You are on page 1of 5

EPMA Liquid Resistance

Starters for Slip-ring


motors. 200 to 20 000 kW.

The EPMA starter has been specifically designed


by AOIP for controlled starting and speed control
of large slip ring motors in arduous applications
such as:

Crushing
Milling
Conveyors
Pumps
Ventilation

In a variety of industries such as mines, quarries,


cement plants, water treatment and associated
Industries.

CSE-Uniserve Pty Limited has adapted this basic


design under license to AOIP to suit the harsh
conditions typical of Australian mining
installations. The starter tanks are manufactured
here in Australia from stainless steel to AS 1554,
and customized to suit outdoor installation, with
minimal maintenance requirements.

All Unistarter units are manufactured in Australia


and in conformance with Australian Standards.

The EPMA rotor starter is used to This type of starter is designed to


control the starting of a slip ring provide the optimum starting
(wound rotor induction) motor. The characteristic, which results in
starting current is generally limited to smooth progressive acceleration
a maximum of 250% Full Load to full load speed. It can also be
Current. Optimal starting torque for used for speed variation and
each application is selected by the torque control. Plug braking can
choice of the initial value of also be implemented with this
resistance. The principle of the liquid system. The variation in the
starter is that of a secondary resistance is achieved by
resistance starter, where by the rotor displacement of the electrodes in
resistance is reduced to a minimum the electrolyte. At the end of the
during the starting period. acceleration, the electrodes are
shorted out.

Electrical Engineering Excellence


Description Electrode control system......... EPMA DUO starter...............

EPMA starter The moving electrodes travel For starting machines of large
An EPMA unit comprises: vertically inside the insulating powers, or to reduce mechanical
container, guided by a nylon rod. stress, it may some-times be
The electrolytic resistance contained Two solid brass rods, fixed to a preferable to use two motors which
within a tank complete with electrodes transversal carrier, support the total the rated power rather than a
of a size rated for the specific kW assembly. This carrier is common to single one. (Such as a dual drive
rating. A separate H.V enclosure all three electrodes and constitutes mill) A dual EPMA starter is then
houses the Shorting contactor, and a n the neutral point (start point). used, to ensure synchronized
L.V enclosure contains the control acceleration of both motors.
system (control panel). Displacement of the electrodes is The EPMA DUO comprises two
effect-ed by a motor driven worm electrolyte tanks. The resistance
Tank...................................... screw assembly. This is normally values are equalized between the
controlled by either an electrode two tanks as they use common
The tank is manufactured with 304L drive motor, which is operated by a electrolyte, which is circulated
stainless steel from 2 to 5 mm. The VVVF. A hand wheel is also provided between each tank. The electrode
tanks include lifting points suitable for for emergency manual operation. drive assemblies are mechanically
hoist to facilitate loading, unloading Starting times are adjustable from 8 coupled via a cardin shaft, so as to
and positioning. Tank capacity and to 150 seconds. ensure complete synchronization of
dimensions are deter-mined by the the movement of the two electrode
motor rating. (See characteristics). The assemblies.
tank is filled through a access point in Control and interlocking Limit
the side cover, and emptied through switches are incorporated to control
the electrode travel, and to energize A single four or six pole shorting
valves situated at the base of the unit. contactor is used to short circuit the
The tanks Ingress Protection rating is the shorting contactor. This contactor
is used to short circuit the residual residual resistances of each tank at
IP 54 the end of the motor run up time
resistance at the end of the motor
Electrolyte............................. start-up time.
Heat exchanger starter.............
Various concentrations of sodium The electrode drive motor is
operated by a VVVF drive. The drive The EPMA starter is designed
carbon-ate are normally employed. A suitable for operating a slip ring
float switch monitors electrolyte level includes overload protection, which
prevents the overload of the motor in (wound rotor) motor at variable
and thermostats control the electrolyte speed. The starter is normally
temperature. An RTD per tank with a 4- the case of a drive mechanism
obstruction. An electrical “ready to equipped with a heat exchanger for
20 mA output can be fitted to monitor these applications. This can either be
the tank temperature. start” interlock prevents a restart
before the electrodes return to the of the water-cooled type, (adequate
initial maximum resistance position. supplies of cooling water must be
Electrode Assemblies............... available on site), or an air blast
If a power failure occurs during cooler can be used.
A set consists of three fixed and three
moving electrodes. Polypropylene starting, the electrodes return
automatically to the top (start) Maintenance........................
containers “buckets” shroud the fixed
electrodes to provide adequate position when the supply is restored,
so that a new start is possible. The starters typically require little
isolation between phases. The more than a basic inspection every
electrodes consist of con-centric three months, and a major inspection
cylinders, which mesh with each other Control panels........................
once a year. The electrolyte solution
in the fully lowered (minimum has an anti evaporation oil which
resistance) position. The electrodes The control gear is housed in two
prevents the loss of electrolyte.
are manufacture cast bronze. The fixed separate enclosures. The shorting
electrodes, located inside the insulating contactor, complete with the rotor
containers, are fed from an tinned terminations is housed in the H.V
insulated copper bar. Since this bar enclosure. A separate panel is
does not pass through the tank wall, provided for the L.V controls. The
there is no danger of electrolyte H.V enclosure is normally included
leakage. Current density of the with the starter, but for higher
electrodes is extremely low, typically 1 ratings, it may be supplied in a
amp / cm ² resulting in extremely long separate control panel.
electrode life
The control panel can be fabricated
out of mild steel to minimize costs, or
it can be supplied in a 316 Stainless
Steel enclosure.

Electrical Engineering Excellence


SPECIFICATIONS

A range of models are used for the EPMA starters equipped with heat The temperature of the electrolyte is
control of various motor ratings for exchangers may be used with motors controlled by thermostats.
single and dual EPMA drives. The whose powers exceed those shown on
adjoining table provides a guide to the table. These are determined by the Refer Below
rating the various models of EPMA size of the heat exchanger. Maximum (1) Maximum rating for 1 start/hour
starters. Many factors, such as the rotor voltage between slip rings: 3 500 V. or three consecutive starts from cold
run up time, starts per hour, starting Standard starting times : 20, 30, 40, 60, ST: starting torque -FLT: full load
torque, operating temperature and a 80 and 130 seconds. These are preset torque -The electrolyte is cooled by
range of other factors effect the during manufacture. The electrolyte level natural convection
selection of the starter. is monitored by float switch.

Electrical Engineering Excellence


Electrical Engineering Excellence
Quotation:

The following information is necessary • rotor current For starter with heat exchanger........
so that we may provide an EPMA • starting torque • temperature of cooling water
starter customised to your application. • percentage slip for permanent
For the driven machine.................... slip
General operating conditions ........... • type • speed variation and duty cycle
• ambient temperature • coupling method
• maximum and minimum • speed (rpm) Options.......................................
temperatures • speed control for electrode drive
• moment of inertia
• relative humidity • special paint
• number of consecutive starts
• height above sea level • cable entries
• setting up and installation
• location requirements • anti-freeze control
• anti-condensation heaters
For the motor(s).......................... For the starter control gear...........
• power • protection IP 54 or 55
• speed (rpm) • supply voltage
• stator voltage • control voltage
• rotor voltage

CSE-Uniserve Pty Limited was If you require a simple method of


established in 1978 in Sydney, secondary starting, the most
Australia as a distributor of quality advanced in Slip Energy Recovery
electrical engineering equipment system s, or Dual or single drive
to the mining, process variable speed control; Uniserve can
engineering, power generation, engineer a package to suit all of
transmission, distribution and your requirements.
manufacturing industries. We
have a strong international CSE- Uniserve, with over 25 years of
business with clients on all experience, can offer the best
continents supported by offices in solution for your slip ring motor
Victoria, Western Australia, system. Should you require further
Queensland, New Zealand, and information, please do not hesitate
Canada. to contact us.

Sydney: +61 2 8853 4200.


Melbourne: +61 3 9245 1700.
Brisbane: +61 7 3861 7777.
Perth: +61 8 6380 0900.
Auckland: +64 9 262 3290.

More information on CSE-Uniserve can


be found at: www.cse-uniserve.com.au.

Electrical Engineering Excellence

You might also like