You are on page 1of 7

Flow Measurement

Size 1/2 (15mm)


Fig. No. D931
Fixed orifice devices for standard applications
Kvs = 2.2
6000 60
5000 50
4000 40

3000 30

2000 20
SIGNAL (mm H 2 O)

1000 10
(kPa)

500 5
400 4

300 3 FLOWRATE

Q = K VS p
200 2

Where 36
Q = Flowrate l/s

100 1 p = Signal kPa


K VS = Signal Coefficient
70 0.7
0.05 0.1 0.2 0.3 0.4 0.5 1 2 3 4 5
Flowrate l/s

HEAD / PRESSURE LOSS


CR

The loss resulting from the insertion of the


AN
E

device in the pipeline may be calculated by multiplying


the signal by the appropriate factor

Fig. No. Factor


D931 (Fully open) 1.38 D931
Flow Measurement
Size 3/4 (20mm)
Fig. No.D931
Fixed orifice devices for standard applications
Kvs = 4.7
6000 60
5000 50
4000 40

3000 30

2000 20
SIGNAL (mm H 2 O)

1000 10
(kPa)

500 5
400 4

300 3 FLOWRATE

Q = K VS p
200 2
36
Where
Q = Flowrate l/s

100 1 p = Signal kPa


K VS = Signal Coefficient
70 0.7
0.05 0.1 0.2 0.3 0.4 0.5 1 2 3 4 5
Flowrate l/s

HEAD / PRESSURE LOSS


The loss resulting from the insertion of the
CR

device in the pipeline may be calculated by multiplying


AN
E

the signal by the appropriate factor

Fig. No. Factor


D931 (Fully open) 2.24
D931
Flow Measurement
Size 1 (25mm)
Fig. No. D931
Fixed orifice devices for standard applications
Kvs = 8.6
6000 60
5000 50
4000 40

3000 30

2000 20
SIGNAL (mm H 2 O)

1000 10
(kPa)

500 5
400 4

300 3 FLOWRATE

Q = K VS p
200 2
36
Where
Q = Flowrate l/s

100 1 p = Signal kPa


K VS = Signal Coefficient
70 0.7
0.05 0.1 0.2 0.3 0.4 0.5 1 2 3 4 5
Flowrate l/s
HEAD / PRESSURE LOSS
The loss resulting from the insertion of the
CR
AN

device in the pipeline may be calculated by


E

multiplying
the signal by the appropriate factor

Fig. No. Factor D931


D931 (Fully open) 2.37
Flow Measurement
Size 11/4 (32mm)
Fig. No. D931
Fixed orifice devices for standard applications
Kvs = 16.6
6000 60
5000 50
4000 40

3000 30

2000 20

1000 10
SIGNAL (mm H O)
2

(kPa)

500 5
400 4

300 3
FLOWRATE

Q = K VS p
200 2
36
Where
Q = Flowrate l/s

100 1 p = Signal kPa


K VS = Signal Coefficient
70 0.7
0.05 0.1 0.2 0.3 0.4 0.5 1 2 3 4 5
Flowrate l/s
HEAD / PRESSURE LOSS
CR

The loss resulting from the insertion of the


AN
E

device in the pipeline may be calculated by multiplying


the signal by the appropriate factor

Fig. No. Factor


931 (Fully open) 2.37 D931
Flow Measurement
Size 11/2 (40mm)
Fig. No. D931
Fixed orifice devices for standard applications
Kvs = 24.5
6000 60
5000 50
4000 40

3000 30

2000 20
SIGNAL (mm H 2 O)

1000 10
(kPa)

500 5
400 4

300 3 FLOWRATE

Q = K VS p
200 2

Where 36
Q = Flowrate l/s

100 1 p = Signal kPa


K VS = Signal Coefficient
70 0.7
0.5 1 2 3 4 5 10 50
Flowrate l/s

HEAD / PRESSURE LOSS


The loss resulting from the insertion of the
CR
AN

device in the pipeline may be calculated by multiplying


E

the signal by the appropriate factor

Fig. No. Factor


D931
D931 (Fully open) 1.83
Flow Measurement
Size 2 (50mm)
Fig. No. D931
Fixed orifice devices for standard applications
Kvs = 46.1
6000 60
5000 50
4000 40

3000 30

2000 20
SIGNAL (mm H 2 O)

1000 10
(kPa)

500 5
400 4

300 3 FLOWRATE

Q = K VS p
200 2

Where 36
Q = Flowrate l/s

100 1 p = Signal kPa


K VS = Signal Coefficient
70 0.7
0.5 1 2 3 4 5 10 50
Flowrate l/s

HEAD / PRESSURE LOSS


CR

The loss resulting from the insertion of the


AN
E

device in the pipeline may be calculated by multiplying


the signal by the appropriate factor

Fig. No. Factor


D931 (Fully open) 2.5
D931