Loading Calculation for Door Panel Board Fixing

Door Frame Fixing on AAC Brick Walls


Fixing Base Assumed (AAC Wall) with SXR 10 on all the sides
A) Size of Board Panel 2300 x 900

Loading Intensity 0.1 kN/m2

Total Load of Board Panel 0.21 kN

Factored Load 0.31 kN

Wind Load 1 kN/M2

Total Wind Load on Panel 2.07 kN

Concrete Loads
Loading Calculation for Door Panel Board Fixing

Brick Loads

**European Technical Approval ETA-07/0121


Factored Shear Load on Panel 3.11 kN

Characteristic Resistance of Screw / Sleeve 0.9 kN (*Whichever is minimum)

Partial Safety Factor 2

Additional Factor of Safety 1

Capacity of SXR 10 Anchors 0.45 kN (*Whichever is minimum)


(SXR 10)

No. of Anchors Required 7 Nos.

No. of Panels 1 Nos.

Assume spacing 300 mm


Total
No. of Anchors on Face 900 3.0 At top and Bottom Level 6

No. of Anchors on Face 2300 2.0 At Left and Right Side 2


8 Nos.
Loading Calculation for Door Panel Board Fixing
900

2300

Required Anchors 7 Nos.

Provided Anchors 8 Nos. Safe


Prepared by,
Uday A. Shikhare,
Shikhare M. Tech. IIT-Roorkee
Technical Manager (West), Fischer India