Modbus Database

MICOM P211
for Firmware Version 6.X

Technical Guide

  




  

1.1 STRUCTURE OF THE MODBUS CHARACTERS 3


1.1.1 Line protocol 3
1.1.2 Serial transmission mode 3
1.1.3 Synchronization of exchanged messages 3
1.1.4 Error checking method 3
1.2 MODBUS PROTOCOL APPLIED TO THE MICOM P211 RANGE 3
1.2.1 Slave number of the MiCOM P211 relay 3
1.2.2 MODBUS functions used by the MiCOM P211 relay 3
1.2.3 Presentation of the MODBUS protocol 3
1.2.4 Format of frames received by the MiCOM P211 4
1.2.5 Format of frames sent by the MiCOM P211 4
1.2.6 Message validity check 4
1.2.7 MiCOM P211 database organization 5

  

2.1 MICOM P211 RELAY DATA STRUCTURE 5


2.2 FUNCTION 3 OR 4 (READING OF N WORDS) 6
2.3 FUNCTION 6 (WRITING OF 1 WORD) 6
2.4 FUNCTION 7 (FAST READ OF 8 BITS) 7
2.5 FUNCTION 16 (WRITE OF N WORDS) 7

  

3.1 DESCRIPTION OF APPLICATION MAPPING. 8


3.2 LIMITATIONS 8
3.3 DATABASE. 9
3.4 DATA FORMATS. 11
 

 

 

 

 

 


 



 



 




 

 



 



  

  
  
  
  
  

 



  



 


   
   
 
   
   

 








 


   
 
   
   










 










 

 

 



 Function  


 code
   
   



















 




 

 







    
  
    
    
 



  






    
  
    
    
 

 





    


    

    


 




    


    

    




    


    

    


 





    


    

    






 

 

 

 





  


  

   



   


   
 
   

 





      


      

    


   




    


    

    


 



  



 

 





   

 
     
 

     

     

     

 



 


 

 


• 


• 


• 


 

 

 

 
Address Hardware
Description Format code Note / Scale
Dec Hex B C U
Read only Product information Function 3 or 4
0 0000 Relay description characters 1 and 2 F10 X X X P2
1 0001 Relay description characters 3 and 4 F10 X X X 11
2 0002 Relay description characters 5 and 6 F10 X X X
3 0003 Unit reference characters 1 and 2 F10 X X X AL
4 0004 Unit reference characters 3 and 4 F10 X X X ST
5 0005 Firmware version F26 X X X
6 0006 Hardware version F28 X X X
7 0007 Phase current range F21 X X X
8 0008 Neutral current range F21 X X
9-15 0009-000F Reserved
Read only Signalling Function 3 or 4
16 0010 Logical input status F12 X X X
17 0011 Protection disable status F20 X X X
18 0012 Reserved
19 0013 Logical output status F13 X X X
20-21 0014-0015 Reserved
22 0016 Loss of phase protection status F16 X X X
23 0017 Earth fault protection status F16 X X
24 0018 Reserved
25 0019 Loss of load protection status F16 X X X
26 001A Thermal overload protection status F16 X X X
27 001B Short-circuit protection status F16 X X X
28 001C Prolong start/Stall rotor protection status F16 X X X
29 001D Unbalance protection status F16 X X X
30 001E Over temperature PTC protection status F16 X X X
31 001F Motor state F30 X X X
32 0020 Remained start number F21 X X X
33-47 0021-002F Reserved
Read only Measurements Function 3 or 4
48 0030 Phase L1 current F21 X X X [A] x fp / 256 x fr
49 0031 Phase L1 current F21 X X X [A] x fr
50 0032 Phase L2 current F21 X X X [A] x fp / 256 x fr
51 0033 Phase L2 current F21 X X X [A] x fr
52 0034 Phase L3 current F21 X X X [A] x fp / 256 x fr
53 0035 Phase L3 current F21 X X X [A] x fr
54 0036 Neutral current F21 X X [A] x fe / 256 x 0.01
55 0037 Neutral current F21 X X [A] x 0.01
56 0038 Thermal image F21 X X X [%]
57-58 0039-003A Reserved
59 003B Reference voltage F21 X [%]
60-61 003C-003D Reserved
Read only Scale factors Function 3 or 4
62 003E Phase current scale factor F21 X X X fp
63 003F Neutral current scale factor F21 X X fe
Read/Write Settings Function 3, 4, 6 or 16
256 0100 Modbus address F21 X X X
257 0101 Baud rate F38 X X X
258 0102 Password F21 X X X
259 0103 Back compatibility mode F27 X X X

  



Address Hardware
Description Format code Note / Scale
Dec Hex B C U
260 0104 On/Off Line F35 X X X
261-262 0105-0106 Reserved
263 0107 Phase current ratio F21 X X X
264 0108 Neutral current ratio F21 X X
265-271 0109-010F Reserved
272 0110 RL1 (P1) configuration F40 X X X
273 0111 RL2 (P2) configuration F41 X X X
274 0112 RL2 (P2) latching mode F33 X X X
275 0113 RL3 (P3) configuration F42 X X
276 0114 RL3 (P3) latching mode F33 X X
277 0115 RL4 (P4) configuration F43 X X
278 0116 Input 1 (T1-T2) configuration F45 X X X
279 0117 Input 2 (S1-S2) configuration F46 X X X
280 0118 Input 3 (V1-C) configuration F47 X X
281 0119 Input 4 (V2-C) configuration F48 X X
282 011A RL2 (P2) status after power on F34 X X X
283 011B RL3 (P3) status after power on F34 X X
284 011C RL4 (P4) latching mode F33 X X firmware ver. 6.B or higher
285-287 011D-011F Reserved
288 0120 Short-circuit configuration F31 X X X
289 0121 I>> F21 X X X [A] x Ib
290 0122 tI>> F21 X X X [s] x 0.01
291 0123 Thermal overload configuration F31 X X X
292 0124 Base current F21 X X X [A] x fr
293 0125 Time constant (t6xIb) F21 X X X [s] x 0.1
294 0126 Theta forbid start F21 X X X [%]
295 0127 Thermal overload latching mode F33 X X X
296 0128 Loss of load configuration F31 X X X
297 0129 I< F21 X X X [%] x Ib
298 012A tI< F21 X X X [s] x 0.01
299 012B Prolong start/Stall rotor configuration F31 X X X
300 012C Istall and Istart detection F21 X X X [A] x Ib
301 012D tIstall F21 X X X [s] x 0.01
302 012E tIstart F21 X X X [s] x 0.01
303 012F Earth fault configuration F31 X X
304 0130 Io> F21 X X [A] x 0.01
305 0131 tIo> F21 X X [s] x 0.01
306 0132 Loss of phase configuration F31 X X X
307 0133 Reserved X X X
308 0134 Time delay F21 X X X [s] x 0.01
309 0135 Unbalance configuration F31 X X X
310 0136 % delta I threshold F21 X X X [%] x Ib
311 0137 % delta I time delay F21 X X X [s] x 0.01
312 0138 Over temperature PTC configuration F31 X X X
313 0139 Over temperature latching mode F33 X X X
314 013A Reserved
315 013B Star/delta configuration F32 X X X
316 013C Current threshold for ECO logic F21 X X X [%] x Ib
317 013D Star during start (1t) F21 X X X [s]
318 013E Time between star and delta (2t) F21 X X X [s] x 0.01
319 013F ECO time delay delta to star (4t) F21 X X X [s]
320 0140 ECO time delay star to delta (5t) F21 X X X [s]
321 0141 Start number configuration F27 X X X
 

 

 

Address Hardware
Description Format code Note / Scale
Dec Hex B C U
322 0142 Allowed start number F21 X X X
323 0143 Start number Treference F21 X X X [s]
324 0144 Star number Lock time F21 X X X [s]
325 0145 delay for motor stop status detection (3t) F21 X X X [s] x 0.1
326 0146 Reaccelleration authorization time F21 X X X [s]
327 0147 Reaccelleration close delay F21 X X X [s]
328 0148 Theta reduction during reaccelerating (Ar) F21 X X X [%]
329 0149 Uref F21 X [%]
330-383 014A-017F Reserved
Write only Remote control Function 6
1024 0400 Remote control F9 X X X
Read only Fault recorder Function 3 or 4
4608 1200 Cause of fault F22 X X X
4609 1201 Phase L1 fault current F21 X X X [A] x fp / 256 x fr
4610 1202 Phase L2 fault current F21 X X X [A] x fp / 256 x fr
4611 1203 Phase L3 fault current F21 X X X [A] x fp / 256 x fr
4612 1204 Neutral fault current F21 X X [A] x fe / 256 x 0.01
4613 1205 Last max start current F21 X X X [A] x fp / 256 x fr
4614 1206 Last start time F21 X X X [s] x 0.01
Read only Relay status Function 7
Relay status F50 X X X



Phase current range fr
0,37 - 0,75 A 0.01
0,75 - 1,50 A 0.01
1,0 - 2,0 A 0.1
1,5 - 3,0 A 0.1
3,0 - 6,0 A 0.1
5,0 - 10,0 A 0.1
10 - 20 A 0.1
20 - 40 A 0.1
40 - 80 A 0.1

 

Code Description
F9 Unsigned integer - Remote control word
1- test
4- reset LED and latching
5- clear fault recorder
7- clear thermal image
8- CB open
16- CB close
41- switch to ON-Line mode
42- switch to OFF-Line mode
F10 Characters ASCII
byte 1 : ASCII character 32-127
byte 2 : ASCII character 32-127
F12 Unsigned integer - Logical input status

  



Code Description
bit 0 : logic input 1 (T1-T2)
bit 1 : logic input 2 (S1-S2)
bit 2 : logic input 3 (V1-C)
bit 3 : logic input 4 (V2-C)
bits 4 to 15 reserved
F13 Unsigned integer - Logical output status
bit 0 : logic output RL1 (P1)
bit 1 : logic output RL2 (P2)
bit 2 : logic output RL3 (P3)
bit 3 : logic output RL4 (P4)
bits 4 to 15 reserved
F16 Unsigned integer - Protection status
bits 0 to 4 reserved
bit 5 : trigger of protection
bit 6 : protection TRIP
bits 7 to 15 reserved
F20 Unsigned integer - Protection disable status
bits 0 to 2 reserved
bit 3 : CB position
bit 4 : reserved
bit 5 : Thermal overload disable
bit 6 : Short-circuit disable
bit 7 : Earth fault disable
bit 8 : Loss of load disable
bit 9 : Prolong start/Stall rotor disable
bits 10 to 11 reserved
bit 12 : Unbalance disabled
bit 13 : Loss of phase disable
bit 14 : Over temperature PTC disable
bit 15 : reserved
F21 Unsigned integer - numerical data
F22 Unsigned integer - Cause of fault code
0 : reserved
1 : I> - thermal overload
2 : I>> - short circuit
3 : I< - loss of load
4 : Stal - stall rotor
5 : Io> - earth fault
6 : Ph.LO - loss of phase
7 : Ph.AS - unbalance
8 : PTC - over temperature
9 : ESTP - emergency stop
10 : TSTP - technological stop
11 : FUSE - fuse trip
12 : ZZ - external protection
13 : Long - prolong start
14 : St.no - start number
F26 Two-digit decimal number - Firmware version
1st digit - major version
2nd digit - minor version
60 : 6.A
61 : 6.B
62 : 6.C
etc...
F27 Unsigned integer - Configuration
0 : disable
1 : enable
F28 Unsigned integer - Hardware version
0:A
1:B
 

 

 

Code Description
2:C
...
19 : U
F30 Unsigned integer - Motor state
0 : stop
1 : start
2 : run
F31 Unsigned integer - Protection configuration
0 : disable
1 : trip
2 : alarm (warning signal)
F32 Unsigned integer - Start-Delta configuration
0 : disable
1 : enable
2 : enable with function ECO
F33 Unsigned integer - Latching mode
0 : without
1 : latching
F34 Unsigned integer - Output status after power
0 : normally open
1 : normally close
F35 Unsigned integer - ON/OFF Line mode
0 : OFF Line
1 : ON Line
F38 Unsigned integer - Baud rate value
12 : 1200 baud
24 : 2400 baud
48 : 4800 baud
96 : 9600 baud
192 : 19200 baud
other values reserved
F40 Unsigned integer - P1 configuration
0 : circuit breaker
1 : contactor without remote control
2 : contactor with remote control
F41 Unsigned integer - P2 configuration
0 : trigger of any protection on trip
1 : trip of any protection (without TSTP)
2 : alarm (warning signal) of any protection
3 : thermal overload trigger, trip or alarm
4 : delta arrangement
5 : remote or local CB close
6 : delayed open based on current criteria
7 : trigger of reaccelaration function
F42 Unsigned integer - P3 configuration
0 : trigger of any protection on trip
1 : trip of any protection (without TSTP)
2 : alarm (warning signal) of any protection
3 : delayed open based on current criteria
5 : star arrangement
6 : motor run
F43 Unsigned integer - P4 configuration
0 : trigger of any protection on trip
1 : trip of any protection (without TSTP)
3 : no protection alarm (warning signal)
4 : no protection trip (without TSTP)
5 : delta arrangement
F45 Unsigned integer - Input 1 (T1-T2) configuration
0 : over temperature protection PTC

  



Code Description
1 : reset of LEDs and latching
2 : blocking of CB close
F46 Unsigned integer - Input 2 (S1-S2) configuration
0 : blocking of RL1 (P1)
1 : reset of LEDs and latching
2 : trigger of RL2 (P2)
3 : trigger of reacceleration
4 : blocking of any remote controls (RS485)
5 : clear thermal image
6 : emergency stop (ESTP)
F47 Unsigned integer - Input 3 (V1-C) configuration
0 : local CB close
1 : external trip ZZ
2 : deenergising of all relay outputs
3 : no action
4 : FUSE trip
F48 Unsigned integer - Input 4 (V2-C) configuration
0 : CB state
1 : external trip ZZ
2 : reset of LEDs and latching
3 : blocking of any remote controls (RS485)
4 : trip and blocking of CB close
5 : trigger of reacceleration
6 : technological stop (TSTP)
F50 Unsigned integer - Relay status
bit 0 : logic output RL1 (P1)
bit 1 : logic output RL2 (P2)
bit 2 : logic output RL3 (P3)
bit 3 : logic output RL4 (P4)
bit 4 : reserved
bit 5 : alarm (warning signal) of any protection
bit 6 : trip of any protection
bit 7 : relay in ON-Line mode

Badanie izolacji przy użyciu megaomomierza wysokonapięciowego (powyżej 250V)
uszkadza elementy półprzewodnikowe zabezpieczenia, co może prowadzić do awarii,
widocznej dopiero po kilku tygodniach od chwili przeprowadzenia badania.
Nieprzygotowanych obwodów zabezpieczenia nie wolno testować przy użyciu miernika
izolacji o napięciu wyższym niż 250V !!! Przygotowanie obwodów polega na połączeniu
biegunów wejść binarnych, wejść zasilania oraz wyjść - zwłaszcza półprzewodnikowych
(o charakterystyce "szybkiej" bądź „mocnej”). Wewnątrz urządzenia – między dowolnymi
jego zaciskami, nie może się pojawić różnica potencjałów o wartości przekraczającej
250 V. W razie braku możliwości takiego przygotowania, wymagane jest odłączenie
sprawdzanych obwodów zewnętrznych od zabezpieczenia na czas wykonywanych badań.

Urządzenie jest obiektem testów wysokonapięciowych podczas procesu produkcji –


zgodnie z normami przedstawionymi w rozdziale opisującym dane techniczne.
Takie badanie jest przeprowadzone tylko raz, z zachowaniem ściśle określonego, bardzo
krótkiego czasu badania.

Obwody komunikacji szeregowej (RS232 / RS485) nie podlegają testom napięciowym -


nie wolno testować ich miernikiem izolacji !!!