Professional Documents
Culture Documents
EPMA Liquid Resistance Starters For Slip-Ring Motors. 200 To 20 000 KW
EPMA Liquid Resistance Starters For Slip-Ring Motors. 200 To 20 000 KW
Crushing
Milling
Conveyors
Pumps
Ventilation
EPMA starter The moving electrodes travel For starting machines of large
An EPMA unit comprises: vertically inside the insulating powers, or to reduce mechanical
container, guided by a nylon rod. stress, it may some-times be
The electrolytic resistance contained Two solid brass rods, fixed to a preferable to use two motors which
within a tank complete with electrodes transversal carrier, support the total the rated power rather than a
of a size rated for the specific kW assembly. This carrier is common to single one. (Such as a dual drive
rating. A separate H.V enclosure all three electrodes and constitutes mill) A dual EPMA starter is then
houses the Shorting contactor, and a n the neutral point (start point). used, to ensure synchronized
L.V enclosure contains the control acceleration of both motors.
system (control panel). Displacement of the electrodes is The EPMA DUO comprises two
effect-ed by a motor driven worm electrolyte tanks. The resistance
Tank...................................... screw assembly. This is normally values are equalized between the
controlled by either an electrode two tanks as they use common
The tank is manufactured with 304L drive motor, which is operated by a electrolyte, which is circulated
stainless steel from 2 to 5 mm. The VVVF. A hand wheel is also provided between each tank. The electrode
tanks include lifting points suitable for for emergency manual operation. drive assemblies are mechanically
hoist to facilitate loading, unloading Starting times are adjustable from 8 coupled via a cardin shaft, so as to
and positioning. Tank capacity and to 150 seconds. ensure complete synchronization of
dimensions are deter-mined by the the movement of the two electrode
motor rating. (See characteristics). The assemblies.
tank is filled through a access point in Control and interlocking Limit
the side cover, and emptied through switches are incorporated to control
the electrode travel, and to energize A single four or six pole shorting
valves situated at the base of the unit. contactor is used to short circuit the
The tanks Ingress Protection rating is the shorting contactor. This contactor
is used to short circuit the residual residual resistances of each tank at
IP 54 the end of the motor run up time
resistance at the end of the motor
Electrolyte............................. start-up time.
Heat exchanger starter.............
Various concentrations of sodium The electrode drive motor is
operated by a VVVF drive. The drive The EPMA starter is designed
carbon-ate are normally employed. A suitable for operating a slip ring
float switch monitors electrolyte level includes overload protection, which
prevents the overload of the motor in (wound rotor) motor at variable
and thermostats control the electrolyte speed. The starter is normally
temperature. An RTD per tank with a 4- the case of a drive mechanism
obstruction. An electrical “ready to equipped with a heat exchanger for
20 mA output can be fitted to monitor these applications. This can either be
the tank temperature. start” interlock prevents a restart
before the electrodes return to the of the water-cooled type, (adequate
initial maximum resistance position. supplies of cooling water must be
Electrode Assemblies............... available on site), or an air blast
If a power failure occurs during cooler can be used.
A set consists of three fixed and three
moving electrodes. Polypropylene starting, the electrodes return
automatically to the top (start) Maintenance........................
containers “buckets” shroud the fixed
electrodes to provide adequate position when the supply is restored,
so that a new start is possible. The starters typically require little
isolation between phases. The more than a basic inspection every
electrodes consist of con-centric three months, and a major inspection
cylinders, which mesh with each other Control panels........................
once a year. The electrolyte solution
in the fully lowered (minimum has an anti evaporation oil which
resistance) position. The electrodes The control gear is housed in two
prevents the loss of electrolyte.
are manufacture cast bronze. The fixed separate enclosures. The shorting
electrodes, located inside the insulating contactor, complete with the rotor
containers, are fed from an tinned terminations is housed in the H.V
insulated copper bar. Since this bar enclosure. A separate panel is
does not pass through the tank wall, provided for the L.V controls. The
there is no danger of electrolyte H.V enclosure is normally included
leakage. Current density of the with the starter, but for higher
electrodes is extremely low, typically 1 ratings, it may be supplied in a
amp / cm ² resulting in extremely long separate control panel.
electrode life
The control panel can be fabricated
out of mild steel to minimize costs, or
it can be supplied in a 316 Stainless
Steel enclosure.
A range of models are used for the EPMA starters equipped with heat The temperature of the electrolyte is
control of various motor ratings for exchangers may be used with motors controlled by thermostats.
single and dual EPMA drives. The whose powers exceed those shown on
adjoining table provides a guide to the table. These are determined by the Refer Below
rating the various models of EPMA size of the heat exchanger. Maximum (1) Maximum rating for 1 start/hour
starters. Many factors, such as the rotor voltage between slip rings: 3 500 V. or three consecutive starts from cold
run up time, starts per hour, starting Standard starting times : 20, 30, 40, 60, ST: starting torque -FLT: full load
torque, operating temperature and a 80 and 130 seconds. These are preset torque -The electrolyte is cooled by
range of other factors effect the during manufacture. The electrolyte level natural convection
selection of the starter. is monitored by float switch.
The following information is necessary • rotor current For starter with heat exchanger........
so that we may provide an EPMA • starting torque • temperature of cooling water
starter customised to your application. • percentage slip for permanent
For the driven machine.................... slip
General operating conditions ........... • type • speed variation and duty cycle
• ambient temperature • coupling method
• maximum and minimum • speed (rpm) Options.......................................
temperatures • speed control for electrode drive
• moment of inertia
• relative humidity • special paint
• number of consecutive starts
• height above sea level • cable entries
• setting up and installation
• location requirements • anti-freeze control
• anti-condensation heaters
For the motor(s).......................... For the starter control gear...........
• power • protection IP 54 or 55
• speed (rpm) • supply voltage
• stator voltage • control voltage
• rotor voltage