You are on page 1of 4

Data sheet

Project: Climatizador de Precisión STULZ


Editor: Eduardo Muñoz
Date : 05.10.2017

Unit
Unit type: ASU 281 A
Cooling capacity (total): 27,2 kW Airflow: 7.000 m³/h
Cooling capacity (sensible): 27,2 kW Air velocity: 2,7 m/s
Net total cooling capacity: 25,4 kW Return air temperature: 24 °C
Net sensible cooling capacity: 25,4 kW Return air humidity: 40 rel.%
Condensing temperature: 48 °C Supply air temperature: 12 °C
EER: 3,24 kW/kW Altitude above sea level: 500 m
AER: 0,26 W/(m³/h) Height: 1.980 mm
Sound power level: 78,0 dB(A) Width: 950 mm
LpA (2m freefield): 59,1 dB(A) Depth: 890 mm
Number of refrigerant circuits: 1 Weight: 342 kg
Number of compressors: 1 Refrigerant: R407C
Power supply: 380-415/3/50

Fan (Data per unit)


Fan type: R3G595 Power consumption: 1,8 kW

Number: 1 ESP external static pressure: 100 Pa


Max. revolutions: 1.408 U/min Total pressure drop: 562 Pa
Nominal power: 2,9 kW Control voltage: 8,1 V
Revolutions: 1.202 rpm Motor-efficiency: 89 %

Compressor (Data per compressor)


Electrical power consumption: 6,6 kW
Heat rejection: 33,8 kW
COP: 4,13 kW/kW
Number: 1
Evaporating temperature: 7,9 °C

Condenser
Unit type: KSV045A21p Weight: 142 kg
Ambient temperature: 35 °C Current consumption (per fan): 2,30 A
Sound pressure group: Standard Power consumption (per fan): 0,53 kW
Required condenser capacity: 33,8 kW Height: 1.066 mm
Available condenser capacity: 43,5 kW Width: 1.860 mm
Difference: 28,7 % Depth: 920 mm
Number of fans: 2 Airflow: 12.100 m³/h
Number of condensers: 1 LpA (5m freefield): 54,6 dB(A)

Noise data
63 125 250 500 1000 2000 4000 8000 Total NR 1;5 Mean sound pressure level at 2m
1 (dBA) 49,6 53,1 54,6 53,1 47,1 42,1 34,1 24,1 59,1 distance at free field conditions
2 (dBA) 61,9 67,9 70,9 70,9 63,9 55,9 47,9 40,9 75,9 2;6 Casing radiated sound power level
3 (dBA) 68,9 71,9 72,4 70,4 64,4 59,4 51,4 41,4 76,4 without discharge and inlet
4 (dBA) 47,7 51,9 72,3 69,6 70,3 71,1 69,2 59,1 77,7
3;7 Suction side sound power level
5 (dB) 75,8 69,2 63,2 56,3 47,1 40,9 33,1 25,2 76,9 55
6 (dB) 88,1 84,0 79,5 74,1 63,9 54,7 46,9 42,0 90,1 73
7 (dB) 95,1 88,0 81,0 73,6 64,4 58,2 50,4 42,5 96,0 76 4;8 Discharge sound power level in
accordance to fan-manufacturer dat
8 (dB) 73,9 68,0 80,9 72,8 70,3 69,9 68,2 60,2 83,0 74

The above mentioned data are subject to the measuring tolerances of Eurovent. Unless otherwise stated, all data refer to a product in basic version. Page 1 of 1
StulzSelect Vers. 3.0.1 - Proj.: # ST-LPISA 2017 ASU 281 A 1 x ASU 281 A
1980
Condensate drain

175
A

624
866 950

Electrical connection
Pressure pipe
Liquid line

890

919
510
478

A
90

125
136 Liquid line circuit 1 solder connection 16mm
208 Pressure pipe circuit 1 solder connection 22mm

ASU_281_A_R407C_50Hz page 1 / 1
Data sheet
Project: Climatizador de Precisión STULZ
Editor: Eduardo Muñoz
Date : 28.09.2017

Unit
Unit type: ASD 281 A
Cooling capacity (total): 27,2 kW Airflow: 7.000 m³/h
Cooling capacity (sensible): 27,2 kW Air velocity: 2,7 m/s
Net total cooling capacity: 25,5 kW Return air temperature: 24 °C
Net sensible cooling capacity: 25,5 kW Return air humidity: 40 rel.%
Condensing temperature: 48 °C Supply air temperature: 12 °C
EER: 3,28 kW/kW Altitude above sea level: 500 m
AER: 0,24 W/(m³/h) Height: 1.980 mm
Sound power level: 77,7 dB(A) Width: 950 mm
LpA (2m freefield): 57,6 dB(A) Depth: 890 mm
Number of refrigerant circuits: 1 Weight: 352 kg
Number of compressors: 1 Refrigerant: R407C
Power supply: 380-415/3/50

Fan (Data per unit)


Fan type: R3G595 Power consumption: 1,7 kW

Number: 1 ESP external static pressure: 100 Pa


Max. revolutions: 1.408 U/min Total pressure drop: 539 Pa
Nominal power: 2,9 kW Control voltage: 8,0 V
Revolutions: 1.182 rpm Motor-efficiency: 89 %

Compressor (Data per compressor)


Electrical power consumption: 6,6 kW
Heat rejection: 33,8 kW
COP: 4,13 kW/kW
Number: 1
Evaporating temperature: 7,9 °C

Condenser
Unit type: KSV045A21p Weight: 142 kg
Ambient temperature: 35 °C Current consumption (per fan): 2,30 A
Sound pressure group: Standard Power consumption (per fan): 0,53 kW
Required condenser capacity: 33,8 kW Height: 1.066 mm
Available condenser capacity: 43,5 kW Width: 1.860 mm
Difference: 28,7 % Depth: 920 mm
Number of fans: 2 Airflow: 12.100 m³/h
Number of condensers: 1 LpA (5m freefield): 54,6 dB(A)

Noise data
63 125 250 500 1000 2000 4000 8000 Total NR 1;5 Mean sound pressure level at 2m
1 (dBA) 48,1 51,6 53,1 51,6 45,6 40,6 32,6 22,6 57,6 distance at free field conditions
2 (dBA) 60,4 66,4 69,4 69,4 62,4 54,4 46,4 39,4 74,4 2;6 Casing radiated sound power level
3 (dBA) 67,4 70,4 70,9 68,9 62,9 57,9 49,9 39,9 74,9 without discharge and inlet
4 (dBA) 46,2 50,4 70,8 68,1 68,8 69,6 67,7 57,6 76,2
3;7 Suction side sound power level
5 (dB) 74,3 67,7 61,7 54,8 45,6 39,4 31,6 23,7 75,4 53
6 (dB) 86,6 82,5 78,0 72,6 62,4 53,2 45,4 40,5 88,6 71
7 (dB) 93,6 86,5 79,5 72,1 62,9 56,7 48,9 41,0 94,5 74 4;8 Discharge sound power level in
accordance to fan-manufacturer dat
8 (dB) 72,4 66,5 79,4 71,3 68,8 68,4 66,7 58,7 81,5 73

The above mentioned data are subject to the measuring tolerances of Eurovent. Unless otherwise stated, all data refer to a product in basic version. Page 1 of 1
StulzSelect Vers. 3.0.1 - Proj.: # ST-LPISA 2017 ASD 281 A 1 x ASD 281 A
560
159
Electrical connection
50 Control cable

40
60
Humidifier

89

174
Condensate drain 3/4"

Liquid line
Pressure pipe

527
81
1991

1980
950 1548
890

Liquid line solder connection 16mm


919

Pressure pipe solder connection 22mm

ASD_281_A_R407C_50Hz page 1 / 1