Unit type: ALU 311 GE Airflow: 9.000 m³/h
Cooling capacity (total): 32,5 kW Return air temperature: 24 °C
Cooling capacity (sensible): 26,7 kW Return air humidity: 50 rel.%
Net total cooling capacity: 31,3 kW Supply air temperature: 13 °C
Net sensible cooling capacity: 25,5 kW Altitude above sea level: 2.500 m
Condensing temperature: 45 °C Height: 1.980 mm
Evaporating temperature: 10 °C Width: 1.750 mm
EER: 4,11 kW/kW Depth: 890 mm
Sound power level: 70,4 dB(A) Weight: 557 kg
LpA (2m freefield): 49,9 dB(A) Refrigerant: R407C
Frequency: 60 Hz