Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
[T-G-AH2-01] [T-G-AH2-01]
Duct RA temp. detector [AHU] 1 A 2 SD 30 2 12 4 5.5kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 1 DOL 20 2 3 4 4.0kW Extract fan
Duct RA Air Quality Detector [AHU] 1 A 2
Duct LL temp detector [AHU] 1 A 2
Room temp. detector Room 1 A 2
Room hum detector Room 1 A 2
Mixing damper 1 [AHU] 1 A 3
Mixing damper 2 [AHU] 1 A 3
T-G-MCC-01
[T-G-PAH3-01] [T-G-PAH3-01]
Duct SA temp. detector [AHU] 1 A 2 SD 30 2 7 4 5.5kW Supply fan
Duct SA Hum. detector [AHU] 1 A 2 2 DOL 20 2 3 4 4.0kW Extract fan
Duct IA temp. detector [AHU] 1 A 2 DOL 2 2 3 1.5 0.2kW Heat Wheel
Duct IA Hum. detector [AHU] 1 A 2
Motorised damper 1 [AHU] 1 D 3
Motorises damper 2 [AHU] 1 D 3
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Rotary wheel starter [MCC] 2 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Exract fan isolator [AHU] 1 D 2
Rotary wheel isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-G-PAH3-02] [T-G-PAH3-02]
Duct SA temp. detector [AHU] 1 A 2 DOL 16 2 3 2.5 2.2kW Supply fan
Duct SA Hum. detector [AHU] 1 A 2 3 DOL 16 2 3 2.5 2.2kW Extract fan
Duct IA temp. detector [AHU] 1 A 2 DOL 2 2 3 1.5 0.2kW Heat Wheel
Duct IA Hum. detector [AHU] 1 A 2
Motorised damper 1 [AHU] 1 D 3
Motorises damper 2 [AHU] 1 D 3
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Rotary wheel starter [MCC] 2 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Exract fan isolator [AHU] 1 D 2
Rotary wheel isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-G-PAH2-01] [T-G-PAH2-01]
Duct SA temp. detector [AHU] 1 A 2 SD 30 2 12 4 5.5kW Supply fan 2 speed
Room temp. detector Room 1 A 2 4
Motorised damper 1 [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
RE6309/D1368 Rev 0/2003 15910/1 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel Plant Room # 1, MCC-01
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
[T-G-PAH2-02] [T-G-PAH2-02]
T-G-MCC-01 (contd)
Duct SA temp. detector [AHU] 1 A 2 SD 30 2 7 4 5.5kW Supply fan
Room temp. detector Room 1 A 2 4
Motorised damper 1 [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-G-PAH2-03] [T-G-PAH2-03]
Duct SA temp. detector [AHU] 1 A 2 DOL 16 2 2.2kW Supply fan
Room temp. detector Room 1 A 2 6
Motorised damper 1 [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-G-PAH1-01] [T-G-PAH1-01]
Motorised damper 1 [AHU] 1 D 3 DOL 16 2 3 2.5 2.3kW Supply fan
Supply fan starter [MCC] 3 D 5 7
Supply fan isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-G-SCS-01] [T-G-SCF-01]
Duct SA temp. detector [AHU] 1 A 2 DOL 10 2 3 1.5 1.1kW Supply fan
Motorised Valve [AHU] 1 A 3 8
Filter DP switch [AHU] 1 D 2
Supply fan starter [MCC] 2 D 3
Supply fan isolator [AHU] 1 D 2
[T-G-SCS-02]
Duct SA temp. detector [AHU] 1 A 2
Motorised Valve [AHU] 1 A 3
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
Fire Alarm Interface Unit, zone 2 MCC 1 D 2
Fire Alarm Interface Unit, zone 3 MCC 1 D 2
[T-G-EF-02] [T-G-EF-02]
Supply fan starter [MCC] 3 D 5 DOL 2 3 1.5kW Extract Fan
Supply fan isolator [Field] 1 D 2 9
[T-G-EF-03]
[T-G-EF-03]
Supply fan starter [MCC] 3 D 5
DOL 2 3 1.5kW Extract Fan
Supply fan isolator [Field] 1 D 2
10
RE6309/D1368 Rev 0/2003 15910/2 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel Plant Room #1 - MCC-02
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
[T-G-HWG-01] T-G-P-03
Immersion temp. detector Pipe 1 A 2 DOL 4 2 3 2.5 0.37kW Shunt pump
Motorised Valve Pipe 1 A 3 1
Pump Starter MCC 3 D 5
Pump isolator Field 1 D 2
T-G-MCC-02
[T-G-HWG-02] T-G-P-04
Immersion temp. detector Pipe 1 A 2 DOL 4 2 3 2.5 0.37kW Shunt pump
Motorised Valve Pipe 1 A 3 2
Pump Starter MCC 3 D 5
Pump isolator Field 1 D 2
[T-G-HWG-03] T-G-P-05
Immersion temp. detector Pipe 1 A 2 DOL 4 2 3 2.5 0.37kW Shunt pump
Motorised Valve Pipe 1 A 3 3
Pump Starter MCC 3 D 5
Pump isolator Field 1 D 2
[T-G-P-01] T-G-P-01
Pump Starter MCC 3 D 5 DOL 10 2 3 2.5 1.1kW HWS pump
Pump isolator Field 1 D 2 4
[T-G-CWG-01] T-G-P-02
Immersion temp. detector Pipe 1 A 2 DOL 6 2 3 2.5 0.75kW Shunt pump
5
ChW Motorised Valve Pipe 1 A 3
CCWS Motorised Valve Pipe 1 A 3
Pump Starter MCC 3 D 5
Pump isolator Field 1 D 2
[T-G-HP-01] T-G-P-06
HRChW temp inlet detector Pipe 1 A 2 DOL 16 2 3 4 2.2kW Shunt pump
HRChW temp outlet detector Pipe 1 A 2 6 T-G-P-08
HRLTHW temp inlet detector Pipe 1 A 2 DOL 25 2 3 6 4.5kW Shunt pump
HRLTHW temp outlet detector Pipe 1 A 2
Enable / disable HP 1 D 2
Common alarm HP 1 D 2
ChW shunt pump starter MCC 3 D 5
LTHW shunt pump starter MCC 3 D 5
HRChW shunt pump isolator Field 1 D 2
HRLTHW shunt pump isolator Field 1 D 2
[T-G-P-07(A,B)]
P-07A inverter enable / alarm / status MCC 4 D 5 T-G-P-07A
P-07A inverter speed control / feedback MCC 2 A 4 7 INV 100 2 4 35 25kW Pump
P-07B inverter enable / alarm / status MCC 4 D 5
P-07B inverter speed control / feedback MCC 2 A 4
P-07A Pressure Switch 1 Pipe 1 D 2
P-07A Pressure Switch 2 Pipe 1 D 2
P-07B Pressure Switch 1 Pipe 1 D 2
P-07B Pressure Switch 2 Pipe 1 D 2
P-07A isolator Field 1 D 2 T-G-P-07B
Standby
P-07B isolator Field 1 D 2 8 INV 100 2 4 35 25kW Pump
Diff pressure detector Field 1 A 2
RE6309/D1368 Rev 0/2003 15910/3 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel Plant Room #1 - MCC-02
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
[T-G-P-09(A,B)]
P-09A inverter enable / alarm / status MCC 4 D 5 T-G-P-09A
P-09A inverter speed control / feedback MCC 2 A 4 9 INV 50 2 4 16 11kW Pump
P-09B inverter enable / alarm / stautus MCC 4 D 4
P-09B inverter speed control / feedback MCC 2 A 4
P-09A Pressure Switch 1 Pipe 1 D 2
P-09A Pressure Switch 2 Pipe 1 D 2
P-09B Pressure Switch 1 Pipe 1 D 2
P-09B Pressure Switch 2 Pipe 1 D 2
P-09A isolator Field 1 D 2 T-G-P-09B
P-09B isolator Field 1 D 2 10 INV 50 2 4 16 11kW Pump
Diff pressure detector Field 1 A 2
[Water Meters]
Main Kitchen Field 1 P 2
Bakery Field 1 P 2
Banquet Field 1 P 2
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
Fire Alarm Interface Unit, zone 2 MCC 1 D 2
Fire Alarm Interface Unit, zone 3 MCC 1 D 2
[Sprinkler]
Sprinkler zone alarm LG - centre Field 1 D 2
Sprinkler zone alarm L1 - centre Field 1 D 2
Sprinkler zone alarm L2 - centre Field 1 D 2
Sprinkler zone alarm L3 - centre Field 1 D 2
Sprinkler zone alarm L4 - centre Field 1 D 2
[FM200 Systems]
Security room alarm Field 1 D 2
Computer room alarm Field 1 D 2
[Coldroom Equipment]
Monitoring system common alarm Field 1 D 2
Fridge condensing unit common alarm Field 1 D 2
RE6309/D1368 Rev 0/2003 15910/4 BEMS Point Schedule + MCC Load Diagram
Device
Location
Field
3
Nr of Points
D
Analouge or Digital
4
15910/5
Compartment #
Town Hotel Plant Room #1 - MCC-02
Cable Type
Cable Cores
Cable Size
Load Item
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
RE6309/D1368 Rev 0/2003 15910/6 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Main Tank Room
Cable Cores
Nr of Points
Cable Type
Cable Type
Load Item
Location
Device
T-G-MCC-03
[T-G-BS-01] SF 4 33kW Booster Set
Booster Set enable BS 1 D 2 1 integral MCC
Booster set status BS 8 D 9
Booster set alarm BS 1 D 2
TSE Booster set isolator BS 1 D 2
High Level float switch 1 Tank 1 D 2
High Level float switch 2 Tank 1 D 2
Tank contents detector #1 Tank 1 A 2 DOL 4 5kW UV Steriliser
Tank contents detector #2 Tank 1 A 2 2 to be confirmed by W&WW specialist
Delivery pressure BS 1 A 2
UV steriliser enable Field 1 D 2
UV striliser alarm Field 1 D 2
[T-G-BS-02]
Booster Set enable BS 1 D 2 SF 4 45kW Booster Set
Booster set status BS 8 D 9 3 integral MCC
Booster set alarm BS 1 D 2
TSE Booster set isolator BS 1 D 2
High Level float switch 1 Tank 1 D 2
High Level float switch 2 Tank 1 D 2
Tank contents detector #1 Tank 1 A 2
Tank contents detector #2 Tank 1 A 2 DOL 4 5kW UV Steriliser
Delivery pressure BS 1 A 2 4 to be confirmed by W&WW specialist
UV steriliser enable Field 1 D 2
UV striliser alarm Field 1 D 2
RE6309/D1368 Rev 0/2003 15910/7 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 1 Plant Room # 1
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
[T-1-AH2-01] [T-1-AH2-01]
T-1-MCC-01
Duct RA temp. detector [AHU] 1 A 2 SD 30 2 7 6 5.5kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 1
Duct RA Air Quality Detector [AHU] 1 A 2 DOL 16 2 3 4 2.2kW Extract fan
Duct LL temp detector [AHU] 1 A 2
Damper 1 [AHU] 1 A 3
Supply fan isolator [AHU] 1 D 2
Extract fan isolator [AHU] 1 D 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-1-AH2-02]
[T-1-AH2-02]
Duct RA temp. detector [AHU] 1 A 2 DOL 20 2 3 4 4.0kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 2
Duct RA Air Quality Detector [AHU] 1 A 2 DOL 16 2 3 2.5 1.5kW Extract fan
Duct LL temp detector [AHU] 1 A 2
Damper 1 [AHU] 1 A 3
Damper 2 [AHU] 1 A 3
Supply fan isolator [AHU] 1 D 2
Extract fan isolator [AHU] 1 D 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-1-PAH2-01] [T-1-PAH2-01]
Duct SA temp. detector [AHU] 1 A 2 SD 35 2 12 10 7.5kW Supply fan 2 speed
Room temp. detector Room 1 A 2 3
Motorised damper 1 [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-1-SCS-01] T-1-SCF-01
Duct SA temp. detector [AHU] 1 A 2 DOL 6 2 3 2.5 0.75kW Supply fan
Motorised Valve [AHU] 1 A 3 4
Filter DP switch [AHU] 1 D 2
Supply fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
[T-1-SCS-02] T-1-SCF-02
Duct SA temp. detector [AHU] 1 A 2 DOL 6 2 3 2.5 0.55kW Supply fan
Motorised Valve [AHU] 1 A 3 5
Filter DP switch [AHU] 1 D 2
Supply fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
RE6309/D1368 Rev 0/2003 15910/8 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 1 Plant Room # 1
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
[T-1-PAH1-01] [T-1-PAH1-01]
Motorised damper 1 [AHU] 1 D 3 DOL 6 2 3 2.5 0.75kW Supply fan
Supply fan starter [MCC] 3 D 5 6
Supply fan isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
[Coldroom Equipment]
Fridge condensing unit common alarm Field 1 D 2
RE6309/D1368 Rev 0/2003 15910/9 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 2, Plant Room #1
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
T-2-AH2-01
T-2-MCC-01
Duct RA temp. detector [AHU] 1 A 2 SD 35 2 7 10 7.5kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 1
Duct RA Air Quality Detector [AHU] 1 A 2 DOL 20 2 3 6 4.0kW Extract fan
Duct LL temp detector [AHU] 1 A 2
Mixing damper 1 [AHU] 1 A 3
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator Field 1 D 2
Extract fan isolator Field 1 D 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
T-2-AH2-02
Duct RA temp. detector [AHU] 1 A 2 SD 35 2 7 10 7.5kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 2
Duct RA Air Quality Detector [AHU] 1 A 2 DOL 20 21 3 6 4.0kW Extract fan
Duct LL temp detector [AHU] 1 A 2
Mixing damper 1 [AHU] 1 A 3
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator Field 1 D 2
Extract fan isolator Field 1 D 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
T-2-AH2-07
Duct RA temp. detector [AHU] 1 A 2 SD 30 6 5.5kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 3
Duct RA Air Quality Detector [AHU] 1 A 2 DOL 20 2 3 4 3.0kW Extract fan
Duct LL temp detector [AHU] 1 A 2
Mixing damper 1 [AHU] 1 A 3
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator Field 1 D 2
Extract fan isolator Field 1 D 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
RE6309/D1368 Rev 0/2003 15910/10 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 2, Plant Room #2
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
T-2-AH2-03
Duct RA temp. detector [AHU] 1 A 2 SD 50 2 7 16 11kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 1
uct RA Air Quality Detector [AHU] 1 A 2 SD 35 2 7 6 7.5kW Extract fan
Duct LL temp detector [AHU] 1 A 2
T-2-MCC-02
Mixing damper 1 [AHU] 1 A 3
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator Field 1 D 2
Extract fan isolator Field 1 D 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
T-2-AH2-04
Duct RA temp. detector [AHU] 1 A 2 SD 35 2 7 6 7.5kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 2
uct RA Air Quality Detector [AHU] 1 A 2 DOL 20 2 3 4 4.0kW Extract fan
Duct LL temp detector [AHU] 1 A 2
Mixing damper 1 [AHU] 1 A 3
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator Field 1 D 2
Extract fan isolator Field 1 D 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-2-AH2-06]
Duct RA temp. detector [AHU] 1 A 2
SD 30 2 7 6 5.5kW Supply fan
Duct RA Hum detector [AHU] 1 A 2
3
uct RA Air Quality Detector [AHU] 1 A 2
DOL 20 2 3 4 3.0kW Extract fan
Duct LL temp detector [AHU] 1 A 2
Damper 1 [AHU] 1 A 3
Damper 2 [AHU] 1 A 3
Supply fan isolator [AHU] 1 D 2
Extract fan isolator [AHU] 1 D 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[Fire Alarm]
larm Interface Unit, zone 1 MCC 1 D 2
4. Numbers of Points and control cable cores are given for guidance. Tenderer to review against written specified requirements and make due allowance for what is required
RE6309/D1368 Rev 0/2003 15910/11 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 2, Plant Room #3
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
T-2-AH2-05
T-2-MCC-03
Duct RA temp. detector [AHU] 1 A 2 SD 20 2 7 4 4.0kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 1
Duct RA Air Quality Detector [AHU] 1 A 2 DOL 16 2 3 2.5 2.2kW Extract fan
Duct LL temp detector [AHU] 1 A 2
Mixing damper 1 [AHU] 1 A 3
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator Field 1 D 2
Extract fan isolator Field 1 D 2
Motorised Valve [AHU] 1 D 3
Motorised Valve [AHU] 1 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-2-PAH3-01]
Duct SA temp. detector [AHU] 1 A 2 DOL 16 2 3 2.5 2.5kW Supply fan
Duct SA Hum. detector [AHU] 1 A 2 2 DOL 16 2 3 2.5 1.5kW Extract fan
Duct IA temp. detector [AHU] 1 A 2 DOL 2 2 3 1.5 0.2kW Heat Wheel
Duct IA Hum. detector [AHU] 1 A 2
Motorised damper 1 [AHU] 1 D 3
Motorises damper 2 [AHU] 1 D 3
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Rotary wheel starter [MCC] 2 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Exract fan isolator [AHU] 1 D 2
Rotary wheel isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
RE6309/D1368 Rev 0/2003 15910/12 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 3, Plant Room #1
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
T-3-AH2-01
T-3-MCC-01
Duct RA temp. detector [AHU] 1 A 2 DOL 20 2 3 4 4.0kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 1
Duct RA Air Quality Detector [AHU] 1 A 2 DOL 20 2 3 2.5 3.0kW Extract fan
Duct LL temp detector [AHU] 1 A 2
Mixing damper 1 [AHU] 1 A 3
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator Field 1 D 2
Extract fan isolator Field 1 D 2
Motorised Valve [AHU] 1 D 3
Motorised Valve [AHU] 1 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-3-AH2-02]
Duct RA temp. detector [AHU] 1 A 2 SD 35 2 7 6 7.5kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 2
Duct RA Air Quality Detector [AHU] 1 A 2 DOL 20 2 3 2.5 4.0kW Extract fan
Duct LL temp detector [AHU] 1 A 2
Damper 1 [AHU] 1 A 3
Damper 2 [AHU] 1 A 3
Supply fan isolator [AHU] 1 D 2
Extract fan isolator [AHU] 1 D 2
Motorised Valve [AHU] 1 D 3
Motorised Valve [AHU] 1 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
T-3-AH2-03
Duct RA temp. detector [AHU] 1 A 2 INV 35 2 6 6 7.5kW Supply fan
Duct RA Hum detector [AHU] 1 A 2 3
Duct RA Air Quality Detector room #1 [AHU] 1 A 2 INV 30 2 6 6 5.5kW Extract fan
Duct RA Air Quality Detector room #2 [AHU] 1 A 2
Duct RA Air Quality Detector room #3 [AHU] 1 A 2
Duct RA Air Quality Detector room #4 [AHU] 1 A 2
Duct RA Air Quality Detector room #5 [AHU] 1 A 2
Duct RA Air Quality Detector room #6 [AHU] 1 A 2
Duct LL temp detector [AHU] 1 A 2
Mixing damper 1 [AHU] 1 A 3
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator Field 1 D 2
Extract fan isolator Field 1 D 2
Motorised Valve [AHU] 1 D 3
Motorised Valve [AHU] 1 D 3
Supply fan inverter, control / feedback [MCC] 2 A 4
Extract fan inverter, control / feedback [MCC] 2 A 4
Supply fan Inverter, enable / alarm / status [MCC] 4 D 5
Extract fan Inverter, enable / alarm / status [MCC] 4 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
T-3-KEF-01
Extract fan starter [MCC] 3 D 5 SD 35 2 7 6 7.5kW Extract fan
Electrostatic Filter enable Field 1 D 2 3
Electrostatic filter alarm Field 1 D 2 DOL 15 2 4 2.5 1kW Electrostatic filter
Extract fan isolator Field 1 D 2
Electrostatic filter isolator Field 1 D 2
RE6309/D1368 Rev 0/2003 15910/13 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 3, Plant Room #1
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
T-3-KEF-02
Extract fan starter [MCC] 3 D 5 SD 35 2 7 6 7.5kW Extract fan
Electrostatic Filter enable Field 1 D 2 4
Electrostatic filter alarm Field 1 D 2 DOL 15 2 4 2.5 1kW Electrostatic filter
Extract fan isolator Field 1 D 2
Electrostatic filter isolator Field 1 D 2
T-3-KEF-03
T-3-MCC-01 cont…
Extract fan starter [MCC] 3 D 5 SD 35 2 7 6 7.5kW Extract fan
Electrostatic Filter enable Field 1 D 2 5
Electrostatic filter alarm Field 1 D 2 DOL 15 2 4 2.5 1kW Electrostatic filter
Extract fan isolator Field 1 D 2
Electrostatic filter isolator Field 1 D 2
T-3-KEF-04
Extract fan starter [MCC] 3 D 5 DOL 20 2 3 2.5 3.0kW Extract fan
Electrostatic Filter enable Field 1 D 2 6
Electrostatic filter alarm Field 1 D 2 DOL 15 2 4 2.5 1kW Electrostatic filter
Extract fan isolator Field 1 D 2
Electrostatic filter isolator Field 1 D 2
T-3-KEF-05
Extract fan starter [MCC] 3 D 5
DOL 20 2 3 2.5 3.0kW Extract fan
Electrostatic Filter enable Field 1 D 2
7
Electrostatic filter alarm Field 1 D 2
DOL 15 2 4 2.5 1kW Electrostatic filter
Extract fan isolator Field 1 D 2
Electrostatic filter isolator Field 1 D 2
T-3-KEF-06
Extract fan starter [MCC] 3 D 5 DOL 10 2 3 1.5 1.1kW Extract fan
Extract fan isolator Field 1 D 2 8
T-3-KEF-07
Extract fan starter [MCC] 3 D 5 DOL 10 2 3 1.5 1.1kW Extract fan
Extract fan isolator Field 1 D 2 9
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
Fire Alarm Interface Unit, zone 2 MCC 1 D 2
RE6309/D1368 Rev 0/2003 15910/14 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Zone 6, Level 3, Plantroom #2
Cable Cores
Cable Type
Cable size
Load Item
Location
Device
Cable
[T-3-PAH3-01]
Duct SA temp. detector [AHU] 1 A 2 DOL 15 2 3 2.5 1.5kW Supply fan
T-3-MCC-02
Duct SA Hum. detector [AHU] 1 A 2 1
Duct IA temp. detector [AHU] 1 A 2 DOL 15 2 3 2.5 1.1kW Extract fan
Duct IA Hum. detector [AHU] 1 A 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Rotary wheel starter [MCC] 2 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Exract fan isolator [AHU] 1 D 2
Rotary wheel isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
T-3-KEF-08
Extract fan starter [MCC] 3 D 5 SD 20 2 7 2.5 9kW Extract fan
Electrostatic Filter enable Field 1 D 2 2
Electrostatic filter alarm Field 1 D 2 DOL 15 2 4 2.5 1kW Electrostatic filter
Extract fan isolator Field 1 D 2
Electrostatic filter isolator Field 1 D 2
T-3-KEF-09
Extract fan starter [MCC] 3 D 5 SD 20 2 7 2.5 9kW Extract fan
Electrostatic Filter enable Field 1 D 2 3
Electrostatic filter alarm Field 1 D 2 DOL 15 2 4 2.5 1kW Electrostatic filter
Extract fan isolator Field 1 D 2
Electrostatic filter isolator Field 1 D 2
T-3-KEF-10
Extract fan starter [MCC] 3 D 5 DOL 6 2 3 1.5 0.55kW Extract fan
Extract fan isolator Field 1 D 2 4
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
Fire Alarm Interface Unit, zone 2 MCC 1 D 2
RE6309/D1368 Rev 0/2003 15910/15 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 4, Plant Room #1
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
[T-4-AH2-01]
Duct RA temp. detector [AHU] 1 A 2
Duct RA Hum detector [AHU] 1 A 2 SD 35 2 7 6 7.5kW Supply fan
Duct RA Air Quality Detector [AHU] 1 A 2 1
Duct LL temp detector [AHU] 1 A 2 DOL 20 2 3 4 4.0kW Extract fan
Mixing damper 1 [AHU] 1 A 3
Mixing damper 2 [AHU] 1 A 3
Mixing damper 3 [AHU] 1 A 3
Supply fan isolator Field 1 D 2
Extract fan isolator Field 1 D 2
Motorised Valve [AHU] 1 D 3
Motorised Valve [AHU] 1 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[T-4-PAH3-01]
Duct SA temp. detector [AHU] 1 A 2 DOL 10 2 3 1.5 1.1kW Supply fan
Duct SA Hum. detector [AHU] 1 A 2 2
Duct IA temp. detector [AHU] 1 A 2 DOL 6 2 3 1.5 0.55kW Extract fan
Duct IA Hum. detector [AHU] 1 A 2
Motorised damper 1 [AHU] 1 D 3
Motorises damper 2 [AHU] 1 D 3
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Rotary wheel starter [MCC] 2 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Exract fan isolator [AHU] 1 D 2
Rotary wheel isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
RE6309/D1368 Rev 0/2003 15910/16 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 5 Plant Room 1, Zone 2 East
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
T-5-MCC-01
Duct IA Hum. detector [AHU] 1 A 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Rotary wheel starter [MCC] 2 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Exract fan isolator [AHU] 1 D 2
Rotary wheel isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
RE6309/D1368 Rev 0/2003 15910/17 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 5 Plant Room 2, Zone 2 Centre
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Location
Device
T-5-MCC-02
Duct IA Hum. detector [AHU] 1 A 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Rotary wheel starter [MCC] 2 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Exract fan isolator [AHU] 1 D 2
Rotary wheel isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
4. Numbers of Points and control cable cores are given for guidance. Tenderer to review against written specified requirements and make due allowance for wh
RE6309/D1368 Rev 0/2003 15910/18 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 5 Plant Room 3, Zone 2 West
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
T-5-MCC-03
Duct IA Hum. detector [AHU] 1 A 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Rotary wheel starter [MCC] 2 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Exract fan isolator [AHU] 1 D 2
Rotary wheel isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
[Sprinkler]
Sprinkler zone alarm LG - centre Field 1 D 2
Sprinkler zone alarm L1 - centre Field 1 D 2
Sprinkler zone alarm L2 - centre Field 1 D 2
Sprinkler zone alarm L3 - centre Field 1 D 2
Sprinkler zone alarm L4 - centre Field 1 D 2
Sprinkler zone alarm L5 - centre Field 1 D 2
RE6309/D1368 Rev 0/2003 15910/19 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 5 Plant Room 4, Zone 3 East
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
T-5-MCC-04
Duct IA Hum. detector [AHU] 1 A 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Rotary wheel starter [MCC] 2 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Exract fan isolator [AHU] 1 D 2
Rotary wheel isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
RE6309/D1368 Rev 0/2003 15910/20 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 5 Plant Room 5, Zone 3 Centre
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
T-5-MCC-05
Duct IA Hum. detector [AHU] 1 A 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Rotary wheel starter [MCC] 2 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Exract fan isolator [AHU] 1 D 2
Rotary wheel isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[Sprinkler]
Sprinkler zone alarm LG - centre Field 1 D 2
Sprinkler zone alarm L1 - centre Field 1 D 2
Sprinkler zone alarm L2 - centre Field 1 D 2
Sprinkler zone alarm L3 - centre Field 1 D 2
Sprinkler zone alarm L4 - centre Field 1 D 2
Sprinkler zone alarm L5 - centre Field 1 D 2
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
4. Numbers of Points and control cable cores are given for guidance. Tenderer to review against written specified requirements and make due allowance for what is required
RE6309/D1368 Rev 0/2003 15910/21 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Level 5 Plant Room 6 Zone 3, West
Compartment #
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
T-5-MCC-06
Duct IA Hum. detector [AHU] 1 A 2
Motorised Valve [AHU] 1 A 3
Motorised Valve [AHU] 1 A 3
Rotary wheel starter [MCC] 2 D 3
Supply fan starter [MCC] 3 D 5
Extract fan starter [MCC] 3 D 5
Supply fan isolator [AHU] 1 D 2
Exract fan isolator [AHU] 1 D 2
Rotary wheel isolator [AHU] 1 D 2
Pre Filter DP switch [AHU] 1 D 2
Main Filter DP switch [AHU] 1 D 2
[Fire Alarm]
Fire Alarm Interface Unit, zone 1 MCC 1 D 2
RE6309/D1368 Rev 0/2003 15910/22 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Childrens Pool Plant Room
Cable Cores
Nr of Points
Cable Type
Cable Size
Load Item
Location
Device
[Children's Pool]
T-G-MCC-04
Chilled water motorised Valve Field 1 A 3
LTHW motorised Valve Field 1 A 3
Return immersion detector pool Field 1 A 3
Common Alarm MCC 1 D 3
[Spa 1]
Chilled water motorised Valve Field 1 A 3
LTHW motorised Valve Field 1 A 3
Return immersion detector pool Field 1 A 3
Common Alarm MCC 1 D 3
[Spa 2]
Chilled water motorised Valve Field 1 A 3
LTHW motorised Valve Field 1 A 3
Return immersion detector pool Field 1 A 3
Common Alarm MCC 1 D 3
RE6309/D1368 Rev 0/2003 15910/23 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Main and Formal Pools
T-G-MCC-05
[Main Pool]
Chilled water motorised Valve Field 1 A 3
LTHW motorised Valve Field 1 A 3
Return immersion detector pool Field 1 A 3
Common Alarm MCC 1 D 3
[Formal Pool]
Chilled water motorised Valve Field 1 A 3
LTHW motorised Valve Field 1 A 3
Return immersion detector pool Field 1 A 3
Common Alarm MCC 1 D 3
RE6309/D1368 Rev 0/2003 15910/24 BEMS Point Schedule + MCC Load Diagram
BEMS POINT SCHEDULE & MCC LOAD DIAGRAM
Town Hotel, Lazy River West Plant Room
Cable Cores
Cable Type
Load Item
Location
Device
Cable
T-G-MCC-06
[Lazy River West]
Chilled water motorised Valve Field 1 A 3
LTHW motorised Valve Field 1 A 3
Return immersion detector pool Field 1 A 3
Common Alarm MCC 1 D 3
RE6309/D1368 Rev 0/2003 15910/25 BEMS Point Schedule + MCC Load Diagram