3/1/EN/2
Displacement
Flow Diffusers
Types QLE · QLF
for low turbulence air supply
Description 2 The displacement flow units types QLE and QLF are primarily
employed in comfort conditioning.
Construction · Dimensions 3
Materials 3 As opposed to the familiar principle of mixed air flow through ceiling
or wall diffusers, displacement flow units guarantee low-turbulence
Nomenclature 4 air supply. The discharge velocity is very low. While with mixed flows
Quick Selection 5 it is preferable to achieve as high an induction as possible (by mixing
Selection Examples 5 room air with the supply air stream), the principle of displacement
flow ventilation is to achieve an induction rate as low as possible.
Pressure Drop · Acoustic Data 6 Depending on the degree of activity of the persons in the occupied
Aerodynamic Data QLE 8 zone, the supply air can enter the space with a temperature difference
Aerodynamic Data QLF 9 of -1K to -6K in relation to the room air. The air spreads out on the
floor and is lifted up by convection currents from heat sources
Order Details 16 (machines, electrical equipment, people, etc.). The fresh air, therefore,
finds its own path to the heat source from which the heat load must
be removed. Should the heat source be people, this provides them
also with fresh air.
With the principle of displacement ventilation, the exhaust air
locations should be arranged at high room level.
With an even distribution of displacement flow diffusers, even large
halls (e. g. auditoria, industrial factories) can be air-conditioned
without draughts in an economical manner.
Type QLE
2
Construction · Dimensions · Materials
QLE-U
Size A H
150 350 150
300 350 300
450 485 450
600 700 600
750 770 750
applicable for all widths (1000 / 1250 / 1500) Fitting of the face plate
3
Construction · Dimensions · Nomenclature
Nomenclature:
‡ in l/s · m; m3/h · m: Volume flow rate per meter (width)
‡t in l/s; m3/h Total volume flow rate per diffuser
L in m: Distance from diffuser to calculate ƒL and ∆tL
ƒL in m/s: Maximum flow velocity at distance L from
diffuser and distance 0.1 m above floor
tZ in °C: Supply air temperature ∆tL
t1,1 in °C: Temperature at 1.1 m room height
t0,1 in °C: Temperature at 0.1 m above floor
∆tZ in K: Temperature difference t1.1 - tZ
∆t0,1 in K: Temperature difference t0.1 - t
∆pt1 in Pa: Pressure drop for discharge in one direction
∆pt3 in Pa: Pressure drop for discharge in three directions
(~ 0.9 x ∆pt1)
LWA in dB(A): A-weighted sound power level
vtotmin = 0.1 m/s
∆tL in K: Temperature difference at distance L
between room and core temperature vtotmax = 0.3 m/s
Construction QLF
1-directional 3-directional
Type QLF-O Type QLF-U discharge discharge
A C C
37
H+70
H+70
H*
H*
37
B*
A
B+70 B* T T
B+70
Dimensions QLF
Size Dimensions in mm
H* x B* A C T
450 x 300 160 80 185
450 300 80 185
600 x 300 160 80 185
450 300 80 185
600 360 150 235
750 x 450 300 80 185
600 360 150 235
Rectangular air connection spigot, 750 625 150 235
either on top or bottom 1000 x 600 360 150 235
Perforated face plate 750 625 150 235
1250 x 600 360 150 235
Casing 750 625 150 235
Integral perforated sheet steel basket 1500 x 750 625 150 235
1000 715 200 287
Perforated side plates right and left 1750 x 750 625 150 235
for 3-directional discharge 1000 715 200 287
1250 890 200 287
2000 x1000 715 200 287
1250 890 200 287
4
Quick Selection · Examples
5
Pressure Drop · Acoustic Data
Type QLE
1 Pressure drop QLE B = 1000 mm 2 Pressure drop QLE B = 1250 mm
e
Siz
e
Siz
35
3300
20 20
30
2255
15 15
25
Pressure drop ∆pt1 in Pa
(A
dB
20
)
(A
10
dB
in
10
1155
in
LW
15
A
LW
7
7
5
5
4 4
20 l/s 25 30 40 50 60 80 100 30 l/s 40 50 60 80 100 125 150
‡t ‡t
75 m3/h 100 150 200 300 120 150 200 m3/h 300 500
6
Pressure Drop · Acoustic Data
6 Sound power level and pressure drop 7 Sound power level and pressure drop
QLF 750 x ... 450 600 750 QLF 1000 x ... 600 750
40 40
30 30
35
35
20 20
30
30
15 15
25
25
20
20
)
(A
)
(A
10 10
dB
dB
in
in
15
15
A
LW
A
LW
7 7
5 5
4 4
60 l/s 80 100 125 150 200 250 300 80 l/s 100 125 150 200 250 300 400
‡t ‡t
220 300 500 m3/h 700 1000 300 m3/h 500 700 1000 1250
8 Sound power level and pressure drop 9 Sound power level and pressure drop
QLF 1250 x ... 600 750 QLF 1500 x ... 750 1000
40 40
30 30
35
35
20 20
30
30
15 15
Pressure drop ∆pt1 in Pa
Pressure drop ∆pt1 in Pa
25
25
20
)
(A
20
10 10
)
(A
dB
dB
in
15
in
15
A
LW
A
LW
7 7
5 5
4 4
100 l/s 125 150 200 250 300 400 500 150 l/s 200 250 300 400 500 600 750
‡t ‡t
400 500 m3/h 700 1000 1500 m3/h 700 1000 1500 2000 2500
10 Sound power level and pressure drop 11 Sound power level and pressure drop
QLF 1750 x ... 750 1000 1250 QLF 2000 x ... 1000 1250
40 40
30 30
35
35
20 20
30
30
15 15
Pressure drop ∆pt1 in Pa
Pressure drop ∆pt1 in Pa
25
25
)
(A
20
10 10
20
dB
)
(A
dB
in
A
in
15
15
LW
7
A
7
LW
5 5
4 4
200 250 300 l/s 400 500 600 800 1000 250 300 l/s 400 500 600 800 1000 1250
‡t ‡t
720 1000 m3/h 1500 2000 2500 3500 1000 m3/h 1500 2000 2500 3500 4500
7
Aerodynamic Data QLE
Distance L Distance L
Distance L Distance L
Distance L Distance L
8
Aerodynamic Data QLE · QLF
Distance L Distance L
Distance L Distance L
Type QLF
22 Air flow velocity size 450 x 300 23 Temperature difference size 450 x 300
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
25 90
30
0, ‡ 20 72
, 25 t=
25
2,5
0 15 54
20 20
0, (9 10 36
2,0
15 0)
vL in m/s
(7
15 2)
0, (5
10 4)
1,5
l/s
10 (3
0, (m 3 )
6
/h ∆tZ
1,0
∆tL in K
) in K
-2
0,8
-4
-6
0,5
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung
Distance L
L in
in m
m
Entfernung
Distance L in m
9
Aerodynamic Data QLF
24 Air flow velocities size 450 x 450 25 Temperature difference size 450 x 450
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
30 108
25 90
30
0, 20 72
‡
, 25 t=
2,5
0 30 15 54
2 0 25 (1
0, 20 08
2,0
vL in m/s
(9 )
15 15 0)
0, (7
l/s 2)
1,5
(5
10 (m 3 4)
0, /h
)
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
-6
0,5
0,4 0,5 0,7 1 2 3 4 5
0,
0,
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung
Distance L in m Distance L in m
Entfernung
26 Air flow velocities size 600 x 300 27 Temperature difference size 600 x 300
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
40 144
30 108
30 ‡ 20
0, t=
40 72
25 (1 15 54
0,
2,5
30 44
)
20 (1
0, 20 08
2,0
)
vL in m/s
15 15 (7
0, 2)
l/s
1,5
(5
10 (m 3 4)
0, /h
)
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
-6
0,5
0,5 0,7 1 2 3 4 5 6
0,
0,
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung
Distance L in m
Entfernung
Distance L in m
m
28 Air flow velocities size 600 x 450 29 Temperature difference size 600 x 450
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
50 180
40 144
30
0, ‡
30 108
, 25 t= 25 90
2,5
0 50
20 40 (1
0, 80
2,0
30 (1 )
vL in m/s
44
15 25 )
0, (1
08
l/s
)
1,5
(
(m 3 90)
10
0, /h
)
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
-6
0,5
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung
Distance LL in
in m
m Entfernung
Distance LL in m
10
Aerodynamic Data QLF
30 Air flow velocities size 600 x 600 31 Temperature difference size 600 x 600
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
60 216
50 180
30
0, 40 144
, 25 ‡
t= 30 108
2,5
0 60
2 0 50
0, (2
1
2,0
40 (1 6)
vL in m/s
15 80
0, 30 (1 )
44
l/s )
1,5
(1
0
10 (m 3 8)
0, /h
)
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
-6
0,5
0,4 0,5 0,7 1 2 3 4 5
0,
0,
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung
Distance LL in
in m
m Entfernung
Distance L in
in m
m
32 Air flow velocities size 750 x 450 33 Temperature difference size 750 x 450
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
50 180
40 144
30 ‡ 30 108
0, t=
50
25 20 72
0,
2,5
40 (1
80
20
0, 30 (1
44
)
2,0
vL in m/s
(1 )
15 20 08
0, )
l/s (7
1,5
2)
10 (m 3
0, /h
)
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
-6
0,5
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung
Distance LL in
in m Entfernung
Distance L in
in m
m
34 Air flow velocities size 750 x 600 35 Temperature difference size 750 x 600
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
70 252
60 216
30 ‡ l/s 50 180
0, t=
70
, 25 (m 3 40 144
2,5
0 60 (2 /h)
20 50 52
0, (2 )
(1 16)
2,0
40
vL in m/s
15 80
0, (1
44 )
)
1,5
10
0,
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
-6
0,5
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung
Distance LLininmm
Entfernung
Distance L in m
11
Aerodynamic Data QLF
36 Air flow velocities size 750 x 750 37 Temperature difference size 750 x 750
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
100 360
80 288
30 60 216
0, ‡
25 t= 50 180
, 10
2,5
0 0
20 80 (3
0, 6
(2 0)
2,0
60
vL in m/s
88
15 50 (2 )
0, l/s (1 16)
80
1,5
(m 3 )
10 /h
0, )
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
-6
0,5
0,4 0,5 0,7 1 2 3 4 5
0,
0,
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung
Distance LL in m Entfernung
Distance LL ininmm
38 Air flow velocities size 1000 x 600 39 Temperature difference size 1000 x 600
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
120 432
‡ 100 360
t=
12 80 288
30 10 0
0, 0 (4 60 216
25 80 (3 32
0, 6 )
2,5
60 (2 0)
20 8
0, l/s (2 8)
2,0
16
vL in m/s
(m 3 )
15
0, /h
)
1,5
10
0,
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
-6
0,5
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung
Distance L in m Entfernung
Distance LL in
in m
40 Air flow velocities size 1000 x 750 41 Temperature difference size 1000 x 750
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
120 432
100 360
‡ 80 288
=1
30
t
0, 20 60 216
25 10 (4
, 0
2,5
0 3
80 (3 2)
20 6
0, 60 (2 0)
8
2,0
(2 8)
vL in m/s
l/s
15 1
0, (m 3 6)
/h
1,5
)
10
0,
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
0,5
-6
0,4 0,5 0,7 1 2 3 4 5
0,
0,
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung Entfernung
Distance LL ininmm
Distance L
L in
in m
m
12
Aerodynamic Data QLF
42 Air flow velocities size 1250 x 600 43 Temperature difference size 1250 x 600
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
130 468
110 396
‡
t= 90 324
13
70
30 11 0 252
0, 90 0 ( (468
25 3
, 70 (3 96 )
2,5
0
2 0 l/s (2 24) )
0, 5
(m 3 2)
2,0
vL in m/s
15 /h
0, )
1,5
10
0,
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
-6
0,5
0,4 0,5 0,7 1 2 3 4 5
0,
0,
0,
1,
1,
2,
5
6
8
0
5
0
Distance L in m
Entfernung Entfernung
Distance LL ininmm
44 Air flow velocities size 1250 x 750 45 Temperature difference size 1250 x 750
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
140 504
120 432
‡ 100 360
t=
14 80 324
30 1 0
0, 10 20 (50
25 4
90 0 (3(43 )
0,
2,5
20 l/s (3 60 2)
0, 2 )
(m 3 4)
2,0
vL in m/s
/h
15 )
0,
1,5
10
0,
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
-6
0,5
0,
1,
1,
2,
5
6
8
0
5
0
Distance LL in
inm
m Entfernung
Distance LL in
in m
m
Entfernung
46 Air flow velocities size 1500 x 750 47 Temperature difference size 1500 x 750
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡
t=
16
30 13 0
0,
10 0 ( (576
160 576
, 25 0 46 ) 130 468
2,5
0
70 (36 8)
20 (2 0)
100 360
0, l/s 70 252
2,0
5
vL in m/s
(m 3 2) m3/h
15 ‡t in l/s
0, /h
)
1,5
10
0,
∆tZ
∆tL in K
1,0
in K
-2
0,8
-4
-6
0,5
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung
DistanceLLininmm Entfernung
Distance LLininmm
13
Aerodynamic Data QLF
48 Air flow velocities size 1500 x 1000 49 Temperature difference size 1500 x 1000
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡
t=
25
30
0, 2 0
15 00 ( (900
25 0 72 )
0, 10 (5 0)
0 4 900
2,5 3,0
0 250
0,
2 l/s (3 0) 720
60 200
vL in m/s
(m 3 ) 150 540
15 /h
0, ) 100 360
m3/h
2,0
‡t in l/s
10
0,
1,5
∆tZ
∆tL in K
in K
-2
1,0
-4
-6
0,8
0,4 0,5 0,7 1 2 3 4 5
0,
0,
0,
1,
1,
2,
5
6
8
0
5
0
Entfernung
Distance LL in
in m
m Entfernung
Distance LL ininmm
50 Air flow velocities size 1750 x 750 51 Temperature difference size 1750 x 750
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
250 900
200 720
‡ 150 540
t=
25
0 100
2 0 (
360
,4
0 15 00 90
30 0 (72 0)
0, 10
0
(5 0)
40
25
vL in m/s
0, l/s (36 )
4,0
20 (m 3 0)
0, /h
)
15
0,
3,0
∆tZ
∆tL in K
in K
10
2,5
0, -2
2,0
-4
-6
1,5
0,
1,
2,
3,
0
5
6
DistanceLLininmm Entfernung
Distance L ininm
m
Entfernung
52 Air flow velocities size 1750 x 1000 53 Temperature difference size 1750 x 1000
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
400 1440
300 1080
‡ 200 720
t=
0 40 150 540
4 30 0
0,
20 0 (144
30 15 0 (10 0)
0,
25
0 (72 80)
vL in m/s
, l/s
4,0
0 (5 0)
20 (m 3 40)
0, /h
)
15
0,
3,0
∆tZ
∆tL in K
0 in K
1
2,5
0, -2
2,0
-4
-6
1,5
0,
1,
2,
3,
0
5
6
Entfernung
Distance LL ininmm
Entfernung
Distance L
L in
in m
m
14
Aerodynamic Data QLF
54 Air flow velocities size 1750 x 1250 55 Temperature difference size 1750 x 1250
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h ‡t in l/s m3/h
400 1440 400 1440
300 1080 300 1080
200 720 200 720
150 540 150 540
40
0,
30
0,
25
vL in m/s
4,0
0
20
0,
15
0,
3,0
∆tZ
∆tL in K
0 in K
1
2,5
0, -2
2,0
-4
-6
1,5
0,4 0,5 0,7 1 2 3 4 5
1,
0,
0,
0,
1,
2,
3,
0
5
6
Entfernung
Distance LLininmm
Distance LL ininmm
Entfernung
56 Air flow velocities size 2000 x 1000 57 Temperature difference size 2000 x 1000
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
500 1800
400 1440
300 1080
200 720
40
0,
30
0,
25
vL in m/s
0,
4,0
20 200 720
0, 300 1080
400 1440
15
0, 500 1800
3,0
in K
10
2,5
0, -2
2,0
-4
-6
1,5
0,
1,
2,
3,
0
5
6
Entfernung
Distance LLininmm
Distance LL ininm
Entfernung m
58 Air flow velocities size 2000 x 1250 59 Temperature difference size 2000 x 1250
∆tZ = -6 -4 -2K ∆tZ = -6 -4 -2K
‡t in l/s m3/h
800 2880
600 2160
400 1440
200 720
40
0,
30
0,
25
vL in m/s
,
4,0
0
20 200 720
0, 400 1440
600 2160
15
0, 800 2880
3,0
0 in K
1
2,5
0, -2
2,0
-4
-6
1,5
0,
1,
2,
3,
0
5
6
15
Order Details
Specification Text
The displacement flow units types QLE and QLF consist of a Materials
casing with a perforated metal face plate (for one-directional Casing, perforated face plate and perforated sheet steel
discharge) or additional perforated metal side plates (for three- basket are made of galvanised sheet steel.
directional discharge), a rectangular spigot located either on
top or at the bottom of the unit as required, and an internal Casing and perforated plates are pre-treated and powder-
perforated plate basket for even air distribution. coated white RAL 9010, gloss level 50 %, any other RAL
colour is optional.
The rear surface ot the casing and the perforated sheet steel
basket are coated black RAL 9005.
Order code
These codes do not need to be completed for standard products
Accessories
Fixing material
QLF-BM / P1 / RAL9016
(2 fixing angles, 4 self tapping screws)
16