER SECTION FAN SECTION COOLING COIL

SIDE VIEW

COMMENTS

1. This is a factory assembled, blow-through central be made in a single plane, located in a duct common
station unit. The subject of the test is the fan section, to all branches. In this example, a measurement
which is rated by the manufacturer as an assembly of plane which provides a satisfactory velocity profile
the fan and the cabinet in which the fan has been cannot be located upstream of the fan or between the
installed. As a blow-through unit, the performance point of connection of the branch ducts and the fan
ratings for the fan section are based on operation outlet. The alternative, as indicated in the diagram, is
without the fan outlet ducted. Before proceeding with to make a velocity pressure measurement traverse in
the test, it is essential that all dampers (outside air, each branch. The velocity pressure for each branch
return air, mixing box, multizone, face and bypass, or is determined by using the root mean square of the
volume control) be fixed in the positions agreed upon velocity pressure measurements made in the
by all interested parties as being applicable for the traverse. The static pressure at each traverse plane
installation. Also, the temperatures of heating and is determined by averaging the static pressure
cooling coils must be kept constant throughout the measurements made in the same traverse. These
test period. It may be necessary to lock out, static pressure values are used in determining the
disconnect, or otherwise modify automatic control densities at the traverse plane. Procedures for
devices in order to prevent the positions of the traverses are described in Section 9.4. In order to
dampers and temperatures of the coils from changing determine the air flow rates it is necessary to
during the test. In instances in which a cooling coil is measure the area of each traverse plane.
located between a velocity pressure traverse plane
and the fan, as in this example, the flow of the cooling 3. Determine Ps1 by averaging the static pressure
medium should be stopped or its temperature raised measurements made in a traverse of Plane 1. Ps5
to a level sufficient to prevent condensation on the may be determined in a similar manner or by
cooling coil, otherwise the moisture condensed will averaging the pressure measurements at each of
not be properly taken into account in the four static pressure taps. If it is possible to install
determination of fan air flow rate. Refer to Section suitable pressure taps, their use is preferred in the
17.5.2 for additional considerations affecting the test regions of the fan outlet. Due to the abrupt expansion
procedure in this type of installation. in area from Plane 2 to Plane 5, it is assumed that
there is no conversion of velocity pressure at Plane 2
2. Normally, velocity pressure measurements would to static pressure at Plane 5. Therefore, it is assumed

87
AMCA 203-90 (R2007)

that Ps2 = Ps5. Measure the area of Plane 1 for use in tw3a = 71.5°F
calculating Pv1. td3b = 60°F
tw3b = 58°F
4. Measure the dry-bulb and wet-bulb temperatures Ps1 = -2.43 in. wg
at Planes 1, 3a, and 3b. Determine pb for the general Ps5 = 6.55 in. wg
vicinity of the air conditioning unit. These Ps3a = 5.35 in. wg
measurements are used to determine densities at the Ps3b = 5.1 in. wg
planes of interest. The measurements of additional Pv3a = 0.53 in. wg
wet-bulb temperatures were made in this example in
Pv3b = 0.60 in. wg
order to provide data which may be used to
N = 1695 rpm
determine whether the moisture content of the air
changed between Plane 1 and Planes 3a and 3b. A1 = 68.9 ft2
A3a = 5.37 ft2
5. Measure the fan speed and the motor amps, volts, A3b = 6.78 ft2
and if possible, watts. Record all pertinent motor
nameplate data, including volts (NPV), and full load MEASURED MOTOR DATA
amps (FLA). If the motor power output is to be
estimated by using the phase current method Volts = 570, 575, 565
described in Annex K, it is not necessary to measure = 570 av
motor watts; however, it may be necessary to Amps = 81.5, 82.5, 81
disconnect the drive and measure the no load amps = 81.7
(NLA) if the motor is not operating at or near its full NLA = 19
load point. Refer to Annex K.
MOTOR NAMEPLATE DATA
6. Since the performance ratings for the fan section
are based on operation without the fan outlet ducted, 100 hp, 3 phase, 60 hertz
an SEF does not apply for the unducted position. 575 volts, 1790 rpm, 95 FLA

7. To calculate the Fan Section Static Pressure: GENERAL

Ps = Ps2 - Ps1 - Pv1 Fan connected to motor through belt drive.

Where: CALCULATIONS

Ps2 = Ps5 DENSITIES


Pv1 = (Q1/1096 A1)2 ρ1
Q1 = Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1) For Plane 1 conditions of:

The calculation of Pv1 is often ignored in instances td1 = 65°F


similar to this example on the basis that the tw1 = 60°F
calculated value of Pv1 is relatively small, and its
omission does not affect the test results significantly. p1 = pb + (Ps1/13.6)
= 28.85 + (-2.43/13.6)
8. In order to compare the test results to the quoted = 28.67 in. Hg
fan section curve drawn for operation at 1650 rpm
and 0.075 lbm/ft3 density, it is necessary to convert Use Figure N.1 in Annex N to obtain ρ1 = 0.0720
the results to the specified conditions. The basis for lbm/ft3.
the calculations is described in Section 14.
For Plane 3a conditions of:
OBSERVATIONS
td3a = 100°F
SITE MEASUREMENTS tw3a = 71.5°F

pb = 28.85 in. Hg p3a = pb + (Ps3a/13.6)


td1 = 65°F = 28.85 + (5.35/13.6)
tw1 = 60°F = 29.24 in. Hg
td3a = 100°F

88
AMCA 203-90 (R2007)

Use Figure N.1 in Annex N to obtain ρ1 = 0.0720 Hmo = (85.3 + 81.8)/2


lbm/ft3. = 83.6 hp

For Plane 3b conditions of: Reference to Figure L.1 in Annex L indicates


estimated belt drive loss of 4.2%.
td3b = 60°F
tw3b = 58°F HL = 0.042 Hmo
= 0.042 × 83.6
p3b = pb + (Ps3b/13.6) = 3.5 hp
= 28.85 + (5.1/13.6)
= 29.23 in. Hg H = Hmo - HL
= 83.6 - 3.5
Use Figure N.1 in Annex N to obtain ρ3b = 0.0741 = 80.1 hp
lbm/ft3.
FAN SECTION STATIC PRESSURE
FLOW RATES
Pv1 = (Q1/1096 A1)2 ρ1
V3a = 1096 (Pv3a/ρ3a)0.5 = (37405/1096 × 68.9)2 0.0720
= 1096 (0.53/0.0691)0.5 = 0.02 in. wg
= 3035 fpm
It is assumed that Ps2 = Ps5
V3b = 1096 (Pv3b/ρ3b)0.5
Ps = Ps2 - Ps1 - Pv1
= 1096 (0.60/0.0741)0.5
= 6.55 - (-2.43) - 0.02
= 3119 fpm
= 8.96 in. wg
Q3a = V3aA3a
CONVERSION TO SPECIFIED CONDITIONS
= 3035 × 5.37
= 16298 fpm Qc = 37405 (1650/1695)
= 36412 cfm
Q3b = V3bA3b
= 3119 × 6.78
Psc = 8.96 (1650/1695)2 (0.075/0.0720)
= 21147 cfm
= 8.84 in. wg
Q = Q1
= Q3a (ρ3a/ρ1) + Q3b (ρ3b/ρ1) Hc = 80.1 (1650/1695)3 90.075/0.0720)
= 16298 (0.0691/0.0720) + 21147 (0.0741/0.0720) = 77.0 hp
= 37405 cfm

FAN POWER INPUT

Measured amps/FLA = (81.7/95)


= 0.86
= 86%

Annex K indicates that the average of the results of


Equation A and Equation B will provide a reasonably
accurate estimate of motor power output for a 100 hp
motor operating at 86% of FLA.

Eqn. A = 100 (81.7/95) (570/575)


= 85.3 hp

Eqn. B = 100 [(81.7 - 19)/(95 - 19)] (570/575)


= 81.8 hp

89
AMCA 203-90 (R2007)

EXAMPLE 5A: FREE INLET, FREE OUTLET ROOF VENTILATOR

TEMPORARY DUCT 2 De
WITH SQUARE
CROSS-SECTION, 1.5 De
De = EQUIVALENT
DIAMETER OF DUCT

COMMENTS

1. The subject of the test in this example is the roof be discharging from the ventilator into a region in
ventilator assembly. Before proceeding with the test, which the atmospheric pressure is somewhat
refer to Section 17.4 for considerations affecting the different from that to which all other pressure
test procedure in this type of installation. measurements are referred. When this possibility
exists, it is essential that the static pressure in the
2. Determine Pv3 by using the root mean square of region of the discharging air be measured, referred to
the velocity pressure measurements made in a the same atmospheric pressure as used in all other
traverse of Plane 3, located in the duct which has pressure measurements. In this example, Ps2 was
been installed on the inlet side of the ventilator. measured, referred to the same atmospheric pressure
Determine Ps3 by averaging the static pressure as in the static pressure measurements made at
measurements made in the same traverse. Plane 3.
Procedures for traverses are described in Section
9.4. Measure the area of the traverse plane, A3, 4. Measure the dry-bulb and wet-bulb temperatures
which is located at the tip of the Pitot-static tube. The at the velocity traverse plane. Determine pb for the
duct, temporarily installed for purposes of the test, is general vicinity of the ventilator. These measurements
square in cross-section. Its cross-sectional dimensions are used to determine densities at the planes of interest.
were selected as the maximum permissible for its
installation into the opening in the ventilator mounting 5. Measure the fan speed and the motor amps and
curb. The length of the duct is twice its equivalent volts. Record all pertinent motor nameplate data. For
diameter and the entrance to the duct is flared in oder the horsepower rating of the motor in this example, it
to reduce inlet losses. The installation of a duct of this is recommended that the fan power input be
size and cross-sectional configuration is judged as determined by using the measured watts input to the
creating no significant effect on the performance of motor and motor performance data, obtained from
the ventilator in this example. the motor manufacturer.

3. Ps2, the static pressure at the outlet of the 6. To calculate the Fan Static Pressure:
ventilator, is zero gauge pressure, referred to the
atmospheric pressure in the region of the ventilator Ps = Ps2 - Ps1 - Pv1
outlet. In situations such as this example, the air may = Ps2 - (Ps1 + Pv1)

90
AMCA 203-90 (R2007)

Where: FLOW RATE

Ps1 + Pv1 = Ps3 + Pv3 V3 = 1096 (Pv3/ρ3)0.5


= 1096 (0.077/0.0727)0.5
7. In order to compare the test results to the quoted = 1128 fpm
fan curve drawn for operation at 1180 rpm and 0.075
lbm/ft3 density, it is necessary to convert the results Q = Q1 = Q3
to the specified conditions. The basis for the = V3A3
calculations is described in Section 14. = 1128 × 5.58
= 6294 cfm
OBSERVATIONS
FAN POWER INPUT
SITE MEASUREMENTS
At the measured power input value of 755 watts, the
pb = 29.37 in. Hg data supplied by the motor manufacturer indicate
td3 = 73.5°F efficiency of 61% for the motor.
tw3 = 58.1°F
Ps2 = 0.037 in. wg Hmo = (755 × 0.61)/746
Ps3 = -0.085 in. wg = 0.62 hp
Pv3 = 0.077 in. wg
N = 1177 rpm Since the fan is direct connected to the motor, there
A3 = 5.58 ft2 is no drive loss, and:

MEASURED MOTOR DATA H = Hmo


= 0.62 hp
Volts = 235, 230, 230
= 232 av FAN STATIC PRESSURE
Watts = 755
Ps1 + Pv1 = Ps3 + Pv3
MOTOR NAMEPLATE DATA = -0.085 + 0.077
= -0.008 in. wg
1 hp, 3 phase, 60 hertz Ps = Ps2 - (Ps1 + Pv1)
230 volts, 1175 rpm, 3.6 FLA = 0.037 - (-0.008)
= 0.045 in. wg
General
CONVERSION TO SPECIFIED CONDITIONS
Fan direct connected to motor. Motor efficiency data
supplied by motor manufacturer. Qc = 6294 (1180/1177)
= 6310 cfm
CALCULATIONS
Psc = 0.045 (1180/1177)2 (0.075/0.0727)
DENSITIES = 0.047 in. wg

For Plane 3 conditions of: Hc = 0.62 (1180/1177)3 (0.075/0.0727)


= 0.64 hp
td3 = 73.5°F
tw3 = 58.1°F

p3 = pb + (Ps3/13.6)
= 29.37 + (-0.085/13.6)
= 29.36 in. Hg

Use Figure N.1 in Annex N to obtain ρ3 = 0.0727


lbm/ft3.

It is assumed that ρ1 = ρ3.

91
AMCA 203-90 (R2007)

EXAMPLE 5B: FREE INLET, FREE OUTLET PROPELLER FAN

2 De
2
3
1.5 De

D2

TEMPORARY DUCT
WITH SQUARE
CROSS-SECTION,
De = EQUIVALENT
DIAMETER OF DUCT

COMMENTS

1. The subject of the test in this example is the such as this example, the air may be discharging
propeller fan assembly. Before proceeding with the from the fan into a region in which the atmospheric
test, refer to Section 17.4 for considerations affecting pressure is somewhat different from that to which all
the test procedure in this type of installation. other pressure measurements are referred. When
this possibility exists, it is essential that the static
2. Determine Pv3 by using the root mean square of pressure in the region of the discharging air be
the velocity pressure measurements made in a measured, referred to the same atmospheric
traverse of Plane 3, located in the duct which has pressure as used in all other pressure
been installed on the inlet side of the fan. Determine measurements. In this example, Ps2 was measured,
Ps3 by averaging the static pressure measurements referred to the same atmospheric pressure as in the
made in the same traverse. Procedures for traverses static pressure measurements made at Plane 3.
are described in Section 9.4. Measure the area of the
traverse plane, A3, which is located at the tip of the 4. Measure the dry-bulb and wet-bulb temperatures
Pitot-static tube. The duct, temporarily installed for at the velocity traverse plane. Determine pb for the
purposes of the test, is square in cross-section, with general vicinity of the fan. These measurements are
side dimension of 1.5 D2. The shape and area of the used to determine densities at the planes of interest.
duct cross-section were selected on the basis of
minimizing the effect of the duct on the performance 5. Measure the fan speed and the motor amps and
of the fan while providing velocity pressure readings volts. Record all pertinent motor nameplate data. For
of measurable magnitudes. The length of the duct is the horsepower rating of the motor in this example, it
twice its equivalent diameter, and the entrance to the is recommended that the fan power input be
duct is flared in order to reduce inlet losses. The determined by using the measured watts input to the
installation of the duct is judged as creating no motor and motor performance data obtained from the
significant effect on the performance of the fan in this motor manufacturer.
example.
6. To calculate the Fan Static Pressure:
3. Ps2, the static pressure at the outlet of the fan, is
zero gauge pressure, referred to the atmospheric Ps = Ps2 - Ps1 - Pv1
pressure in the region of the fan outlet. In situations = Ps2 - (Ps1 + Pv1)

92
AMCA 203-90 (R2007)

Where: FLOW RATES

Ps1 + Pv1 = Ps3 + Pv3 V3 = 1096 (Pv3/ρ3)0.5


= 1096 (0.025/0.0715)0.5
7. In order to compare the test results to the quoted = 648 fpm
fan curve drawn for operation at 1725 rpm and 0.075
lbm/ft3 density, it is necessary to convert the results Q = Q1 = Q3
to the specified conditions. The basis for the = V 3 A3
calculations is described in Section 14. = 648 × 5.06
= 3279 cfm
OBSERVATIONS
FAN POWER INPUT
SITE MEASUREMENTS
At the measured power input value of 637 watts, the
pb = 29.65 in. Hg data supplied by the motor manufacturer indicate
td3 = 85°F efficiency of 65% for the motor.
tw3 = 74°F
Ps2 = 0 in. wg Hmo = (637 × 0.65)/746
Ps3 = -0.027 in. wg = 0.56 hp
Pv3 = 0.025 in. wg
N = 1775 rpm Since the fan is direct connected to the motor, there
A3 = 5.06 ft2 is no drive loss, and:

MEASURED MOTOR DATA H = Hmo


= 0.56 hp
Volts = 230, 225, 230
= 228 av FAN STATIC PRESSURE
Watts = 637
Ps1 + Pv1 = Ps3 + Pv3
MOTOR NAMEPLATE DATA = -0.027 + 0.025
= -0.002 in. wg
3/4 hp, 3 phase, 60 hertz
230 volts, 1760 rpm, 4.8 FLA Ps = Ps2 - (Ps1 + Pv1)
= 0 - (-0.002)
GENERAL = 0.002 in. wg

Fan direct connected to motor. Motor efficiency data This small value is attributed to the loss at the duct
supplied by motor manufacturer. inlet, and the fan is considered to be operating at free
delivery (Ps = 0).
CALCULATIONS
CONVERSION TO SPECIFIED CONDITIONS
DENSITIES
Qc = 3279 (1725/1775)
For Plane 3 conditions of: = 3187 cfm

td3 = 85°F Psc = 0 in. wg


tw3 = 74°F
Hc = 0.56 (1725/1775)3 (0.075/0.0715)
p3 = pb + (Ps3/13.6) = 0.54 hp
= 29.65 + (-0.027/13.6)
= 29.65 in. Hg

Use Figure N.1 in Annex N to obtain ρ3 = 0.0715


lbm/ft3.

It is assumed that ρ1 = ρ3

93
AMCA 203-90 (R2007)

EXAMPLE 5C: FREE INLET, FREE OUTLET ROOF VENTILATOR

COMMENTS

1. The subject of the test in this example is the roof 4. Measure the dry-bulb and wet-bulb temperatures
ventilator assembly. Before proceeding with the test, in the region of the inside pressure measurement.
refer to Section 17.1 for considerations affecting the Also, determine pb in the same vicinity.
test procedure in this type of installation.
5. Measure the fan speed and the motor amps and
2. Ps3, the static pressure in the vicinity of the volts. Record all pertinent motor nameplate data. For
ventilator inlet, would normally be determined by the horsepower rating of the motor in this example, it
averaging the static pressure measurements made in is recommended that the fan power input be
a Pitot tube traverse. But in this example, a determined by using the measured watts input to the
temporary duct was not installed and the Pitot tube motor and motor performance data obtained from the
traverse could not be accomplished. In this method motor manufacturer.
for testing a nonducted fan, consider the fan static
pressure (Ps) as the differential pressure, as read on 6. Airflow rates are determined from the fan
a manometer, between the pressure measured inside manufacturer’s certified performance ratings. Draw a
the room (Ps3) and the pressure measured outside fan performance curve from these ratings converted
the room in the vicinity of the ventilator outlet (Ps2). to operation at the test values of fan speed and
These pressures are measured at a sufficient entering air density. The basis for these calculations
distance from the ventilator so as to be unaffected by is described in Section 14. The fan airflow rate is then
the velocity of the entering or leaving air. determined by entering this curve at the test values of
fan static pressure and fan power input.
3. Ps2 is considered to be zero gauge pressure, but
since this measurement is actually part of the OBSERVATIONS
differential pressure described in paragraph 2, it is
necessary to make only one density correction; the SITE MEASUREMENTS
correction is to the differential pressure, which is the
fan static pressure. pb = 29.19 in. Hg
td3 = 79°F
tw3 = 63°F
Ps2 - Ps3 = 0.13 in. wg
N = 1735 rpm

94
AMCA 203-90 (R2007)

MEASURED MOTOR DATA FAN STATIC PRESSURE

Volts = 229, 229, 232 The fan static pressure is considered to be the
= 230 av differential static pressure.
Watts = 1390
Ps = Ps2 - Ps3
MOTOR NAMEPLATE DATA = 0.13 in. wg

1.5 hp, 3 phase, 60 hertz It is assumed that Ps1 = Ps3


230 volts, 1740 rpm, 4.8 FLA
CONVERSION OF MANUFACTURER’S FAN
GENERAL RATINGS TO OPERATING CONDITIONS

Fan direct connected to motor. Motor efficiency data Rating Point #1


supplied by motor manufacturer.
Q1c = 8900 (1735/1750)
Fan performance, at standard air density, as supplied = 8824 cfm
by fan manufacturer for 1750 rpm.
Ps1c = 0
Point CFM Ps HP
H1c = 1.45 (1735/1750)3 (0.0715/0.0750)
1) 8900 0 1.45
= 1.35 hp
2) 8520 1/8 1.50
3) 8060 1/4 1.55
Rating Point #2

CALCULATIONS Q2c = 8520 (1735/1750)


= 8447 cfm
DENSITIES
Ps2c = 0.125 (1735/1750)2 (0.0715/0.0750)
For Plane 3 conditions of:
= 0.117 in. wg
td3 = 79°F
H2c = 1.50 (1735/1750)3 (0.0715/0.0750)
tw3 = 63°F
= 1.39 hp
pb3 = pb + (Ps2 - Ps1)/13.6
Rating Point #3
= 29.19 + (0.13/13.6)
= 29.2 in. Hg Q3c = 8060 (1735/1750)
= 7991 cfm
Use Figure N.1 in Annex N to obtain ρ3 = 0.0715
lbm/ft3. Ps3c = 0.25 (1735/1750)2 (0.0715/0.0750)
= 0.234 in. wg
It is assumed that ρ1 = ρ3.
H3c = 1.55 (1735/1750)3 (0.0715/0.0750)
FAN POWER INPUT
= 1.44 hp
At the measured power input value of 1395 watts, the
Draw a performance curve for these operating
data supplied by the motor manufacturer indicate
conditions. Enter the measured values for static
efficiency of 77% for the motor.
pressure and horsepower on the appropriate curves.
Ideally, these two points will coincide at the same
Hmo = (1390 × 0.77)/746
cfm. However, usually they will not coincide and
= 1.43 hp
should be averaged to determine the fan airflow rate.
Since the fan is direct connected to the motor, there
If this difference is small, such as in this example, it
is no drive loss, and:
is only a reflection of test inaccuracies. If, however,
these differences exceed 10%, the system should be
H = Hmo
reanalyzed for SEFs that may have been overlooked,
= 1.43 hp or for procedural errors in the initial testing.
95
AMCA 203-90 (R2007)

Qa = 8070 cfm (based upon horsepower)


Qb = 8400 cfm (based upon static pressure)

Use:

Q = 8235 cfm (average of above).

.40 1.50
x
x BHP

BHP (H)
x

.30 1.25

.20 1.00
STATIC PRESSURE IN. WG (Ps)

x
.10
SP

0 x
7000 8000 9000

CFM(Q)

Fan Performance at 0.0715 Air Density

96
AMCA 203-90 (R2007)

Annex B. Pitot Static Tubes

16D 8D

0.8D 0.5D Radius

0.4D
3D Radius D

Head shall be free from nicks and burrs.


90° ± 0.1°
All dimensions shall be within ±2%.

SECTION A-A 8 holes - 0.13D, not to exceed 0.04 in.,


diameter equally spaced and free from burrs.
Hole depth shall not be less than the hole
diameter.

Static Pressure
Note: Surface finish shall be 32 micro in. or better. The static
orifices may not exceed 0.04 in. diameter. The minimum Pitot
tube stem diameter recognized under this standard shall be
0.10 in. In no case shall the stem diameter exceed 1/30 of the
Total Pressure test duct diameter.

PITOT-STATIC TUBE WITH SPHERICAL HEAD

All other dimensions are the same


X/D V/D X/D V/D
as for spherical head pitot-static
tubes.
0.000 0.500 1.602 0.314
8D 0.237 0.496 1.657 0.295
0.336 0.494 1.698 0.279
0.474 0.487 1.730 0.266
0.622 0.477 1.762 0.250

D 0.741 0.468 1.796 0.231


X
0.936 0.449 1.830 0.211
1.025 0.436 1.858 0.192
1.134 0.420 1.875 0.176
1.228 0.404 1.888 0.163
0.2D Diameter

V 1.313 0.388 1.900 0.147


1.390 0.371 1.910 0.131
1.442 0.357 1.918 0.118
1.506 0.343 1.920 0.109
1.538 0.333 1.921 0.100
1.570 0.323

ALTERNATE PITOT-STATIC TUBE WITH ELLIPSOIDAL HEAD

Figure B.1
97
AMCA 203-90 (R2007)

Annex C. Double Reverse Tubes


AIR FLOW
TUBE ENDS MUST BE SMOOTH
AND FREE FROM BURRS

IMPACT TUBE REVERSE TUBE

SECTION VIEW
STAINLESS STEEL
TUBING PREFERRED
APPROX. 0.375 in. OD

FLEXIBLE TUBING
TOTAL PRESSURE = READING A
CORRECTED FOR MANOMETER
CALIBRATION

READING A ING B
READ

VELOCITY PRESSURE = READING B CORRECTED FOR


MANOMETER CALIBRATION AND
CALIBRATION FACTOR FOR THE
DOUBLE REVERSE TUBE.
Notes:

1. For use in dirty or wet gas streams.

2. The double reverse tube must be calibrated and used in the same orientation as used in its calibration

3. Also referred to as impact reverse tube, combined reverse tube, and type S tube.

Figure C.1 - Double Reverse Tube


98
AMCA 203-90 (R2007)

Annex D. Pitot-Static Tube Holder

0.312 in. DIA. PITOT-STATIC TUBE


SPLIT BRASS BUSHING
THERMOCOUPLE PRESS TO FIT INTO TUBING

DUCT WALL

1½ in. PIPE
HALF-COUPLING
WELDED TO DUCT

BRASS 1½ in. PIPE


BUSHINGS NIPPLE
12 in. LONG

STAINLESS STEEL TUBING


1 in. OUTSIDE DIA. × 8 ft. LONG
SLIP FIT IN BRASS BUSHINGS

Notes:

¼ in. OUTSIDE DIA. 1. Apparatus for mounting Pitot-static tube on duct


STAINLESS STEEL TUBING 2. For use in large ducts or high velocity gas streams
FOR GAS SAMPLING 3. 1 in. diameter tube slides inside 1.5 in. pipe, which
can be unscrewed and moved to another traverse
location
4. The gas sampling tube and thermocouple may be
omitted if these data are obtained in other manners

SPLIT BRASS CUT-OFF AND REBRAZE


BUSHING AFTER ASSEMBLY

Figure D.1 - Pitot-Static Tube Holder (Typical)

99
AMCA 203-90 (R2007)

Annex E. Static Pressure Tap

MAXIMUM 0.125 in. DIAMETER


FOR USE IN RELATIVELY
CLEAN GASES. MAY BE
NECESSARY TO INCREASE
DUCT WALL TO 0.312 in. DIAMETER
FOR DIRTY OR WET GASES

½ in. PIPE HALF-COUPLING


OR SIMILAR ARRANGEMENT

INSIDE SURFACE OF DUCT AND


EDGE OF HOLE ARE TO BE
SMOOTH AND FREE FROM BURRS

Figure E.1 - Static Pressure Tap

MINIMUM OF FOUR TAPS,


LOCATED 90° APART AND
NEAR THE CENTER OF
EACH WALL

STATIC PRESSURE MEASUREMENT


REQUIRED AT EACH TAP. USE
THE AVERAGE OF THE MEASUREMENTS
AS THE STATIC PRESSURE FOR THE PLANE

Figure E.2 - Locations of Static Pressure Taps

100
AMCA 203-90 (R2007)

Annex F. Pitot-Static Tube Connections

PLANE 2 PLANE 1 PLANE 4 PLANE 3

*SEF 1

Ps4 Ps3
FAN STATIC PRESSURE
Ps = - Ps1 - Pv1 + SEF 1
where Ps1 = Ps4 P v3
Pv1 = Pv3
Figure F.1 - Fan with Inlet Duct Only *SEF 1 is due to
Ps2 = 0
no duct at fan outlet
PLANE 3 PLANE 5 PLANE 2 PLANE 1

FAN STATIC PRESSURE


Ps3 Ps5 Ps = Ps2
where Ps2 = Ps5
P v3 Pt1 = 0

Figure F.2 - Fan with Outlet Duct Only

ALTERNATE
PLANE 3 PLANE 5 PLANE 2 PLANE 1 PLANE 4 PLANE 3

FAN STATIC PRESSURE


Ps = Ps2 - Ps1 - Pv1 Ps3
Ps5 Ps4
where Ps2 = Ps5
Ps1 = Ps4
Pv1 = Pv3 P v3

Figure F.3 - Fan with Inlet Duct and Outlet Duct

101
AMCA 203-90 (R2007)

Annex G. Manometer Data

10 in. wg
1:1
SLOPE
RATIO

2 in. wg
5:1 SLOPE RATIO

0.5 in. wg 1 in. wg


20:1 SLOPE RATIO 10:1 SLOPE RATIO

Figure G.1 - Manometer Data

102
AMCA 203-90 (R2007)

PERCENT UNCERTAINTY IN VELOCITY DETERMINATION


USING PITOT-STATIC TUBE AND MANOMETER DUE TO MANOMETER SLOPE

Based on an uncertainty equivalent to an indicating column length of 0.05 in. wg in a vertical manometer (1:1 slope
ratio)

VELOCITY PRESSURE READING, in. wg


.01 .02 .04 .06 0.1 0.2 0.4 0.6 1 2 3 4 6 8 10
10.0

8.0

6.0
5.0

4.0
% UNCERTAINTY IN VELOCITY DETERMINATION

3.0

2.0

1.0

MA OPE
SL
NO RA
0.8

ME TIO
TE
1:1

0.6
0.5 R
2:1

0.4
5:1
10
20

:1
:1

0.3

0.2

0.3 0.4 0.6 0.8 1 2 3 4 6 8 10 15

STANDARD AIR VELOCITY, fpm (×1000)

Figure G.2 - Uncertainty in Velocity Determination

103
AMCA 203-90 (R2007)

Annex H. Distribution of Traverse Points

In order to obtain a representative average velocity in a duct, it is necessary to locate each traverse point
accurately. It is recommended that the number of traverse points increase with increasing duct size. The
distributions of traverse points for circular ducts, as indicated below, are based on log-linear Pitot traverse method.

60º X1 X2

X3

X4

D Xn

Xa = D × Ka

Where:
D is the inside diameter of the duct
Ka is the factor corresponding to the duct size and the traverse point location as indicated in the table below

NUMBER OF
INSIDE TRAVERSE
DIAMETER POINTS IN K1 K2 K3 K4 K5 K6 K7 K8 K9 K10 K11 K12 K13 K14 K15 K16
OF DUCT EACH OF 3
DIAMETERS
LESS THAN
8 .021 .117 .184 .345 .655 .816 .883 .979
8 ft.
8 ft.
THROUGH 12 .014 .075 .114 .183 .241 .374 .626 .759 .817 .886 .925 .986
12 ft.
GREATER
16 .010 .055 .082 .128 .166 .225 .276 .391 .609 .724 .775 .834 .872 .918 .945 .990
THAN 12 ft.

Figure H.1 - Distribution of Traverse Points for Circular Ducts


104
AMCA 203-90 (R2007)

The recommended minimum number of traverse points for rectangular ducts is indicated below in Figure H.3. For
rectangular ducts with cross-sectional areas of 24 square feet and less, the recommended minimum number is 24.
For cross-sectional areas greater than 24 square feet, the minimum number of points increases as indicated in
Figure H.3. The points are to be located in the centers of equal areas with the areas as nearly square as practical
(see Figure H.2). If the flow conditions at the traverse plane are less than satisfactory, the accuracy of the
determination of flow rate may be improved by using more than the recommended minimum number of points.
Fewer points may be used if the flow is very uniform; however, the maximum area covered per point should not
exceed 3 square feet.

Y Y
X
2
2

Figure H.2 - Distribution of Traverse Points for Rectangular Duct

100
90
80
70
NUMBER OF TRAVERSE POINTS

60
50

40

30
25

20

15

10
10 15 20 25 30 40 50 60 70 80 100 150 200 250 300

DUCT CROSS-SECTIONAL AREA, ft2

Figure H.3 - Recommended Minimum Number


of Traverse Points for Rectangular Ducts

105
AMCA 203-90 (R2007)

Annex J. Instrumentation Characteristics

Table J.1 - Temperature Measurement

Approximate Precision
Range
No. Measurement Means Application F F Limitations
1. Glass-stem thermometers
Mercury-glass thermometer Temp of gases and liquids by contact -38/575 Less than In gases, accuracy af-
0.1 to 10 fected by radiation
Alcohol-glass thermometer ” -100/100 ” ”
Pentane-glass thermometers ” -200/70 ” ”
Jena or quartz mercury nitrogen
thermometers ” -38/1000 ” ”
2. Gas thermometer Primary standard -459/1000 Less than Requires consid-
0.01 erable skill to use
3. Resistance thermometers
Platinum-resistance thermometer Precision; remote readings; temp of -320/1800 Less than High cost; accuracy
fluids or solids by contact 0.02 to 5 affected by radiation
in gases
Nickel-resistance thermometer Remote readings; temp by contact -150/300 0.3 Accuracy affected by
radiation in gases
Thermistors ” Up to 600 0.1
4. Thermocouples
Pt-Pt-Rh thermocouple Standard for thermocouples 500/3000 0.1 to 5 High cost; also, re-
quires expensive
measuring device
Chromel-alumel thermocouple General testing of high temp; remote Up to 2200 0.1 to 15 Less accurate than
rapid readings by direct contact above
Iron-constantain thermocouple ” Up to 1500 0.1 to 15 Subject to oxidation
Copper-constantan thermocouple Same as above, especially suited for Up to 700 0.1 to 15
Chromel-constantan thermocouple low temp
5. Beckman thermometers For differential temp in same applica- 9 diff 0.018 Must be set for temp
(metastatic) tions as in glass stem thermometer to be measured
6. Bimetallic thermometers For approx temp 0/1000 1, usually Time lag; unsuitable
much more for remote use; un-
reliable
7. Pressure-bulb thermometers
Gas-filled bulb Remote-testing -100/1000 2 Caution must be ex-
ercised so that in-
stallation is correct
Vapor-filled bulb ” 20/500 2 ”
Liquid-filled bulb ” -50/2100 2 ”
8. Optical pyrometers For intensity of narrow spectra band 1500 upward 15
of high temp radiation (remote)
9. Radiation pyrometers For intensity of total high temp radi- Any range
ation (remote)
10. Seger cones (fusion pyrometers) Approx temp (within temp source) 1000/3600 50
11. Indicating crayons Approx temp (in surface) 125/900 ±1%
12. Melting and boiling points of Standards All except ex- Extremely For laboratory use
materials tremely high precise only
temp

Reprinted by permission from ASHRAE Handbook - 1989 Fundamentals

106
AMCA 203-90 (R2007)

Table J.2 - Differential Pressure Measurement

No. Measurement Means Application Range Precision Limitations


1. Micromanometer Very low press. diff. 0 to 6 in. H20 0.005 to Not readily portable; not easy to
0.001 in. H20 use with pulsating pressure
2. Draft gauges Moderately low press. diff. 0 to 10 in. H20 0.005 to Must be leveled carefully
0.05 in. H20
3. Manometer Medium press diff. 0 to 100 in. H20 0.05 in. Where used with liquid must be
or Hg compensated for liquid density
4. Swinging-vane-type gauge Moderately low press. diff. 0 to 0.5 in. H20 5% Generally usable to atmospheric
0 to 20 in. H20 pressure only
5. Bourdon-tube type Medium to high press. diff., Any 0.05 to 5% Subject to damage due to over
usually to atmosphere press-shock or pulsation
6. Pressure transducers- Remote reading, responds 0.05 to 50,000 0.1 to 0.5% Requires electronic amplifier and
strain gauge, capacity, po- to rapid changes of pressure psi readout device
tentiometer, crystal, magnet

Table J.3 - Velocity Measurement

No. Measurement Means Application Range Precision Limitations


1. Smoke puff or airborne Low air velocities in rooms; 5 to 50 10 to 20% Awkward to use but valuable in
solid tracer highly directional tracing air movement
2. Deflecting-vane Air velocities in rooms, at 30 to 24,000 5% Not well suited for duct readings;
anemometer outlets, etc; directional needs periodic check calibration
3. Revolving-vane Moderate air velocities in 100 to 3000 5 to 20% Extremely subject to error with
anemometer ducts and rooms; some- variations in velocities with space
what directional or time; easily damaged; needs
periodic calibration
4. Pitot tube Std instrument for mea- 180 to 10,000 1 to 5% Accuracy falls off at low end of
surement of duct velocities with micromanometer range
600 to 10,000 with
draft gauges; 10,000
up with manometer
5. Impact tube and side- High velocities, small 120 to 10,000 1 to 5% Accuracy depends upon constancy
wall or other static tap tubes and where air direc- with micromanometer; of static pressure across stream
tion may be variable 600 to 10,000 with section
draft gauges; 10,000 up
with manometer
6. Heated thermocouple Air velocities in ducts, 10 to 2000 3 to 20% Accuracy of some types not good
anemometer velocity distributions at lower end of range; steady
state measurements only
7. Hot-wire anemometer (a) Low air velocities; di- 1 to 1000 1 to 20% Requires accurate calibration at
rectional and nondirec- frequent intervals; complex,
tional available costly
(b) High air velocities up to 60,000 1 to 20%
(c) Transient velocity and
turbulence

Reprinted by permission from ASHRAE Handbook - 1989 Fundamentals

107
AMCA 203-90 (R2007)

Annex K. Phase Current Method for Use Equation A to estimate the Hmo for motors of 5
Estimating the Power Output of Three horsepower and greater, operating at 90% or more of
FLA. The uncertainties will be less than 5%.
Phase Fan Motors
Use the average of Equation A and Equation B to
The power output of three phase motors can be
estimate the Hmo for all motors operating at less than
estimated based on the relationship of motor current
and motor power output. Two equations can be used 90% of FLA and for 3 horsepower and smaller motors
in estimating the motor power output. The equations operating above 90% of FLA. An estimated Hmo less
are as follows: than 50% of NPH can contain 15% uncertainties or
greater.
Equation A:
Figure K.1 represents the relationship of motor
current and motor power output. The “dashed” lines
⎛ Measured amps ⎞ ⎛ Measured volts ⎞ between 0% NPH and 100% NPH for motor sizes
Hmo = NPH ⎜ ⎟⎜ ⎟
⎝ FLA ⎠⎝ NPV ⎠ shown represents Equation B. The solid lines
between these same end points for the motor sizes
Where: shown represent the general shape of typical motor
calibration amp/load curves. The solid line from
Hmo = motor power output 100% NPH and 100% FLA to 0% NPH and 0% FLA
NPH = nameplate horsepower represents Equation A. These curves indicate that if
FLA = full load amps you average the results of Equation A and Equation
NPV = nameplate volts B for a specific measured amp draw, that your results
measured volts = average of the measured phase approach the typical calibration curve. It also points
volts out that the uncertainties are low if just Equation A is
measured amps = average of the measured phase used above 90% FLA, especially in the larger integral
amps motor horsepowers.

Equation B: Many fractional horsepower and small integral


horsepower motors do not have a significant change
in current from no load to full load. The actual amps-
⎛ Measured amps - NLA ⎞ ⎛ Measured volts ⎞
Hmo = NPH ⎜ ⎟⎜ ⎟ load characteristics for motors of the same
⎝ FLA - NLA ⎠⎝ NPV ⎠ horsepower rating can vary greatly from motor
manufacturer to motor manufacturer. No load
Where: amperage (NLA) varies significantly for the same size
motor between manufacturers. In addition, various
NLA = average of the measured phase values of no motor design requirements result in different amp-
load amps load characteristics even though the horsepower
NPH = nameplate horsepower ratings of the motors are the same. These are some
FLA = full load amps of the reasons that Figure K.1 cannot be used to
NPV = nameplate volts determine the motor output directly. The chart is only
intended to indicate the accuracy and suitability of
NLA can usually be obtained with the motor operating using the above equations for estimating motor
and the motor shaft coupling or belt drive power output.
disconnected. In the case where the fan impeller is
mounted directly on the motor shaft, it will be
necessary to remove the impeller in order to obtain
NLA measurements.

108
AMCA 203-90 (R2007)

GENERALIZED CURVES ILLUSTRATING THE RELATIONSHIP OF


HORSEPOWER TO AMPS FOR THREE PHASE MOTORS

Do not use for determining actual motor horsepower

DOTTED LINES PER EQUATION B: Hmo ∝ MEASURED AMPS - NLA/FLA - NLA

100

90
RATED
HORSEPOWER
1
80 2

70
3

60

5
50

10

40

400
30

2500
20

10

0
0 10 20 30 40 50 60 70 80 90 100

% NAMEPLATE HORSEPOWER

PER EQUATION A: Hmo ∝ MEASURED AMPS


FLA

CAUTION: THIS CHART IS REPRESENTATIVE ONLY! SINCE THE AMP-LOAD CHARACTERISTICS OF THE
SAME SIZE MOTOR WILL VARY BETWEEN THE VARIOUS MOTOR MANUFACTURERS, IT CANNOT BE USED
TO DETERMINE THE HORSEPOWER OUTPUT OF A MOTOR. USE THE EQUATIONS AS DIRECTED ON THE
PREVIOUS PAGE.

109
AMCA 203-90 (R2007)

Annex L. Estimated Belt Drive Loss 3) A larger belt section than required will increase
the drive loss.
Drive loss is defined as follows:
4) A badly undertensioned drive will increase the
Percent drive loss equals power to driving sheave drive loss.
minus power from driven sheaves times 100, divided
by power to driving sheave. 5) Misaligned drives will increase the drive loss.

There are several things which can affect belt drive Drive loss is manifested as heat in belt drives. Under
efficiencies. Some of these are: ambient conditions of less than 100°F, well designed
drives that operate efficiently will be warm to the
1) Over-designed drives. This was considered good touch immediately after being shut down. If the drive
practice at one time because the drive would last is uncomfortable to the touch (approximately 140°F
longer. It will still last longer but it is more or more), then the drive loss is high. Obviously poorly
inefficient. tensioned and misaligned drives should be corrected
before estimating brake horsepowers and drive
2) Multiple belts on subminimum diameter sheaves losses.
are less efficient than fewer belts on larger
diameter sheaves. Both the National Electric
Motor Association and the Rubber
Manufacturer’s Association publish data dealing
with minimum recommended sheave diameters.
As these minimum sheave diameters are
approached, the drive loss becomes greater.

110
AMCA 203-90 (R2007)

100
80
60

40
DRIVE LOSS, % MOTOR POWER OUTPUT*

30

20 RANGE OF DRIVE LOSSES FOR STANDARD BELTS

15

10
8
6

4
3

1.5

1
0.3 0.4 0.6 0.8 1 2 3 4 6 8 10 20 30 40 60 80 100 200 300 400 600

MOTOR POWER OUTPUT, hp

HIGHER BELT SPEEDS TEND TO HAVE HIGHER LOSSES


THAN LOWER BELT SPEEDS AT THE SAME HORSEPOWER

*Drive losses are based on the conventional V-belt, which has been the “work horse” of the drive industry for
several decades.

EXAMPLE

• Motor power output, Hmo, is determined to be 13.3 hp


• The belts are the standard type and just warm to the touch immediately after shutdown
• From chart, drive loss = 5.1%
• Drive loss, HL = 0.051 × 13.3
= 0.7 hp
• Fan power input, H = 13.3 - 0.7
= 12.6 hp

Figure L.1 - Estimated Belt Drive Loss

111
AMCA 203-90 (R2007)

Annex M. Density Determinations p 1 = pb


= 28.60 in. Hg
M.1 General
The wet-bulb depression is:
This annex contains examples illlustrating the
procedures for determining densities. Determinations td1 - tw1 = 78 - 62
of densities are shown for air and for gases other = 16°F
than air.
For wet-bulb depression of 16°F, dry-bulb
M.2 Determination of the density of air, temperature of 78°F and absolute pressure of 28.60
general case in. Hg, obtain ρ1 = 0.0701 lbm/ft3 by using the
Psychrometric Density Chart in Figure N.1 in Annex N.
Determine air density by using the Psychrometric
Density Chart, shown in Figure N.1 in Annex N, the EXAMPLE M2.2
Psychrometric Density Table, shown in Annex N, or a
calculation procedure which makes use of perfect The conditions at a fan inlet, located at an elevation
gas relationships and the modified Apjohn equation of 1000 ft above sea level are:
for partial vapor pressure. Examples of the use of
these procedures are included in this section. Each Ps1 = -3.45 in. wg
of the procedures requires knowledge of the td1 = 85°F
pressure, dry-bulb temperature and wet-bulb tw1 = 75°F
temperature of the air.
Barometric pressure, obtained from a nearby airport,
The Psychrometric Density Chart and the is 29.82 in. Hg at sea level.
Psychrometric Density Table are limited to the
temperatures and pressures normally encountered in Using the data in Figure N.3 in Annex N, the
fan applications. barometric pressure at 1000 ft above sea level is:

Limit the use of the calculation procedure that is pb = 29.82 × 0.964


based on perfect gas relationships and illustrated in = 28.75 in. Hg
Example M2.3, to instances in which the dry-bulb
temperature is 180°F or less. Accurate wet-bulb The absolute pressure at the fan inlet is:
temperature measurements are difficult to obtain
when the dry-bulb temperature exceeds 180°F. p1 = pb + (Ps1/13.6)
= 28.75 + (-3.45/13.6)
When the dry-bulb temperature exceeds 180°F, it = 28.50 in. Hg
may be necessary to rely on site personnel for the
water vapor content of the air. Alternately, The wet-bulb depression is:
commercially available instrumentation for dew point
determination may be used. For the procedure td1 - tw1 = 85 - 75
required to determine density based on the data
= 10°F
provided in either of the above cases, refer to
Psychrometric Tables and Charts by Zimmerman and
For dry-bulb temperature of 85°F, absolute pressure
Lavine.1 of 28.50 in. Hg and wet-bulb depression of 10°F, use
the Psychrometric Density Table in Figures N.5 in
EXAMPLE M2.1 Annex N to obtain:
The conditions that exist at the inlet of a fan that is ρ1 = 0.06829 + 10 × 0.000041
not ducted on the inlet side are:
= 0.0687 lbm/ft3
td1 = 78°F
Example M2.3
tw1 = 62°F
The conditions at a fan inlet are:
Since:
Ps1 = -8.75 in. wg
Ps1 = 0
td1 = 146°F
tw1 = 93°F
1. O. T. Zimmerman and I. Lavine, Psychrometric Tables and Charts, 2nd ed. (Dover, N.H.: Industrial Research Service Inc., 1964)
112
AMCA 203-90 (R2007)

The barometric pressure, pb, measured for the Barometric pressure, obtained from a nearby
atmosphere to which Ps1 is referred, is 28.15 in. Hg. airport, is 29.24 in. Hg at sea level.

The absolute pressure at the fan inlet is: Using the data in Figure N.3 in Annex N, the
barometric pressure at 1000 ft above seal level is:
p1 = pb + (Ps1 /13.6)
= 28.15 + (-8.75/13.6) pb = 29.24 × 0.964
= 27.51 in. Hg = 28.19 in. Hg

Use Figure N.2 in Annex N to obtain saturated vapor The absolute pressure at the fan inlet is:
pressure, pe, of 1.562 in. Hg for the wet-bulb
temperature of 93°F. p1 = pb + (Ps1/13.6)
= 28.19 + (-15/13.6)
Use the modified Apjohn equation for partial vapor = 27.09 in. Hg
pressure, pp, to obtain:
Dry air at 29.92 in. Hg and 70°F has a density of
pp = pe - p1 (td1 - tw1)/2700 0.075 lbm/ft3.
= 1.562 - 27.51 (146 - 93)/2700
= 1.022 in. Hg Consider the density of air to be directly
proportional to absolute pressure and inversely
ρ1 is calculated by using perfect gas relationships: proportional to absolute temperature. The density
of the air at the fan inlet is calculated as follows:

1.3257 ( p1 − 0.378 pp ) ρ1 = 0.075 (p1/29.92) [(70 + 460)/(td1 + 460)]


ρ1 =
( td1 + 460 ) = 0.075 (27.09/29.92) [530/(95 + 460)]
= 0.0648 lbm/ft3

1.3257 ( 27.51 − 0.378 × 1.022 ) EXAMPLE M3.2


=
(146 + 460 )
Saturated air is enterting a fan inlet, located at an
elevation of 1500 ft above sea level. The pressure
= 0.0593 lbm/ft 3 and temperature at the inlet are:

M.3 Determination of the density of air, Ps1 = - 6.75 in. wg


special cases td1 = 103°F

The procedures for the determination of the density Barometric pressure, obtained from a nearby
of air that are described in Section M.2 are valid for airport, is 29.66 in. Hg at sea level.
dry air, air that is saturated with water vapor and air
that is partially saturated with water vapor. This Using the data in Figure N.3 in Annex N, the
section contains alternate procedures for cases in barometric pressure at 1500 ft above sea level is:
which it is known that the air is either dry or saturated.
Knowledge that the air is either dry or saturated pb = 29.66 × 0.947
eliminates the usual requirement of the wet-bulb = 28.09 in. Hg
temperature determination; however, it should be
noted that an incorrect assumption of either of these The absolute pressure at the fan inlet is:
conditions can result in a significant uncertainty in the
density determination. p1 = pb + (Ps1/13.6)
= 28.09 + (-6.75/13.6)
EXAMPLE M3.1 = 27.59 in. Hg

Dry air is entering a fan inlet, located at an elevation Refer to Figure N.4 in Annex N to obtain saturated
of 1000 ft above sea level. The pressure and air density of 0.06868 at 103°F and 29.92 in. Hg.
temperature at the inlet are:
Assuming the density of saturated air to be directly
Ps1 = -15 in. wg proportional to absolute pressure, the density at the
td1 = 95°F fan inlet is calculated as follows:

113
AMCA 203-90 (R2007)

Barometric pressure, obtained from a nearby airport,


ρ1 = 0.06868 (p1/29.92) is 29.92 in. Hg at sea level. The composition of the
= 0.06868 (27.59/29.92) gas is 5.5% CO2, 1% CO, 15% O2, 1% H2, and 77.5%
= 0.0633 lbm/ft3 N2, by volume.

Assuming the density of saturated air to be directly The apparent molecular weight of the gas is
proportional to absolute pressure is an determined as follows:
approximation. The uncertainty in the density
determination as a result of this approximation Volume Molecular
increases with increasing temperature and Component Fraction × Weight = lb/mole
increases with increasing variation between the
actual absolute pressure and 29.92 in. Hg, which is CO2 0.055 44 2.42
the stated pressure for the data in Figure N.4. The CO 0.01 28 0.28
uncertainty will be approximately 1% or less under O2 0.15 32 4.80
the following conditions: H2 0.01 2 0.02
N2 0.775 28 21.70
• At 120°F and at an absolute pressure within 20%
of 29.92 in. Hg
• At 150°F and at an absolute pressure within 10% 1.00 29.22
of 29.92 in. Hg
• At 180°F and at an absolute pressure within 4% Apparent molecular weight = (29.22/1.00)
of 29.92 in. Hg = 29.22

M.4 DETERMINATION OF THE DENSITY OF A The density of the gas at 70°F and 29.92 in. Hg is
GAS OTHER THAN AIR calculated as follows:

The determination of the density of a gas other than Apparent molecular weight 29.22
=
air may require the use of complex equipment. 386.7 386.7
Unless specifically qualified, an expert should be
consulted for the proper use of the equipment. If the
gas is a complex mixture of various consitutuents, as = 0.0756 lbm/ft 3
found in certain industrial processes, it is suggested
that the company chemist be consulted for the gas Using the data in Figure N.3 in Annex N, the
analysis. Particular care should be used if the gas is barometric pressure at 2000 ft above sea level is:
toxic, corrosive or explosive; and in these cases,
consideration should be given to substituting air for pb = 29.92 × 0.930
the test. = 27.83 in. Hg

The first two examples in this section illustrate gas The absolute pressure at the fan inlet is:
density determinations based on analyses that
provide the relative amounts of the gas constituents. p1 = pb + (Ps1/13.6)
Typical flue gas density data, which is provided in = 27.83 + (-22/13.6)
Figure N.6 in Annex N, is illustrated in Example M4.3. = 26.21 in. Hg
Since the actual density may be significantly different
from the density determined by using typical data, it Consider the density of the gas to be directly
is recommended that the typical data be used only in proportional to absolute pressure and inversely
the even that more specific information is not proportional to absolute temperature. The density of
available. the gas at the fan inlet is calculated as follows:

EXAMPLE M4.1 ρ1 = 0.0756 (p1/29.92)[(70 + 460)/(td1 + 460)]


= 0.0756 (26.21/29.92) [530/(230 + 460)]
A gas is entering a fan inlet located at an elevation of
= 0.0509 lbm/ft3
2000 ft above sea level. The pressure and
temperature at the inlet are:
EXAMPLE M4.2
Ps1 = - 22 in. wg
The conditions that exist at the inlet of a fan are Ps1 =
td1 = 230°F
-19.5 in. wg and td1 = 240°F. The barometric pressure,

114
AMCA 203-90 (R2007)

pb, measured for the atmospheric to which Ps1 is EXAMPLE M4.3


referred is 29.35 in. Hg. The composition of the gas
is 5.5% CO2, 1% CO, 15% O2, 1% H2, and 77.5% N2 Flue gas is flowing at Plane 3, the Pitot traverse
by weight. measurement plane. The flue gas is the result of
using natural gas as the fuel. The conditions that
The apparent molecular weight of the gas is exsit at Plane 3 are:
determined as follows:
Ps3 = 5.74 in. wg
Volume Molecular td3 = 680°F
Component Fraction × Weight = lb/mole
The barometric pressure, pb, measured for the
CO2 0.055 44 0.00125 atmosphere to which Ps3 is referred is 28.85 in. Hg.
CO 0.01 28 0.00036
O2 0.15 32 0.0047 The absolute pressure at Plane 3 is:
H2 0.01 2 0.005
N2 p3 = pb + (Ps3/13.6)
0.775 28 0.0277
= 28.85 + (5.74/13.6)
1.00 0.0390 = 29.27 in. Hg

Refer to Figure N.6 in Annex N to obtain typical flue


Apparent molecular weight = 1/0.0390
gas density when natural gas is used as the fuel of
= 25.6
0.0725 lbm/ft3 at 70°F and 29.92 in. Hg.
The density of the gas at 70°F and 29.92 in. Hg is
calculated as follows: Consider the density of the flue gas to be directly
proportional to absolute pressure and inversely
proportional to absolute temperature. The density of
Apparent molecular weight 25.6 the gas at Plane 3 is calculated as follows:
=
386.7 386.7
ρ1 = 0.0725 (p3/29.92)[(70 + 460)/(td3 + 460)]
= 0.0662 lbm/ft 3 = 0.0725 (29.27/29.92) [530/(680 + 460)]
= 0.0330 lbm/ft3
The absolute pressure at the fan inlet is:

p1 = pb + (Ps1/13.6)
= 29.35 + (-19.5/13.6)
= 27.92 in. Hg

Consider the density of the gas to be directly


proportional to absolute pressure and inversely
proportional to absolute temperature. The density of
the gas at the fan inlet is calculated as follows:

ρ1 = 0.0662 (p1/29.92)[(70 + 460)/(td1 + 460)]


= 0.0662 (27.92/29.92) [530/(240 + 460)]
= 0.0468 lbm/ft3

115
AMCA 203-90 (R2007)

116
AMCA 203-90 (R2007) AMCA 203-90 (R2007)

Annex N. Density Charts and Tables

tw pe tw pe tw pe tw pe tw pe
°F in. Hg °F in. Hg °F in. Hg °F in. Hg °F in. Hg

30 .1646 60 .5219 90 1.423 120 3.451 150 7.580


31 .1724 61 .5408 91 1.468 121 3.548 151 7.770
32 .1805 62 .5603 92 1.515 122 3.647 152 7.963
33 .1879 63 .5804 93 1.562 123 3.749 153 8.161
34 .1956 64 .6011 94 1.611 124 3.853 154 8.362

35 .2036 65 .6225 95 1.662 125 3.960 155 8.569


Fold out for 36 .2118 66 .6445 96 1.714 126 4.069 156 8.779
Figure N.1 - Psychrometric Density Charts 37 .2204 67 .6667 97 1.767 127 4.180 157 8.994
38 .2292 68 .6906 98 1.821 128 4.295 158 9.213
39 .2384 69 .7148 99 1.877 129 4.412 159 9.437

40 .2478 70 .7397 100 1.935 130 4.531 160 9.665


41 .2576 71 .7653 101 1.994 131 4.654 161 9.898
42 .2678 72 .7917 102 2.054 132 4.779 162 10.14
43 .2783 73 .8188 103 2.117 133 4.908 163 10.38
44 .2892 74 .8468 104 2.180 134 5.038 164 10.63

45 .3004 75 .8757 105 2.246 135 5.173 165 10.88


46 .3121 76 .9053 106 2.313 136 5.310 166 11.13
47 .3241 77 .9359 107 2.381 137 5.450 167 11.40
48 .3365 78 .9673 108 2.452 138 5.593 168 11.66
49 .3494 79 .9997 109 2.525 139 5.740 169 11.94

50 .3626 80 1.033 110 2.599 140 5.889 170 12.21


51 .3764 81 1.067 111 2.675 141 6.043 171 12.50
52 .3905 82 1.103 112 2.753 142 6.199 172 12.79
53 .4052 83 1.139 113 2.833 143 6.359 173 13.08
54 .4203 84 1.176 114 2.915 144 6.522 174 13.38

55 .4359 85 1.214 115 2.999 145 6.689 175 13.69


56 .4520 86 1.254 116 3.085 146 6.860 176 14.00
57 .4687 87 1.294 117 3.173 147 7.034 177 14.32
58 .4859 88 1.336 118 3.263 148 7.212 178 14.64
59 .5036 89 1.379 119 3.356 149 7.394 179 14.94
180 15.31

Adapted from ASHRAE Handbook - 1989 Fandamentals

Figure N.2 - Thermodynamic Properties of Water at Absolute Vapor Pressures, Inches of Mercury

117 118
AMCA 203-90 (R2007)

40 0.060

38 0.061

36 0.062
1. Calculate wet-bulb depression. Enter chart at the left.
34 2. Proceed horizontally to the appropriate dry-bulb 0.063
temperature.
32 3. Read vertically to the absolute pressure. 0.064
4. Then read horizontally to the density.
30 Example 0.065

g
• Given: td = 54°F; tw = 50°F; pb = 29.9 in. Hg
28 28.0 0.066

in. H
28.2 • Solution: Wet-bulb depression = 4°F; proceed hori-
28.4 zontally to 54°F dry-bulb temperature;
26 read vertically to 29.9 in. Hg; read horizon- 0.067

URE
28.6 tally to the density -- ρ = 0.0769 lbm/ft3.

SS
28.8
24 29.0 0.068

PRE
29.2

TE
22 29.4 0.069

OLU
29.6
29.8

ABS
20 0.070
30.0

18 0.071
AIR DENSITY, lbm/ft3

16 0.072

WET-BULB DEPRESSION, °F
14 0.073

12 0.074

10 0.075

8 0.076

6 0.077

4 0.078

2 0.079
98 96 94 92 90 88 86 84 82 80 78 76 74 72 70 68 66 64 62 60 58 56 54 52 50 48 46 44 42

0 0.080
DRY-BULB TEMPERATURE, °F

Figure N.1 - Psychrometric Density Chart


AMCA 203-90 (R2007)

ALTITUDE SPECIFIC PRESSURE ALTITUDE SPECIFIC PRESSURE


ft. GRAVITY in. Hg ft. GRAVITY in. Hg

0 1.00 29.92 3000 0.896 26.82


100 0.996 29.81 3200 0.890 26.62
200 0.993 29.70 3400 0.833 26.42
300 0.989 29.60 3600 0.877 26.23
400 0.986 29.49 3800 0.870 26.03

500 0.982 29.38 4000 0.864 25.84


600 0.979 29.28 4200 0.857 25.65
700 0.975 29.17 4400 0.851 25.46
800 0.971 29.07 4600 0.845 25.27
900 0.968 28.96 4800 0.838 25.08

1000 0.964 28.86 5000 0.832 24.90


1100 0.961 28.75 5200 0.826 24.71
1200 0.957 28.65 5400 0.820 24.52
1300 0.954 28.54 5600 0.814 24.34
1400 0.950 28.44 5800 0.807 24.16

1500 0.947 28.33 6000 0.801 23.98


1600 0.944 28.23 6500 0.786 23.53
1700 0.940 28.13 7000 0.772 23.09
1800 0.937 28.02 7500 0.757 22.65
1900 0.933 27.92 8000 0.743 22.22

2000 0.930 27.82 8500 0.729 21.80


2100 0.926 27.72 9000 0.715 21.39
2200 0.923 27.62 9500 0.701 20.98
2300 0.920 27.52 10000 0.688 20.58
2400 0.916 27.42 15000 0.564 16.89

2500 0.913 27.32 20000 0.460 13.75


2600 0.909 27.21 25000 0.371 11.10
2700 0.906 27.11 30000 0.297 8.89
2800 0.903 27.01 35000 0.235 7.04
2900 0.899 26.91 40000 0.185 5.54

Note: Specific gravity of standard air at sea level and 29.92 in. Hg = 1.00

Figure N.3 - Relative Specific Gravity of Air at Various Altitudes1

1. Robert Jorgensen, ed., Fan Engineering, 7th ed. (Buffalo, NY, Buffalo Forge Co., 1970) p.8 - Reprinted by Permission

119
AMCA 203-90 (R2007)

PROPERTIES OF SATURATED AIR2

WEIGHT IN A WEIGHT IN A
WEIGHT OF WEIGHT OF
CUBIC FOOT VOLUME CUBIC FOOT VOLUME
THE VAPOR THE VAPOR
OF MIXTURE OF MIXTURE
Temp ft3/lb Temp ft3/lb
°F OF °F OF
TOTAL lb/lb lb/lb TOTAL lb/lb lb/lb
DRY AIR VAPOR DRY AIR VAPOR
WEIGHT DRY AIR OF OF WEIGHT DRY AIR OF OF
lb lb lb lb
lb DRY AIR MIXTURE lb DRY AIR MIXTURE

-25 .09134 .000018 .09136 10.95 .00020 .00020 46 .07768 .000509 .07819 12.87 .00655 .00651
-20 .09025 .000024 .09027 11.07 .00027 .00027 47 .00750 .000527 .07803 12.90 .00680 .00675
-15 .08922 .000031 .08925 11.21 .00035 .00035 48 .07731 .000545 .07785 12.93 .00705 .00700
-10 .08820 .000041 .08824 11.34 .00046 .00046 49 .07714 .000567 .07771 12.96 .00734 .00728
-5 .08723 .000053 .08728 11.46 .00061 .00061 50 .07694 .000587 .07753 12.99 .00762 .00756

0 .08625 .000068 .08632 11.59 .00080 .00080 51 .07676 .000608 .07737 13.02 .00792 .00786
5 .08529 .000087 .08538 11.72 .00102 .00102 52 .07657 .000632 .07720 13.06 .00823 .00819
10 .08434 .000110 .08445 11.85 .00130 .00130 53 .07637 .000651 .07702 13.09 .00854 .00845
15 .08340 .000140 .08354 11.99 .00168 .00168 54 .07620 .000675 .07687 13.12 .00884 .00877
20 .08247 .000176 .08264 12.12 .00213 .00213 55 .07600 .000700 .07670 13.15 .00921 .00913

21 .08230 .000185 .08248 12.15 .00225 .00224 56 .07582 .000723 .07654 13.19 .00952 .00943
22 .08210 .000193 .08229 12.18 .00235 .00234 57 .07562 .000749 .07637 13.22 .00989 .00980
23 .08193 .000202 .08213 12.20 .00246 .00245 58 .07544 .000775 .07622 13.25 .01026 .01016
24 .08173 .000213 .08194 12.23 .00260 .00259 59 .07524 .000801 .07604 13.29 .01063 .01052
25 .08156 .000222 .08178 12.26 .00272 .00271 60 .07506 .000829 .07589 13.32 .01103 .01091

26 .08136 .000233 .08159 12.29 .00285 .00284 61 .07486 .000857 .07572 13.35 .01143 .01130
27 .08117 .000243 .08141 12.32 .00300 .00299 62 .07468 .000886 .07557 13.39 .01185 .01171
28 .08099 .000254 .08124 12.34 .00314 .00313 63 .07447 .000916 .07539 13.42 .01229 .01214
29 .08083 .000264 .08109 12.37 .00328 .00327 64 .07429 .000947 .07524 13.46 .01273 .01257
30 .08063 .000277 .08090 12.40 .00345 .00344 65 .07408 .000979 .07506 13.49 .01320 .01303

31 .08043 .000290 .08072 12.43 .00362 .00361 66 .07390 .001012 .07491 13.53 .01368 .01349
32 .08025 .000303 .08055 12.46 .00378 .00376 67 .07369 .001045 .07473 13.57 .01417 .01397
33 .08006 .000315 .08038 12.49 .00393 .00392 68 .07350 .001080 .07458 13.60 .01468 .01447
34 .07989 .000327 .08022 12.51 .00409 .00408 69 .07330 .001115 .07441 13.64 .01520 .01497
35 .07970 .000339 .08004 12.54 .00426 .00425 70 .07310 .001152 .07425 13.68 .01576 .01551

36 .07952 .000353 .07987 12.57 .00444 .00442 71 .07290 .001189 .07409 13.71 .01630 .01604
37 .07933 .000364 .07969 12.60 .00460 .00458 72 .07270 .001229 .07393 13.75 .01691 .01662
38 .07916 .000380 .07954 12.63 .00480 .00478 73 .07250 .001268 .07377 13.79 .01748 .01717
39 .07897 .000394 .07936 12.66 .00499 .00496 74 .07229 .001310 .07360 13.83 .01812 .01780
40 .07880 .000409 .07921 12.69 .00519 .00516 75 .07208 .001352 .07343 13.87 .01876 .01841

41 .07860 .000425 .07902 12.72 .00541 .00538 76 .07188 .001395 .07328 13.91 .01941 .01904
42 .07843 .000440 .07887 12.75 .00561 .00558 77 .07166 .001439 .07310 13.95 .02008 .01968
43 .07825 .000456 .07871 12.78 .00583 .00579 78 .07144 .001485 .07293 13.99 .02079 .02036
44 .07805 .000473 .07852 12.81 .00606 .00602 79 .07124 .001532 .07277 14.03 .02150 .02106
45 .07788 .000491 .07837 12.84 .00630 .00626 80 .07104 .001579 .07262 14.08 .0223 .02174

Figure N.4 - Weights of Air, Water Vapor, and Saturated Mixture of Air and
Water Vapor at Different Temperatures and 29.92 in. Hg

2. Jorgensen, op. cit., pp 15-17 Reprinted by Permission

120
AMCA 203-90 (R2007)

PROPERTIES OF SATURATED AIR2

WEIGHT IN A WEIGHT IN A
WEIGHT OF WEIGHT OF
CUBIC FOOT VOLUME CUBIC FOOT VOLUME
THE VAPOR THE VAPOR
OF MIXTURE OF MIXTURE
Temp ft3/lb Temp ft3/lb
°F OF °F OF
TOTAL lb/lb lb/lb TOTAL lb/lb lb/lb
DRY AIR VAPOR DRY AIR VAPOR
WEIGHT DRY AIR OF OF WEIGHT DRY AIR OF OF
lb lb lb lb
lb DRY AIR MIXTURE lb DRY AIR MIXTURE

81 .07081 .001629 .07244 14.12 .02301 .02249 116 .06186 .004427 .06629 16.16 .07157 .06678
82 .07059 .001680 .07227 14.16 .02380 .02325 117 .06154 .004548 .06609 16.24 .07390 .06882
83 .07038 .001733 .07211 14.21 .02462 .02403 118 .06124 .004669 .06591 16.32 .07625 .07084
84 .07015 .001785 .07193 14.26 .02545 .02482 119 .06092 .004794 .06571 16.41 .07869 .07296
85 .06993 .001840 .07177 14.30 .02631 .02566 120 .06060 .004921 .06552 16.50 .08121 .07511

86 .06970 .001898 .07160 14.34 .02723 .02651 121 .06027 .005049 .06532 16.58 .08376 .07729
87 .06947 .001954 .07142 14.39 .02813 .02736 122 .05995 .005183 .06513 16.68 .08646 .07958
88 .06925 .002014 .07126 14.44 .02908 .02826 123 .05960 .005319 .06492 16.77 .08925 .08194
89 .06902 .002072 .07109 14.48 .03002 .02915 124 .05927 .005456 .06473 16.87 .09204 .08428
90 .06880 .002139 .07094 14.53 .03109 .03015 125 .05892 .005598 .06452 16.96 .09502 .08677

91 .06855 .002201 .07075 14.58 .03211 .03111 130 .05713 .006355 .06349 17.49 .11125 .10010
92 .06832 .002267 .07058 14.63 .03318 .03212 135 .05524 .007195 .06244 18.10 .13026 .11523
93 .06809 .002334 .07042 14.69 .03428 .03314 140 .05319 .008128 .06132 18.79 .15280 .13255
94 .06785 .002404 .07025 14.73 .03543 .03422 145 .05100 .009162 .06016 19.60 .17966 .15230
95 .06760 .002474 .07007 14.79 .03660 .03531 150 .04865 .010303 .05895 20.55 .21178 .17478

96 .06736 .002546 .06991 14.84 .03780 .03642 155 .04612 .011547 .05767 21.67 .25038 .20022
97 .06711 .002620 .06973 14.90 .03904 .03757 160 .04340 .012937 .05634 23.03 .29810 .22962
98 .06688 .002692 .06957 14.95 .04025 .03870 165 .04048 .014436 .05492 24.69 .35660 .26285
99 .06660 .002770 .06931 15.01 .04159 .03993 170 .03734 .016118 .05346 26.77 .43168 .30150
100 .06634 .002853 .06919 15.07 .04300 .04124 175 .03398 .017926 .05191 29.43 .52750 .34530

101 .06610 .002937 .06904 15.12 .04443 .04255 180 .03035 .019905 .05036 32.94 .65580 .39525
102 .06583 .003019 .06885 15.18 .04586 .04385 185 .02645 .022062 .04851 37.78 .83410 .45425
103 .06557 .003106 .06868 15.25 .04737 .04523 190 .02228 .024393 .04667 44.85 1.0948 .52270
104 .06530 .003193 .06849 15.31 .04890 .04662 195 .01779 .026957 .04475 56.20 1.5153 .60240
105 .06504 .003283 .06832 15.37 .05048 .04806 200 .01297 .029730 .04270 77.11 2.2923 .69660

106 .06477 .003375 .06814 15.44 .05212 .04953 205 .00782 .032715 .04064 127.9 4.1838 .80500
107 .06451 .003470 .06798 15.50 .05379 .05105 210 .00232 .035942 .03836 431.0 15.493 .93700
108 .06421 .003568 .06778 15.57 .05556 .05264 212 .00000 .037298 .03730 ____ Inf. 1.0000
109 .06394 .003666 .06761 15.64 .05734 .05422
110 .06364 .003766 .06741 15.71 .05917 .05587

111 .06336 .003872 .06723 15.78 .06111 .05760


112 .06306 .003978 .06704 15.85 .06308 .05934
113 .06278 .004085 .06686 15.93 .06507 .06110
114 .06247 .004199 .06667 16.00 .06722 .06299
115 .06216 .004311 .06647 16.08 .06935 .06486

Figure N.4 - Weights of Air, Water Vapor, and Saturated Mixture of Air and
Water Vapor at Different Temperatures and 29.92 in. Hg

2. Jorgensen, op. cit., pp 15-17 Reprinted by Permission

121
AMCA 203-90 (R2007)

Density of Saturated Air for Various Barometric Conditions - lbm/ft3 Approximate


average
Dry-Bulb Barometric Pressure in. Hg Increase in increase in
Temp. °F density per density per
0.1 in. °F wet-bulb
28.5 29.0 29.5 30.0 30.5 31.0 pressure depression

30 .07703 .07839 .07974 .08110 .08245 .08380 .00027 .000017


31 .07687 .07822 .07957 .08093 .08228 .08363 .00027 .000017
32 .07671 .07806 .07940 .08075 .08210 .08345 .00027 .000017
33 .07654 .07789 .07924 .08058 .08193 .08327 .00027 .000018
34 .07638 .07772 .07907 .08041 .08175 .08310 .00027 .000018

35 .07621 .07756 .07890 .08024 .08158 .08292 .00027 .000018


36 .07605 .07739 .07873 .07807 .08141 .08274 .00027 .000018
37 .07589 .07723 .07856 .07990 .08123 .08257 .00027 .000019
38 .07573 .07706 .07840 .07973 .08106 .08239 .00027 .000019
39 .07557 .07690 .07823 .07956 .08089 .08222 .00027 .000019

40 .07541 .07674 .07806 .07939 .08072 .08205 .00027 .000019


41 .07525 .07657 .07790 .07922 .08055 .08187 .00026 .000020
42 .07509 .07641 .07773 .09705 .08038 .08170 .00026 .000020
43 .07493 .07625 .07757 .07889 .08021 .08153 .00026 .000020
44 .07477 .07609 .07740 .07872 .08004 .08135 .00026 .000020

45 .07461 .07592 .07724 .07855 .07986 .08118 .00026 .000020


46 .07445 .07576 .07707 .07838 .07970 .08101 .00026 .000021
47 .07429 .07560 .07691 .07822 .07953 .08084 .00026 .000021
48 .07413 .07544 .07674 .07805 .07936 .08066 .00026 .000021
49 .07397 .07528 .07658 .07788 .07919 .08049 .00026 .000022

50 .07381 .07512 .07642 .07772 .07902 .08032 .00026 .000022


51 .07366 .07496 .07625 .07755 .07885 .08015 .00026 .000022
52 .07350 .07479 .07609 .07739 .07868 .07998 .00026 .000023
53 .07334 .07464 .07593 .07722 .07852 .07981 .00026 .000023
54 .07318 .07447 .07576 .07706 .07835 .07964 .00026 .000023

55 .07302 .07431 .07560 .07689 .07818 .07947 .00026 .000024


56 .07287 .07415 .07544 .07673 .07801 .07930 .00026 .000024
57 .07271 .07399 .07528 .07656 .07784 .07913 .00026 .000025
58 .07255 .07383 .07512 .07640 .07768 .07896 .00026 .000025
59 .07240 .07367 .07495 .07623 .07751 .07879 .00026 .000025

60 .07224 .07352 .07479 .07607 .07734 .07862 .00026 .000026


61 .07208 .07336 .07463 .07590 .07718 .07845 .00026 .000026
62 .07193 .07320 .07447 .07574 .07701 .07828 .00026 .000027
63 .07177 .07304 .07430 .07557 .07684 .07811 .00026 .000027
64 .07161 .07288 .07414 .07541 .07668 .07794 .00026 .000028

Note: Approximate average decrease in density per 0.1°F rise in dry-bulb temperature equals .000017 lbm/ft3.

Figure N.5 - Psychrometric Density Table (I-P)

122
AMCA 203-90 (R2007)

Psychrometric Density Table (I-P)

Density of Saturated Air for Various Barometric Conditions - lbm/ft3 Approximate


average
Dry-Bulb Barometric Pressure in. Hg Increase in increase in
Temp. °F density per density per
0.1 in. °F wet-bulb
28.5 29.0 29.5 30.0 30.5 31.0 pressure depression

65 .07145 .07272 .07398 .07525 .07651 .07770 .00026 .000028


66 .07130 .07256 .07382 .07508 .07634 .07760 .00026 .000029
67 .07114 .07240 .07366 .07492 .07618 .07744 .00026 .000029
68 .07098 .07224 .07350 .07475 .07601 .07727 .00026 .000030
69 .07083 .07208 .07333 .07459 .07584 .07710 .00026 .000030

70 .07067 .07192 .07317 .07442 .07568 .07693 .00026 .000031


71 .07051 .07176 .07301 .07426 .07551 .07676 .00025 .000031
72 .07035 .07160 .07285 .07410 .07534 .07659 .00025 .000032
73 .07020 .07144 .07268 .07393 .07517 .07642 .00025 .000033
74 .07004 .07128 .07252 .07377 .07501 .07625 .00025 .000033

75 .06988 .07112 .07236 .07360 .07484 .07603 .00025 .000034


76 .06972 .07096 .07220 .07343 .07467 .07591 .00025 .000034
77 .06956 .07080 .07203 .07327 .07451 .07574 .00025 .000035
78 .06940 .07064 .07187 .07310 .07434 .07557 .00025 .000036
79 .06925 .07048 .07171 .07294 .07417 .07540 .00025 .000036

80 .06909 .07032 .07155 .07277 .07400 .07523 .00025 .000037


81 .06893 .07015 .07138 .07261 .07383 .07506 .00025 .000038
82 .06877 .07000 .07122 .07244 .07366 .07489 .00024 .000039
83 .06861 .06983 .07105 .07227 .07349 .07472 .00024 .000039
84 .06845 .06967 .07089 .07211 .07333 .07454 .00024 .000040

85 .06829 .06950 .07072 .07194 .07316 .07437 .00024 .000041


86 .06812 .06934 .07056 .07177 .07299 .07420 .00024 .000042
87 .06796 .06917 .07039 .07160 .07281 .07403 .00024 .000043
88 .06780 .06901 .07022 .07143 .07264 .07385 .00024 .000043
89 .06764 .06885 .07005 .07126 .07247 .07368 .00024 .000044

90 .06748 .06868 .06989 .07109 .07230 .07351 .00024 .000045


91 .06731 .06852 .06972 .07092 .07213 .07333 .00024 .000046
92 .06715 .06835 .06955 .07075 .07195 .07316 .00024 .000047
93 .06698 .06818 .06938 .07058 .07178 .07298 .00024 .000048
94 .06682 .06801 .06921 .07041 .07161 .07280 .00024 .000049

95 .06665 .06785 .06904 .07024 .07143 .07263 .00024 .000050


96 .06648 .06768 .06887 .07006 .07126 .07245 .00024 .000051
97 .06632 .06751 .06870 .06989 .07108 .07227 .00024 .000052
98 .06615 .06734 .06853 .06972 .01091 .07209 .00024 .000053
99 .06598 .06717 .06835 .06954 .07073 .07191 .00024 .000054
100 .06581 .06700 .06818 .06937 .07055 .07174 .00024 .000055

Note: Approximate average decrease in density per 0.1°F rise in dry-bulb temperature equals .000017 lbm/ft3.

Figure N.5 - Psychrometric Density Table (I-P)

123
AMCA 203-90 (R2007)

FUEL FLUE GAS DENSITY


lbm/ft3
COAL 0.078

OIL 0.075

NATURAL GAS 0.0725

BAGASSE 0.070

BLAST FURNACE GAS 0.076

LIGNITE 0.073

WOOD 0.070

The above densities at 70°F and 29.92 in. Hg are based on average fuel analyses and moisture contents

Figure N.6 - Typical Densities for Various Flue Gases

124
AMCA 203-90 (R2007)

Annex P. Diffusion at Fan Outlets

BLAST AREA
DISCHARGE DUCT
OUTLET AREA
CUTOFF

25%

50%

75%
CENTRIFUGAL FAN
100% EFFECTIVE DUCT LENGTH

AXIAL FAN

To calculate 100% effective duct length, assume a minimum of 2½ duct diameters for 2500 fpm or less. Add 1 duct
diameter for each additional 1000 fpm.

Example: 5000 fpm = 5 equivalent duct diameters

If the duct is rectangular, with side dimensions equal to a and b, the equivalent duct diameter is equal to (4ab/π)0.5

Figure P.1 - Controlled Diffusion and Establishment of a Uniform


Velocity Profile in a Straight Length of Outlet Duct

125
AMCA 203-90 (R2007)

Annex R. Terminology for Fans and Air Handling Units

CASING

BACKPLATE
RIM
HUB INLET

MOTOR BLADE
GUIDE VANE

IMPELLER

INLET BELL

Tubular Centrifugal Fan - Direct Drive

CASING

BLADE
DIFFUSER
HUB

MOTOR

IMPELLER

CASING

Tubeaxial Fan-Direct Drive


BEARING CASING
(Impeller Downstream)
BELT TUBE

BLADE

HUB

GUIDE VANE
Vaneaxial Fan-Belt Drive
IMPELLER
MECHANISM FOR
CONTROLLING
INLET BOX BEARINGS GUIDE VANES BLADE ANGLE
FAN
CASING

INNER CYLINDER

IMPELLER
DIFFUSER
Vaneaxial Mechanical Draft Fan

Figure R.1 - Common Terminology for Axial and Tubular Centrifugal Fans
126
AMCA 203-90 (R2007)

HOUSING

DIVERTER

FF
TO
CU

CENTER PLATE

BLAST AREA
DISCHARGE
OUTLET AREA

SIDE SHEET
BACKPLATE

BLADE FF
TO
CU

INLET

SCROLL

IMPELLER

FRAME
RIM
BEARING
SUPPORT
INLET COLLAR

Figure R.2 - Common Terminology for Centrifugal Fan


127
AMCA 203-90 (R2007)

Figure R.3 - Common Terminology for Centrifugal Fan Appurtenances


128
AMCA 203-90 (R2007)

HEATING AND VENTILATING DRAW-THROUGH UNIT


MB
FS FB

BELT GUARD EXT


FS CS F & BP INT
MB
F & BP HC FB AS
+

HEATING AND VENTILATING BLOW-THROUGH UNIT


ZONE DAMPERS
FS
MB
BYPASS HC FB
COLD DECK +
+
HOT DECK

+ +

AIR-CONDITIONING DRAW-THROUGH UNIT


MB
AS FS CC HC SS FB ELIM
+ +
+ +
+
+ + +

DRIP TRAY

AIR-CONDITIONING BLOW-THROUGH UNIT


ZONE DAMPERS DIFFUSER
PLATE FS MB
HC HC CC FB
+

HOT DECK
+

+ +
+
COLD DECK
CC
+ + +
FLEXIBLE CONNECTION

AS ACCESS SECTION EXT F & BP EXTERNAL FACE AND BYPASS DAMPER FS FAN SECTION
CS COIL SECTION INT F & BP INTERNAL FACE AND BYPASS DAMPER FB FILTER BOX
CC COOLING COIL ELIM ELIMINATORS MB MIXING BOX
HC HEATING COIL SS SPRAY SECTION

Figure R.4 - Common Terminology for Central Station Air-Handling Units


129
AMCA 203-90 (R2007)

Annex S. Typical Format for Field Test Data Sheet

FIELD TEST DATA SHEET


JOB DESCRIPTION: Location, User, Contractor, Engineer, . . . . .

FAN DESCRIPTION: Mfgr., Size, Type, Ident. No., . . . . .

MOTOR DESCRIPTION: Mfgr., Nameplate Data (Ident. No., hp, volts, FLA, . . . ), Performance Data
Reference, . . . . .
DRIVE DESCRIPTION: Type, Mfgr., Ident. No., Size, . . . . .

REFERENCE DRAWINGS OR
SKETCHES OF INSTALLATION: System Configuration with Dimensions, Measurement Plane
Locations, . . . . .
MEASUREMENTS
AMBIENT DATA: Barometric Pressure, Dry-Bulb Temp., Wet-Bulb Temp, . . . . .

MOTOR DATA: volts, amps, watts, rpm, . . . . .

FAN SPEED

GAS DENSITY DATA:


GAS TEMPERATURES AT MEASUREMENT PLANES:

READING Ps1 or Ps4 Ps2 or Ps5 Ps3 Pv3 Pv3


1
2
3
4
5





n
TOTAL
AVERAGE

CALCULATIONS: (Refer to the various sections of this publication for the appropriate calculation
procedures.)

Figure S.1 - Typical Format for Field Test Data Sheet

130
AMCA 203-90 (R2007)

Annex T. Uncertainty Analysis This applies only to random uncertainties. Systematic


uncertainties should be eliminated by the use of
T.1 Introduction properly calibrated test instruments. This analysis
considers only the uncertainties inherent in testing.
In an attempt to determine the range of uncertainties
likely to be encountered in field testing of fans, a This publication specifies uncertainties in percent.
statistical uncertainty analysis was undertaken. These are, of course, per unit uncertainties,
Maximum and minimum uncertainties were assigned multiplied by 100. Absolute uncertainties which bear
to each quantity to be measured based on the degree the units of the quantity being measured or
of difficulty in measuring the quantity, the previously calculated, are equal to the per unit uncertainty
specified accuracies of instruments and the multiplied by the measured or calculated quantity.
conditions expected to be encountered in field Since the tolerance on measured values is specified
testing. These individual maximum and minimum on the basis of 95% confidence limits, the actual
uncertainties were then combined statistically to deviations in results will be less than the calculated
arrive at the probable range of overall uncertainties deviations 95% of the time.
for the fan flow rate, fan static pressure, and fan
power input. It would be unlikely, however, that any For the purposes of a field test, an uncertainty range
particular field installation would have all minimum or will be defined with minimum and maximum values.
all maximum uncertainties occurring simultaneously. This range of possible uncertainty is necessary to
Therefore, an agreement by the parties as to cover the varying degrees of difficulty encountered in
acceptable measurement tolerances for a given performing tests in field installations. Field test
installation should be established prior to testing. conditions range from near ideal to near impossible.

In Type A tests, it may be sufficient to accept the T.3 Symbols


results of any field test without consideration of the
probable uncertainties in the results. For Type B and In the analysis that follows, certain symbols and
Type C tests, it may be necessary to calculate the notations are used in addition to those shown in
uncertainties. To do this, each measured quantity is Annex Q.
assigned an estimated uncertainty by agreement of
the parties involved and the overall uncertainty is Symbol Quantity
calculated as outlined in this annex.
ex Per Unit Uncertainty in X
T.2 General ΔX Absolute Uncertainty in X
R Gas Constant (ft-lb/lbm —°R)
This analysis is based on the assumption that fan
perfomance can be treated as a statistical quantity Subscript Description
and that the performances derived from repeated
tests would have a normal distribution. The most A area
probable performance would, therefore, be the mean b Barometric Pressure
results based on repeated observations at each point d Dry-bulb Temperature
of operation. Only one set of observations is f Velocity Pressure
specified in this publication. This analysis deals, g Static Pressure
therefore, with the probable uncertainty in the results h Power Input
obtained from a single set of observations. H Fan Power Input
N Fan Speed
The results of a fan field performance test for a single P Fan Static Pressure
point of operation are a combination of variables Q Fan Flow Rate
which are normally presented graphically. Test results w Wet-bulb Depression
will be considered to be the fan static pressure x Generalized Quantity (A, b, ..., ρ)
versus flow rate and fan power input versus flow rate. ρ Density
The uncertainty in results will be expressed in terms
of fan flow rate, fan static pressure, and fan power T.4 Measurement uncertainties
input.
The various measurement uncertainty ranges used in
The accuracies specified in this publication are based this publication are listed below. The considerations
upon two standard deviations. This means that there that led to their adoption include difficulties in field
should be a 95% probability that the actual testing generally not encountered in laboratory
uncertainties will be less than the specified value. testing.

131
AMCA 203-90 (R2007)

T.4.1 Barometric pressure. The estimated ec = 0.015 (min) to 0.075 (max)


uncertainty in measuring barometric pressure is
between 0.3% minimum and 0.7% maximum. The uncertainty range in the Pitot traverse is
estimated on the basis of traverse location, broad
eb = 0.003 (min) to 0.007 (max) range of duct sizes, nonuniform velocity profiles, and
turbulence.
Barometric pressure is generally obtained by
portable aneroid barometer, on-site barometer T.4.7 Flow measurement area. The estimated
(mercury or aneroid) or by use of data obtained from uncertainty in the flow measurement area is between
a nearby airport. The uncertainty range above is 1.0% minimum to 2.0% maximum.
estimated based on the use of portable or on-site
instrumentation and applicable corrections. eA = 0.010 (min) to 0.020 (max)

T.4.2 Dry-bulb temperature. The estimated The estimated uncertainty is based on a broad range
uncertainty in measuring dry-bulb temperature is of duct sizes, accessibility, and the rigidity of ducts
between 0.5% of absolute temperature minimum and under pressure.
2.0% of absolute temperature maximum.
T.4.8 Velocity pressure. An allowance of 2.0%
ed = 0.005 (min) to 0.02 (max) minimum to 5.0% maximum of the reading is
estimated for the mental averaging performed on a
The estimated uncertainty range is based on a broad fluctuating reading. An allowance of 1.0% minimum
temeprature range and the likelihood of stratification. to 2.0% maximum of the reading is estimated for
calibrated manometer uncertainty and relocation of
T.4.3 Web-bulb depression. The estimated the instrument after calibration. In addition, an
uncertainty in measuring wet-bulb depression is allowance of 0.5% minimum to 10.0% maximum of
between 5°F minimum and 10°F maximum. the reading is estimated for instrument precision. No
allowance is included for yaw on the assumption that
ew = 5/(td - tw) (min) to 10/(td - tw) (max) the Pitot-static tube is aligned within 10 degrees of
streamlines. A combined uncertainty can be written
The estimated uncertainty range is based on a broad as:
temperature range with the associated difficulties in
determining wet-bulb readings at high or low ef (min) = [(0.02)2 + (0.01)2 + (0.005)2]0.5
temperatures and the likelihood of stratification. = 0.0229

T.4.4 Fan speed. The estimated uncertainty in ef (max) = [(0.05)2 + (0.02)2 + (0.10)2]0.5
measuring fan speed is between 0.5% minimum and = 0.1136
1.0% maximum.
T.4.9 Static pressure. An allowance of 1.0%
eN = 0.005 (min) to 0.01 (max) minimum to 5.0% maximum of the reading is
estimated for the mental averaging performed on a
The uncertainty range in fan speed is estimated on fluctuating reading. An allowance of 1.0% minimum
the basis of portable instrumentation accuracy and to 2.0% maximum of the reading is estimated for
an allowance for fluctuation in fan speed. calibrated manometer uncertainty and relocation of
the instrument after . In addition, a tolerance of 10%
T.4.5 Power input. The estimated uncertainty in minimum to 20.0% maximum of the fan velocity
measuring power input is betwen 3.0% minimum and pressure should cover the influence of Pitot-static
7.0% maximum. tube yaw or velocity influence on static pressure taps
and other possible effects. A combined uncertainty
eh = 0.03 (min) to 0.07 (max) can be written as:

The estimated uncertainty range is based on the eg (min) = {(0.01)2 + (0.01)2 + (0.005)2 +
various measurement methods and their respective [0.1 Pv/(Ps2 - Ps1)]2}0.5
accuracies, estimated drive losses, and the broad = {0.000225 + [0.1 Pv/(Ps2 - Ps1)]2}0.5
horsepower range encountered in the field.
eg (max) = {(0.05)2 + (0.02)2 + (0.02)2 +
T.4.6 Pitot traverse. A properly performed field [0.2 Pv/(Ps2 - Ps1)]2}0.5
traverse is estimated to have an accuracy of 1.5% = {0.0033 + [0.2 Pv/(Ps2 - Ps1)]2}0.5
minimum to 7.5% maximum.

132
AMCA 203-90 (R2007)

Where the denominator in the final term in each Assuming Δ70.73 and ΔR are both zero:
equation will involve Ps2 or Ps5 and Ps1 or Ps4,
whichever are measured. eρ = (eb2 + ev2 + ed2)0.5

The estimated uncertainty range is based on an It can be shown that:


allowance for fluctuation in the fan-system operation,
lack of ideal measurement locations, turbulence, and ev2 = [(0.00000725 tw - 0.0000542) Δ(td - tw)]2
the relocation of instrumentation after calibration.
Where:
T.5 Combined uncertainties
Δ(td - tw) = Absolute uncertainty in wet-bulb depression.
The uncertainties in the test performance are the
result of using various values, each of which contains
Other methods for determining density are assumed
a probable uncertainty. The combined uncertainty for
to have equal accuracy.
each of the fan performance variables is given below.
T.5.2 Fan flow rate. Fan flow rate directly involves
T.5.1 Density. Air density involves the various
the area at the flow measuring station, the Pitot
psychrometric measurements and the approximate
traverse, the square root of the pressure
formula:
measurement for flow, and the square root of the
density. Uncertainties in fan speed will produce a
70.73 pbV first-power uncertainty in flow rate when making the
ρ=
R ( t d + 460 ) fan law conversions. Combining:

eQ = [ec2 + eA2 (ef/2)2 + (eρ/2)2 + eN2]0.5


Where:

V = 1.0 - 0.378 {(pe/pb) - [(td - tw)/2700]} T.5.3 Fan static pressure. Fan static pressure
directly involves static pressure measurements.
Uncertainties in density will produce a first-power
For random and independant uncertainties in
uncertainty in fan static pressure while uncertainties
products, the combined uncertainty is determined as
in fan speed will produce a second-power uncertainty
follows:
in fan static pressure when making fan law
conversions. Combining:
Δρ/ρ = {(Δ70.73/70.73)2 + (Δpb/pb)2 + (ΔV/V)2 +
(ΔR/R)2 + [Δtd/(td + 460)]2}0.5 ep = [eg2 + eρ2 + (2eN)2]0.5

Table T.1

Measurement Minimum Maximum

eb 0.003 0.007
ed** 0.005 0.020
eW 5/(td - tw) 10/(td - tw)
eN 0.005 0.010
eh 0.030 0.070
ec 0.015 0.075
eA 0.010 0.020
ef 0.0229 0.1136
eg {0.000225 + [0.1 Pv/(Ps2 - Ps1)]2}0.5 {0.0033 + [0.2 Pv/(Ps2 - Ps1)]2}0.5

* These uncertainties do not account for the effect of swirl at the fan inlet. This situation must be corrected in order
to produce acceptable fan-system performance (see Section 5).

** Based on absolute temperature

133
AMCA 203-90 (R2007)

In order to simplify the application of this uncertainty The uncertainty calculations lead to absolute
analysis to the results of field tests, the above uncertainties in fan flow rate, fan static pressure, and
equation was developed on the basis of tests in fan power input that can be applied directly to the
which static pressure measurements are made at a corresponding test results. The uncertainty results
single plane, as would be the case in which a fan is can then be plotted as rectangles around the test
ducted on one side only. However, the equation is point. Intersection of the rectangles with the quoted
reasonably accurate for all other fan-system fan performance within the limitations of a field test.
configurations. See the examples in Section T.7.

Although in most cases the determination of fan static T.7 Examples


pressure involves Pv1, the uncertainty in determining
Pv1 is not included in the above equation on the basis Two examples of the calculation of uncertainties and
that it normally has a very small effect on the overall the method of comparison with the quoted fan curve
uncertainty in fan static pressure. are included in this section. Uncertainty calculations
and comparisons have been developed for Examples
For purposes of this publication, eP is applied directly 2B and 2C of Annex A. Uncertainty calculations for
to Psc, which may include System Effect Factors. Example 2B utilize all minimum uncertainty
tolerances. Uncertainty calculations for Example 2C
T.5.4 Fan power input. Fan power input directly utilize all maximum uncertainty tolerances. It would
involves the power measurement; in addition, when be unlikely that any field installation would lend itself
making fan law conversions, density has a first-power to all minimum or all maximum measurement
effect and speed has a third-power effect on fan tolerances. Agreement of the parties as to acceptable
power input. Combining: measurement tolerances for a given installation
should be established prior to testing.
eH = [eh2 + eρ2 + (3eN)2]0.5

T.6 Summary

The minimum and maximum measurement


uncertainties (See Table T.1) were defined earlier in
Section T.4. Summarizing, the per unit uncertainties
are as shown in Table T.1.

134
AMCA 203-90 (R2007)

EXAMPLE 1: CALCULATION OF UNCERTAINTIES ev2 = [(0.00000725 tw - 0.0000542) Δ(td - tw)]2


IN TEST RESULTS BASED ON MINIMUM = [(0.00000725 × 70.4 - 0.0000542) 5]2
MEASUREMENT UNCERTAINTY = 0.00000520

TEST VALUES eρ = [eb2 + ev2 + ed2)0.5


Reference: Example 2B in Annex A = (0.0032 + 0.00000520 + 0.0052)0.5
= 0.006261
SITE MEASUREMENTS
eP = [eg2 + eρ2 + (2eN)2]0.5
td2 = 91.3°F = [0.020112 + 0.0062612 + (2 × 0.005)2]0.5
tw2 = 70.4°F = 0.0233
Ps1 = -11.4 in. wg
Ps2 = 0.1 in. wg eQ = [ec2 + eA2 + (ef/2)2 + (eρ/2)2 + eN2]0.5
Pv3 = 1.24 in. wg = [0.0152 + 0.0102 + (0.0229/2)2 +
A2 = 1.40 ft2 (0.006261/2)2 + 0.0052]0.5
= 0.0222
A3 = 1.57 ft2
ρ2 = 0.0714 lbm/ft3 eH = [eh2 + eρ2 + (3eN)2]0.5
ρ3 = 0.0705 lbm/ft3
= [0.0302 + 0.0062612 + (3 × 0.005)2]0.5
= 0.0341
CONVERTED RESULTS
ΔP = ePPsc
Qc = 7114 cfm
= 0.0233 × 11.42
Psc = 11.42 in. wg = 0.27 in. wg
Hc = 18.90 hp
Psc + ΔP = 11.42 + 0.27
MEASUREMENT UNCERTAINTIES = 11.69 in. wg

Reference: Minimum values per Section T.6 Psc - ΔP = 11.42 - 0.27


= 11.15 in. wg
eb = 0.003
ed = 0.005 ΔQ = eQQc
ew = 5/(td2 - tw2) = 0.0222 × 7114
eN = 0.005 = 158 cfm
eh = 0.030
ec = 0.015 Qc + ΔQ = 7114 + 158
eA = 0.010 = 7272 cfm
ef = 0.0229
eg = {0.000225 + [0.1 Pv/(Ps2 - Ps1)]2}0.5 Qc - ΔQ = 7114 - 158
= 6956 cfm
CALCULATIONS
ΔH = eHHc
Pv = Pv2 = 0.0341 × 18.90
= 0.64 hp
= Pv3 (A3/A2)2 (ρ3/ρ2)
= 1.24 (1.57/1.40)2 (0.0705/0.0714) Hc + ΔH = 18.90 + 0.64
= 1.54 in. wg
= 19.54 hp
eg = {0.000225 + [0.1 Pv/(Ps2 - Ps1)]2}0.5 Hc - ΔH = 18.90 - 0.64
= {0.000225 + [(0.1 × 1.54)/(0.1 + 11.4)]2}0.5 = 18.26 hp
= 0.02011

135
AMCA 203-90 (R2007)

GRAPHICAL PRESENTATION

Psc + ∆P TEST POINT


Psc MINIMUM UNCERTAINTY RANGE

Psc - ∆P Qc = 7114 cfm


Ps, FAN STATIC PRESSURE

ΔQ = 158 cfm

Psc = 11.42 in. wg


ΔP = 0.27 in. wg

Hc = 18.90 hp
ΔH = 0.64 hp

Qc + ∆Q
Qc - ∆Q

Qc
QUOTED FAN
Q, FAN FLOW RATE
PERFORMANCE
CURVES

Hc + ∆H

Hc
H, FAN POWER INPUT

Hc - ∆H

Qc - ∆Q Qc + ∆Q

Qc
Q, FAN FLOW RATE

Figure T.1

136
AMCA 203-90 (R2007)

EXAMPLE 2: CALCULATION OF UNCERTAINTIES eQ = [ec2 + eA2 + (ef/2)2 + (eρ/2)2 + eN2]0.5


IN TEST RESULTS BASED ON MAXIMUM = [0.0752 + 0.0202 + (0.1136/2)2
MEASUREMENT UNCERTAINTIES + (0.02176/2)2 + 0.0102]0.5
= 0.0973
TEST VALUES
eH = [eh2 + eρ2 + (3eN)2]0.5
Reference: Example 2C in Annex A
= [0.0702 + 0.021762 + (3 × 0.010)2]0.5
SITE MEASUREMENTS = 0.0792

td3 = 86.5°F ΔP = eP Psc


tw3 = 75.5°F = 0.0780 × 2.54
Ps4 = -1.57 in. wg = 0.20 in. wg
Ps5 = 1.22 in. wg
Psc + ΔP = 2.54 + 0.20
Pv2 = 0.61 in. wg
= 2.74 in. wg
CONVERTED RESULTS Psc - ΔP = 2.54 - 0.20
= 2.34 in. wg
Qc = 25964 cfm
Psc = 2.54 in. wg ΔQ = eQQc
Hc = 17.11 hp = 0.0973 × 25964
= 2526 cfm
MEASUREMENT UNCERTAINTIES
Qc + ΔQ = 25964 + 2526
Reference: Maximum values per Section T.6 = 28490 cfm
eb = 0.007 Qc - ΔQ = 25964 - 2526
ed = 0.020 = 23438 cfm
eW = 10/(td3 - tw3)
eN = 0.010 ΔH = eHHc
eh = 0.070 = 0.0792 × 17.11
ec = 0.075 = 1.36 hp
eA = 0.020
ef = 0.1136 Hc + ΔH = 17.11 + 1.36
eg = {0.0033 + [0.2 Pv/(Ps5 - Ps4)]2}0.5 = 18.47 hp

CALCULATIONS Hc - ΔH = 17.11 - 1.36


= 15.75 hp
eg = {0.0033 + [0.2 Pv/(Ps5 - Ps4)]2}0.5
= {0.0033 + [(0.2 × 0.61)/(1.22 + 1.57)]2}0.5
= 0.07219

ev2 = [(0.00000725 tw - 0.0000542) Δ(td - tw)]2


= [(0.00000725 × 75.5 - 0.0000542) 10]2
= 0.0000243

eρ = (eb2 + ev2 + ed2)0.5


= (0.0072 + 0.0000243 + 0.0202)0.5
= 0.02176

eP = [eg2 + eρ2 + (2eN)2]0.5


= [0.072192 + 0.021762 + (2 × 0.010)2]0.5
= 0.0780

137
AMCA 203-90 (R2007)

GRAPHICAL PRESENTATION

TEST POINT
MAXIMUM UNCERTAINTY RANGE

Qc = 25964 cfm
ΔQ = 2526 cfm
Psc + ∆P
Psc = 2.54 in. wg
Psc ΔP = 0.20 in. wg
Ps, FAN STATIC PRESSURE

Hc = 17.11 hp
Psc - ∆P ΔH = 1.36 hp

Qc - ∆Q
Qc + ∆Q

Qsc
Q, FAN FLOW RATE QUOTED FAN
PERFORMANCE
CURVES

Hc + ∆H
H, FAN POWER INPUT

Hc

Hc - ∆H

Qc - ∆Q Qc + ∆Q

Qsc
Q, FAN FLOW RATE

Figure T.2

138
AIR MOVEMENT AND CONTROL
ASSOCIATION INTERNATIONAL, INC.
30 West University Drive
Arlington Heights, IL 60004-1893 U.S.A.
Tel: (847) 394-0150 Fax: (847) 253-0088
E-Mail : info@amca.org Web: www.amca.org

The Air Movement and control Association International, Inc. is a not-for-profit international association of the
world’s manufacturers of related air system equipment primarily, but limited to: fans, louvers, dampers, air
curtains, airflow measurement stations, acoustic attenuators, and other air system components for the industrial,
commercial and residential markets.

You might also like