EN 1751 Test Report Casing Air Leakage Rate

Date: 12-10-2018 Test Reference Number: M121018-02/TAB


Place: Waalwijk Tested by: TAB Witness by: YSP MR/vs010315
Model (name/type): ICV-C-H-100 Result: Class C

Air temperature (ºC) 21


(standard)
Atmospheric pressure (Pa) 101740 Pressure time 120 sec.
2
Correction factor 1,000 Surface Area: 0,31 m
Case width (m) 0,100 Measuring Equipment:
Case Height (m) 0,100 Air leakage tester type:
Duct Length (m) 1 Serial No: Tielenstraat 17, 5145 RC Waalwijk
Other Date certification: sales@inatherm.nl, www.inatherm.nl
Calibration cert.nr.
Approximate
Static Leakage EN 1751 EN 1751 EN 1751 EN 1751
Reading Pressure Leakage Rig Leakage Duct Surface Corrected Class A Class B Class C Class D
2 2 2 2 2
(Pa) (N l/s) (l/s) (l/s/m ) (l/s/m ) (l/s/m ) (l/s/m ) (l/s/m )

1 400 1,04 1,03 0,032 0,032 1,326 0,442 - -


2 1000 1,73 1,67 0,194 0,194 - 0,802 0,267 0,089
3 2000 2,48 2,40 0,258 0,258 - - 0,420 0,140

From DW/144
Duct Pressure Class Static pressure limit
Maximum Air Air leakage limits litres per second per
Velocity square metre of duct surface area
Positive Negative
1 2 3 4 5
Pa Pa m/s l/s/m2

Low - Class A 500 500 10 0.027 x p 0.65


Medium - Class B 1000 750 20 0.009 x p 0.65
High - Class C 2000 750 40 0.003 x p 0.65

D C
B A

1000
OVERPRESSURE Pa

100
0,05 0,50 5,00 Visual
LEAKAGE l/s/m 2 deformation? No
EN 1751 Figure C.2 - Classification of Case Leakage @ Pa: x

Approved and certified by


Certificate nr. :