As per ANSI/IEEE Std 80-1986 code Enter Your Data in White back
:Enter Your Details:
Length of Area Occupied by Earthing Grid la 36 mt
Width of Area Occupied by Earthing Grid lb 30 mt
Fault level at Incoming Bus fault 10000 MVA
Incoming Voltage Vin 66 KV
Outgoing Voltage Vout 11 KV
Soil Resistivity q 21.7 Ω-m
Resistance of Main Eartjing Mat 0.69 Ω
Resistance of surface Material (Crushed Rock ) qs 3000 Ω-m
Thickness of Surface Material (Crushed Rock) hs 0.1 mt
Depth of Earthing Grid Conductor h 0.7 mt
Diameter of Earthing Grid Conductor d 32 mm2
Reference Depth of Grid 1 mt
Area Occupied by Earthing Grid 1080 m2
Spacing between Parallel Conductor of Grid D 5 mt
Duration of Fault (To determine Size of earthing Mat) t 3 sec
Duration of Fault (To determine safe Step & Touch Potential) t 0.5 sec