You are on page 1of 9

DATA SETTINGS Recommended

10
Independent bar 2 ID>1 = 80 A 80

Idiff / ILoadMax
k1 (ID>1) = 10 % 10% 9
IloadMin (1 feeder) 100 A ID>2 = 2000 A 1800
IloadMax (1 CT) 1500 A k2 (ID>2) = 60 % 60% 8
ILoadMax (1 bar) 3000 A IDCZ>2 = 2000 A 1800
Biggest PW 2000 A kCZ = 30 % 30% 7
Icc min (1 bar) 2500 A Box mode 1
VT criteria ? (Y/N) N Phase Comp = 32 % 27% % of In Fill in "CTRatio" page 6

CHECK LIST 5
Minimum Maximum
ID>1 = 4
40 OK 80 OK 80
3
1500 OK ID>2 =
or 1800 OK 2000 OK 2000
2

1500 OK IDCZ>2 =
1
or 1800 OK 2000 OK 2000
kCZ =
0
0.10 OK 0.30 OK 0.30
0 1 2 3 4 5 6 7 8 9 10
Ibias x ILoadMax

or

2% of the Biggest PW < ID>1 = < 0.8 x IloadMin ID>1 = 0.05 x ILoadMax
1.2 x IloadMax (1CT) (or use VT) < ID>2 = < min of (2 x IloadMax & 0.5 (or 0,8) x Icc min) ID>2 = 1.33 x ILoadMax
1.2 x IloadMax (1CT) (or use VT) < IDCZ>2 = < min of (2 x IloadMax & 0.5 (or 0,8) x Icc min) IDCZ>2 = 1.33 x ILoadMax
k (ID>1) < kCZ = < Icc min (1 bar) / (((Independant bar - 1) x IloadMax (1 bar)) + Icc min (1 bar))
See Check Zone Slope calculation.doc for further details
In the event of a half-breaker scheme: see Setting Guide
Busbar
(100%)
ID>1
30
60
ID>2
IDCZ>2

9 10
ONE box mode

CTs of the biggest Zone 1 then 2 then 3 then 4 sum. In CTs infeeds Phase Comp.
CT 1 CT 2 CT 3 CT 4 CT 5 CT 6 CT 7 CT 1 to 7 ID>2
CT Ratio 2000 2000 2000 1500 1000 1000 1000 2000
Z1 Infeeds 2000 2000 0 0 1000 1000 0 6000 27% Zone 1
Z2 Infeeds 0 0 2000 1500 1000 0 1000 5500 29% Zone 2
Z3 Infeeds 0 0 0 0 0 0 0 0 100% Zone 3
Z4 Infeeds 0 0 0 0 0 0 0 0 100% Zone 4

27%

Note 1: For the feeders that can not contribute to the external fault (load only) put 0

THREE box mode

CTs of the biggest Zone 1 then 2 then 3 then 4 (when exis


CT 1 CT 2 CT 3 CT 4 CT 5 CT 6 CT 7 CT 8 CT 9 CT 10 CT 11 CT 12
CT Ratio 2000 2000 2000 2000 2000 2000 1500 1500 1500 1500 1500 1000
Z1 Infeeds 2000 2000 0 0 0 2000 1500 0 1500 0 1500 1000
Z2 Infeeds 0 0 2000 2000 0 2000 1500 1500 0 0 1500 1000
Z3 Infeeds 0 2000 2000 0 2000 0 1500 1500 0 0 1500 1000
Z4 Infeeds 0 2000 0 2000 2000 2000 1500 1500 0 0 1500 1000

Note 1: For the feeders that can not contribute to the external fault (load only) put 0
Zone 1
Zone 2
Zone 3
Zone 4

en 2 then 3 then 4 (when existing) sum. In CTs infeeds Phase Comp.


CT 13 CT 14 CT 15 CT 16 CT 17 CT 18 CT 19 CT 20 CT 21 Feeder 1 to 7 ID>2
1000 1000 1000 1000 1000 1000 1000 1000 1000 2000
0 1000 0 1000 0 0 0 1000 0 14500 11% Zone 1
0 1000 1000 1000 0 0 0 1000 1000 16500 10% Zone 2
0 0 1000 0 1000 0 1000 1000 0 15500 10% Zone 3
1000 1000 0 0 0 1000 0 0 1000 17500 9% Zone 4

9%
DATA TRIPPING CHARACTERISTIC WITH 1 infeed

CT ratio 2000 /1
10

Idiff / ILoadMax
Bias limit = 2640 9

0
0 1 2 3 4 5 6 7 8 9 10
Ibias x ILoadMax

=2*IdiffIbias!G11/100/(1-IdiffIbias!G7/100)*C4
ARACTERISTIC WITH 1 infeed & 1 outfeed

Busbar (100%)

ID>1

30

60

ID>2

IDCZ>2

Phase Comparison
limit

4 5 6 7 8 9 10
s x ILoadMax
k1 (ID>1) = 0.1
k2 (ID>2) = 0.6
kCZ = 0.3

Ibias 100% ID>1 = Slope ID>1 IDCZ>2 = Slope IDCZ>2 ID>2 =


0 0 0.05 0.00 1.33 0.00 1.33
0.5 0.5 0.05 0.05 1.33 0.15 1.33
1 1 0.10 0.10 1.33 0.30 1.33
1.5 1.5 0.15 0.15 1.33 0.45 1.33
2 2 0.20 0.20 1.33 0.60 1.33
2.5 2.5 0.25 0.25 1.33 0.75 1.50
3 3 0.30 0.30 1.33 0.90 1.80
3.5 3.5 0.35 0.35 1.33 1.05 2.10
4 4 0.40 0.40 1.33 1.20 2.40
4.5 4.5 0.45 0.45 1.35 1.35 2.70
5 5 0.50 0.50 1.50 1.50 3.00
5.5 5.5 0.55 0.55 1.65 1.65 3.30
6 6 0.60 0.60 1.80 1.80 3.60
6.5 6.5 0.65 0.65 1.95 1.95 3.90
7 7 0.70 0.70 2.10 2.10 4.20
7.5 7.5 0.75 0.75 2.25 2.25 4.50
8 8 0.80 0.80 2.40 2.40 4.80
8.5 8.5 0.85 0.85 2.55 2.55 5.10
9 9 0.90 0.90 2.70 2.70 5.40
9.5 9.5 0.95 0.95 2.85 2.85 5.70
10 10 1.00 1.00 3.00 3.00 6.00

Outgoing current threshold 0.64


Bias limit = 2.64
Slope ID>2 Phase Comparison limit
0.00 1.33
0.30 1.33
0.60 1.33
0.90 1.33
1.20 1.33
1.50 1.50
1.80 1.95
2.10 2.42
2.40 2.90
2.70 3.38
3.00 3.87
3.30 4.35
3.60 4.84
3.90 5.33
4.20 5.83
4.50 6.32
4.80 6.81
5.10 7.31
5.40 7.80
5.70 8.30
6.00 8.80

You might also like